9
Parallel Operation and control of Synchronous Generator and Double Fed Induction Generator Uppunoori Venkata Reddy 1,i , Bamandlapelli Ravi Kumar 2 , Maddela Sunil Kumar 3 , R N V L H Madhuri 4 1 Department of Electrical and Electronics Engineering, Vardhaman College of Engineering, Hyderabad, [email protected] 2 Department of Electrical and Electronics Engineering, Vardhaman College of Engineering, Hyderabad, [email protected] 3 Department of Electrical and Electronics Engineering, Nalla Narsimha Reddy Engineering College, Hyderabad, [email protected] 4 Department of Electrical and Electronics Engineering, Vardhaman College of Engineering, Hyderabad, [email protected] Abstract. Renewable energy sources are being increasingly used as distributed generators in rural and remote areas for the electrification. These distributed generators configuration a micro grid and supply power to the local patron. Micro/mini hydro power and wind plants are the two of the well liked configuration of the renewable energy sources, being installed in some countries. Micro or Mini hydro power plants utilize synchronous generators, whereas, modern wind power plants utilize doubly fed induction generators. To amalgamate micro hydro turbine steer synchronous generator in micro or mini hydro power plants and wind turbine driven DFIG in wind power plants, the study of parallel operation of a synchronous generator and a doubly fed induction generator is needed. Proper control program needs to be altered for their adequate parallel operation. This paper has employed the conventional voltage and frequency control methods for the synchronous generator and a stator flux oriented vector control technique for the doubly fed induction generator. Conventional Proportional Integral (PI) controllers have been designed to study some of the pointer issues in the parallel operation of the SG and the DFIG; these include frequency and voltage control, proper load sharing between the generator and unity factor operation of DFIG. PI controllers, unity power factor operation of the DFIG are not shielded. However, it provides adequate frequency and frequency control. Keywords: SG, DFIG, Parallel operation of two machines, arbitrary reference frame. 1 Introduction Electrification of rural areas, specifically those which are remotely located, is a challenging task in the under developed as well as developing countries. Electrification of such far-off places, through national grid extension, is not financially feasible due to high cost of the investment in the construction of transmission system and increased power loss in the line. Hence, generation of electricity from locally available energy sources is the best option in rural and remote areas for the electrification [3, 4]. Conventional fossil fuel based power plants are not economical at smaller ratings and these are not environment friendly. Hence, renewable/non-conventional sources are being increasingly used as the distributed generators, forming part of micro grids. Micro/mini hydro and wind power plants are two of the well liked forms of the renewable energy sources [1]. In order to supply power to the remotely located areas, micro grids are being developed interconnecting various renewable energy sources. In a micro grid, the available sources of electricity have to be integrated to supply the local loads. Distributed generations and, located close to the loads, diminishes flows in the transmission network and, hence, diminishes the system loss. Furthermore, the existence of generation, close to demand, increases service grade as seen by the end patron. The development of micro grids, engaging such sources, can contribute to the depletion of emissions and the mitigation of climate changes [7]. Generally, micro/mini hydro power plants utilize synchronous generator and modern wind power plants employ doubly fed induction generators [10]. To utilize the advantages of micro grids, small sources of electricity have to be integrated. International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com 538

Parallel Operation and control of Synchronous Generator ... · induction generator is needed. Proper control program needs to be altered for their adequate parallel operation. This

  • Upload
    others

  • View
    28

  • Download
    2

Embed Size (px)

Citation preview

  • Parallel Operation and control of Synchronous

    Generator and Double Fed Induction Generator

    Uppunoori Venkata Reddy1,i, Bamandlapelli Ravi Kumar2, Maddela Sunil Kumar3,

    R N V L H Madhuri4 1 Department of Electrical and Electronics Engineering, Vardhaman College of Engineering,

    Hyderabad, [email protected] 2 Department of Electrical and Electronics Engineering, Vardhaman College of Engineering,

    Hyderabad, [email protected] 3 Department of Electrical and Electronics Engineering, Nalla Narsimha Reddy

    Engineering College, Hyderabad, [email protected] 4Department of Electrical and Electronics Engineering, Vardhaman College of Engineering,

    Hyderabad, [email protected]

    Abstract. Renewable energy sources are being increasingly used as distributed

    generators in rural and remote areas for the electrification. These distributed

    generators configuration a micro grid and supply power to the local patron.

    Micro/mini hydro power and wind plants are the two of the well liked

    configuration of the renewable energy sources, being installed in some

    countries. Micro or Mini hydro power plants utilize synchronous generators,

    whereas, modern wind power plants utilize doubly fed induction generators. To

    amalgamate micro hydro turbine steer synchronous generator in micro or mini

    hydro power plants and wind turbine driven DFIG in wind power plants, the

    study of parallel operation of a synchronous generator and a doubly fed

    induction generator is needed. Proper control program needs to be altered for

    their adequate parallel operation. This paper has employed the conventional

    voltage and frequency control methods for the synchronous generator and a

    stator flux oriented vector control technique for the doubly fed induction

    generator. Conventional Proportional Integral (PI) controllers have been

    designed to study some of the pointer issues in the parallel operation of the SG

    and the DFIG; these include frequency and voltage control, proper load sharing

    between the generator and unity factor operation of DFIG. PI controllers, unity

    power factor operation of the DFIG are not shielded. However, it provides

    adequate frequency and frequency control.

    Keywords: SG, DFIG, Parallel operation of two machines, arbitrary reference

    frame.

    1 Introduction

    Electrification of rural areas, specifically those which are remotely located, is a

    challenging task in the under developed as well as developing countries.

    Electrification of such far-off places, through national grid extension, is not

    financially feasible due to high cost of the investment in the construction of

    transmission system and increased power loss in the line. Hence, generation of

    electricity from locally available energy sources is the best option in rural and remote

    areas for the electrification [3, 4].

    Conventional fossil fuel based power plants are not economical at smaller ratings

    and these are not environment friendly. Hence, renewable/non-conventional sources

    are being increasingly used as the distributed generators, forming part of micro grids.

    Micro/mini hydro and wind power plants are two of the well liked forms of the

    renewable energy sources [1]. In order to supply power to the remotely located areas,

    micro grids are being developed interconnecting various renewable energy sources. In

    a micro grid, the available sources of electricity have to be integrated to supply the

    local loads.

    Distributed generations and, located close to the loads, diminishes flows in the

    transmission network and, hence, diminishes the system loss. Furthermore, the

    existence of generation, close to demand, increases service grade as seen by the end

    patron. The development of micro grids, engaging such sources, can contribute to the

    depletion of emissions and the mitigation of climate changes [7].

    Generally, micro/mini hydro power plants utilize synchronous generator and

    modern wind power plants employ doubly fed induction generators [10]. To utilize

    the advantages of micro grids, small sources of electricity have to be integrated.

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    538

    mailto:[email protected]:[email protected]:[email protected]:[email protected]

  • Hence, for the amalgamation of the micro/mini hydro power and wind power, it is

    necessary to study the parallel operation of the synchronous generator and doubly fed

    induction generators.

    1.1 Wind Energy Conversion Systems (WECS)

    Turbines have to be more mechanically robust than differentr designs, because of

    the higher structural loads involved. With a fixed speed WECS, it may be necessary

    to use aerodynamic control of the blades to optimize the whole system performance,

    thus introducing additional control systems, complexities, and costs. These turbines

    have to be more mechanically robust than other designs, because of the higher

    structural loads involved [9, 11].

    Another advantage is that variable speed turbines also allow the grid voltage to be

    controlled, as the reactive power generation can be varied [9]. The rotational speed of

    a wind turbine is fairly low and must therefore be adjusted to the electrical frequency.

    The major drawbacks of variable speed systems are that the built-in power electronics

    are sensitive to voltage dips caused by faults and/or switching [14].

    1.2 Variable Speed Wind Turbine with DFIG or SG/PMSG

    Synchronous generators or permanent-magnet synchronous generators can be

    designed with multiple poles, so that there is no need for gearbox. The power

    electronic equipment has to be designed for the full power rating of the generator.

    Future of wind turbine technology lies in PMSG [15, 13]. With the permanent

    magnet, high power densities can be achieved in a less space. Hence, the generators

    become much more compact with high efficiencies. Notable advantage is absence of

    gearbox and its acoustic noise.

    The cost of power converter can be high due to its large size and also the losses in

    the converter are large. One major advantage with this system is it’s well developed

    and robust in control [6].

    The losses in the power electronic equipment can be reduced in comparison to

    power electronic equipment that has to handle the total system power as for a direct-

    driven synchronous generator, apart from the cost saving of using a smaller converter

    [7]. In addition, the cost of the converter becomes lower. The schematic of DFIG with

    stator circuit connected to the grid while the rotor circuit is connected to a converter

    via slip rings is as shown in Fig.3. Doubly-fed induction generators (DFIG) are

    provided with three phase windings on the rotor and on the stator. They may be

    supplied with energy at both rotor and stator terminals [5].

    The back-to-back converter consists of two converters, i.e., Machine-Side

    Converter (MSC) and Parallel Grid-Side Converter (PGSC). Between the two

    converters a dc-link capacitor is placed, as energy storage, in order to keep the voltage

    variations (or 7 ripples) in the dc-link voltage small. With the machine-side converter

    it is possible to control the torque or the speed of DFIG and also the power factor at

    the stator terminals, while the main objective for the Grid-side converter is to keep the

    dc-link voltage constant.

    2 Machine Modelling of Synchronous Generator and DFIG Using

    Conventional PI Controllers

    In paralleling of a synchronous generator and a self excited induction generator

    (SEIG) was presented. As the rotor of the SEIG is short circuited, one cannot control

    the reactive power from the rotor side. When reactive power is controlled from the

    stator side of the induction generator, the power rating of the controlling circuit is

    higher. Ref presents a DFIG based wind farm in parallel with SG based generating

    station. It shows the control compatibility with the conventional power stations, to

    provide voltage support. Modern wind power plants utilize doubly fed induction

    generators (DFIG) and, hence to integrate the micro/mini hydro and wind power

    plants in a micro grid scheme, parallel operation of the SG and the DFIG is required

    to be studied.

    Detailed dynamic model of the synchronous and induction generators, their prime

    movers viz. hydraulic turbine and wind turbine and exciter have been utilized. For the

    synchronous generators, conventional voltage and frequency controls have been

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    539

  • considered. However, a stator flux oriented vector control technique has been used to

    control the reactive power of the DFIG.

    In this paper, the stator and rotor currents are assumed entering the machine for

    motoring mode and outgoing from the machine for the generating mode. This

    assumption implies that the active and reactive powers are positive for the motoring

    mode and negative for the generating modes, respectively. The air gap of the

    induction machine is considered to be uniform and it is assumed that the stator and the

    rotor fluxes are sinusoidally distributed.

    Figure 1: Schematic of Conventional DFIG wind system

    Figure 2: Equivalent circuit of doubly fed induction generator

    2.1. Induction Machine Modeling In ABC Reference Frame

    In abc reference frame, the stator voltage equation, can be written as

    Vabcs = [Rs] iabcs + pΨabcs ------------- (1)

    The rotor voltage equation can be written as

    Vabcr = [Rs] iabcr + pΨabcr ------------ (2)

    In the above equations 1 and 2, the various vector quantities (denoted with

    underscore) are defined as following: Vabcs = [ Vas Vbs Vcs]T

    iabcs = [ ias ibs ics]T

    Vabcr = [ Var Vbr Vcr]T

    iabcr = [ iar ibr icr]T

    Ψabcs = [Ψas Ψbs Ψcs]T

    Ψabcr = [Ψar Ψbr Ψcr]T

    The stator flux linkages Ψ abcs = Ψ abcs(s) + Ψabcs(r) -------- (3) and the rotor flux

    linkages Ψ abcr = Ψ abcr(r) + Ψabcr(s) -------- (4)

    The stator and the rotor voltages can be written as following:

    Vabcs = [Rs]iabcs + p{[Lss]iabcs+ [Lsr]´ iabcr´} ---------------- (5)

    The superscript ´ denotes the rotor quantities referred to stator side.

    Vabcr = [Rs]iabcs + p{[Lrr]iabcr+ [Lsr]T iabcs}

    and the rotor voltage equation referred to the stator side is

    V’abcr = [Rr]´ iabcr´ + p{[Lrr]´ iabcr´ + [Lsr]´T iabcs} -------------------- (6)

    2.2. Vector Control of DFIG

    In this technique, there are two outer loops. If the DFIG is in isolated

    operation, these outer loops, viz. the stator voltage loop to produce flux current and

    the frequency loop to control generator speed. If the DFIG is connected to the power

    grid, its active and reactive powers are controlled in closed loop by producing

    reference flux and torque currents in vector control.

    Let us consider d-q model of the DFIG in synchronous co-ordinates.

    Aligning the system coordinates to stator flux seems most functional, as, at least for

    the grid operation Ψs = Ψds + jΨqs is almost constant, since the stator voltages are

    continual in amplitude, frequency and phase. This is the basic assumption in the

    “stator flux oriented vector control” technique. In this paper, it is assumed that the

    total stator flux is oriented along the d- axis and stator flux along the q-axis is zero.

    Therefore,

    Ψs = Ψds or pΨds=0, and Ψqs = pΨqs=0 ---------- (7)

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    540

  • Figure 3: Vector control of DFIG with PI controllers

    2.3. Exciter Modeling

    In principle, the reactive power output of a synchronous generator (SG) may be controlled

    through its terminal voltage control, which in turn, is performed through excitation (current or

    voltage control). The voltage control quality depends on the exciter dynamics and the SG

    parameters. The basic function of an excitation system is to supply controlled direct current to

    the field winding of the SG as the output varies within capability of the generator.

    Figure 4: IEEE type-I Exciter

    3. Prime Mover Modeling

    In this work, a micro grid consisting of micro hydro turbine driving

    synchronous generator and wind turbine driving induction generator have been

    considered. The models of these prime movers, used in this work, are given below.

    3.1 A First Order Ideal Model of Hydraulic Turbine

    The water velocity in the penstock u is given as

    u = Ku G √H ------------ (7)

    The turbine mechanical power Pm is written as,

    Pm = KpHU ------------- (8)

    Fig 5: A linear model of hydraulic turbine

    3.2. Hydro Turbine Control

    In an electric power system, consumers require uninterrupted power at rated

    frequency and voltage. To maintain these parameters within the prescribed limits,

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    541

  • controls are required on the system. Voltage is maintained through the excitation

    control of the generator and frequency is maintained by eliminating the mismatch

    between active power generation and demand. To maintain the constant frequency,

    governor is required for the generator.

    Fig 6: Block diagram of a micro hydro power plant

    3.3. Wind Turbine Modeling

    Uniformity and strength of the wind are dependent on location, wind mill

    height, and size of local terrain asymmetry. In general, wind air go along may be

    considered stormy. Wind speed increases with height and becomes more uniform.

    Designs with higher height/turbine diameter leads to more uniform flow and higher

    energy extraction. With constant energy conversion, the turbine power increases

    approximately in proportional with the cubic of the wind speed (u2) up to a design

    limit umax. Above umax (Prated), the power of the turbine is kept constant by

    governor control to avoid structural or mechanical over load.

    4. Parallel Operation of SG and DFIG

    The present thesis has explored the performance of the parallel operation of

    SG and DFIG, which will be useful in the integration of MHP and Wind power plants.

    A small micro grid was formed by considering an R-L load which supplied by the

    parallel system. A three phase, 250 kVA, 400 V, 50 Hz, 4-pole, salient pole type

    synchronous generator driven by micro-hydro turbine and a three phase, 160 kVA,

    400 V, 50 Hz, 4- pole wound rotor induction generator driven by wind turbine, are

    considered to form a micro grid. The procedure for the control of active and reactive

    power sharing, voltage and frequency control are explained in the following steps:

    1) As the DFIG is driven by the wind turbine, the active power generated by the DFIG

    is limited by wind speed and is not fully controlled. The wind turbine data is given in

    Appendix A and by using equation (4) and (5), the optimum power output of the wind

    turbine is calculated by assuming the wind speed of 10m/s. This optimum power

    output of the wind turbine sets the active power reference PS* for the DFIG.

    2) To maintain the power factor of the DFIG as unity, the reference reactive power

    QS* is taken as zero in the vector control reactive power loop. The actual reactive

    power is calculated and compared with QS*. The error is processed through the PI

    controller and the output of the PI controller will be idr*.

    3) Similarly, the actual active power output of the and compared with the reference

    active power PS* calculated from step (1) and error is being generated. This error is

    given to the PI controller and the output of this PI controller is iqr*.

    4) In practical system, the rotor currents iabcr can be measured by using current

    sensors and can be converted into idr and iqr by using Park’s transformation. Now, idr

    and iqr are compared with idr* and iqr*, respectively, which are generated by the

    outer power loops and thus, the errors are generated.

    5) The rotor current errors are given to the PI controllers and after adding the coupling

    terms one can obtain Vdr and Vqr. These Vdr and Vqr can be injected into the rotor

    of the DFIG with the help of PWM inverter. In this work, ideal power electronic

    inverter is assumed and modelled as current controlled voltage source. Hence, by

    using Park’s transformation, Vdr and Vqr are converted into three phase voltages and

    injected into the rotor circuit of the DFIG.

    6) The DFIG is supplying part of the active power demand and remaining active

    power to the load is supplied by the SG to keep the real power balance. To achieve

    this, (Pload - PDFIG) is given as reference to the servomotor (Fig 4.2) and it controls

    the SG to maintain the real power balance.

    7) The terminal voltage at PCC (point of common coupling) is maintained nearer to

    1pu with the IEEE type-I Exciter.

    8) In this paralleling scheme, the active power is being controlled from the

    synchronous generator side and the reactive power is being controlled from the DFIG

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    542

  • side without the use of any FACTS devices. Hence, the proposed control scheme is

    simpler and economic for the micro grids.

    5. Simulation Results and Discussions

    In this paper, parallel combination of SG and DFIG, considered as source of

    the generation and one R-L load have been considered to form a micro grid. A 3

    phase, 4-pole .50 Hz, 250 KVA 400V, wind turbine driven induction generator are

    considered in this work. The total generating capacity of the generators is 410KVA.

    A load of 307.5KVA (75% of the total generating capacity) is connected at the pcc

    (point of common coupling). A load power factor of 0.8 lag is considered.

    Hence, load KVA = (307.5 x 0.8) KW + j (307.5 x 0.6) KVAR

    = (246+j184.5) KVA

    Entire simulation work has been carried out using MATLAB/SIMULINK

    The gains of the PI controllers designed using 75% of loading for the test system

    5.1. Synchronous Generator Circuit and Results

    Fig.7. Synchronous Generator with Exciter System

    Fig.7. Speed and Voltage characteristics of SG

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    543

  • Fig.8 Voltage and current of SG

    Fig.9 Synchronous Generator Characteristics

    Fig.10. SG I_01 and V_01

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    544

  • 5.2. DFIG CIRCUIT AND RESULTS

    Fig.11. DFIG Exciter

    Fig.12. Double fed Induction Generator characteristics

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    545

  • References

    1. J. Liu, M. Yushi, T. Ise, J. Yoshizawa and K. Watanabe, "Parallel operation of a synchronous generator and a virtual synchronous generator under unbalanced loading

    condition in microgrids," 2016 IEEE 8th International Power Electronics and Motion

    Control Conference (IPEMC-ECCE Asia), Hefei, 2016, pp. 3741-3748. doi:

    10.1109/IPEMC.2016.7512894.

    2. ] E. Bogalecka, “Dynamics of the power control of double fed induction generator connected to the soft grid,” in Proc. IEEE Int. Symp. Ind. Electron., Budapest, 1993, pp.

    509-513.

    3. A.Tapia, G.Ostolaza and J.X. Saenz, “Modeling and control of a wind turbine driven doubly fed induction generator,” IEEE Energy Conversion, vol. 18, pp. 194–204, June.

    2003.

    4. Yazhou Lei, Alan Mullane, Gordon Lightbody, and Robert Yacamini, “Modeling of the Wind Turbine With a Doubly Fed Inducion Generator for Grid Integration Studies,” IEEE

    Energy Conversion, vol. 21, pp. 257–264, Mar. 2006.

    5. C. S. Demoulias and P. S. Dokopoulos, “Transient behaviour and self excitation of wind-driven induction generator after its disconnection from the power grid,” IEEE Energy

    Conversion, vol. 5, pp. 272–278, 1990.

    6. Pena,R.; Clare, J.C., Asher, G.M.: Doubly fed induction generator using back to back PWM converters and its application to variable-speed wind-energy generation. IEEProc. Electr.

    Power Appl. 1996, No.3. pp.231-240.

    7. Hofmann,W.; Thieme,A.; Dietrich,A. ; Stoev,A.: Design and Control of a Wind Power Station with Double fed Induction Generator EPE’97 Sept. 1997 pp. 2.723 - 2.728.

    8. V.Akhmatov, „Modelling of Variable Speed Wind Turbines with Doubly –Fed Induction Generators in Short Term Stability Analysis, Proceedings of the 3rd International

    Workshop on Transient Networks for Offshore Windfarms ,Stockholm,April 11-12,2012.

    9. Flores mendes V,De Souja C.V,Rocha Silva.S Cezal Rabalo “modeling and ride through control of Doubly Fed induction generator during symmetricak sags”,IEEE

    transactions on energy conversion ,dec 2011

    10. Slootweg J.G.,H.Polinder,W.L.Kling; Dynamic modeling of a wind turbine with doubly fed induction generator .Proceedings.2001 IEEE Power Engineering Society Summer

    Meating,IEEE Power Engineering Society,S.l.,2001,p.1-6.

    11. L. Congwei, W. Haiqing, S. Xudong, and L. Fahai, “Research of stability of double fed induction motor vector control system,” in Proc. of the Fifth International Conference on

    Electrical Machines and Systems, vol. 2, Shenyang, China, Aug., 18–20, 2001, pp. 1203–

    1206.

    12. A. Dittrich and A. Stoev, “Grid voltage fault proof doubly-fed induction generator system,” in Proc. Power Electronics and Applications (EPE), Toulouse, France, Sep. 2003.

    13. J. B. Ekanayake, L. Holdsworth, and N. Jenkins, “Comparison of 5th order and 3rd order machine models for doubly fed induction generator (DFIG) wind turbines,” Electric Power

    Systems Research, vol. 67, pp. 207–215, Dec. 2003.

    14. A. Feijoo, J. Cidr ´ as, and C. Carrillo, “A third order model for the doubly-fed induction machine,” Electric Power Systems Research, vol. 56, pp. 121–127, Nov. 2000.

    15. M. Heller and W. Schumacher, “Stability analysis of doubly-fed induction machines in stator flux reference frame,” in Proc. of 7th European Conference on Power Electronics and

    Applications, vol. 2, Brussels, Belgium, Sept., 8–10, 1997, pp. 707–710.

    International Journal of Applied Engineering Research ISSN 0973-4562 Volume 12, Number 1 (2017) © Research India Publications. http://www.ripublication.com

    546