Asset: P.S. 132 - QUEENS, 132-15 218 STREET, New York, 11413 Inspection Id Inspection Type Time In Last Edited SA : Q132 Architectural - Senior 2018-10-22 12:57 PM 2018-11-09 3:41 PM AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment Area Ways, Chimney, Louvers, and Exterior side Transom as well as Stair Cheek/Flank Walls all Inaccessible due to Scaffolding Student non use Concrete and Pavers are fenced off. Other inaccessible components: Site/Playgrounds - Westside Site/Seating/Benches Concrete Site/Seating/Bleachers-Concrete Site/Paving/Student Use Pavers Security Lights due to scaffolding Principal(s) Information Principal Name Alicia Hawkins Davis Organization P.S. 132 - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. General Toilet Room upgrades . 2. Water fountain not functioning properly. 3. Public Address (PA)System upgrades is a priority as not all of the classrooms can here announcements. 4. Clocks malfunctioning. 5. Video Cameras needed. 6. Sound system in Auditorium is not clear Custodian Was not present Fireman Was not present Building Square Footage 51000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 19 Comments on the Year Built 1928 Student Population 365 Staff Population 70 Weather Fair Facade Photo Corner of 218th Street and 132nd Road - Northeast View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q132 PB/A&W Print Date: 6/21/2019 Page 1 of 36

NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Asset: P.S. 132 - QUEENS, 132-15 218 STREET, New York, 11413

Inspection Id Inspection Type Time In Last Edited

SA : Q132 Architectural - Senior 2018-10-22 12:57 PM 2018-11-09 3:41 PM

AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment Area Ways, Chimney, Louvers, and Exterior side Transom as well asStair Cheek/Flank Walls all Inaccessible due to Scaffolding

Student non use Concrete and Pavers are fenced off. Otherinaccessible components:Site/Playgrounds - WestsideSite/Seating/Benches ConcreteSite/Seating/Bleachers-Concrete Site/Paving/Student Use Pavers

Security Lights due to scaffolding

Principal(s) Information

Principal Name Alicia Hawkins Davis

Organization P.S. 132 - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows: 1. General Toilet Roomupgrades . 2. Water fountain not functioning properly. 3. PublicAddress (PA)System upgrades is a priority as not all of the classroomscan here announcements. 4. Clocks malfunctioning. 5. Video Camerasneeded. 6. Sound system in Auditorium is not clear

Custodian Was not present

Fireman Was not present

Building Square Footage 51000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+B

Comments on the Number of Classrooms 19

Comments on the Year Built 1928

Student Population 365

Staff Population 70

Weather Fair

Facade Photo

Corner of 218th Street and 132nd Road -Northeast View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 1 of 36

Page 2: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Main Entrance Photo

Facade A - 218th Street

Roof Photo

Roof 3 - South View

Have any Systems/Major Building Components been upgraded? Yes

Systems: Schoolyard and Playground upgrade; Library Flooringreplacement; Classroom Flooring replacement (10);Partial Ash Hoist Vault Foundation Walls and Slabs, AshHoist Doors replacements

Year: 2014

Systems: Cafeteria Flooring replacement

Year: 2012

Systems: Exterior Doors and Frames replacement

Year: 2008

Systems: Sidewalk, Areaway Curbs and Grating. Ash Hoist Doors,Coping, Parapets, Exterior Handrails replacement,Exterior Walls repointing.

Year: 2007

Systems: Roofing, Roof Drains, Windows, Window Guardsreplacement; Bulkhead, Chimney repointing

Year: 1997

Have there been any New Building Additions? No

Tandem Schools? No

Leased Space? No

Priority Condition

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 2 of 36

Page 3: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? No

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings No No

Interior Routes

Corridor and Lobby H/C Lifts No Yes

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies No Change in Elevation

Interior Elevators No

Interior Lobby Doors and Hardware Yes

Interior Ramps No

Rooms & Spaces

Art Rooms No

Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route

Yes Yes

Cafeteria 1st Floor Yes No Not on Accessible Route Yes Yes

Classrooms None on Accessible Route Yes No Not on Accessible Route

Computer Rooms Rooms 309, 319 Yes No Not on Accessible Route

Gymnasium 3rd Floor Yes No Not on Accessible Route Yes Yes

Library Room 209 Yes No Not on Accessible Route

Main Office Room 255 Yes No Not on Accessible Route

Multi-purpose Room No

Nurse's Room Room 264 Yes No Not on Accessible Route

Pool No

Science Lab No

Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route

Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 3 of 36

Page 4: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InaccessibleInstance on AW10-AW10

Instance Quantity 10

Instance Quantity Uom EACH

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inaccessible

COPING Under Construction

CORNICE Does not Exist

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 3 - Fair

Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 4 of 36

Page 5: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo1

Facade G-Exit 7

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency STEEL: MINOR RUSTING

Roof Plan reference

Deficiency Quantity 15

Quantity Uom L.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

TRANSOM/SIDE LIGHT Inspected

Condition 3 - Fair

Deficiency METAL: BROKEN GLASS

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 5 of 36

Page 6: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

EXTERIOR

DOORS

TRANSOM/SIDE LIGHT

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency METAL: DENTED, MINOR RUSTING

Roof Plan reference

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 38,000

Replacement Uom S.F.

Under ConstructionInstance on All Facades

Instance Quantity 38,000

Instance Quantity Uom S.F.

EXTERIOR SOFFITS Does not Exist

LOADING DOCK Does not Exist

LOUVER Inaccessible

PARAPETS Inspected

Material Type(s) Masonry

Replacement Quantity 5,200

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 6 of 36

Page 7: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

EXTERIOR

PARAPETS

Replacement Uom C.F.

Under ConstructionInstance on All Facades

Instance Quantity 5,200

Instance Quantity Uom C.F.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 17,400

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inaccessible

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inaccessible

ROOF BARRIER Does not Exist

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

Under ConstructionInstance on Built-Up: All Roofs

Instance Quantity 17,400

Instance Quantity Uom S.F.

ROOFING DRAINS Inaccessible

Specialties Inspected

BULKHEAD/PENTHOUSE Under Construction

CUPOLA/ SPIRES/ TOWERS Does not Exist

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Inaccessible

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inaccessible

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 5 - Poor

Deficiency CONCRETE: CRACKS/SPALLING - MAJOR

Roof Plan reference

Deficiency Quantity 150

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 7 of 36

Page 8: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade C - Exit 3/4, 5/6 and Facade A - Exit 2

Violations No violations recorded.

WINDOWS Inspected

Replacement Quantity 4,500

Replacement Uom S.F.

EXTERIOR GUARDS Inaccessible

LINTELS Inaccessible

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: All Facades

Instance Condition 3 - Fair

Instance Quantity 4,500

Instance Quantity Uom S.F.

Installation Year 1997

Source of Installation Inspector Estimate

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 3 - Fair

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Storage Room, Boiler Room, Equipment Room, Fan Room

Deficiency Quantity 70

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 8 of 36

Page 9: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Deficiency Photo1

Boiler Room

Violations No violations recorded.

Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement - Mechanical Equipment Room, Boiler Room

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Mechanical Equipment Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Storage Room near Stairs

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 9 of 36

Page 10: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Deficiency Photo1

Storage Room near Stairs

Violations No violations recorded.

Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS

Deficiency Location/Instance Basement - Boiler Room, Basement - Oil tank Storage space

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete, Masonry

Condition 3 - Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance Basement - Tool Storage, Basement - Mechanical Equipment Room,Basement - Boiler Room

Deficiency Quantity 75

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 10 of 36

Page 11: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS

Deficiency Photo1

Basement - Boiler Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

VAULTS-BUNKERS Inspected

Foundation Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CRACKS, SPALLING

Deficiency Location/Instance Ash Hoist Vault

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

Ash Hoist Vault

Violations No violations recorded.

Slab Structure Inspected

Condition 3 - Fair

Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING

Deficiency Location/Instance Vault Area

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 11 of 36

Page 12: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STRUCTURAL

VAULTS-BUNKERS

Slab Structure

Deficiency Photo1

Vault Area

Violations No violations recorded.

Vault/Ash Hoist Doors and Framing Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

AUDITORIUM Inspected

InspectedInstance on 1st Floor - 562 seats

Ceiling

InspectedInstance on 1st Floor - 562 seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor - 562 seats

Condition 4 - Between Fair and Poor

Deficiency METAL: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Stage left

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stage left

Violations No violations recorded.

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Main Entrance

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 12 of 36

Page 13: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

AUDITORIUM

Door(s)

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance

Violations No violations recorded.

Fixed H/C Lift

Does not ExistInstance on 1st Floor - 562 seats

Fixed Seating

InspectedInstance on 1st Floor - 562 seats

Condition 4 - Between Fair and Poor

Deficiency DAMAGED/BROKEN/INOPERABLE

Deficiency Location/Instance Seat C/2, 6, 7, 19, 24, Q/2, and others

Deficiency Quantity 40

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Seat C/2

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor - 562 seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor - 562 seats

Stage

InspectedInstance on 1st Floor - 562 seats

Stage Inspected

InspectedInstance on 1st Floor - 562 seats

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 13 of 36

Page 14: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

AUDITORIUM

Stage

Stage Inspected

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 1st Floor - 562 seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

InspectedInstance on 1st Floor - 562 seats

Condition 3 - Fair

Deficiency WORN/DETERIORATED

Deficiency Location/Instance Main curtain

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main curtain

Violations No violations recorded.

Walls

InspectedInstance on 1st Floor - 562 seats

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stage rear

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stage rear

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 14 of 36

Page 15: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

AUDITORIUM

Walls

Violations No violations recorded.

Window Curtains/Shades/Blinds

InspectedInstance on 1st Floor - 562 seats

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CAFETERIA Inspected

InspectedInstance on 1st Floor

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Exit Vestibule 2

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit Vestibule 2

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 1st Floor

Condition 3 - Fair

Deficiency DAMAGED/MISSING

Deficiency Location/Instance Rear of Room

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 15 of 36

Page 16: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

CAFETERIA

Floor Finish

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 1st Floor

Stage

Does not ExistInstance on 1st Floor

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on 1st Floor

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 219, Corridor near Rooms 305, 314

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 219

Violations No violations recorded.

Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING

Deficiency Location/Instance Corridor near Room 150

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 16 of 36

Page 17: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling Inspected

Deficiency Photo1

Corridor near Room 150

Violations No violations recorded.

Door(s) Inspected

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Room 304

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 304

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES

Deficiency Location/Instance Room 319

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 17 of 36

Page 18: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Room 319

Violations No violations recorded.

Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET

Deficiency Location/Instance Room 319

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

Deficiency Photo1

Room 319

Violations No violations recorded.

Deficiency TERRAZZO: CRACKS

Deficiency Location/Instance Corridor near Room 154

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 154

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 18 of 36

Page 19: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Near near Exit 1, by Room 105

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Exit 1

Violations No violations recorded.

Deficiency SALT GLAZED BRICK: CRACKS/SPALLING

Deficiency Location/Instance Room 299, 300

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 299

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 201, 219, 319, 362

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 19 of 36

Page 20: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Walls

Deficiency Photo1

Room 319

Violations 35316951Y

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on 3rd Floor

Ceiling

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Office

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Door(s)

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR AND FRAME

Deficiency Location/Instance Office

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 20 of 36

Page 21: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

GYMNASIUM

Door(s)

Deficiency Photo1

Office

Violations No violations recorded.

Fixed Equipment

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Seating

InspectedInstance on 3rd Floor

Condition 3 - Fair

Deficiency DAMAGED FIXED SEATING

Deficiency Location/Instance Near the windows

Deficiency Quantity 1

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the windows

Violations No violations recorded.

Sliding-folding Partition

Does not ExistInstance on 3rd Floor

Stage

Does not ExistInstance on 3rd Floor

Walls

InspectedInstance on 3rd Floor

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 21 of 36

Page 22: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

GYMNASIUM

Walls

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Office

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Office

Violations No violations recorded.

Deficiency SALT GLAZED BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near the windows

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near the windows

Violations No violations recorded.

Window Curtains/Shades/Blinds

Does not ExistInstance on 3rd Floor

INTERIOR DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on 1st Floor

Ceiling

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 22 of 36

Page 23: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

KITCHEN

Ceiling

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 1st Floor

Condition 4 - Between Fair and Poor

Deficiency METAL: DAMAGED LOUVER

Deficiency Location/Instance Main Entrance

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Main Entrance

Violations No violations recorded.

Floor Finish

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 1st Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 209

Built-in Furnishing

Does not ExistInstance on Room 209

Ceiling

InspectedInstance on Room 209

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 209

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 209

Condition 2 - Between Good and Fair

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 23 of 36

Page 24: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

LIBRARY

Floor Finish

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 209

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Does not Exist

MULTI-PURPOSE ROOM Does not Exist

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Does not Exist

SCIENCE PREP ROOM Does not Exist

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Exit Vestibule 9

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit Vestibule 9

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair C/3

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 24 of 36

Page 25: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Ceiling

Deficiency Photo1

Stair C/3

Violations 35316951Y

Door(s) Inspected

Condition 5 - Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stair A/1, B/1

Deficiency Quantity 4

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/1

Violations No violations recorded.

Partition Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Railings Inspected

Condition 3 - Fair

Deficiency METAL: MISSING

Deficiency Location/Instance Exit Vestibule 1, 7

Deficiency Quantity 14

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 25 of 36

Page 26: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Railings

Deficiency Photo1

Exit Vestibule 1

Violations No violations recorded.

Stairs and Landings Inspected

Condition 3 - Fair

Deficiency ROLLED ASPHALT: CRACKS

Deficiency Location/Instance Stair B/3

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/3

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency BRICK: CRACKS/SPALLING

Deficiency Location/Instance Exit Vestibule 9

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 26 of 36

Page 27: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Walls

Deficiency Photo1

Exit Vestibule 9

Violations No violations recorded.

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair C/3

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 4

Deficiency Photo1

Stair C/3

Violations 35316951Y

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Stair A/1

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair A/1

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 27 of 36

Page 28: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 3 - Fair

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Room 356

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 356

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 5 - Poor

Deficiency PLASTER: CRACKS/SPALLING

Deficiency Location/Instance Stair B/1

Deficiency Quantity 200

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair B/1

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 28 of 36

Page 29: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

TOILET ROOMS - STAFF

Walls

Violations No violations recorded.

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Room 356

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 356

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/ MISSING

Deficiency Location/Instance Room 357

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 29 of 36

Page 30: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Walls

Deficiency Photo1

Room 357

Violations No violations recorded.

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Does not Exist

SITE Inspected

CONTAINERIZATION Inspected

Condition 5 - Poor

Deficiency CONTAINER DAMAGED

Deficiency Location/Instance 132nd Avenue

Deficiency Quantity 2

Quantity Uom EACH

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

132nd Avenue

Violations No violations recorded.

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 30 of 36

Page 31: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

SITE

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance Exit to 218th Street

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit to 218th Street

Violations No violations recorded.

Deficiency WROUGHT IRON: RUST - MAJOR

Deficiency Location/Instance 218th Street

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

218th Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance 218th Street

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 31 of 36

Page 32: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

SITE

FENCES

Deficiency Photo1

218th Street

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED/DETERIORATED

Deficiency Location/Instance 132nd Road, 132nd Avenue

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

132nd Road

Violations No violations recorded.

Deficiency CHAIN LINK: DAMAGED POST/RAIL

Deficiency Location/Instance 132nd Road, 132nd Avenue

Deficiency Quantity 20

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

132nd Road

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 32 of 36

Page 33: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

SITE

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Does not Exist

Concrete Inaccessible

Pavers Inaccessible

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 4 - Between Fair and Poor

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Does not Exist

Pavers Inaccessible

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 132nd Road, 218th Street, 132nd Avenue

Deficiency Quantity 150

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 33 of 36

Page 34: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

SITE

PAVING Inspected

DOT Sidewalk

Concrete

Deficiency Photo1

132nd Road

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard - East side

InaccessibleInstance on Schoolyard - West side

Benches

Does not ExistInstance on Schoolyard - East side

Fence

Does not ExistInstance on Schoolyard - East side

Pavement

Does not ExistInstance on Schoolyard - East side

Play Equipment

InspectedInstance on Schoolyard - East side

Condition 1 - Good

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard - East side

Condition 1 - Good

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Schoolyard - East side

PLAYING SURFACE Inspected

Playing Field Inspected

InspectedInstance on West side

Instance Condition 1 - Good

Deficiency No deficiencies recorded

Running Track Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT

Deficiency Location/Instance 132nd Avenue

Deficiency Quantity 10

Quantity Uom L.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 34 of 36

Page 35: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

SITE

RETAINING WALLS

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

132nd Avenue

Violations No violations recorded.

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

SEATING Inspected

Benches Inspected

Concrete Inaccessible

Metal/Wood/Plastic Inspected

Condition 1 - Good

Deficiency No deficiencies recorded

Bleachers Inspected

Concrete Inaccessible

Metal/Wood/Plastic Does not Exist

SITE WALLS (NOT RETAINING WALLS) Inspected

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR

Deficiency Location/Instance 132nd Avenue

Deficiency Quantity 30

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 35 of 36

Page 36: NYC Department of Education - NYCSCA · AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM Asset Data Question Answer Was the building fully accessible for

Question Response

SITE

SITE WALLS (NOT RETAINING WALLS)

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

132nd Avenue

Violations No violations recorded.

STAIRS/RAMPS: EXTERIOR Inspected

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Cheek/flank Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs/ramps Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q132

PB/A&W Print Date: 6/21/2019Page 36 of 36