Asset: I.S. 53 - QUEENS, 10-45 NAMEOKE STREET, New York, 11691 Inspection Id Inspection Type Time In Last Edited SA : Q053 Architectural - Senior 2018-10-11 7:50 AM 2018-11-09 2:38 PM AA : Q053 Architectural - Associate 2018-10-11 8:52 AM 2018-10-30 4:32 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Security Lighting, Exterior Soffits, Exterior Guards and Window Lintels were inaccessible due to construction scaffolding and netting. Boys Locker Room was being used for storage and the Boys Shower Room has been sealed - both rooms were inaccessible for inspection. Principal(s) Information Principal Name Andrea Yard Organization I.S. 53 - Brian Piccolo School - Queens Did you meet with this Principal? No Did this Principal provide feedback? No Principal Name Doris Lee Organization Village Academy - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: The Auditorium in need of renovation. Seating is in poor condition. Principal Name Ty Redmond Organization Success Academy - Queens Did you meet with this Principal? No Did this Principal provide feedback? No Custodian David Paretti Fireman Daniel Hourihan Building Square Footage 164000 Comments on the Area None Comments on the Stories (Floors) plus Basements 4+B (Partial) Comments on the Number of Classrooms 64 Comments on the Year Built 1972 Student Population 890 Staff Population 157 Weather Fair Facade Photo NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q053 PB/A&W Print Date: 6/21/2019 Page 1 of 33

NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Asset: I.S. 53 - QUEENS, 10-45 NAMEOKE STREET, New York, 11691

Inspection Id Inspection Type Time In Last Edited

SA : Q053 Architectural - Senior 2018-10-11 7:50 AM 2018-11-09 2:38 PM

AA : Q053 Architectural - Associate 2018-10-11 8:52 AM 2018-10-30 4:32 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment Security Lighting, Exterior Soffits, Exterior Guards and WindowLintels were inaccessible due to construction scaffolding and netting.

Boys Locker Room was being used for storage and the Boys ShowerRoom has been sealed - both rooms were inaccessible for inspection.

Principal(s) Information

Principal Name Andrea Yard

Organization I.S. 53 - Brian Piccolo School - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? No

Principal Name Doris Lee

Organization Village Academy - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: The Auditorium in need ofrenovation. Seating is in poor condition.

Principal Name Ty Redmond

Organization Success Academy - Queens

Did you meet with this Principal? No

Did this Principal provide feedback? No

Custodian David Paretti

Fireman Daniel Hourihan

Building Square Footage 164000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 4+B (Partial)

Comments on the Number of Classrooms 64

Comments on the Year Built 1972

Student Population 890

Staff Population 157

Weather Fair

Facade Photo

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 1 of 33

Page 2: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Nameoke Street - North view

Main Entrance Photo

Facade A - Nameoke Street

Roof Photo

Roof 1 - West view

Have any Systems/Major Building Components been upgraded? Yes

Systems: Girls Locker Room converted to Exercise Room

Year: 2018

Systems: Toilet renovations all Toilets 1st to 4th Floor

Year: 2017

Systems: Courtyard repairs to Parapets, Coping and Flashing; Roof4 Railing Replacement.

Year: 2013

Systems: New Student Toilet Rooms in the Cafeteria and the 3rdFloor; Partial Coping replacement; New Window Guards;New Gymnasium Floor

Year: 2008

Systems: New Schoolyard and Window Curtains; Repairs toAuditorium Ceiling.

Year: 2007

Systems: New Roofing, Flashing and Skylights; Exterior Masonryrepointing and repairs.

Year: 1997

Have there been any New Building Additions? No

Tandem Schools? No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 2 of 33

Page 3: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No Potential FallingDebris

Deterioratedspalled concretefloor slab withexposedreinforcement isa potentialfalling debrishazard.

INTERIOR |STRUCTURAL| FLOORSTRUCTURE

Room B13 -Science LabAcid TankStorage Room

Daniel Hourihan Fireman

No Potential FallingDebris

Leaning Fenceis a potentialsafety hazard

SITE | FENCES South ofSchoolyard

Daniel Hourihan Fireman

No ProtrudingElements

Protruding metalwith sharp edgeis a potentialsafety hazard.

INTERIOR |AUDITORIUM| Fixed Seating

Seats B/2, D/2 Daniel Hourihan Fireman

No Tripping Hazard Heaving SafetySurface is apotentialtripping hazard

SITE |PLAYGROUNDS | SafetySurfacing

Left Side Daniel Hourihan Fireman

Yes Tripping Hazard Heaving DOT isa potentialsafety hazard.

SITE | PAVING| DOT Sidewalk| Concrete

Bayport Place Daniel Hourihan Fireman

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 3 of 33

Page 4: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps Yes No Railing Height < 34 or >38 Inches

Rooms & Spaces

Art Rooms No

Auditorium 3rdFloor Yes No H/C Lift Inoperable No No

Cafeteria 1st Floor Yes Yes Yes Yes

Classrooms 1st - 4th Floors Yes Yes

Computer Rooms Room 268 Yes Yes

Gymnasium 1st Floor Yes Yes Yes Yes

Library Room 347 Yes Yes

Main Office Room 109 - I.S. 53 - Queens, Room 311 -Success Academy, Room 447B - VillageAcademy

Yes Yes

Multi-purpose Room No

Nurse's Room Room 113 Yes Yes

Pool No

Science Lab Room 279, Room 406, Room 408 Yes Yes

Toilet Rooms (Boys) 1st - 4th Floors Yes Yes

Toilet Rooms (Girls) 1st - 4th Floors Yes Yes

Toilet Rooms (Staff) 1st - 4th Floors Yes Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 4 of 33

Page 5: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1

Instance Condition 3 - Fair

Instance Quantity 1

Instance Quantity Uom EACH

Deficiency AREAWAY GRATINGS: MAJOR RUSTING AND / OR BROKENSUPPORTS

Roof Plan reference

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 5 of 33

Page 6: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

EXTERIOR

AREAWAY

Deficiency Photo1

AW1

Violations No violations recorded.

AWNINGS AND CANOPIES Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CHIMNEY Under Construction

COPING Under Construction

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 5 - Poor

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION

Roof Plan reference

Deficiency Quantity 8

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Exit 5

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 6 of 33

Page 7: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

EXTERIOR

DOORS

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Does not Exist

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 72,000

Replacement Uom S.F.

Under ConstructionInstance on All Facades

Instance Quantity 72,000

Instance Quantity Uom S.F.

EXTERIOR SOFFITS Inaccessible

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry, Concrete

Replacement Quantity 9,000

Replacement Uom C.F.

Under ConstructionInstance on Brick

Instance Quantity 8,000

Instance Quantity Uom C.F.

Under ConstructionInstance on Concrete

Instance Quantity 1,000

Instance Quantity Uom C.F.

PLAZA DECK Inspected

Under ConstructionInstance on Concrete: Roof 4

Instance Quantity 10,000

Instance Quantity Uom S.F.

ROOF Inspected

Roofing Inspected

Replacement Quantity 48,500

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Does not Exist

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Under Construction

ROOF BARRIER Under Construction

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

Under ConstructionInstance on Modified Bitumen: Roofs 1, 2, 3, 5

Instance Quantity 48,500

Instance Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 7 of 33

Page 8: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

EXTERIOR

ROOF

Roofing Inspected

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Under Construction

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Inspected

Condition 2 - Between Good and Fair

Deficiency HEIGHT LESS THAN 18"

Roof Plan reference

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 1

Deficiency Photo1 No photo recorded

Violations No violations recorded.

SKYLIGHT/ROOF VENT Under Construction

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Does not Exist

RAILINGS Under Construction

STAIRS/RAMPS Under Construction

WINDOWS Inspected

Replacement Quantity 20,000

Replacement Uom S.F.

EXTERIOR GUARDS Inaccessible

LINTELS Inaccessible

WINDOWS Inspected

Material Type(s) Aluminum

Under ConstructionInstance on Aluminum - Double Hung: All Facades

Instance Quantity 2,000

Instance Quantity Uom S.F.

Under ConstructionInstance on Aluminum - Other: All Facades

Instance Quantity 18,000

Instance Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 8 of 33

Page 9: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency CONCRETE BEARING WALL:CRACKED/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Room 446 - 4th Floor Fan Room, Facade B

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Facade B view from Rom 279

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 4 - Between Fair and Poor

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Multiple locations throughout the cations throughout the Basementincluding the Electrical Room, Fan Room, Corridors and StorageRoms

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Room B11

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Room B13 - Science Lab Acid TankRoom

Deficiency Quantity 25

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 9 of 33

Page 10: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Potential Action REPAIR

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Room B13 - Science Lab Acid TankRoom

Violations No violations recorded.

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Room 446, 4th Floor connecting corridor, Kitchen Storage Room, OilTank Room

Deficiency Quantity 160

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Room 446 - Fan Room(Room 446, 4th Floor connecting corridor,Kitchen Storage Room , Oil Tank Room similar)

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 3 - Fair

Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE

Deficiency Location/Instance Corridor near AW1

Deficiency Quantity 70

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 10 of 33

Page 11: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo1

Corridor near AW1

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Room 447, Corridor near Stair D

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Room 447 ( Corridor new Stair D similar)

Violations No violations recorded.

VAULTS-BUNKERS Does not Exist

AUDITORIUM Inspected

InspectedInstance on 3rd Floor - 695 Seats

Ceiling

InspectedInstance on 3rd Floor - 695 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 3rd Floor - 695 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed H/C Lift

InspectedInstance on 3rd Floor - 695 Seats

Condition 5 - Poor

Deficiency INOPERABLE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 11 of 33

Page 12: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

AUDITORIUM

Fixed H/C Lift

Deficiency Location/Instance Right Side

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Fixed Seating

InspectedInstance on 3rd Floor - 695 Seats

Condition 5 - Poor

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats B/2, D/2

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Seat D/2

Violations No violations recorded.

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seats A/7, C/4, D/4, F/2, H/6 and others

Deficiency Quantity 80

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Seat A/7

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 12 of 33

Page 13: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

AUDITORIUM

Floor Finish

InspectedInstance on 3rd Floor - 695 Seats

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Near Entrance, Near Stage

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Entrance

Violations No violations recorded.

Sliding-folding Partition

InspectedInstance on 3rd Floor - 695 Seats

Condition 5 - Poor

Deficiency MOTOR: INOPERABLE

Deficiency Location/Instance Center of Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Stage

InspectedInstance on 3rd Floor - 695 Seats

Stage Inspected

InspectedInstance on 3rd Floor - 695 Seats

Condition 3 - Fair

Deficiency DAMAGED FASCIA

Deficiency Location/Instance Right Side

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 13 of 33

Page 14: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

AUDITORIUM

Stage

Stage

Deficiency Photo1

Right Side

Violations No violations recorded.

Deficiency DAMAGED FLOOR

Deficiency Location/Instance Right Side

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Right Side

Violations No violations recorded.

Stage Curtain Rigging Inspected

InspectedInstance on 3rd Floor - 695 Seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 3rd Floor - 695 Seats

Condition 3 - Fair

Deficiency WORN/DETERIORATED

Deficiency Location/Instance Left Side

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 14 of 33

Page 15: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

AUDITORIUM

Stage

Stage Curtains

Deficiency Photo1

Left Side

Violations No violations recorded.

Walls

InspectedInstance on 3rd Floor - 695 Seats

Condition 2 - Between Good and Fair

Deficiency MASONRY: CRACKS/SPALLING

Deficiency Location/Instance Stage

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stage

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 3rd Floor - 695 Seats

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

Does not ExistInstance on 1st Floor

Door(s)

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on 1st Floor

Floor Finish

InspectedInstance on 1st Floor

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 15 of 33

Page 16: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

CAFETERIA

Floor Finish

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Rooms 163, 159, 157, 155

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 163

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 3 - Fair

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Lobby, Corridor near Gymnasium, Corridor near Cafeteria

Deficiency Quantity 2,700

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 16 of 33

Page 17: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Lobby

Violations No violations recorded.

Deficiency EPOXY FLOORING: DETERIORATED SUBSTRATE

Deficiency Location/Instance Room 279, 279A

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 279

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Corridor near Room 377, 285, 279

Deficiency Quantity 90

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 377

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 17 of 33

Page 18: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Rooms 461, 445, 268, 159, Corridor near Room 319 and others

Deficiency Quantity 400

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 455

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency MASONRY: CRACKS/SPALLING

Deficiency Location/Instance Corridor near Room 477

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 477

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Rooms 461, 447A, 127

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 18 of 33

Page 19: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Photo1

Room 447A

Violations No violations recorded.

Specialties Inspected

Classroom Locker(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Seating Does not Exist

GYMNASIUM Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 4 - Between Fair and Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Office

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 19 of 33

Page 20: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

GYMNASIUM

Floor Finish

InspectedInstance on 1st Floor

Condition 4 - Between Fair and Poor

Deficiency WOOD: DAMAGED/DETERIORATED

Deficiency Location/Instance Near Office (Picture doesn't show bubbling of the Floor)

Deficiency Quantity 350

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance Office

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Seating

Does not ExistInstance on 1st Floor

Sliding-folding Partition

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency WALL PADDING: DETERIORATED

Deficiency Location/Instance Near Entrance

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 20 of 33

Page 21: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

GYMNASIUM

Walls

Deficiency Photo1

Near Entrance

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Locker room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Locker room

Violations No violations recorded.

Floor Finish

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 21 of 33

Page 22: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

KITCHEN

Floor Finish

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency QUARRY TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Center

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Center

Violations No violations recorded.

Deficiency CONCRETE: CRACKS

Deficiency Location/Instance Room 128

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 128

Violations No violations recorded.

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

Under ConstructionInstance on Room 347

LOCKER ROOM Inspected

InaccessibleInstance on 1st Floor

MULTI-PURPOSE ROOM Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 22 of 33

Page 23: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Inspected

InspectedInstance on Room 279

Alternative use No

InspectedInstance on Room 406

Alternative use No

InspectedInstance on Room 408

Alternative use No

Fixed Equipment

InspectedInstance on Room 406

Condition 3 - Fair

Deficiency CABINETRY: MISSING/DAMAGED

Deficiency Location/Instance Room 406

Deficiency Quantity 8

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 406

Violations No violations recorded.

SCIENCE PREP ROOM Inspected

InspectedInstance on Room 279A

Alternative use No

InspectedInstance on Room 414

Alternative use Yes

Fixed Equipment

InspectedInstance on Room 414

Condition 1 - Good

Deficiency No deficiencies recorded

InspectedInstance on Room 279A

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SHOWER ROOM Inspected

InaccessibleInstance on 1st Floor

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 23 of 33

Page 24: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Door(s)

Condition 3 - Fair

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Stair E/1,4

Deficiency Quantity 3

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair E/4

Violations No violations recorded.

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency METAL: MISSING

Deficiency Location/Instance Corridor near Room 373

Deficiency Quantity 7

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Corridor near Room 373

Violations No violations recorded.

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 24 of 33

Page 25: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

TOILET ROOMS - STAFF

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Boys Locker Room

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Boys Locker Room

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency RUST - MAJOR

Deficiency Location/Instance Boys Locker Room

Deficiency Quantity 1

Quantity Uom EACH

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 25 of 33

Page 26: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Stalls

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Boys Locker Room

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency FENCING MISSING

Deficiency Location/Instance Near Exit 2

Deficiency Quantity 750

Quantity Uom S.F.

Potential Action INSTALL NEW

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance Near Exit 2

Deficiency Quantity 4

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 26 of 33

Page 27: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

CONTAINERIZATION

Deficiency Photo1

Near Exit 2

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Inspected

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Does not Exist

DRINKING FOUNTAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

FENCES Inspected

Condition 3 - Fair

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance South of Schoolyard

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

South of Schoolyard

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 27 of 33

Page 28: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

FENCES Inspected

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Near Exit 2

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Exit 2

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Near Exit 2

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Exit 2

Violations No violations recorded.

Pavers Does not Exist

Student Use Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 28 of 33

Page 29: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

PAVING Inspected

Student Use

Gravel Exists? No

Asphalt Inspected

Condition 4 - Between Fair and Poor

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 1,050

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Sidewalks & Walkways Inspected

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Back of Building

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Back of Building

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 29 of 33

Page 30: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

PAVING

Site Sidewalks & Walkways

Asphalt Inspected

Violations No violations recorded.

Concrete Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Nameoke Street

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Nameoke Street

Violations No violations recorded.

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 4 - Between Fair and Poor

Deficiency HEAVING

Deficiency Location/Instance Bayport Place

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Bayport Place

Violations No violations recorded.

Deficiency HEAVING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 30 of 33

Page 31: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Location/Instance Bayport Place

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Bayport Place

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Nameoke Street, Beach 18th Street, Foam Place, Bayport Place

Deficiency Quantity 1,225

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Nameoke Street

Violations No violations recorded.

Deficiency DAMAGED CURBS

Deficiency Location/Instance Nameoke Street, Beach 18th Street

Deficiency Quantity 50

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 31 of 33

Page 32: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Photo1

Nameoke Street

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard

Benches

Does not ExistInstance on Schoolyard

Fence

Does not ExistInstance on Schoolyard

Pavement

Does not ExistInstance on Schoolyard

Play Equipment

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency DETERIORATED/MISSING

Deficiency Location/Instance Left Side

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Left Side

Violations No violations recorded.

Unpaved Area

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 32 of 33

Page 33: NYC Department of Education - NYCSCA · NYC Department of Education Architectural Inspection Building Condition Assessment Survey ... Toilet renovations all Toilets 1st to 4th Floor

Question Response

SITE

PLAYGROUNDS Inspected

Unpaved Area

Does not ExistInstance on Schoolyard

PLAYING SURFACE Inspected

Playing Field Inspected

InspectedInstance on Schoolyard

Instance Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Running Track Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SEATING Inspected

Benches Inspected

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS: EXTERIOR Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q053

PB/A&W Print Date: 6/21/2019Page 33 of 33