4
Also available in three phase with Motor Control Center (MCC). Separate spec sheets are available for these configurations. The three phase P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as clean water and wastewater treatment, mining, process control, power and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide. The XMCC Series is a 3 Phase electric actuator with the same rugged industrial features ProMation is known for: Clutchless Manual Override Easy to see raised position indicator Ruggedboard internal soldered connections NEMA 4X enclosures The XMCC Series features a polyphase motor and is designed for use with your existing 3 phase motor control center (phase monitoring and motor control must be provided in any 3 phase installation). Product Notes: 1. The 3 Phase P Series can be ordered as an on/off (two position) model that can also be used in bump/jog applications. 2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control signals, generates multiple feedback signals, and has look-ahead fault prevention. 3. Care must be taken during installation to make sure local phasing is correct for this actuator. SD15_P213_XMCC Ver D_050515 Page 1 of 4 P2/3 XMCC Series Product is shipped at MID-STROKE position to allow up to 6 seconds run time after power up to determine if the actuator is running in the correct direction. If it is not, immediately remove power to avoid possible damage to the actuator end stops. Actuator Specifications P2 P3 Torque “lb/Nm 800”lbs/90Nm 1335“lbs/150Nm Supply Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60 Max Inrush Current 1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9A Running Current 0.8A 0.4A 0.4A 0.4A 0.8A 0.4A 0.4A 0.4A Motor Polyphase Runtime (90°@60Hz/vdc) 15 sec 22 sec Runtime (90°@50Hz) 17 sec 26 sec Duty Cycle On/Off/Jog: 25%, Proportional: Managed (75% maximum) Motor Starts 1200 per hour Weight 26lbs/12kg Mechanical Connections ISO5211 F07 8pt 22mm Electrical Entry (2) 3/4” NPT Electrical Terminations 12-16ga Environmental Rating NEMA 4/4X Manual Override 5” Handwheel Control On/Off/Jog / Proportional Actuator Case Material Aluminum Alloy, Powder coated Motor Protection 230°F/110°C Thermal F* Class *Totally Enclosed Non-Ventilated Motors Ambient Temperature Operating Range -22°F to +125°F -30°C to +52°C Data Sheet P2/3 3 Phase XMCC On/Off/Jog/Proportional ISO5211 F07 8P22

P2/3 XMCC N4 Data Sheet P2/3 3 Phase XMCC · Dime n soal tf rP2~ 3 Ac u E ng i er Cha Notc Change Date Descrip tion Name A B ... Actuator Specifi cations P2 P3 Torque “lb/Nm 800”lbs/90Nm

  • Upload
    lyquynh

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Also available in three phase with Motor Control Center (MCC). Separate spec sheets are available for these configurations.

The three phase P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as clean water and wastewater treatment, mining, process control, power and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide.The XMCC Series is a 3 Phase electric actuator with the same rugged industrial features ProMation is known for:

• Clutchless Manual Override • Easy to see raised position indicator • Ruggedboard internal soldered connections • NEMA 4X enclosures

The XMCC Series features a polyphase motor and is designed for use with your existing 3 phase motor control center (phase monitoring and motor control must be provided in any 3 phase installation).

Product Notes:1. The 3 Phase P Series can be ordered as an on/off (two position) model that can also be used in bump/jog applications.2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control

signals, generates multiple feedback signals, and has look-ahead fault prevention. 3. Care must be taken during installation to make sure local phasing is correct for this actuator.

SD

15_P213_X

MC

C Ver D

_050515

Page 1 of 4 P2/3 XMCC Series

Product is shipped at MID-STROKE position to allow up to 6 seconds run time after power up to determine if the actuator is running in the correct direction. If it is not, immediately remove power to avoid possible damage to the actuator end stops.

P2/3 XMCC N4

Wire Sizing Chart

ActuatorSpecifications P2 P3Torque “lb/Nm 800”lbs/90Nm 1335“lbs/150NmSupply Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60Max Inrush Current 1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9ARunning Current 0.8A 0.4A 0.4A 0.4A 0.8A 0.4A 0.4A 0.4AMotor PolyphaseRuntime (90°@60Hz/vdc) 15 sec 22 secRuntime (90°@50Hz) 17 sec 26 secDuty Cycle On/Off/Jog: 25%, Proportional: Managed (75% maximum)Motor Starts 1200 per hourWeight 26lbs/12kgMechanical Connections ISO5211 F07 8pt 22mmElectrical Entry (2) 3/4” NPT Electrical Terminations 12-16gaEnvironmental Rating NEMA 4/4X Manual Override 5” HandwheelControl On/Off/Jog / ProportionalActuator Case Material Aluminum Alloy, Powder coated

Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors

Ambient Temperature Operating Range

-22°F to +125°F-30°C to +52°C

Data Sheet

P2/3 3 Phase XMCCOn/Off/Jog/Proportional

ISO5211 F07 8P22

P Series Exploded View

Easily distinguishable yellow/red position

indicator

Worm Drive

Heavy Duty Drive Motor

Easily accessible switch &

cam stacks

Modular ControlCards

Clutchless OverrideHandwheel

Aluminum Casting4X Protection

Mechanical Stop Screws (2)

Epicyclic Gearing

Aluminum Casting4X Protection

NEMA 4Cover Seal

(Typical)

Application Notes:1. These actuators are to be mounted ONLY between a horizontal and upright position.2. When installing conduit, use proper techniques for entry into the actuator. Use drip loops to prevent

conduit condensate from entering the actuator. 3. Both NPT conduit ports MUST use proper equipment to protect the NEMA 4X integrity of the housing. 4. The anti-condensate heater is to be used in ALL applications. 5. Do not install or store the actuator outdoors or in humid environments without power to the heater.6. Use proper wire size to prevent actuator failure (see wire sizing chart). 7. Mechanical travel stops exist to prevent over-rotation for manual override only. They are not intended

to stop motor driven rotation.8. Do not parallel wire multiple actuators together without utilizing isolation relays! If this is your

intention, please contact ProMation Engineering for a multiple actuator parallel wiring diagram.

Switch Logic Map and Switch/Cam Arrangement

Term

inal

ID#

12

11

10

9

8

7

-5° 0°CW CCW

85°5° 90° 95°

SW3 CCW AUX(Factory Set - Adj)

SW4 CW AUX(Factory Set - Adj)}

}Closed Common

Open Common

}Used by Controller

Open

Not Closed

Closed

Not Open

Switch sequencing data is provided in the table below to show the change-of-state points during the rotation of the actuator from OPEN to CLOSED and back again. The red bar indicates when that terminal makes with it’s respective common.

SW1 and SW2 are set at the factory and should NOT be changed. The INCLUDED auxiliary switches SW3 & SW4 are forterminals7thru12andthosesetpointsmaybemodifiedifneed be. When so optioned, SW5 & SW6 auxiliary switches are initially set to function the same as auxiliary switches SW3 & SW4.

On/Off Switch/Cam arrangement shown

SD

15_P

213_

XM

CC

Ver

D_0

5051

5

Page 2 of 4 P2/3 XMCC Series

P2/3 Series Dimensional Data1

1

2

2

A A

B B

Drawn By

Finish

Promation Engineering Inc.16138 Flight Path Drive

Brooksville, Fl 34604Phone: 352-544-8436Fax: 352-544-8439

This Document is the property of ProMation Engineering,Inc. Distribution of this document without the written

consent of the owner is Strictly forbidden. Failure to comply will incur a liability for Damages.

Checked By4/8/2015

P2~P3 Dim Data Rev.

G

NO SCALE Sheet Number: 1

Material

ProMation Engineering, Inc.KHL

KHL

4/25/2013

P2_3 F07 8P22 DimData.idw

Created:

Last Checked:

Part No.

Dwg. Name

Dimensional Data for P2~P3 Actuators

Engineering Change NoticeChange Date Description Name

04.25.13 Document transferred to Inventor format KHL

11.12.13 Added rounded edges on Drive Coupling Data KHL

04.15.2014 Added tolerance on drive coupling data KHL

10.07.2014 Pushed square dimension to three decimal places KHL

REV

A

B

C

D

E

F

Dimensional Tolerances (Unless Otherwise Noted):X ± 2.5mm [X.X ± .1]

X.X ± .3mm [X.XX ± .01"]X.XX ± .13mm [X.XXX ± .005"]

ALL TOLERANCE FEATURES IN mm

G 04.08.2015 Added Isometric view of Drive Coupling and "Depth" tag for clarity KHL

H

Drive Coupling Fabrication Data

22.00 - .13.00+ mm

0.866 - 0.0050.000+ in

22.00 - .13.00+ mm

0.866 - 0.0050.000+ in

30.00 mm1.181 inDepth

30.00 mm1.181 in

229 mm9.0 in

324 mm12.8 in

211 mm8.3 in

123 mm4.8 in

180 mm7.1 in

90 mm3.5 in

287 mm11.3 in

Add 257mm

[10.1"] to allowfor coverremoval

70 mm2.8 inBHC

22 mm0.9 in

(4) M8x1.25

20mm0.8"

F07 ISO Flange

(2) 3/4" NPTEMT Entry

125 mm4.9 in

86 mm3.4 in

Existing Switchgear

Existing Switchgear

Wire sizing data is provided in the table below to assist in the selection of the proper wire size for these actuators using various wire sizes over distance.

Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each model.

• Field Control Device may be relay contact, Switch or Triac type.

• Pilot device 10A MAX. Auxiliary switches are rated 10A @ 250vac MAX.

• Terminals 7-12 are dry type Form C.

• Terminals accept 12-16ga solid/stranded wire.

SAMPLE DIAGRAMSRefer to the proper IOM for your actuator for the correct wiring diagram or visit www.promationei.com.

On/Off/Jog Control

Proportional Control

• See page 4 for Control Input/Outputs

• Pilot device 10A MAX. Auxiliary switches are rated 10A @ 250vac MAX.

• Terminals 7-12 are dry type Form C.

• Terminals accept 12-16ga solid/stranded wire.

Product is shipped at MID-STROKE position to allow up to 6 seconds run time after power up to determine if the actuator is running in the correct direction. If it is not, immediately remove power to avoid possible damage to the actuator end stops.

SD

15_P213_X

MC

C Ver D

_050515

Page 3 of 4 P2/3 XMCC Series

NOT OPEN*

OPEN COM*

OPEN*

NOT CLOSED*

CLOSED COM*

CLOSED*

C

B

12

11

10

9

8

7

LINE IN

480/3Ø

* CONNECTIONSOPTIONAL

GND Screw

GND

6

5

4

3

2

1

GRN

SW3

SW4

AUXILIARYSWITCH

(STANDARD)

ALL SWITCHESSHOWN WITHACTUATOR IN

FULL OPENPOSITION

AUXILIARYSWITCH

(STANDARD)

E1E2

Actuator ships in Mid-Stroke position!

J1

HEATER

SW2

SW1

J2

E1E2J3

112

43

Items within dotted line locatedinside actuator housing

430-10100 Switch Card

SW1

SW2

SW3

SW4

Switch StackDetail

A

5 6

21 22

3 4

1 2

A1 A2MC1

MC2

ØA

ØB

ØC NO

C

NC

REV Ø RELAY

120VAC COIL

120VAC COIL

5 6

21 22

3 4

1 2

A1 A2

ABCDEF WHT

BLU

RED

Correct Phase errors within 6 sec after power-up.

Supplied by others

410-50100TL25-1800

Heater is 25W120V

120vac Control ONLY

M410-92383380V/3Ø

WHT

WHT

WHT

120VAC

380VAC

T1 380/120

FB OUT

INSignal OUT+

Signal IN+

430-10102Controller

Signal COMCOM

A

P2/3-483PN4-XMCCUse For:

WD

-85

0-2

82

42

P2/3 XMCC N4

MAX distance between Actuator and Supply (feet)

Actuator P2 P3Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60

1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9A

16 1701 3401 5291 5772 1701 3401 5291 577214 2747 5495 8547 9324 2747 5495 8547 932412 4202 8403 13072 14260 4202 8403 13072 1426010 7143 14286 22222 24242 7143 14286 22222 242428 10661 21322 33167 36183 10661 21322 33167 36183

WireGage

Amps

Wire Sizing Chart

ActuatorSpecifications P2 P3Torque “lb/Nm 800”lbs/90Nm 1335“lbs/150NmSupply Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60Max Inrush Current 1.4A 0.7A 0.9A 0.9A 1.4A 0.7A 0.9A 0.9ARunning Current 0.8A 0.4A 0.4A 0.4A 0.8A 0.4A 0.4A 0.4AMotor PolyphaseRuntime (90°@60Hz/vdc) 15 sec 22 secRuntime (90°@50Hz) 17 sec 26 secDuty Cycle 25%Motor Starts 1200 per hourWeight 26lbs/12kgMechanical Connections ISO5211 F07 8pt 22mmElectrical Entry (2) 3/4” NPT Electrical Terminations 12-16gaEnvironmental Rating NEMA 4/4X Manual Override 5” HandwheelControl On/Off/JogActuator Case Material Aluminum Alloy, Powder coated

Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors

Ambient Temperature Operating Range

-22°F to +125°F-30°C to +52°C

Wiring Diagrams for P2/3 Series

NOT OPEN*

OPEN COM*

OPEN*

NOT CLOSED*

CLOSED COM*

CLOSED*

RUN CW

RUN CCW

C

B

12

11

10

9

8

7

LINE IN

230/3Ø

* CONNECTIONSOPTIONAL

FIELDCONTROL

DEVICE

GND Screw

GND

6

5

4

3

2

1

GRN

SW3

SW4

AUXILIARYSWITCH

(STANDARD)

ALL SWITCHESSHOWN WITHACTUATOR IN

FULL OPENPOSITION

AUXILIARYSWITCH

(STANDARD)

E1E2

Actuator ships in Mid-Stroke position!

J1

HEATER

SW2

SW1

J2

E1E2J3

112

43

Items within dotted line locatedinside actuator housing

430-10100 Switch Card

SW1

SW2

SW3

SW4

Switch StackDetail

A

5 6

21 22

3 4

1 2

A1 A2MC1

MC2

ØA

ØB

ØC NO

C

NC

120VAC

230VAC

REV Ø RELAY

T1 230/120

120VAC COIL

120VAC COIL

5 6

21 22

3 4

1 2

A1 A2

ABCDEF WHT

BLU

RED

Correct Phase errors within 6 sec after power-up.

Supplied by others

410-50100TL25-1800

Heater is 25W120V

120vac Control ONLY

M410-92233230V/3Ø

BRN

BLU

BLK

P2/3-233N4-XMCC

B

Use For:

WD

-85

0-2

61

42

Use your smart phone barcode scanner app here.

16138 Flight Path Drive Brooksville, FL 34604

Phone (352) 544-8436 Fax (352) 544-8439email: [email protected]

ProMation Engineering follows a policy of continual product updates and enhancements. Our website is the best place to obtain the latest product documentation, including the wiring diagrams for these controllers. Visit us at www.promationei.com or use the QR code below to link to the site.

ProMation Product Line

PL SeriesLinear Drive

Up to 4400lbs down/up force.

P SeriesNon-Spring Return

55”lbs through 40,000”lbs.

PA~PD Series Spring Return

445”lbs through 2300”lbs.

PBU Battery Back-Up Systems

Provides battery power to drive open

The Premium controller offers a full array of features - such as various control and feedback signals, alphanumeric readout, several fault indicators for operational diagnostics,

Control Signal Inputs(selectable using program menu):0-10vdc, 1-5vdc, 2-10vdc, 4-20mA

Factory set with common isolated from ground. Ground reference is possible.

ProMation Premium Controller:

Signal Input Impedance Sensitivity

0-10vdc 140k ohms 50mV

1-5vdc 250k ohms 20mV

2-10vdc 140k ohms 40mV

4-20mA 250 ohms 80µA

Feedback Signal Output (Can be different than input): 0-10vdc, 1-5vdc, 2-10vdc, 4-20mA

Max Load: 250 ohms

extensive data logging that provides full proportional control for all industrial applications. ModBus communications are also an option on this controller.

Full Proportional Control Featuring:• Autocalibration• Programmable• High resolution• Alarm Outputs• Data logging• Simple User Interface• Field Selection Friendly• Thermal Management

Auxi l iary Signal Output (programmable):A larm Contacts a l low for signaling of 5 different fault conditions. 2 Position ControlContacts and capability for 2 position (only) override of the actuator.

Proportional Control

• Premium Proportional Controller Option. Converts 2 position to proportional control.• Mechanical Torque Switch Assembly• IP68 Protection, tested to 0.7kgf/cm2 for 72 hours. P2~P8 only.• 1k ohm position feedback potentiometer.• 5k ohm position feedback potentiometer.• 10k ohm position feedback potentiometer.• 4-20mA feedback generator for On/Off/Jog actuators.• Auxiliary Switch set. Provides 3rd and 4th auxiliary switches (Form C x 2).• Integral Thermostat for Heater Control - turns on at 32°F, turns off at 50°F.• Cold weather auxiliary heater option. Thermostatically controlled, On 32°F, Off

at 50°F, auto reset, hermetically sealed, 120/230vac On/Off/Jog type actuators. 175W Internal Heater, 2A power consumption.

• Chain wheel override for applications where an actuator is mounted some distancefromthefloor.(UsewithLCS).

• Epoxy coating for increased environmental protection.• Nylon coating for increased environmental protection.• Stainless Steel actuator enclosure. P2~P6 Only.

Cold Weather Heater Option keeps your actuator operational in cold weather applications. Automatically compensates internal temperatures in response to severe external conditions.

AVAILABLE OPTIONS (Factory Installed)

SD

15_P

213_

XM

CC

Ver

D_0

5051

5

Page 4 of 4 P2/3 XMCC Series