Operation and Maintenance of AC Generator

Embed Size (px)

Citation preview

  • 7/28/2019 Operation and Maintenance of AC Generator

    1/31

    Operation and

    Maintenance of

    AC Generator

  • 7/28/2019 Operation and Maintenance of AC Generator

    2/31

    Maintenance

    To supply stabilized power, generatormust always be set at the condition of

    fully enabling the exhibition of its

    performance. In case of handling and

    maintaining the generator, its

    performance must be fully understood

    and the unexpected fault must be

    avoided by taking proper means ofmaintenance.

  • 7/28/2019 Operation and Maintenance of AC Generator

    3/31

    Maintenance

    The particular points that need to bepaid consistent attention are the

    following: - Isnt there any abnormality of the

    respective parts of generator itself?

    Isnt there any harmful matter in the

    surrounding atmosphere

  • 7/28/2019 Operation and Maintenance of AC Generator

    4/31

    When abundant dust is in presence in the windpassage, such dust will stick to coil and the dust

    will lead to the cause of short-circuit failure andgrounding failure. When the generator is startedafter a long time, since there may be chances oflowering the insulation resistance of coil, performthe drying thoroughly.

    please pay due attention by comparing thetemperature rise and vibration through the feelingobtained by touching your hand on the generator,and by sensing abnormal noise or odor.

    As for the confirmation of abnormal odor, pleaseconfirm it by opening the covers once in a while.

  • 7/28/2019 Operation and Maintenance of AC Generator

    5/31

    As for drying there are methods likeresorting to space heater and the method

    of permitting the flow of current directlythrough the coils.

    For either of the above two methods,please avoid over-heating locally as well

    as raising the temperature above 80C.Though inspection in details of the

    respective parts is carried out at the timeof trimming the generator, during dailyinspection, please inspect the machineby your sense as whether anyabnormality compared to previouscondition has arisen or not.

  • 7/28/2019 Operation and Maintenance of AC Generator

    6/31

    1.1 Periodical inspection

    To avoid failure in advance, it is

    indispensable to watch and inspect the

    generator at all times.

    By preparing checklist, please perform

    the inspection and trimming

    periodically. Hereunder, points that

    need to be paid attention especially dateof inspection and methods of inspection

    are given.

  • 7/28/2019 Operation and Maintenance of AC Generator

    7/31

    Respective tightening bolts

    and connecting location

    Inspection and maintenance within the extent

    considered possible must be performed once a year

    without taking out the rotor. In particular,

    inspection of stator winding and re tightening ofrespective bolts and nuts must be carried out.

    Tightening of set bolts must be done once after half

    a month from the date of commencing running and

    furthermore inspection and re tightening of these

    bolts must be done at the rate over 3 times withinone year thereafter.

  • 7/28/2019 Operation and Maintenance of AC Generator

    8/31

    BearingPrior to starting, always confirm the flow of lubricating

    oil by observing flow sight. After the starting ifbearing is overheated considerably within a shorttime or if abnormality of noise or odor is detected,there is the need of dismantling and inspection.

    The causes of overheating of bearing are given

    hereunder. Lubricating oil does not flow Use of filthy oil Deficient erection and coupling

    Defect of oil supply pipe is in presence and shortageof lubricating oil arises. Generation of rust or presence of scar on the journal

    part during the time generator is laid of. Deficient magnetic center.

  • 7/28/2019 Operation and Maintenance of AC Generator

    9/31

    1.2 Major requirement of

    inspection and maintenanceat respective time is tabulated

    in the following table: -

  • 7/28/2019 Operation and Maintenance of AC Generator

    10/31

    Item

    Item

    Place of

    inspection

    Daily

    inspection

    (during

    running)

    Monthly

    inspection

    (during

    stop)

    Annual

    inspection

    1.Static part

    1.Noise

    2.Temperatu

    re

    3.Vibration

    1.Insulation

    Resistance.

    2.Air gap

    3.Cleaning

    1.Maintenance of

    winding.

    2.Maintenance of

    core

    Parts.

    3.Inspection oflead wires.

    4.Inspection of

    bolt and

    Nuts.

    2.Rotating

    part1.Noise

    1.Inspectio

    n

    resistance.

    1.Loosening of

    spigot fitting part

    and balanceweight.

    2.Contact with

    static part.

    3.Inspection of

    lead wires.

    4.Retightening ofbolts and nuts.

  • 7/28/2019 Operation and Maintenance of AC Generator

    11/31

    3.Bearingpart

    1.Noise

    2.Tempera

    ture

    3.Vibratio

    nLubricatin

    g

    condition.(

    oil leak, oilquantity)

    1.Oil leak2.Cleanin

    g

    1.Examinatio

    n of

    Impairment

    of journal.

    2. Wear of

    journal

    3. Magnetic

    center

    4.

    Others

    1.Odour

    2.Abnorm

    al noise

  • 7/28/2019 Operation and Maintenance of AC Generator

    12/31

    1.2(1). WINDING AND

    INSULATION RESISTANCE

    1.2(a) Measurement of InsulationResistance

    Insulation resistance is the resistance against

    leakage current that flows in the interior and on thesurface of insulation when certain value of D.C.voltage is imposed. In case the generator is installedat a place where high humidity exists or when thegenerator is kept idle over a long period of time,

    generally the insulation resistance drops due todeposit of moisture on the insulation surface.Therefore insulation resistance should be measuredprior to running of the generator.

  • 7/28/2019 Operation and Maintenance of AC Generator

    13/31

    Measurement of insulation resistance indicates theinsulated condition of the equipment in a verysimple way. However, the value of insulation

    resistance measured indicates the condition ofinsulation deterioration. Measurement is essential before running the

    generator. Although the measured value indicatesthe absolute value corresponding to the condition ofinsulation at the instant of measurement, acomparative value has more significance. It isessential to measure periodically and to check incomparison the condition of change with referenceto earlier measured values.

    Although the insulation resistance increases withtime after the imposition of D.C. voltage the valuethat settles down to a constant should be registered.In case the insulation resistance increases graduallylittle by little this insulation resistance value isindicated by 30 seconds value or 1-minute value.

    Si h i l i i h l

  • 7/28/2019 Operation and Maintenance of AC Generator

    14/31

    Since the insulation resistance has a closerelationship with the temperature of insulation, whenmeasuring insulation resistance, it is always requiredto measure temperature of insulation at that time andrecord this temperature along with the insulation

    resistance. It serves convenient for maintenancepurposes if the relationship between the insulationresistance value and winding temperature at clean anddry condition of winding is available. Generally, theinsulation resistance value drops rapidly together with

    the rise of temperature and the relationship betweenthe logarithm of insulation resistance value andtemperature changes as straight line approximately inthe temperature range of usage.

    Insulation resistance value differs from the process by

    the insulation composition of equipment and thetemperature rise. There are generally three types ofclassification as given below.

    1. Initially the insulation resistance drops at once andthen starts rising as the drying effect progresses. This

    is most generally seen.

  • 7/28/2019 Operation and Maintenance of AC Generator

    15/31

    2. In case the absorbed moisture on the surface issignificant first the insulation resistance rises by thedrying effect and thereafter follows the sameprocess as (1).

    3. In the case of drying on site the equipment thathas absorbed moisture excessively and/or large sizemachines, this type of characteristic is frequentlyexperienced. In the case of equipment that hasabsorbed moisture excessively, since the amount ofmoisture absorbed is large, the insulationcharacteristic is to be absorbed before the dryingeffect appears. In the case of large size machines along time is required for the temperature rise ofequipment and the drop portion due to insulationcharacteristic offsets the rise portion due to drying

    effect. In both the above cases, a fairly low value forthe measured insulation resistance by meggershould continue without change. About 3 full days(days and nights) may be required to reach therising point

  • 7/28/2019 Operation and Maintenance of AC Generator

    16/31

    NOTE: -At the time of measuring insulation

    resistance, attention should be paid to the following

    points: If rotating type megger is used, rotating it for one-

    minute at least should do measurement.

    If battery driven megger is used, error increases as

    the battery voltage drops.

    Prior to measurement, residual electric charge of

    winding should be removed. To exclude the effect of connected auxiliary devices,

    other circuits should be disconnected at an easy

    convenient part and then measurement should be

    done.

    After the measurement the residual charges should

    be discharged.

  • 7/28/2019 Operation and Maintenance of AC Generator

    17/31

    1.2 (b) Insulation Resistance (IR) values

    required for Running

    The minimum permissible insulation resistancevalue changes extensively by the type, rating,dimension and insulation method of generator. Ageneral value cannot be determined. However, thefollowing guideline can be approximately used when

    the windings are at normal temperature, forpermitting normal running.

    Greater than 1 Meg-Ohm for low voltage statorwinding and the field winding.

    Greater than 5 Meg-Ohm for 3.3kV and 6.6kV statorwindings.

    Greater than 10 Meg-Ohm for 11kV stator windings.

  • 7/28/2019 Operation and Maintenance of AC Generator

    18/31

    Alternatively, the following formula may be used for the

    minimum insulation resistance value:

    Rated Voltage (V)

    __________________________________

    Rated Output (kW or KVA + 1000)

    Rated Voltage (V)+1/3(rpm)

    ___________________________________________Rated Output (kW or KVA)+2000+0.5M-ohm

  • 7/28/2019 Operation and Maintenance of AC Generator

    19/31

    1.2(c) Prevention of IR Drop It is desirable to run the generator with its winding

    condition always set clean and dry. Dust deposited

    on the winding surface prevents heat dissipationand becomes the cause of deterioration dependenton its kind. Also, the intrusion of moisture into theinterior forms the cracks on insulation leads to thedrop of insulation resistance. Therefore, daily

    attention to cleaning and prevention againstmoisture absorption leads to prevention of IR dropespecially for exciter, which is open type. Althoughgenerators interior presents dry condition duringrunning, there may be moisture absorption duringstoppage of generator at times of high humidity suchas rainy season. To prevent such situations, it isrequired to put-on the space heater immediatelyafter stopping the generator and to raise thetemperature of generator interior higher than theambient temperature.

  • 7/28/2019 Operation and Maintenance of AC Generator

    20/31

    1.2(d) Cleaning Method of Winding

    Dust accumulated on the insulation reduces theventilation area and the cooling effect. This may

    result in over-heating of the generator. Even though

    the accumulated dust is not conductive by itself, it

    absorbs moisture and becomes conductive thereby

    causing short circuit of winding and ground fault.Therefore, it is essential to keep the winding always

    in a clean condition. Any of the following methods

    may be used for cleaning the windings.

  • 7/28/2019 Operation and Maintenance of AC Generator

    21/31

    1.2(e)Wiping with cloth:

    This method is especially effective for cleaning the

    local parts where the contamination is severe. Dryand clean cloth from which thread pieces do not

    come out should be used. Attention should be paid

    as not to impair the insulation by rubbing strongly.

  • 7/28/2019 Operation and Maintenance of AC Generator

    22/31

    1.3 FAULT DIAGNOSIS

    CHART tabulated in thefollowing table: -

  • 7/28/2019 Operation and Maintenance of AC Generator

    23/31

    FAULTS POSSIBLE CAUSE REMEDY

    EXCITATION CURRENT VARRYING,

    INDIVIDUAL WINDING SECTION

    OVERHEAT

    OVER LOAD REDUCE LOADING

    EXCITATION CURRENT VARRYING,

    INDIVIDUAL WINDING SECTION

    OVERHEAT, HUMM DURING START

    UP/RUNNING, RADIAL

    OSCILLATIONS

    ONE SUPPLY PHASE OPEN

    CIRCUITED, ONE SUPPLY

    PHASE OPEN CIRCUIT AFTER

    SWITCH ON, OPEN CIRCUIT IN

    FIELD CIRCUIT

    CHECK SWITCHGEAR & SUPPLY

    CIRCUIT

  • 7/28/2019 Operation and Maintenance of AC Generator

    24/31

    FAULTS POSSIBLE CAUSE REMEDY

    EXCITATION CURRENT VARRYING

    ,HUMM DURING START

    UP/RUNNING, RADIAL

    OSCILLATIONS

    STATOR WINDING

    INCORRECTLY CONNECTED

    CHECK WINDING

    CONNECTIONS

    EXCITATION CURRENT VARRYING

    ,HUMM DURING STARTUP/RUNNING, RADIAL

    OSCILLATIONS

    INTERTURN SHORT CIRCUIT INSTATOR WINDING

    DISCONNECT M/CS, FEEL

    SURFACE OF ENDTURNS &CHECK TEMP. RISE.REMOVE

    SHORT CIRCUIT.

  • 7/28/2019 Operation and Maintenance of AC Generator

    25/31

    FAULTS POSSIBLE CAUSE REMEDY

    EXCITATION CURRENT VARYING,

    AXIAL OSCILLATIONS

    INTERTURN SHORT CIRCUIT IN

    FIELD WINDING

    CHECK TEMP RISE.

    DISCOLOURED VARNISH MAY

    BE A HINT.REMOVE SHORT

    CIRCUIT. CHECK AIR GAP &

    REALIGN AVOID NARROW

    GAPS OR SHARP CORNERS

    SCREECHING NOISE

    ROTOR CORE RUBBING

    AGAINST STATOR

    CORE.WINDAGE NOISE,

    SMALL GAPS OR SHARP

    CORNERS IN AIR CIRCUIT

    GRINDING NOISEROTATING PARTS RUB AGAINST

    STATOR PARTS

    REALIGN M/C, CHECK

    RUBBING NOISE.

  • 7/28/2019 Operation and Maintenance of AC Generator

    26/31

  • 7/28/2019 Operation and Maintenance of AC Generator

    27/31

    FAULTS POSSIBLE CAUSE REMEDY

    BEARING OVERHEATS

    OIL AGED OR

    CONTAMINATED, HIGH

    VISCOCITY

    CLEAN BEARING HOUSING,

    RENEW OIL, CHECK VISCOCITY

    BEARING OVERHEATS, BEARING

    TEMP VARRIES OR RISES ABRUPTLY

    WITHOUT EXTERNALLY TRACEABLECAUSE

    LOW OIL LEVEL, OIL RING OUT

    OF TRUE, ROTATES

    IRREGULARLY OR STALLESPECIALLY AT LOW SPEEDS

    CHECK OIL LEVEL & TOP UP, IF

    NECESSARY, CHECK OIL RINGS

    FOR ROUNDNESS, REALIGN &

    STRAIGHTEN OR EVEN REPLACE

    THEM

    OIL BLACKENS PREMATURELY OR

    CONTAINS ABRADED MATTER

    VISCOCITY OF OIL TOO LOWCHECK VISCOCITY, CHANGE

    OIL IF LOW

    BEARING LOSS OIL

    OIL VISCOCITY TOO HIGH DUE

    TO LOW OIL TEMP,

    ESPECIALLY DURING START UP

    HEAT BEARINGS OR OIL

    DURING OR PRIOR TO STARTUP

  • 7/28/2019 Operation and Maintenance of AC Generator

    28/31

    FAULTS POSSIBLE CAUSE REMEDY

    BEARING LOSS OIL, OIL DRAWN

    INTO MACHINE

    OIL FOAMS

    INSPECT BEARING VENT, USE

    DIFFERENT OIL TYPE AFTER

    ENQUIRING WITH SUPPLIER. USEANTIFOAM ADDITIVE

    BEARING OVERHEATS, BEARING

    TEMP VARRIES OR RISES ABRUPTLY

    WITHOUT EXTERNALLY TRACEABLE

    CAUSE.

    FORCED LUBRICATION FAILS.

    OIL OR COOLING WATER

    FAILURE

    INSPECT OIL SUPPLY SYSTEM,

    REMOVE DISTURBANCES

    OIL DRAWN INTO MACHINE

    OIL PRESSURE OF FORCED

    LUBRICATION SYSTEM TOO

    HIGH, MORE THAN 0.5 BAR

    REDUCE OIL PRESSURE, INSTALL

    PRESSURE REDUCING VALVE

    BEARING LOSES OILFORCED LUBRICATED

    BEARING FLODDED

    ADJUST CORRECT OIL

    RATE.CHECK OIL DISCHARGE

    FOR OBSTRUCTION. CHECK OIL

    LEVEL IN BEARINGS

  • 7/28/2019 Operation and Maintenance of AC Generator

    29/31

    FAULTS POSSIBLE CAUSE REMEDY

    BEARING OVERHEATS, BEARING

    TEMP VARRIES OR RISES ABRUPTLY

    WITHOUT EXTERNALLY TRACEABLECAUSE, OIL BLACKENS

    PREMATURELY OR CONTAINS

    ABRADED MATTER

    RESIDUAL OIL PRESSURE OF

    BEARINGS WITH JACKING OIL

    ARRANGEMENT DROPS

    DURING OPERATION WITH

    JACKING INOPERATIVE

    CHECK OIL PRESSURE PIPING &

    NON RETURN VALVE, CHECK

    BEARING SHELLS FOR

    CANTING. REMEDY

    DISTURBANCES

    BEARING OVERHEATS

    EXCESSIVE AXIAL THRUST,

    THRUST FROM COUPLING

    EXCESSIVE RADIAL LOAD,

    INADEQUATE RADIAL PLAY

    INSPECT FOR MAGNETIC

    CENTRE. CHECK

    ALIGNMENT.REALIGN

    BEARINGS

    AND/MACHINE.REREAM

    BEARING SHELLS.

    OIL BLACKENS PREMATURELY OR

    CONTAINS ABRADED MATTEREXCESSIVE RADIAL PLAY

    CHANGE OIL AFTER

    CONSULTATION WITH

    SUPPLIER,USE OIL WITH HIGH

    VISCOCITY

  • 7/28/2019 Operation and Maintenance of AC Generator

    30/31

    FAULTS POSSIBLE CAUSE REMEDY

    BEARING LOSES OIL

    OIL RETURN OPENING IN OR

    UNDER LOWER SEALING

    RINGHALF CLOGGED

    CLEAN OIL RETURN OPENINGS

    BEARING OVERHEATS, BEARING

    TEMP VARRIES OR RISES ABRUPTLY

    WITHOUT EXTERNALLY TRACEABLE

    CAUSE, OIL BLACKENS

    PREMATURELY OR CONTAINS

    ABRADED MATTER

    DAMAGE TO BEARING

    LINING. DEFECTIVE BOND

    BETWEEN LINING &

    SUPPORTING BLOCK OF

    BEARING SHELL

    INSPECT BOND. REPLACE

    LINING.(ENSURE CORRECT

    SHAPE OF OIL POCKETS & OIL

    GROOVES)

    BEARING OVERHEATS

    TOO SMALL OIL PACKETS,

    TRANSITION TO BEARING

    SURFACENOT SMOOTH

    ENOUGH

    REFINISH OIL POCKETS

    BEARING LOSES OIL, OIL DRAWN

    INTO MACHINE

    SEALING RINGS DEFECTIVE.

    GAP BETWEEN SHAFT AND

    SEALING RING TOO LARGE.

    REFINISH OIL RINGS

  • 7/28/2019 Operation and Maintenance of AC Generator

    31/31

    FAULTS POSSIBLE CAUSE REMEDY

    BEARING OVERHEATS, BEARINGTEMP VARRIES OR RISES ABRUPTLY

    WITHOUT EXTERNALLY TRACEABLE

    CAUSE, OIL BLACKENS

    PREMATURELY OR CONTAINS

    ABRADED MATTER

    BEARING CURRENTSINSPECT BEARING INSULATION&

    REPLACE IF NECESSARY.

    ENCLOSURES VIBRATE

    SHOCKS TRANSMITTED FROM

    COUPLED MACHINE

    RESONANCES, INSUFFICIENT

    RIGIDITY

    CHECK COUPLED MACHINE.

    OBTAIN INSTRUCTIONS FROM

    SUPPLIER, REINFORCE

    ENCLOSURE