130
Operator/Installation/Service/Parts Owner’s Manual Transfer Switch GTEC 20-2000 Amps English 4-2009 914-0100 (Issue 8)

Owner's Manual 0914-0100_I8_200904

Embed Size (px)

DESCRIPTION

Owner's Manual

Citation preview

  • Operator/Installation/Service/Parts

    Owners Manual

    Transfer Switch

    GTEC

    202000 Amps

    English 4-2009 9140100 (Issue 8)

  • i

    Table of Contents

    SECTION TITLE PAGE

    SAFETY PRECAUTIONS V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    1. INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operators Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Switch Application 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Switch Function 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model Identification 1-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How to Obtain Service 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation Overview 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Application and Installation 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Considerations 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    GTEC Features 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    2. TRANSFER SWITCH START-UP 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    3. DESCRIPTION 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabinet 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Panel 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Control Function LEDs 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ATS Status LEDs 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Membrane Pushbuttons 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Electronic Control System 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Inhibit Input 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Retransfer Inhibit Input 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Test Input 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two-Wire Starting 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Transfer Switch 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Contact Assemblies 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electro Mechanical Actuator 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Contacts 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Voltage Sensing 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Line-to-Neutral Voltage Sensing 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Line-to-Line Voltage Sensing 3-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Options 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Float Battery Charger Option 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-Amp Battery Charger 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Exercise Clock Option 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Elevator Relay Option 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Manual Restore Option 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

  • ii

    Table of Contents

    SECTION TITLE PAGE

    4. OPERATION 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time Delays 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Time Delay Engine Start (TDES) 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time Delay Engine Cooldown (TDEC) 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time Delay Normal to Emergency (TDNE) 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time Delay Emergency to Normal (TDEN) 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time Delay Programmed Transition (TDPT) 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Time Delay Elevator (TDEL) Pre-Transfer 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Elevator Post Transfer Delay 4-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Manual Operation 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pushbutton Operation 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Test Pushbutton 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Override Pushbutton 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Set Exercise Pushbutton 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Test With or Without Load 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test With Load Sequence of Events 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Without Load Sequence of Events 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Sensors 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Utility Sensor 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Generator Sensor 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Phase Check Sensor 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Return to Programmed Transition 4-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Generator Set Exerciser 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exercise With or Without Load 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Exerciser 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Loss Backup 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Integrated Exercise Period 4-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Canceling Repeat Exercise Periods 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Canceling An Active Exercise Period 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Source Failure During An Active Exercise Period 4-9. . . . . . . . . . . . . . . . . . Exercise Without Load Sequence of Events 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exercise With Load Sequence of Events 4-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Optional External Exerciser 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exercise With or Without Load 4-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using the Menu Button 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using the +/ Buttons 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using the ok Button 4-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the Clock with Summer/Winter Time (Daylight Savings Time) 4-11. . . . . . . Setting Exercise Start and Stop Times 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checking the Programs 4-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reviewing Exercise Start/Stop Times 4-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Deleting Exercise Start/Stop Times 4-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Erasing (Clearing) A Programmed Exercise Period 4-19. . . . . . . . . . . . . . . . . . . . . . . Erasing (Clearing) All Programmed Exercise Periods 4-21. . . . . . . . . . . . . . . . . . . . .

  • iii

    Table of Contents

    SECTION TITLE PAGE

    Initiating or Overriding an Exercise Program 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . Initiating an Exercise 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overriding an Exercise 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting Permanent On/Off Mode 4-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selecting Permanent On/Off Mode Without an Active Exercise 4-23. . . . . . . . . . . . Selecting Permanent On/Off Mode With an Active Exercise 4-23. . . . . . . . . . . . . . . Adding A Security Code 4-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . After Programming the Exerciser Clock 4-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Resetting the Timer 4-25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Planned Maintenance 4-27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    5. CONTROL PANEL CONFIGURATION 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Accessing the Front Panel Configuration Editor 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . Modifying the Configuration 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    6. INSTALLATION MOUNTING 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Location 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Methods 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Wall Mounting 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Free-Standing 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Open Construction 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    7. INSTALLATION WIRING 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AC Connections 7-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Connections 7-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Connecting Transfer Switch to Genset 7-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Auxiliary Contacts 7-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Start-Stop Connections 7-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Test Input 7-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Inhibit Input 7-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Retransfer Inhibit Inhibit 7-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Override Input 7-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Inspection and Cleanup 7-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    8. TROUBLESHOOTING 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Panel LED Indicators 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Troubleshooting Procedures for Operators and Service Personnel 8-3. . . . . . . . . .

    Power Outage Occurs, But Generator Set Does Not Start 8-3. . . . . . . . . . . . . . . . Generator Set Starts During Normal Power Service 8-4. . . . . . . . . . . . . . . . . . . . . . Generator Set Does Not Exercise 8-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . After a Power Failure, Generator Set Starts But Does Not Assume the Load 8-5After Power Returns, Transfer Switch Does Not Return To Normal Position 8-5. Generator Set Continues to Run After Retransfer of Load to Normal Power 8-6. System Does Not Test With Load 8-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . System Does Not Exercise With Load 8-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Exercise Clock Does Not Start An Exercise 8-7. . . . . . . . . . . . . . . . . . . . . External Exerciser Does Not Repeat an Exercise 8-7. . . . . . . . . . . . . . . . . . . . . . . .

  • iv

    Table of Contents

    SECTION TITLE PAGE

    Battery Charger Fails To Charge (If Equipped) 8-7. . . . . . . . . . . . . . . . . . . . . . . . . . Battery Loses Water 8-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Battery Loses Charge 8-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Troubleshooting Procedures for Experienced Service Personnel 8-8. . . . . . . . . . . . About Customer Inputs 8-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Panel LED Indicators 8-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Sequence of Events 8-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Normal to Emergency Sequence of Events 8-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Emergency to Normal Sequence of Events 8-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Troubleshooting With Symptoms 8-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Switch Operation 8-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Utility Power Failure 8-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Utility Power Is Restored 8-22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Miscellaneous Troubleshooting Issues 8-26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    9. TRANSFER SWITCH SERVICE 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Switch Assembly Removal/Replacement Procedure 9-1. . . . . . . . . . . . . . . . . . . . . . Switch Removal and Replacement Procedure 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Disconnect AC Power 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Switch Assembly Removal 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Transfer Switch Replacement 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reconnecting AC Power (When Finished) 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    10. PARTS INFORMATION 10-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    11. WIRING DIAGRAMS 11-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    California

    Proposition 65 WarningDiesel engine exhaust and some of its constituents are knownto the State of California to cause cancer, birth defects, andother reproductive harm.

  • v

    Safety Precautions

    This manual includes the following symbols to indi-cate potentially dangerous conditions. Read themanual carefully and know when these conditionsexist. Then take the necessary steps to protect per-sonnel and the equipment.

    DANGER This symbol warns of immediatehazards that will result in severe personal injuryor death.

    WARNING This symbol refers to a hazard orunsafe practice that can result in severe per-sonal injury or death.

    CAUTION This symbol refers to a hazard orunsafe practice that can result in personal inju-ry or product or property damage.

    ELECTRICAL SHOCK CAN CAUSESEVERE PERSONAL INJURY OR DEATH

    High voltage in transfer switch components pres-ents serious shock hazards that can result in severepersonal injury or death. Read and follow thesesuggestions.Keep the transfer switch cabinet closed and locked.Make sure only authorized personnel have the cabi-net keys.Due to the serious shock hazard from high voltageswithin the cabinet, all service and adjustments tothe transfer switch must be performed only by anelectrician or authorized service representative.

    UTILITY-TO-GENSET APPLICATIONSIf the cabinet must be opened for any reason:

    1. Move the operation selector switch on the gen-erator set to Stop.

    2. Disconnect the battery charger.

    3. Disconnect the starting batteries of the genera-tor set or sets (remove the ground [] lead first).

    4. Remove AC power to the automatic transferswitch. If the instructions require otherwise,use extreme caution due to the danger ofshock hazard.

    GENERAL PRECAUTIONSPlace rubber insulative mats on dry wood platformsover metal or concrete floors when working on anyelectrical equipment. Do not wear damp clothing(particularly wet shoes) or allow skin surfaces to bedamp when handling any electrical equipment.

    Jewelry is a good conductor of electricity andshould be removed when working on the electricalequipment.

    Wear safety glasses whenever servicing the trans-fer switch and and do not smoke near the batteries.

    Do not work on this equipment when mentally orphysically fatigued, or after consuming alcohol orany drug that makes the operation of equipment un-safe.

    WARNING

    INCORRECT SERVICE OR REPLACEMENT OF PARTS CAN RESULT INDEATH, SEVERE PERSONAL INJURY, AND/OR EQUIPMENT DAMAGE. SER-VICE PERSONNEL MUST BE QUALIFIED TO PERFORM ELECTRICAL AND/OR MECHANICAL SERVICE.

    OTEC-1

  • vi

    THIS PAGE LEFT INTENTIONALLY BLANK

  • 1-1

    1. Introduction

    OPERATORS MANUAL

    This manual covers models produced under theCummins Power Generation brand names.

    This manual provides information necessary foroperation, installation, and service of an GTECtransfer switch. This manual also includes parts in-formation.

    This is an open transition transfer switch that in-cludes an automatic transfer switch (ATS) control.With an open transition switch, there is never a timewhen both sources are supplying power to the load.

    Programmed transition switches briefly pause inthe neutral position of the transfer switch, betweenswitched positions, so that transient voltages fromthe load can diminish before the load is switched tothe other source.

    FIGURE 1-1. GTEC TRANSFER SWITCH WITH DOOR OPEN (125 AMP, 4 POLE SWITCH SHOWN WITHOPTIONAL 2 AMP BATTERY CHARGER)

    Copyright 2009 Cummins Power Generation. All rights reserved.Cummins, Onan, and PowerCommand are registered trademarks of Cummins Inc.

  • 1-2

    TRANSFER SWITCH APPLICATION

    Transfer switches are an essential part of a build-ings standby or emergency power system. Theutility line (normal power), is backed up by a gener-ator set (emergency power). The transfer switchautomatically switches the electrical load from onesource to the other.

    The load is connected to the common of the ATS(Figure 1-2). Under normal conditions, the load issupplied with power from the utility (as illustrated).If utility power is interrupted, the load is transferredto the generator set (genset). When utility power re-turns, the load is retransferred to the utility. Thetransfer and retransfer of the load are the two mostbasic functions of a transfer switch.

    TRANSFER SWITCH FUNCTION

    Automatic transfer switches, capable of automaticoperation without operator intervention, performthe basic function of transferring the load to theavailable power source. The controller monitorseach source for allowable voltage and frequencyrange.

    This automatic transfer switch, capable of automat-ic operation without operator intervention, is de-signed for utility-to-genset applications. In utility-to-genset applications, the transfer switch performsthe following functions:

    1. Senses the interruption of utility power.2. Sends a start signal to the genset.3. Transfers the load to the genset.4. Senses the return of utility power.5. Retransfers the load to the utility.6. Sends a stop signal to the genset.

    LOAD

    UTILITY(NORMAL POWER)

    GENERATOR SET(EMERGENCY POWER)

    OVERCURRENT PRO-TECTIVE DEVICE

    (CUSTOMER SUPPLIED)

    OVERCURRENT PRO-TECTIVE DEVICE

    (CUSTOMER SUPPLIED)

    FIGURE 1-2. LOAD TRANSFER SWITCH(TYPICAL FUNCTION)

  • 1-3

    MODEL IDENTIFICATION

    Identify your model by referring to the Model andSpecification number as shown on the nameplate.Electrical characteristics are shown on the lowerportion of the nameplate (see Figure 1-3), which islocated on the cabinet door.

    If it is necessary to contact a distributor regardingthe transfer switch, always give the complete Mod-el and Serial number. This information is necessaryto properly identify your unit among the many typesmanufactured.

    Cummins Power Generation

    Model No. GT30160EQ5KA000Serial No. F05W000072Current Rating: 160AVoltage Rating: 110/190VFrequency: 50 HertzClass: PCUtilization Category: AC-31B

    Feature:S903;R971;A028;A045;A035;B004;A042;L989;M034

    Enclosure Rating: NoneApplication: Utility to GensetWiring Diagram: 06302993Outline Drawing: 03006012Conditional Short Circuit Current: 38,000A @480 VACFuse type: RT16NT-2Max. Fuse Rating: 250A

    THIS PRODUCT CONFORMS TOEN 60947-6-1 AND EN 60439-1

    FIGURE 1-3. STANDARD NAMEPLATE

    Model No:

    The model number is made up of code segmentsthat designate various features or options:

    GT 3 0500 M N 5 2 A 000| | | | | | | | |1 2 3 4 5 6 7 8 9

    1. GT = GTEC - Global transfer switch with opentransition and delay transition

    2. Number of Poles: 2, 3, or 4

    3. Current Rating: 20, 40, 63, 100, 125, 160, 200,225, 250, 350, 400, 500, 630, 800, 1000, 1250,1600, or 2000 amps

    4. Voltage Code:A = 110 VAC*B = 115 VAC*C = 120 VAC*D = 127 VAC*E = 110/190 VAC**F = 115/200 VAC**G = 120/208 VAC**H = 127/220 VAC** I = 220 VAC*J = 230 VAC*K = 240 VAC*L = 139/240 VAC**N = 220/380 VAC**O = 230/400 VAC**P = 240/416 VAC**Q = 255/440 VAC**S = 277/480 VAC**X = 110/190V, 115/200V, 120/208V, 127/220V, 139/240VY = 220/380V, 230/400V, 240/416VZ = 255/440V, 277/480V

    * = Single Phase, 2 Wire** = Three Phase, 3 or 4 Wire OR

    Single Phase, 3 Wire

    5. Control Type:L = 12VDC, Powered Line-to-Line Sensing

    ControlN = 12VDC, Powered Line-to-Neutral Sensing

    ControlP = 24VDC, Powered Line-to-Line Sensing

    ControlQ = 24VDC, Powered Line-to-Neutral Sensing

    Control

    6. Frequency:5 = 50 Hertz6 = 60 Hertz7 = 50/60 Hertz

    7. Construction Type:2 = IP32 Enclosure3 = IP54 EnclosureK = Kit (open construction)

    8. Revision Letter:Factory Assigned (A thru Z)

    9. Spec Number:Factory Assigned (000999)

  • 1-4

    Serial No:

    The serial number is made up of nine characters.

    K 05 W 000001| | | |1 2 3 4

    1. Character 1 = Month manufacturedA = 1B = 2C = 3D = 4E = 5F = 6G = 7H = 8I = 9J = 10K = 11L = 12

    2. Characters 2 and 3 = Year built05 = 2005

    3. Character 4 = Plant location:0 = Fridley, Minnesota1 = SML (Portables)2 = Cummins (USA)3 = Huntsville, Alabama4 = Onan Power Electronics5 = Singapore6 = Westinghouse (Transfer Switches and Breakers)7 = Canada (Linamar)8 = Lister-Petter9 = Kubota (K-Series Portables)A = Australia (Dunlite and Adelaide)B = South America (Columbia)C = Italy (DIEM)L = LibbyM = Libby (Military)R = Robin (Fuji Engines) USAU = PGIK = UK (Kent)S = Mexico (Cumsa)T = BrazilX = Canada (Linamar early production)W = Nexage Wuxi, China

    4. Characters 5 thru 10 = Manufacturing OrderNumber (Sequentially assigned number)

    HOW TO OBTAIN SERVICE

    When the transfer switch requires servicing, con-tact your nearest Cummins Power Generation dis-tributor. Factory-trained Parts and Service repre-sentatives are ready to handle all your serviceneeds.

    To contact your local Cummins Power Generationdistributor in the United States or Canada, call1-800-888-6626 (this automated service utilizestouch-tone phones only). By selecting Option 1(press 1), you will be automatically connected tothe distributor nearest you.

    If you are unable to contact a distributor using theautomated service, consult the Yellow Pages. Typi-cally, our distributors are listed under:

    Generators-Electric,Engines-Gasoline or Engines-Diesel, orRecreational Vehicles-Equipment,Parts and Service.

    In Asia, contact:

    Cummins Power Generation (S) Pte.Ltd10, Toh Guan Road #0701TT International TradeparkPh (65) 6417 2388Fax (65) 6417 2399

    In Great Britain, contact the CPGK AftermarketGroup:

    Aftermarket GroupCummins Power Generation Pty LtdManston ParkColumbus Avenue, ManstonRamsgate, Kent CT12 5BFEngland, UKPhone: +44 (0) 1843 255000Parts Support:

    Email: [email protected] Support;

    Email: [email protected]

    For other locations outside North America, call Cum-mins Power Generation, 1-763-574-5000, 7:30 AM to4:00 PM, Central Standard Time, Monday throughFriday. Or, send a fax to Cummins Power Generationusing the fax number 17635287290.

    When contacting your distributor, always supplythe complete Model, Specification, and SerialNumber as shown on the equipment nameplate.

  • 1-5

    INSTALLATION OVERVIEW

    These installation recommendations apply to typi-cal installations. Whenever possible, these recom-mendations also cover factory designed options ormodifications. However, because of the many vari-ables in any installation, it is not possible to providespecific recommendations for every situation. Ifthere are any questions not answered by thismanual, contact your nearest Cummins/Onan dis-tributor for assistance.

    Application and Installation

    Installations must be carefully planned and correct-ly installed for proper operation. This involves twoessential elements: application and installation.

    Application refers to the design of the completestandby power system that usually includes powerdistribution equipment, transfer switches, ventila-tion equipment, mounting pads, cooling systems,exhaust systems, and fuel systems. Each compo-nent must be correctly designed so the completesystem functions as intended. Application and de-sign is an engineering function generally done byspecifying engineers or other trained specialists.Specifying engineers are responsible for the de-sign of the complete standby system and for select-ing the materials and products required.

    Installation refers to the actual set-up and assem-bly of the standby power system. The installers setup and connect the various components of the sys-tem as specified in the system design plan. Thecomplexity of the standby system normally re-quires the special skills of qualified electricians,plumbers, sheet metal workers, etc. to completethe various segments of the installation. This isnecessary so all components are assembled usingstandard methods and practices.

    Safety Considerations

    The transfer switch has been carefully designed toprovide safe and efficient service when properlyinstalled, maintained, and operated. However, theoverall safety and reliability of the complete systemdepends on many factors outside the control of themanufacturer. To avoid possible safety hazards,make all mechanical and electrical connections tothe transfer switch exactly as specified in thismanual. All systems external to the transfer switchmust comply with all applicable codes. Make cer-tain all required inspections and tests have beencompleted and all code requirements have beensatisfied before certifying the installation is com-plete and ready for service.

    Verify that both power source voltages match thenameplate rating prior to installation.

  • 1-6

    GTEC FEATURES

    FEATURE DESCRIPTION FEATUREOPTION

    Poles:2 Poles3 Poles4 Poles

    A027A028A029

    Application:Utility to Genset A035

    Frequency:60 Hertz50 Hertz

    A044A045

    Phase:Single Phase, 2 or 3 WireThree Phase, 3 or 4 Wire

    A041A042

    Cabinet:IP32IP54Open Construction

    B901B014B004

    Battery Chargers:2 Amp, 12/24VDC K001-7

    Voltage Ratings:110/190 VAC115/200 VAC120/208 VAC127/220 VAC139/240 VAC220/380 VAC230/400 VAC240/416 VAC255/440 VAC277/480 VAC110VAC115VAC120VAC127VAC220VAC230VAC240VAC

    R971R972R973R974R975R976R977R978R979R980R981R982R983R984R985R986R987

    FEATURE DESCRIPTION FEATUREOPTION

    Current Ratings:20 Amp40 Amp63 Amp100 Amp125 Amp160 Amp200 Amp225 Amp250 Amp350 Amp400 Amp500 Amp630 Amp800 Amp1000 Amp1250 Amp1600 Amp2000 Amp

    S820S840S901S902S048S903S904S905S906S907S053S908S909S055S056S910S916S920

    Control Options:External Exercise ClockElevator Signal RelayManual Restore Switch

    J030-7M032-7S006-7

    Auxiliary Relays:24 VDC Coil

    Emergency PositionNormal Position

    12 VDC CoilEmergency PositionNormal Position

    L101-7L102-7L103-7L201-7L202-7L203-7

    Miscellaneous:Terminal Block 10 Position M002-7

    Controller Type:Line to NeutralLine to Line

    L989L990

    Starting Battery:12V, Genset Starting Voltage24V, Genset Starting Voltage

    M033M034

    Neutral Connection:Neutral Bar Assembly N016-7

  • 2-1

    2. Transfer Switch Start-Up

    The GTEC transfer switch is preset at the factory tooperate using default settings. The control will op-erate the transfer switch when power is applied.However, you may wish to adjust some of the set-tings for better performance.

    The transfer switch must be installed correctly, withDC power present, before any adjustments to theconfiguration can be made. If the transfer switch isconnected to utility power, the Utility Power Con-nected LED will be lit if battery power is available.Utility or genset voltage need not be present to ad-just the configuration.

    The following tables show which control functionsshould not be changed (Table 2-1) and which func-tions can be changed for your application (Table2-2). Refer to Section 5 for more details.

    TABLE 2-1. FUNCTIONS THAT SHOULD NOT BECHANGED

    Function Factory Setting

    System NominalVoltage Table

    Set for your system voltage

    System NominalVoltage

    Set for your system voltage

    System NominalFrequency

    Set for your systemfrequency

    System Phase Set for your system

    ExternalExercise

    Set to On if the externalexerciser option wasordered; otherwise, set toOff

    TABLE 2-2. FUNCTIONS THAT CAN BE CHANGED

    Function FactorySetting

    TDES (Time Delay EngineStart)

    3 Seconds

    TDNE (Time Delay Normal toEmergency)

    5 Seconds

    TDEN (Time Delay Emergencyto Normal)

    10 Minutes

    TDEC (Time Delay EngineCooldown)

    10 Minutes

    TDPT (Time DelayProgrammed Transition)

    0 Seconds

    TDEL (Time Delay ElevatorSignal)

    0 Seconds

    Test With or Without Load Without Load

    Exercise With or Without Load Without Load

    Utility Undervoltage Pickup 90%

    Utility Undervoltage Dropout 85%

    Utility Overvoltage Pickup 120%

    Utility Overvoltage Dropout 125%

    Utility Underfrequency Pickup 80%

    Utility Underfrequency Dropout 70%

    Utility Overfrequency Pickup 130%

    Utility Overfrequency Dropout 140%

    Phase Check Off

    Return to ProgrammedTransition

    Off

    Elevator Post Transfer Delay Off

    Exercise Repeat Interval Every 7 Days

    NOTE: Utility overvoltage and under/over frequen-cy can be eanbled or disabled but the setpoints can not be changed.

  • 2-2

    THIS PAGE LEFT INTENTIONALLY BLANK

  • 3-1

    3. Description

    This section describes the control cabinet, theswitch mechanism, and the standard and optionalcontrol features available with the GTEC transferswitch.

    CABINET

    The GTEC transfer switch uses an IP32 type cabi-net. These Ingress Protection (IP) cabinets are de-

    signed to prevent entrance of foreign objects thatare 2.5 mm and larger and can keep out fallingdrops of water up to a 15-degree incidence angle.

    Examples of cabinets are shown in Figures 3-1 thru3-4.

    The GTEC is also available for open constructioninstallations.

    BATTERYCHARGER

    OPTION

    CONTROLPANEL

    NEUTRALBAR

    TRANSFERSWITCH

    RAILASSEMBLY

    CONTROLWIRING

    TERMINALS

    RELAYCOILS K1THRU K4

    FUSEBLOCK

    OPTIONALEXERCISER

    CLOCK

    TB1

    FIGURE 3-1. INTERIOR COMPONENTS: 20125 AMP, 4 POLE SWITCH

  • 3-2

    TRANSFERSWITCH

    BATTERYCHARGER

    OPTION

    RAILASSEMBLY

    NEUTRAL BARCONTROL

    PANEL

    RELAYCOILS K1THRU K4 FUSE

    BLOCK

    OPTIONALEXERCISER

    CLOCK

    TB1

    FIGURE 3-2. INTERIOR COMPONENTS: 160500 AMP, 4 POLE SWITCH

  • 3-3

    TRANSFERSWITCH

    BATTERYCHARGER

    OPTION

    RAILASSEMBLY

    NEUTRALBAR

    CONTROLPANEL

    TB1

    RELAYCOILS K1THRU K4

    FUSEBLOCK

    OPTIONALEXERCISER

    CLOCK

    FIGURE 3-3. INTERIOR COMPONENTS: 6301250 AMP, 4 POLE SWITCH

  • 3-4

    CONTROLPANEL

    NEUTRALBAR

    FUSEBLOCK

    RALAYCOILS K1THRU K4

    TB1 BATTERYCHARGER OPTION

    RAILASSEMBLY

    TRANSFERSWITCH

    FIGURE 3-4. INTERIOR COMPONENTS: 16002000 AMP, 4 POLE SWITCH

  • 3-5

    CONTROL PANEL

    Figure 3-5 shows the control panel on the cabinetdoor. Two types of controls are available with GTECtransfer switches.

    TS1311 controls are used on transfer switcheswith line-to-neutral voltage sensing.

    TS1310 controls are used on transfer switcheswith line-to-line voltage sensing.

    The front of the control panel is the same for bothtypes of controls.

    The control features are divided into three groups:

    Control Function LEDs ATS Status LEDs Membrane Pushbuttons

    Control Function LEDs

    The control panel (see Figure 3-5) includes eightLEDs that display codes that indicate various con-trol functions that can be configured. The first fiveLEDs display the function code and the last threeLEDs display the value code for the displayed func-tion. For information on configuring these func-tions, see Section 5.

    With the exception of the first LED (Test), normallythese LEDs are off and are only lit when in Configu-ration Mode. The Test LED is also used to notify theuser of test periods.

    ATS Status LEDs

    The control panel includes six LEDs that provideAutomatic Transfer Switch (ATS) status informa-tion.

    Utility Power Available This green LED is litwhen the utility power source has acceptable out-put voltage.

    Genset Power Available This amber LED is litwhen the genset power source has acceptable out-put voltage and frequency.

    Both power source LEDs can be lit simultaneously.

    Utility Power Connected This green LED is litwhen utility power is supplying power to the load.

    This LED flashes once per second if there is a fail-ure to connect to or disconnect from utility power,

    when commanded. The control makes five at-tempts (there is ten seconds between each at-tempt) to connect to or disconnect from utility pow-er before it flashes the failure.

    Genset Power Connected This amber LED is litwhen the genset is supplying power to the load.

    This LED flashes once per second if there is a fail-ure to connect to or disconnect from the genset,when commanded. The control makes five at-tempts (there is ten seconds between each at-tempt) to connect to or disconnect from the gensetbefore it flashes the failure.

    Test This amber LED is lit when there is an activetest period. This LED flashes twice per secondwhen the Test pushbutton is pressed to set or can-cel a test period.

    Exercise This amber LED lights when repeat ex-ercise periods have been set. This LED flashestwice per second when the Set Exercise pushbut-ton is pressed to set or cancel an exercise. ThisLED flashes once per second during an active ex-ercise period.

    Membrane Pushbuttons

    The control panel includes three membrane push-buttons.

    Test The Test pushbutton is used to set or cancela test period. The control can be configured to testthe genset with or without load. For more informa-tion, see Section 4.

    The Test pushbutton is also used in the Configura-tion Mode to step through the function codes (seeSection 5).

    Override The Override pushbutton is used to ter-minate or bypass some time delays, to stop thePower Connected LEDs from flashing as a result ofa failure to connect to or disconnect from a powersource, and to cancel an active exercise period.For more information, see Section 4.

    The Override pushbutton is also used in the Config-uration Mode to step through the value codes (seeSection 5).

    Set Exercise The Set Exercise pushbutton isused to set or cancel repeat exercise periods usingthe integrated exerciser. For more information, seeIntegrated Exercises on page 4-8.

  • 3-6

    Test Override Set Exer-cise

    Exercise

    Test

    Control operation could be delayed by externalsource.

    FUNCTION CODE LEDS VALUE CODE LEDS

    PowerCommand

    UTILITYPOWER

    AVAILABLELED

    GENSETPOWER

    AVAILABLELED

    UTILITY POWERCONNECTED LED

    GENSETPOWER

    CONNECTEDLED

    ACTIVEEXERCISE

    LED

    TESTACTIVITY LED

    TESTPUSHBUTTON

    OVERRIDEPUSHBUTTON

    SET EXERCISEPUSHBUTTON

    FIGURE 3-5. CABINET DOOR

  • 3-7

    ELECTRONIC CONTROL SYSTEM

    This section describes the standard and optionalcomponents of the electronic control system.

    WARNING Improper calibration or adjustmentof electronic control modules can cause death,severe personal injury, and equipment or prop-erty damage. Calibration and adjustment ofthese components must be performed by tech-nically qualified personnel only.

    Installation of these components and calibrationand adjustment procedures are described in Sec-tion 7.

    WARNING AC power within the cabinet andthe rear side of the cabinet door presents ashock hazard that can cause severe personalinjury or death. When the cabinet door is open,use extreme caution to avoid touching electri-cal contacts with body, tools, jewelry, clothes,hair, etc.

    Transfer Inhibit Input

    A transfer inhibit input is set up by connecting a dry(voltage free) contact between TB1-6 and TB1-8.Closing the contact enables the feature and open-ing the contact disables it.

    RETRANSFER INHIBIT

    COMMON

    GENSET START

    REMOTE TEST

    TRANSFER INHIBIT

    TB1

    GND

    GENSET START

    B+

    1

    2

    3

    4

    5

    6

    7

    8

    FIGURE 3-6. TB1 CONNECTIONS FORTRANSFER INHIBIT

    This feature is used to control load transfer to gen-sets. When enabled, load transfer will not takeplace unless the Override pushbutton on the con-trol panel is pressed or the transfer inhibit input isdisabled.

    Pressing the Override pushbutton on the controlpanel bypasses the transfer inhibit input and by-passes TDNE. The TDNE runs if the transfer inhibitinput is disabled.

    Retransfer Inhibit Input

    A retransfer inhibit input is set up by connecting adry (voltage free) contact between TB1-7 andTB1-8. Closing the contact enables the feature andopening the contact disables it.

    This feature is used to prevent the ATS from auto-matically transferring the load back to the utility.When enabled, load transfer will not take place un-less the Override pushbutton on the control panel ispressed, the retransfer inhibit input is disabled, orthe genset fails. If the genset fails, retransfer inhibitis ignored.

    Pressing the Override pushbutton on the controlpanel bypasses the retransfer inhibit input and by-passes the TDEN. The TDNE runs if the retransferinhibit input is disabled.

    RETRANSFER INHIBIT

    COMMON

    GENSET START

    REMOTE TEST

    TRANSFER INHIBIT

    TB1

    GND

    GENSET START

    B+

    1

    2

    3

    4

    5

    6

    7

    8

    FIGURE 3-7. TB1 CONNECTIONS FORRETRANSFER INHIBIT

  • 3-8

    Remote Test Input

    The transfer switch may be wired for a remote testinput. The switch is used to start and stop manuallyinitiated system tests. As with the control panel Testpushbutton, the remote test input can be config-ured to test with or without load. More informationon testing is included in Section 4.

    A remote test input is set up by connecting a dry(voltage free) contact between TB1-5 and TB1-8.Closing the contact starts a test and opening thecontact cancels the test. The Test LED flashes tosignify the start of a test and stays on during thetest.

    Closing the contact causes the transfer switch tosense a (simulated) utility power failure and sendsa start/run signal to the genset. If the control is setup to test with load, the load is transferred to thegenset when the genset becomes available. TheUtility Power Available LED remains on to showthat the utility did not fail.

    RETRANSFER INHIBIT

    COMMON

    GENSET START

    REMOTE TEST

    TRANSFER INHIBIT

    TB1

    GND

    GENSET START

    B+

    1

    2

    3

    4

    5

    6

    7

    8

    FIGURE 3-8. TB1 CONNECTIONS FOR REMOTETEST TRANSFER

    Two-Wire Starting

    The starting circuit is a basic supervisory functionof the electronic control. Water-cooled generatorsets use a two-wire start control.

    Although the logic is more involved, the two-wirestarting circuit can be thought of as a single pole,single throw switch. A closed switch starts the gen-erator set. An open switch stops the generator.

    NOTE: Three-wire starting is not available onGTEC transfer switches.

    TRANSFER SWITCH

    The transfer switch (see Figures 3-1 thru 3-4)opens and closes the contacts that transfer theload between the power sources. The switch is me-chanically interlocked to prevent simultaneousclosing to both power sources. The main parts ofthe switch discussed here are the contact assem-blies, linear actuator, and auxiliary contacts.

    Contact Assemblies

    The automatic transfer switch has either two, three,or four poles. Three pole transfer switches are pro-vided with a neutral bar. The contact assembliesmake and break the current flow. When closed toeither power source the contacts are mechanicallyheld. A mechanical interlock prevents them fromclosing to both power sources at the same time.

    Electro Mechanical Actuator

    Actuator operation is initiated automatically by thetransfer switch control. Manual operation of theswitch is also possible. Refer to Manual Operationin Section 4.

  • 3-9

    Auxiliary Contacts

    Auxiliary contacts are provided on the utility andgenset sides of the transfer switch (see Figure 3-9).They are actuated by operation of the transferswitch during transfer and retransfer. The utilityauxiliary contact switch is actuated when the trans-fer switch connected to the utility. The genset auxil-iary contact switch is actuated when the transferswitch is connected to the genset. The auxiliarycontacts have current ratings of 5 amperes at 250VAC. The contacts are wired to terminal block TB1.

    UTILITYAUXILIARYCONTACTS

    GENSETAUXILIARYCONTACTS

    FIGURE 3-9. AUXILIARY CONTACTS

    VOLTAGE SENSING

    GTEC transfer switches are available with eitherline-to-neutral or line-to-line voltage sensing.

    Line-to-Neutral Voltage Sensing

    The following is true if your transfer switch is config-ured for line-to-neutral voltage sensing.

    There is a letter N or Q in the model numberjust after the voltage code.

    The controller is identified as TS1311 on thewhite label on its case.

    The P3 connector on the back of the controllerhas 11 pins.

    Line-to-Line Voltage Sensing

    The following is true if your transfer switch is config-ured for line-to-line voltage sensing.

    There is a letter L or P in the model numberjust after the voltage code.

    The controller is identified as TS1310 on thewhite label on its case.

    The P3 connector on the back of the controllerhas 9 pins.

  • 3-10

    OPTIONS

    Float Battery Charger Option

    A float-charge battery charger (Figure 3-10) regu-lates its charge voltage to continuously chargewithout damage to the battery. As the battery ap-proaches full charge, the charging current auto-matically tapers to zero amperes or to steady-stateload on the battery.

    2-AMP BATTERYCHARGER

    LED

    FIGURE 3-10. BATTERY CHARGERS

    2-Amp Battery Charger

    The battery charger is rated for 2 amperes at 12 or24 VDC. The input voltage range for the 2ampbattery charger is between 100 and 240VAC.

    The 2-amp battery charger includes one LED thatdisplays the following conditions.

    Red On solid indicates the unit is charging Green On solid indicates the unit is fully

    charged.

  • 3-11

    External Exercise Clock Option

    The optional external exercise clock includes a7-day, real-time clock that keeps track of the timeand date. The clock can be set for automaticchangeover for summer/winter (Daylight Savings/Standard) time. The exercise clock can be usedwith 12 or 24 VDC operation.

    FIGURE 3-11. EXTERNAL EXERCISE CLOCK

    Programs are available to set exercise start andstop times. One program is required to start an ex-ercise period and a second one is required to stopan exercise period.

    The exercise clock has a built-in test feature thatcan be used to initiate an exercise that hasnt beenprogrammed or cancel a programmed exercise inprocess.

    Information on setting the clock is included in Sec-tion 4.

    NOTE: The clock includes a non-replaceable lithi-um battery with a life expectancy of at leastten years. If the clock battery is weak duringa power failure, the clock will need to be re-placed.

    Elevator Relay Option

    Connections to the elevator relay are made directlyto the relay terminals. The elevator relay ismounted on the DIN rail. The terminals accept wiresizes from one number 18 AWG (1.0 mm2) wire totwo number 12 AWG (4.0 mm2) wires. For connec-tion to the screw terminal, strip the insulation back3/8 inch (10 mm).

    There are two types of relay coils (12 VDC and 24VDC).

    The relay has two sets of Form-C contacts that arerated for 5 amperes at 250 VAC (see Figure 3-12).

    FIGURE 3-12. ELEVATOR RELAY

  • 3-12

    Manual Restore Option

    The optional Manual Restore key switch (see Fig-ure 3-13) is located on the front panel below theControl Panel.

    When the switch is set to Retransfer Inhibit, theload remains connected to Source 2 after a trans-fer. When the switch is set to Force Retransfer toUtility, the load is transferred back to Utility power.

    A manual restore input is set up by connecting a dry(voltage free) contact between P4-2 on the back ofthe control panel and TB1-7 and TB1-8 (see Figure3-14). Closing the contact enables the feature andopening the contact disables it.

    CONTROLPANEL

    MANUAL RESTOREKEY SWITCH

    FIGURE 3-13. MANUAL RESTORE KEY SWITCH

    RETRANSFER INHIBIT

    COMMON

    GENSET START

    REMOTE TEST

    TRANSFER INHIBIT

    TB1

    GND

    GENSET START

    B+

    1

    2

    3

    4

    5

    6

    7

    8

    FIGURE 3-14. CONNECTIONS FOR MANUAL RESTORE INPUT

  • 4-1

    4. Operation

    TIME DELAYS

    The transfer switch control uses various time de-lays to break from one power source and reconnectto the other source. The control panel can be usedto adjust these time delays (see Section 5).

    In the following descriptions of time delays, it is im-portant to remember that:

    When the transfer switch is connected to Nor-mal, it is connected to the utility power source.

    When the transfer switch is connected toEmergency, it is connected to the Genset pow-er source.

    When the transfer switch is in the Neutral posi-tion, it is not connected to either power source.

    Time Delay Engine Start (TDES)

    This time delay prevents the generator from start-ing during brief utility power interruptions. This tim-er starts the instant the utility fails, as detected bythe Undervoltage Sensor.

    When the control senses a utility failure, the controlstarts the Time Delay Engine Start (TDES) timer.This time delay is configurable for 0 (disabled), 0.5,1, 2, 3, 4, 6, or 10 seconds (default = 3 seconds).

    If utility power returns while the TDES timer is ac-tive, the timer is reset. When the timer expires, thecontrol de-energizes the start relay, closing thestart contact signalling the generator to start. Thetimer is not reset until utility power returns. If theOverride pushbutton is pressed or the Override in-put is grounded while the TDES timer is active, theTDES timer immediately expires.

    Time Delay Engine Cooldown (TDEC)

    This time delay allows the generator to cool down(under no load conditions) before the control turnsit off.

    The Time Delay Engine Cooldown (TDEC) startstiming when the load is retransferred to utility pow-er. This time delay is configurable for 0 (disabled),0.1, 5, 10, 15, 20, 25 or 30 minutes (default = 10minutes).

    When the TDES expires, the stop signal is sent tothe generator and the timer is reset. Pressing the

    Override pushbutton or grounding the Override in-put has no effect on this time delay.

    Time Delay Normal to Emergency (TDNE)

    This time delay allows the generator to stabilize be-fore the load is applied.

    While connected to Normal, this time delay startsafter utility power fails and the generator becomesavailable (the amber Genset Power Available LEDis lit). This time delay also starts after the generatorbecomes available when a with load Test or Exer-cise period is activated.

    The time delay is configurable for 0 (disabled), 1, 2,3, 5, 30, 120, or 300 seconds (default = 5 seconds).If the generator fails any time during a TDNE, thecontrol resets the timer and restarts it once the gen-erator is again available.

    If the Override pushbutton is pressed or the Over-ride input is grounded while the TDNE timer is ac-tive, the TDNE timer immediately expires. TheTDNE timer will not begin if a Transfer Inhibit inputis active.

    Time Delay Emergency to Normal (TDEN)

    While connected to Emergency, this time delay al-lows utility power to stabilize before the retransfercommand is issued. This delay also allows the gen-erator to operate under load for a minimum amountof time before transferring back to utility power.

    This time delay starts with the transfer switch con-nected to the generator and after the utility be-comes available following an outage (The greenUtility Power Available LED is lit). This time delayalso starts when an active Test or Exercise period isended. After the delay, the transfer switch can re-transfer the load to the utility power source.

    The time delay is configurable for 0 (disabled), 0.1,5, 10, 15, 20, 25 or 30 minutes (default = 10 min-utes). If the utility fails any time during this timedelay, the control resets the timer and restarts itonce utility power becomes available. If the gener-ator fails at any time during this time delay, the timerexpires and the normal retransfer sequence takesplace.

    If the Override pushbutton is pressed or the Over-ride input is grounded while the TDEN timer is ac-tive, the TDEN timer immediately expires. The

  • 4-2

    TDEN timer will not begin if a Retransfer Inhibit in-put is active.

    Time Delay Programmed Transition(TDPT)

    This feature causes the transfer switch to pause inthe Neutral position for an adjustable period of timewhenever there is a transfer from one source toanother. The intentional delay allows the residualvoltage of an inductive load to sufficiently decay be-fore connecting it to another power source. Thisdelay prevents potentially damaging voltage andcurrent transients in the customers power system.If TDPT is set to zero, then the transfer switchtransfers from one source to the other with no neu-tral position delay.

    The control activates a Program Transition TimeDelay (TDPT) whenever the transfer switch hasdisconnected from one source and is in the Neutralposition. The time delay is configurable for 0 (dis-abled), 0.5, 1, 2, 3, 4, 6 or 10 seconds (default = 0seconds). The control also detects if the transferswitch has disconnected from the first source be-fore connecting it to the second source.

    If there is a power source failure while the TDPT isactive, the control only transfers to the remainingactive power source. The control does not termi-nate the TDPT timer if either source fails while thetransfer switch is in the Neutral position.

    Time Delay Elevator (TDEL) Pre-Transfer

    Primarily used in elevator applications, this delaysets a time to wait for an elevator pre-transfer sig-nal. This signal allows the elevator to come to acomplete stop before the switch transfers.

    The elevator pre-transfer signal and associatedtime delay, is used to signal an elevator control sys-tem that there is an impending transfer or retransfer(i.e., the elevator is going to see a brief power fail-ure).

    This delay is disabled during an actual source fail-ure. If the timer is set for more than 0 seconds, then

    the control activates the elevator pre-transfer out-put and time delay prior to transferring the transferswitch between two live sources. If the control is ina Test or Exercise sequence, the control adds anadditional delay prior to activating the transfer andretransfer commands. After the TDNE (and/orTDEN) time delay expires, the control activates theElevator output and starts the TDEL timer.

    The output relay has two normally open and twonormally closed contacts, rated 5 amps at 380volts.

    When the timer expires, the control issues thetransfer (or retransfer) command. When the timeris inactive or expires, the control deactivates therelay output.

    The Elevator Pre-transfer Time Delay is configur-able for 0 (disabled), 1, 2, 3, 5, 30, 120, or 300 sec-onds (default = 0 seconds).

    Transfer Inhibit and Retransfer Inhibit do NOT af-fect or delay the elevator pre-transfer delay while itis active.

    The Override pushbutton or Override input has noeffect on this time delay.

    The GTEC control also includes a feature calledElevator Post Transfer Delay that keeps the eleva-tor output active for the same TDEL time period af-ter the transfer switch transfers. For more informa-tion, see Elevator Post Transfer Delay below.

    Elevator Post Transfer Delay

    The Elevator Post Transfer Delay feature keeps theelevator output active for the same TDEL time peri-od after the transfer switch transfers. Instead of de-activating the elevator output when the pre-transfertime delay expires, the control keeps the output ac-tive and starts the TDEL timer again after it sensesthat the transfer switch has transferred. When theTDEL timer expires the second time, the control de-activates the elevator output. The Elevator PostTransfer Delay is configurable to be enabled (On)or disabled (Off) (default = Off).

  • 4-3

    MANUAL OPERATION

    The transfer switch has an operator handle formanually transferring the load (see Figure 4-1).Manual operation must be performed by qualifiedpersonnel under NO-LOAD CONDITIONS ONLY.Use the following procedure:

    WARNING Manual operation of the transferswitch under load presents a shock hazard thatcan cause severe personal injury or death. Donot attempt to operate the switch manuallywhen it is under load. Disconnect both sourcesof power before operating manually.

    1. Verify that the transfer switch is not under load.

    2. Open the cabinet door of the automatic trans-fer switch.

    3. Remove power to the control by removing theFB fuse (see Figure 4-1).

    4. To close Side A:

    a. Place the handle on the transmissionshaft.

    b. Rotate it upwards until the switch locks.

    To open either side (Side A or Side B):

    a. Remove the manual operation handle.

    b. Press the trip with a screwdriver.

    To close Side B:

    a. Place the handle on the transmissionshaft.

    b. Press and hold Select with a screwdriverwhile rotating the handle upwards until theswitch locks.

    NOTE: Remember that the transfer switchtransfers the load to the active powersource. (If both power sources areavailable, it transfers the load to theutility.)

    WARNING If not removed, automatictransfer switch operation results in rapidmovement of the manual operator handleand presents a hazard of severe personalinjury. Remove the handle before switch-ing back to automatic operation. Store themanual operation handle in a safe location(for example, the bottom of the cabinet).

    5. Make sure the manual operation handle is re-moved from the transmission shaft and storedin a safe location.

    6. To return to automatic operation, restore pow-er to the control by reinserting the FB fuse.

    7. Close the cabinet door.

    TRANSFER SWITCHMANUAL OPERATION

    HANDLE

    FB FUSE

    FUSE HOLDERSON DIN RAIL

    TRANSMISSIONSHAFT

    FIGURE 4-1. MANUAL OPERATION HANDLE

  • 4-4

    PUSHBUTTON OPERATION

    The following describes operation of the threepushbuttons located on the control panel.

    Test Pushbutton

    The Test pushbutton is used to:

    Start a genset test. The Test LED flashes andstays on if the Test pushbutton is pressed andheld for two seconds.

    Terminate a genset test. The Test LED flashesfor two seconds and goes out if the Test push-button is momentarily pressed.

    More information on testing is included on the fol-lowing pages.

    Override Pushbutton

    The Override pushbutton is used to:

    Terminate the following system time delays:

    Time Delay Engine Start (TDES)

    Time Delay Normal to Emergency (TDNE)

    Time Delay Emergency to Normal (TDEN) Bypass the TDNE timer and transfer the load

    immediately during an active Transfer Inhibitinput.

    Bypass the TDEN timer and retransfer the loadimmediately during an active Retransfer Inhib-it input.

    Stop the Utility Power Connected LED fromflashing as a result of a failure to connect to ordisconnect from the utility when commanded.

    Stop the Genset Power Connected LED fromflashing as a result of a failure to connect to ordisconnect from the genset when command-ed.

    Cancel an active exercise period.

    The Program Transition (TDPT), Elevator signal(TDEL), and Engine Cool Down (TDEC) time de-lays are not affected by pressing this pushbutton.

    Set Exercise Pushbutton

    This pushbutton is only used with the integrated ex-erciser and only functions if the External Exercisefunction is disabled (set to Off). Information on con-figuring the control panel is included in Section 5.

    The Set Exercise pushbutton is used to:

    Set a delayed repeat exercise period when thepushbutton is pressed and held for five sec-onds.

    Start an immediate exercise period (that alsorepeats) if the pushbutton is pressed momen-tarily within ten seconds of starting the delayedexercise period.

    Cancel a repeatable exercise period if thepushbutton is pressed and held for five sec-onds.

    More information on using the integrated exerciseris included on page 4-8.

  • 4-5

    TEST WITH OR WITHOUT LOAD

    This feature allows a transfer switch operator totest the transfer switch and generator power sys-tem. The test is configurable to be with load or with-out load. A test with load initiates a load transfer. Atest without load just starts the generator and runs itwithout load.

    1. Verify that the transfer switch is set to test withor without load, as desired (see Section 5).

    2. To start a test, press and hold the Test Push-button for two seconds or ground the RemoteTest input.

    3. To end the test, momentarily press the Testpushbutton or remove the ground from the Re-mote Test input.

    NOTE: When ending a test with load, you canbypass the retransfer time delay(TDEN) and cause the immediate loadretransfer by pressing the Overridebutton. The generator stops after theengine cooldown time delay (TDEC).

    Test With Load Sequence of Events

    The following describes the sequence of events ofan GTEC transfer switch during a test with load. Inthis example, TDPT is set to zero, the phase checksensor is disabled, the Transfer Inhibit and Retran-sfer Inhibit inputs are inactive, and TDEL is set tozero.

    The utility must be acceptable during the entire testevent. Acceptability is determined by the activesource sensor (undervoltage sensor). If, at anytime, the undervoltage sensor determines that theutility is not acceptable, the Test is terminated.

    Before a test can begin, the transfer switch must beconnected to the utility power source and utilitypower must be available.

    1. Verify that the transfer switch is set to test withload.

    2. Verify that the green Utility Power ConnectedLED on the control panel is lit.

    3. Verify that the green Utility Power AvailableLED on the control panel is lit.

    4. Press and hold the control panel Test pushbut-ton for two seconds or ground the Remote Testinput to initiate the Test. The Test LED flashestwo times per second for two seconds, ac-knowledging that the test was activated. Oncethe test period starts, the Test LED stays oncontinuously.

    5. The control simulates a utility power failure butthe Utility Power Available LED remains lit aslong as the utility is still available.

    6. The control starts the TDES timer. After thetimer expires, the control de-energizes thestart relay, closing the start contact to signalthe generator to start.

    7. When the generator output is acceptable (theGenset Power Available LED is lit) the controlstarts the TDNE timer.

    8. After the TDNE timer expires, the transferswitch transfers to the genset (the GensetPower Connected LED is lit).

    9. The control continues to run the generator withthe transfer switch connected to the genset un-til the control panel Test pushbutton is momen-tarily pressed or the ground is removed fromthe Remote Test input.

    10. After this action, the control starts the TDENtimer. The Test LED flashes twice per secondfor two seconds to acknowledge the operationand then the Test LED goes out.

    11. After the TDEN timer expires, the transferswitch retransfers back to the utility (the UtilityPower Connected LED is lit).

    12. Once the transfer switch is connected to utilitypower, the control starts the TDEC timer.

    13. After the timer expires, the control energizesthe start relay, opening the start contact to sig-nal the generator to stop.

  • 4-6

    Test Without Load Sequence of Events

    The following describes the sequence of events ofa GTEC transfer switch during a test without load.In this sequence of events, the generator is startedand runs without load for the duration of the test.

    The utility must be acceptable during the entire testevent. Acceptability is determined by the activesource sensor (undervoltage sensor). If, at anytime, the undervoltage sensor determines that theutility is not acceptable, the Test is terminated.

    Before a test can begin, the transfer switch must beconnected to the utility and utility power must beavailable.

    1. Verify that the transfer switch is set to test with-out load.

    2. Verify that the green Utility Power ConnectedLED on the control panel is lit.

    3. Verify that the green Utility Power AvailableLED on the control panel is lit.

    4. Press and hold the control panel Test pushbut-ton for two seconds or ground the Remote Testinput. The Test LED flashes twice per secondfor two seconds acknowledging that the testwas activated. Once the test period starts, theTest LED stays on continuously.

    5. The control de-energizes the start relay, clos-ing the start contact to signal the generator tostart. When the genset starts and producespower, the amber Genset Power AvailableLED lights.

    6. The control continues to run the generatorwithout load until the control panel Test push-button is momentarily pressed or the ground isremoved from the Remote Test input.

    7. After the control panel Test pushbutton is mo-mentarily pressed or the ground is removedfrom the Remote Test input, the control flashesthe Test LED twice per second for two secondsto acknowledge the operation and then goesout.

    8. The control energizes the start relay, openingthe start contact to signal the generator to stop.

  • 4-7

    SENSORS

    Utility Sensor

    The utility sensor monitors all phases of the utilityfor undervoltage conditions. Both the pickup anddropout set points are adjustable. The set pointsare listed in Table 4-1. Refer to Section 5 for infor-mation on how to make adjustments.

    TABLE 4-1. UTILITY UNDERVOLTAGE SET POINTS

    Description Available Set Points

    Undervoltage Pickup (% of Nominal)

    95%

    90%

    Undervoltage Dropout (% of Nominal)

    90%

    85%

    80%

    70%

    Overvoltage Pickup 120%

    Overvoltage Dropout 125%

    Underfrequency Pickup

    80%

    Underfrequency Dropout

    70%

    Overfrequency Pickup 130%

    Overfrequency Dropout

    140%

    NOTE: If the utility undervoltage pickup is set at90%, then the dropout has to be set lowerthan 90%.

    Figure 4-2 illustrates how the pickup and dropoutsettings work.

    VOLTS

    NominalSetpoint(240V)

    Pick-upSetting(216V)

    Drop-outSetting(194V)

    90% ofNominal

    85% ofNominal

    Example using Default Settingsfor Nominal Voltage of 240 VAC

    FIGURE 4-2. UNDERVOLTAGE SENSING

    Generator Sensor

    The generator sensor is a single phase sensor thatmonitors undervoltage and underfrequency condi-tions. All the pickup and dropout settings are fixedand are not adjustable. The genset undervoltageand underfrequency set points are listed in Table4-2.

    TABLE 4-2. GENSET UNDERVOLTAGE ANDUNDERFREQUENCY SET POINTS

    Description Set Point

    Undervoltage Pickup (% of Nominal) 90%

    Undervoltage Dropout (% of Nominal) 75%

    Underfrequency Pickup(% of Nominal) 90%

    Underfrequency Dropout(% of Nominal) 85%

    Phase Check Sensor

    The phase check sensor can be enabled (set toOn) for applications that require a fast transfer of aload between two live sources (both power sourceavailable LEDs are lit). The phase check sensordetermines when the relative phase difference(less than 25 degrees and approaching 0) and thefrequency difference (less than 1 Hz) of the twosources are within specified limits. When all condi-tions are met, a transfer is initiated. If enabled, thephase check sensor is activated after all time de-lays have expired, just before the transfer switchtransfers the load, and only when both sources areavailable. Information on configuring the PhaseCheck On/Off function is included in Section 5.

    Return to Programmed Transition

    This feature can be used in conjunction with thephase check sensor. If, for some reason the twosources do not fall within the specified limits of thephase check sensor for a period of two minutes,then the control bypasses the phase check sensor,returns to the Programmed Transition sequence ofoperation, and transfers the load. If this feature isenabled, the programmed transition time delay(TDPT) should be set greater than zero. The actualsetting depends on your load.

  • 4-8

    GENERATOR SET EXERCISER

    Run the generator at least once each week with atleast 50 percent load (if possible). If you do notwant to use the exerciser, use the Test pushbutton,as described earlier in this section, to test the gen-erator set each week.

    The control panel includes an integrated exerciserthat is set by pressing the Set Exercise pushbutton.In addition, there may also be an optional fully pro-grammable external exerciser clock installed andwired to a control input (see page 4-10).

    If both types of exercisers are available, only oneexerciser can operate at a time. The control panelmust be configured for the type of exerciser beingused. This is done by setting the External Exerciserfunction On or Off. If the integrated exerciser isused, the External Exercise On/Off function mustbe set to Off. If the external exerciser is used, theExternal Exercise On/Off function must be set toOn. If the external exerciser is factory supplied, theExternal Exercise On/Off function is set to On at thefactory. If the external exerciser is not factoryinstalled, the External Exercise On/Off function isset to Off. Information on configuring the control isincluded in Section 5. Information on the optionalexternal exerciser is included later in this section.

    Exercise With or Without Load

    The exercise with/without load configuration workswith both types of exercisers (default = withoutload) see Section 5. When With Load is se-lected, the load is transferred to the genset. WhenWithout Load is selected, the genset runs with noload for the duration of the exercise period.

    Integrated Exerciser

    This function is standard and is built into the con-trol. With this exerciser, the exercise period is 20minutes and it repeats every 7, 14, 21, or 28 days(default = 7 days) see Section 5.

    The integrated exercise function cannot be usedunless the External Exercise function is disabled(set to Off).

    Before an exercise can begin, the transfer switchmust be connected to utility power and utility powermust be available (the green Utility Power Avail-able LED must be lit).

    Power Loss Backup

    If DC power is removed from the control panel, theexercise clock uses a replaceable lithium battery(part number 4161250) to back up the time set-ting. The battery is good for ten years and doesntneed to be serviced. The battery is attached to thetime chip on the control board.

    If no exercise period is set, the Exercise LED is off(see Figure 3-5).

    Setting the Integrated Exercise Period

    1. Verify that the Exercise LED is off and the Ex-ternal Exercise function is disabled (set to Off see Section 5). If the External Exercise func-tion is enabled, the integral exerciser is dis-abled.

    2. To set the exercise start time for a repeat exer-cise period, press and hold the Set Exercisepushbutton for 5 seconds. The Exercise LEDflashes at a rate of twice per second for 5 sec-onds and then stays on when the exercise pe-riod is set. A delayed 20 minute exercise pe-riod will start in 12 hours. At that time, the Exer-cise LED flashes at a rate of once per secondduring the entire exercise period. When the ex-ercise period is over, the Exercise LED quitsflashing and remains on to signify that repeatexercise periods are enabled.

    3. To start an immediate exercise period andhave it repeat, momentarily press the Set Ex-ercise pushbutton a second time within tenseconds of starting the delayed exercise peri-od. Momentarily pressing and releasing theSet Exercise pushbutton a second time startsan immediate 20 minute exercise periodinstead of waiting for 12 hours. The ExerciseLED flashes at a rate of once per second dur-ing the entire exercise period. When the exer-cise period is over, the Exercise LED stopsflashing and remains on to signify that repeatexercise periods are enabled.

  • 4-9

    Canceling Repeat Exercise Periods

    With the control panel Exercise LED on steady,press and hold the Set Exercise pushbutton for 5seconds. The Exercise LED flashes at a rate oftwice per second for 5 seconds and then goes outto signify that repeat exercise periods are can-celled.

    Canceling An Active Exercise Period

    Active exercise periods can be canceled by press-ing the Override pushbutton on the control panel orby grounding the remote override input (P4-2) onthe back of the control panel.

    Power Source Failure During An ActiveExercise Period

    If either power source fails during an active exer-cise period, the control immediately terminates theexercise and proceeds with the automatic mode ofoperation.

    Exercise Without Load Sequence of Events

    1. When an exercise period becomes active, theExerciser LED flashes at a rate of once persecond.

    2. The control signals the generator to start andrun for 20 minutes.

    3. After the exercise period has ended, the con-trol signals the generator to stop.

    4. The Exercise LED stops flashing and remainson to signify that repeat exercise periods areset (unless there are no repeat exercise peri-ods). If there are no repeat exercise periods,the Exercise LED goes out.

    Exercise With Load Sequence of Events

    1. When an exercise period becomes active, theExerciser LED flashes at a rate of once persecond.

    2. The control signals the generator to start.

    3. When the generator output is acceptable, thecontrol transfers the load to the generator, fol-lowing the configuration set points.

    4. After the exercise period has ended, the con-trol retransfers the load back to the utility, fol-lowing the configured set points.

    5. Once the load is connected to utility power, thecontrol runs the genset unload for the durationof the cooldown timer (TDEC).

    6. After the TDEC timer expires, the control sig-nals the genset to stop.

    7. Unless the repeat exercise periods have beencanceled, the Exercise LED quits flashing andremains on to signify that repeat exercise peri-ods are set. If the exerciser is not set up to re-peat exercises, the Exercise LED goes out.

  • 4-10

    OPTIONAL EXTERNAL EXERCISER

    The optional external exercise clock is a 7-day,24-hour clock that, when installed, can store andexecute several start/stop programs per day andrepeat exercise periods every week. It can be pro-grammed to run exercise periods at different timeson different days. Unlike the integrated exerciser,the external exercise can schedule an exercise pe-riod for something other than 20 minutes.

    If the External Exercise function is enabled (set toOn), then the integrated exerciser is disabled.

    NOTE: After a period of inactivity, the clock enterssleep mode and turns off the display. To re-activate the display, briefly press the Menubutton.

    Up to 28 programs are available to set exercisestart and stop times. One program is required tostart an exercise period and a second one is re-quired to stop an exercise period.

    The exerciser clock also has a built-in test featurethat can be used to initiate a genset start and runcycle.

    The exerciser clock contains a lithium battery thatis used as a backup power source. The battery is

    not replaceable. When the clock is running off theinternal battery, three flashing dots are displayedbetween the hour and minute values (see Figure4-3). Unless the clock battery fails, exercise pro-grams are stored and are not lost during a poweroutage.

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    11:30AM

    Auto

    03 01 04Off

    .

    FIGURE 4-3. INDICATOR OF CLOCK RUNNINGOFF THE INTERNAL BATTERY

    Figure 4-4 illustrates the face of the exercise clockand provides information on the display and thefunction of the buttons.

    Exercise With or Without Load

    The external exercise clock does not include an ex-ercise with or without load function. This functionmust be configured using the transfer switch con-trol panel. For more information, see Section 5.

    RESET BUTTON USED ONLY IN CASE OF EMERGENCIESTO DELETE INDIVIDUAL SETTINGS (SEE PAGE 4-25)

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    11:30AM

    Auto

    03 01 04Off

    ok BUTTON USED TOCONFIRM SELECTION

    SUMMER/WINTERCHANGEOVER INDICATOR

    DATE (MONTH, DAY, AND YEAR)

    TIME OF DAY INDICATORS

    EXERCISE STATEINDICATOR (ON/OFF)

    DAY OF WEEK INDICATOR(1 = MONDAY, 7 = SUNDAY)

    TIME OF DAY

    MENU SELECTION BUTTON USED TOSELECT ONE OF FOUR DISPLAY MODES

    OR TO ABORT ADJUSTING PARAMETERS

    = SUMMER= WINTER

    +/ BUTTONS USED TO INCREASE/DECREASEVALUES, TO SCROLL THROUGH MENUS, AND TOSELECT SPECIAL FUNCTIONS

    INDICATORS OF WHENEXERCISES ARE SCHEDULEDFOR THE CURRENT DAY

    DISPLAY MODE (AUTO,PROG, , OR MAN)

    SPECIAL FUNCTION INDICATORS= OVERRIDE ON/OFF= PERMANENT ON/OFF

    FIGURE 4-4. EXERCISE CLOCK FEATURES

  • 4-11

    Using the Menu Button

    The Menu selection button is used to select threedisplay modes that have adjustable menus.

    The Clock mode ( ) is used to set the correctdate and time. This mode can also be used toautomatically switch to the correct summer/win-ter time. See page 4-11.

    The Program mode (Prog) is used to set (seepage 4-14), review (see page 4-17), and clearexercise start/stop times (see pages 4-19 and4-21).

    The Manual mode (Man) is used to enter a4-digit code to prevent changing settings by un-authorized personnel. See page 4-24.

    When adjustments are completed, the Home menu(Auto mode) is redisplayed (see Figure 4-4). TheMenu button can also be used to abort adjustingparameters and return to the Home menu.

    Using the +/ Buttons

    Pressing the + or button is used to:

    Increase or decrease a parameter in an adjust-able menu

    Select the next or previous menu.

    Simultaneously pressing the + and buttons isused to select special functions.

    Initiate an exercise (see page 4-22)

    Override an active exercise (see page 4-22)

    Select permanent on/off mode (see page 4-23)

    Using the ok Button

    The ok button is used to confirm the menu selec-tion or program adjustments you have made. Uponpressing the ok button, the next available menu isdisplayed and, if any program adjustments weremade, the changes are saved.

    Setting the Clock with Summer/WinterTime (Daylight Savings Time)

    The clock is programmed with the correct date andcentral USA standard time and with the correctdaylight savings time settings. If it is necessary tochange these settings, the following describes howto adjust the time and date and how to set the clock

    to automatically switch to summer/winter time(daylight savings time).

    01 01 03

    12:00 PMOff

    Auto

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    1. Press the Menu button on the exercise clock.The Program menu is displayed.

    PROGRAM

    Auto Prog Man

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    2. Press the + button. The Date/Time menu isdisplayed.

    DAT/TIME

    Auto Prog Man

    FLASHES

    11:07 AM0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    3. Press the ok button to display the Year menu.

    YEAR

    20 03FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    4. Press the + or button to set the correct year.Press the ok button to display the Monthmenu.

    MONTH

    03FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

  • 4-12

    5. Press the + or button to set the correctmonth. Press the ok button to display the Daymenu.

    DAY

    03.05FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    6. Press the + or button to set the correct day.Press the ok button to display the Hour menu.A small triangle is displayed above the as-signed number in the display for the day of theweek (1 = Monday, 7 = Sunday).

    HOUR

    11:08 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    TRIANGLE

    7. Press the + or button to set the correct hour.A line is displayed on the screen indicating thehour of the day selected (the left side of thescreen is for the first half of the day [AM] andthe top of the screen is for the second half ofthe day [PM]). Press the ok button to displaythe Minute menu.

    MINUTE

    11:09 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    8. Press the + or button to set the correct min-ute. Press the ok button to display the Sum-mer/Winter menu.

    FLASHESSUM/WIN

    11:09 AM0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    NOTE: If you do not wish to set the clock forautomatic summer/winter changeoverat this time, press the + or button.End is displayed on the screen.

    Press the ok button to return to theHome menu.

    FLASHESEND

    11:09 AM0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    9. Press the ok button to display the No Summer/Winter menu.

    NO SU/WI

    11:10 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    10. Press the + or button to display the WithSummer/Winter menu.

    WITH S/W

    11:10 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    11. Press the ok button to display the World Areamenu.

    USA/CAN

    11:10 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    12. Either select one of the world areas that hasbeen programmed for automatic time correc-tion or else set up your own changeover times.

    NOTE: With the Daylight Savings Time pro-gram set for North America, The second Sunday in March

    moves the time forward one hour.

    The first Sunday in November moves the time back one hour.

    If you wish to select one of the world areas(Europe, GP/P, SF/GR/TR, USA/CAN)that has been programmed for automatic

  • 4-13

    time correction, press the + or buttonsuntil the correct world area is selected. Goto step 19.

    EUROPE

    11:10 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    If you wish to set up your own changeovertimes, continue with step 13.

    13. To set up your own changeover times, pressthe + or buttons from the World Area menuuntil the word Free is displayed.

    FREE

    11:10 AMFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    14. Press the ok button to display the menu forsetting the month when the Summer change-over will take place. Press the + or buttonsuntil the desired month is displayed.

    MONTH SUAM01.01

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    15. Press the ok button to display the menu forsetting the week when the Summer change-

    over will take place. Press the + or buttonsuntil the desired week (1 thru 5 [1 = first week,4 = fourth week, 5 = last week]) is displayed.

    WEEK SUAM06.01

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    16. Press the ok button to display the menu forsetting the hour of the day when the Summerchangeover will take place. Press the + or buttons until the desired hour (1 thru 3) is dis-played.

    HOURAM01:

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    NOTE: The starting time can only be set for1:00, 2:00, or 3:00 AM.

    17. Press the ok button to display the menu forsetting the month when the Winter change-over will take place. Press the + or buttonsuntil the desired month is displayed.

    MONTH WIAM02.01

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

  • 4-14

    18. Press the ok button to display the menu forsetting the week when the Winter changeoverwill take place. Press the + or buttons untilthe desired week (1 thru 5 [1 = first week, 4 =fourth week, 5 = last week]) is displayed.

    WEEK WIAM09.04

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    NOTE: The starting time for the winterchangeover is the same time thatwas set in step 16.

    19. Press the ok button. The Home menu is redis-played and the appropriate summer/wintersymbol is displayed.

    03 01 04

    11:12 AMOff

    Auto

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    Setting Exercise Start and Stop Times

    Up to 28 programs can be used to set exercise startand stop times. One program is required to start anexercise period and a second one is required tostop an exercise period.

    NOTE: If the Menu button is pressed before aStart/Stop program is saved, the wordEscape is displayed on the screen. Theprogram settings are lost and the Homemenu is displayed after two seconds orby pressing the ok button.

    ESCAPE

    Prog FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    1. From the Home menu, press the Menu button.The Program menu is displayed.

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    PROGRAM

    Auto Prog Man

    FLASHES

    2. Press the ok button. The New Program menuis displayed.

    NEW PROG

    Prog FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    3. Press the ok button. The number of availableprogrammable time periods (maximum of 28)is temporarily displayed.

    FREE

    Prog

    28

    NUMBER OFAVAILABLE

    PROGRAMMABLETIME PERIODS

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    4. The Starting Time (Time On) menu is dis-played. Press the ok button.

    TIME ON

    Prog

    OnFLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

  • 4-15

    5. The Hour menu is displayed. Press the + or buttons to set the desired exercise startinghour (default = 12:00 AM). A line is displayedon the screen indicating the hour of the day se-lected (the left side of the screen is for the firsthalf of the day [AM] and the top of the screenis for the second half of the day [PM]). Pressthe ok button.

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    HOUR

    Prog

    On

    12:00AMFLASHES

    6. The Minute menu is displayed. Press the + or buttons to set the desired exercise startingminute. Press the ok button.

    MINUTE

    Prog

    On

    11:30 PM

    FLASHES

    0

    3

    6

    9

    12 15 18 21 24

    1 2 3 4 5 6 7

    7. A menu is displayed for selecting the day of theweek the exercise is to begin (default =Monday). Press the + or buttons to select thedesired day of the