OZW772 V3 Energy Consumption Allocation. Synco Web Server V3 Topology. KNX devices with consumption data: QAX913 → collects up to 20 meters Synco 700 controller → collects 2…4 meters Web server OZW772… → collects up to 512 meters. Apartment A. KNX RF. Pulse meter. Pulse meter. - PowerPoint PPT Presentation
Citation preview
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 2/23 Building Technologies
Synco Web Server V3Topology
KNX devices with consumption data:
QAX913 → collects up to 20 meters
Synco 700 controller → collects
2…4 meters Web server
OZW772… → collects up to
512 meters
KNX RF
KNX TP1
M-bus meter
M-bus meter
M-bus meter
Pulsemeter
Pulsemeter
Apartment A
Apartment B
Basement
Pulsemeter
Pulsemeter
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 3/23 Building Technologies
Synco Web Server OZW772… Version 3
Main Feature
Energy consumption allocation
Other Features
New devise OZW772.250 replaces OZW772.64
https encryption
E-mail with TLS -encryption
User defined Logos
System definition update
Schedule
Market Release January 2011
On stock mid of February 2011
Logistics
Prices unchanged
OZW772.250 for the price of the .64
OZW772.64 will be sold out in April
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 4/23 Building Technologies
Meter Data flow
KNX RFKNX TP1
M-bus Meter
Pulsemeter
M-bus
Pulse
M-bus meter readings are periodically queried by the WRI982
Consumption data of meters are periodically queried by the QAX9x3
Pulses are constantly counted by the WRI982
Consumption data are periodically queried by the OZW772
www
The file with the consumption data is sent periodically via E-mail or can be downloaded via Web Browser
Pulsemeter
Pulsemeter
Pulses are constantly counted by the Synco 700 controller
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 5/23 Building Technologies
Timing of the Meter Data flow
KNX RFKNX TP1
M-bus Meter
Pulsemeter
M-bus
Pulse
www
Pulsemeter
Pulsemeter
Every 4 h
Actual Values every 4 hMonthly Values every 24 h
Actual Values1x daily starting at 05:00
Monthly ValuesOn the 3th day of month
Pulses are constantly counted
• Setting the Period for E-mail sending
• File is ready for downloading any time
Pulses are constantly counted
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 6/23 Building Technologies
Polling time for Meter data
Actual Values (1x daily starting at 05:00)
Number of Meter
Polling time
[20 Telegram / min]
Finishedat
10100512
5 min50 min
5 h
05:0505:5010:00
Monthly Values (On the 3th day of month)
Number of Meter
Polling time
[20 Telegram / min]
Finishedat
10100512
20 min4 h17 h
05:2009:0022:00
KNX TP1www
Conclusion: on the 4th day of month,the monthly Values of the last month are collected
Conclusion: daily at 10:00,all actual Values are collected
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 7/23 Building Technologies
Commissioning
All Meter of the generated KNX-Devices are in the file of the Consumption data.
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 8/23 Building Technologies
File of Consumption data
With generate, for all Meter the following Information are read: • Name• Medium (Heat, Cool, Warm Water, Electricity, Gas, …) (only QAX903 / 913)• Fabrication number (only QAX903 / 913)• Identification number (only QAX903 / 913)• Unit• Format (RMx7xx)• Meter changed identifier (only QAX903 / 913)
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 9/23 Building Technologies
File of Consumption dataExample Part 1 Information
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 10/23
Building Technologies
File of Consumption dataExample Part 2 Values
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 11/23
Building Technologies
Meter replacement
A Meter change is recognized:• Manuel by hand with “Device Webpage > Generate“• Automatically by daily read-out of the Meter Values (after the next 00:00 is a automatic “Generate”)
Data of the „Meter changed“ are deleted:• By the user via Web Browser: the whole section can be deleted• 2 Year old Data are removed automatically
Action by Meter replacement
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 12/23
Building Technologies
Consumption data read out
Web Browser
Int*net
Variant 1:Download the File with Web Browser via USB or Ethernet
Variant 2:File are periodically sent to a E-mail Server
Mail Server
Int*net
E-mailDownload
Application:The final energy bill is often made of the Consumption data, the Allocation key and the General expenses
Download
Web Browser
USB
Ethernet
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 13/23
Building Technologies
Download of Consumption data
• No Setting• Data are daily updated• Chose the File type by Click
Web Browser
Int*net
Download
Web Browser
USB
Ethernet
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 14/23
Building Technologies
File Format
csv-file (comma separated values)is a unformated text file
xml-file is formatted for Excel
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 15/23
Building Technologies
Sending of Consumption data
The Consumption data are put in a File and periodically sent as E-mail attachment.
Settings:
Consumption data Receiver 1…2 • Period
• Never• Daily• Weekly• Monthly
• File type (.xml / .csv)• E-mail Address
Mail Server
Int*net
E-mailDownload
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 16/23
Building Technologies
https Encryption
URL starts with "http://", Port 80 is used URL starts with "https://", Port 443 is used Both Ports are open, it is up to the user The Ports are not forwarded
"https://" Certificate is not from a certificate authority, it is a self-signed Certificate from Siemens with a lease time of 20 years
The reaction depends of the Web Browser. Usually this Certificate can be installed.
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 17/23
Building Technologies
https with Internet Explorer 7
Installation of the Certificate
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 19/23
Building Technologies
Router – Port Forwarding
10
10
2
2
Port 80 (http) Web Server Operation with Web BrowserPort 443 (https) Encrypted Web Server Operation with Web Browser
Port 21 (ftp) ACS File transfer (Message history and Offline Trend)Port 50005 () ACS Operation
Port 22 (scp) HQ Zug OZW Web Server Remote Support
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 20/23
Building Technologies
Firmware update – Full Backup and Restore
Port 80 (http) Web Browser generate web pages or Port 443Port 21 (ftp) ACS File transfer (optional for Offline Trend definition)Port 50005 () ACS device listPort 22 (scp) Web data backup and restore
• Send the IP-Address and the Login-Data, Name and Password, with Admin. -rights off the Web server via E-mail to [email protected]
• HQ-Zug makes a complete Backup via Internet
Via local USB connection
• Read with ACS the Parameter settings of the Web server OZW772
• Proceed the Firmware-update
• Write with ACS the Parameter settings of the Web server OZW772
Via Internet
• HQ-Zug makes a complete Backup via Internet
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 21/23
Building Technologies
E-mail with Encryption
Authentification with User name / Password without Encryption (normally Port 25)
Authentification with User name / Password with TLS-Encryption (normally Port 587)
Automatic recognition → No Settings
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 22/23
Building Technologies
Upload of User defined Logos
Rev 1.1, 17-Jan-2011
Pius Hausheer, 4866page 24/23
Building Technologies
Update of System Definition
1. Firmware update per PC-Tool via USB (incl. System definition)
2. or System definition update per Web Browser: Via USB or Ethernet (Date size 35 Mbyte) Update are for required for:
New Device types (Device description) Text catalog