Asset: P.S. 132 - QUEENS, 132-15 218 STREET, New York, 11413
Inspection Id Inspection Type Time In Last Edited
SA : Q132 Architectural - Senior 2018-10-22 12:57 PM 2018-11-09 3:41 PM
AA : Q132 Architectural - Associate 2018-10-22 1:05 PM 2018-11-09 11:27 AM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Area Ways, Chimney, Louvers, and Exterior side Transom as well asStair Cheek/Flank Walls all Inaccessible due to Scaffolding
Student non use Concrete and Pavers are fenced off. Otherinaccessible components:Site/Playgrounds - WestsideSite/Seating/Benches ConcreteSite/Seating/Bleachers-Concrete Site/Paving/Student Use Pavers
Security Lights due to scaffolding
Principal(s) Information
Principal Name Alicia Hawkins Davis
Organization P.S. 132 - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. General Toilet Roomupgrades . 2. Water fountain not functioning properly. 3. PublicAddress (PA)System upgrades is a priority as not all of the classroomscan here announcements. 4. Clocks malfunctioning. 5. Video Camerasneeded. 6. Sound system in Auditorium is not clear
Custodian Was not present
Fireman Was not present
Building Square Footage 51000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 19
Comments on the Year Built 1928
Student Population 365
Staff Population 70
Weather Fair
Facade Photo
Corner of 218th Street and 132nd Road -Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 1 of 36
Main Entrance Photo
Facade A - 218th Street
Roof Photo
Roof 3 - South View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Schoolyard and Playground upgrade; Library Flooringreplacement; Classroom Flooring replacement (10);Partial Ash Hoist Vault Foundation Walls and Slabs, AshHoist Doors replacements
Year: 2014
Systems: Cafeteria Flooring replacement
Year: 2012
Systems: Exterior Doors and Frames replacement
Year: 2008
Systems: Sidewalk, Areaway Curbs and Grating. Ash Hoist Doors,Coping, Parapets, Exterior Handrails replacement,Exterior Walls repointing.
Year: 2007
Systems: Roofing, Roof Drains, Windows, Window Guardsreplacement; Bulkhead, Chimney repointing
Year: 1997
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 2 of 36
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium 1st Floor Yes No No Stage AccessNot on Accessible Route
Yes Yes
Cafeteria 1st Floor Yes No Not on Accessible Route Yes Yes
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms Rooms 309, 319 Yes No Not on Accessible Route
Gymnasium 3rd Floor Yes No Not on Accessible Route Yes Yes
Library Room 209 Yes No Not on Accessible Route
Main Office Room 255 Yes No Not on Accessible Route
Multi-purpose Room No
Nurse's Room Room 264 Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 3 of 36
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InaccessibleInstance on AW10-AW10
Instance Quantity 10
Instance Quantity Uom EACH
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inaccessible
COPING Under Construction
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 3 - Fair
Deficiency METAL CLAD: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 4 of 36
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade G-Exit 7
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency STEEL: MINOR RUSTING
Roof Plan reference
Deficiency Quantity 15
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
TRANSOM/SIDE LIGHT Inspected
Condition 3 - Fair
Deficiency METAL: BROKEN GLASS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 5 of 36
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency METAL: DENTED, MINOR RUSTING
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 38,000
Replacement Uom S.F.
Under ConstructionInstance on All Facades
Instance Quantity 38,000
Instance Quantity Uom S.F.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inaccessible
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 5,200
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 6 of 36
Question Response
EXTERIOR
PARAPETS
Replacement Uom C.F.
Under ConstructionInstance on All Facades
Instance Quantity 5,200
Instance Quantity Uom C.F.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 17,400
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inaccessible
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inaccessible
ROOF BARRIER Does not Exist
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
Under ConstructionInstance on Built-Up: All Roofs
Instance Quantity 17,400
Instance Quantity Uom S.F.
ROOFING DRAINS Inaccessible
Specialties Inspected
BULKHEAD/PENTHOUSE Under Construction
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inaccessible
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inaccessible
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 5 - Poor
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 150
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 7 of 36
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C - Exit 3/4, 5/6 and Facade A - Exit 2
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 4,500
Replacement Uom S.F.
EXTERIOR GUARDS Inaccessible
LINTELS Inaccessible
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 3 - Fair
Instance Quantity 4,500
Instance Quantity Uom S.F.
Installation Year 1997
Source of Installation Inspector Estimate
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Storage Room, Boiler Room, Equipment Room, Fan Room
Deficiency Quantity 70
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 8 of 36
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo1
Boiler Room
Violations No violations recorded.
Deficiency CONCRETE COLUMNS/BEAMS:CRACKED/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Mechanical Equipment Room, Boiler Room
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Mechanical Equipment Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Storage Room near Stairs
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 9 of 36
Question Response
INTERIOR
STRUCTURAL
FLOOR STRUCTURE
Deficiency Photo1
Storage Room near Stairs
Violations No violations recorded.
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Boiler Room, Basement - Oil tank Storage space
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete, Masonry
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement - Tool Storage, Basement - Mechanical Equipment Room,Basement - Boiler Room
Deficiency Quantity 75
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 10 of 36
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS, SPALLING
Deficiency Location/Instance Ash Hoist Vault
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Ash Hoist Vault
Violations No violations recorded.
Slab Structure Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: MINOR RUSTING
Deficiency Location/Instance Vault Area
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 11 of 36
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Slab Structure
Deficiency Photo1
Vault Area
Violations No violations recorded.
Vault/Ash Hoist Doors and Framing Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
AUDITORIUM Inspected
InspectedInstance on 1st Floor - 562 seats
Ceiling
InspectedInstance on 1st Floor - 562 seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor - 562 seats
Condition 4 - Between Fair and Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Stage left
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stage left
Violations No violations recorded.
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Main Entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 12 of 36
Question Response
INTERIOR
AUDITORIUM
Door(s)
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Fixed H/C Lift
Does not ExistInstance on 1st Floor - 562 seats
Fixed Seating
InspectedInstance on 1st Floor - 562 seats
Condition 4 - Between Fair and Poor
Deficiency DAMAGED/BROKEN/INOPERABLE
Deficiency Location/Instance Seat C/2, 6, 7, 19, 24, Q/2, and others
Deficiency Quantity 40
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Seat C/2
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor - 562 seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor - 562 seats
Stage
InspectedInstance on 1st Floor - 562 seats
Stage Inspected
InspectedInstance on 1st Floor - 562 seats
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 13 of 36
Question Response
INTERIOR
AUDITORIUM
Stage
Stage Inspected
Deficiency No deficiencies recorded
Stage Curtain Rigging Inspected
InspectedInstance on 1st Floor - 562 seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stage Curtains Inspected
InspectedInstance on 1st Floor - 562 seats
Condition 3 - Fair
Deficiency WORN/DETERIORATED
Deficiency Location/Instance Main curtain
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main curtain
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor - 562 seats
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stage rear
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stage rear
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 14 of 36
Question Response
INTERIOR
AUDITORIUM
Walls
Violations No violations recorded.
Window Curtains/Shades/Blinds
InspectedInstance on 1st Floor - 562 seats
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CAFETERIA Inspected
InspectedInstance on 1st Floor
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Exit Vestibule 2
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit Vestibule 2
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 1st Floor
Condition 3 - Fair
Deficiency DAMAGED/MISSING
Deficiency Location/Instance Rear of Room
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 15 of 36
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on 1st Floor
Stage
Does not ExistInstance on 1st Floor
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on 1st Floor
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 219, Corridor near Rooms 305, 314
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 219
Violations No violations recorded.
Deficiency ACOUSTIC TILES ON PLASTER: DAMAGED/MISSING
Deficiency Location/Instance Corridor near Room 150
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 16 of 36
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling Inspected
Deficiency Photo1
Corridor near Room 150
Violations No violations recorded.
Door(s) Inspected
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Room 304
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 304
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Room 319
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 17 of 36
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 319
Violations No violations recorded.
Deficiency VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET
Deficiency Location/Instance Room 319
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Room 319
Violations No violations recorded.
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Corridor near Room 154
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 154
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 18 of 36
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Near near Exit 1, by Room 105
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Exit 1
Violations No violations recorded.
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Room 299, 300
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 299
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 201, 219, 319, 362
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 19 of 36
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Walls
Deficiency Photo1
Room 319
Violations 35316951Y
Specialties Does not Exist
GYMNASIUM Inspected
InspectedInstance on 3rd Floor
Ceiling
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Door(s)
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Office
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 20 of 36
Question Response
INTERIOR
GYMNASIUM
Door(s)
Deficiency Photo1
Office
Violations No violations recorded.
Fixed Equipment
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Seating
InspectedInstance on 3rd Floor
Condition 3 - Fair
Deficiency DAMAGED FIXED SEATING
Deficiency Location/Instance Near the windows
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the windows
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on 3rd Floor
Stage
Does not ExistInstance on 3rd Floor
Walls
InspectedInstance on 3rd Floor
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 21 of 36
Question Response
INTERIOR
GYMNASIUM
Walls
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Office
Violations No violations recorded.
Deficiency SALT GLAZED BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near the windows
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on 3rd Floor
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on 1st Floor
Ceiling
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 22 of 36
Question Response
INTERIOR
KITCHEN
Ceiling
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on 1st Floor
Condition 4 - Between Fair and Poor
Deficiency METAL: DAMAGED LOUVER
Deficiency Location/Instance Main Entrance
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance
Violations No violations recorded.
Floor Finish
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls
InspectedInstance on 1st Floor
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 209
Built-in Furnishing
Does not ExistInstance on Room 209
Ceiling
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 23 of 36
Question Response
INTERIOR
LIBRARY
Floor Finish
Deficiency No deficiencies recorded
Walls
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Exit Vestibule 9
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit Vestibule 9
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair C/3
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 24 of 36
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Ceiling
Deficiency Photo1
Stair C/3
Violations 35316951Y
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Stair A/1, B/1
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/1
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 3 - Fair
Deficiency METAL: MISSING
Deficiency Location/Instance Exit Vestibule 1, 7
Deficiency Quantity 14
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 25 of 36
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Railings
Deficiency Photo1
Exit Vestibule 1
Violations No violations recorded.
Stairs and Landings Inspected
Condition 3 - Fair
Deficiency ROLLED ASPHALT: CRACKS
Deficiency Location/Instance Stair B/3
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/3
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency BRICK: CRACKS/SPALLING
Deficiency Location/Instance Exit Vestibule 9
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 26 of 36
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Exit Vestibule 9
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair C/3
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 4
Deficiency Photo1
Stair C/3
Violations 35316951Y
Deficiency STONE: CRACKS/SPALLING
Deficiency Location/Instance Stair A/1
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair A/1
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 27 of 36
Question Response
INTERIOR
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 356
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 356
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 5 - Poor
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair B/1
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 28 of 36
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room 356
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 356
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Room 357
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 29 of 36
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Walls
Deficiency Photo1
Room 357
Violations No violations recorded.
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Inspected
Condition 5 - Poor
Deficiency CONTAINER DAMAGED
Deficiency Location/Instance 132nd Avenue
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
132nd Avenue
Violations No violations recorded.
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 30 of 36
Question Response
SITE
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Exit to 218th Street
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Exit to 218th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: RUST - MAJOR
Deficiency Location/Instance 218th Street
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
218th Street
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance 218th Street
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 31 of 36
Question Response
SITE
FENCES
Deficiency Photo1
218th Street
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance 132nd Road, 132nd Avenue
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
132nd Road
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED POST/RAIL
Deficiency Location/Instance 132nd Road, 132nd Avenue
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
132nd Road
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 32 of 36
Question Response
SITE
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inaccessible
Pavers Inaccessible
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Inaccessible
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 132nd Road, 218th Street, 132nd Avenue
Deficiency Quantity 150
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 33 of 36
Question Response
SITE
PAVING Inspected
DOT Sidewalk
Concrete
Deficiency Photo1
132nd Road
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard - East side
InaccessibleInstance on Schoolyard - West side
Benches
Does not ExistInstance on Schoolyard - East side
Fence
Does not ExistInstance on Schoolyard - East side
Pavement
Does not ExistInstance on Schoolyard - East side
Play Equipment
InspectedInstance on Schoolyard - East side
Condition 1 - Good
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard - East side
Condition 1 - Good
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard - East side
PLAYING SURFACE Inspected
Playing Field Inspected
InspectedInstance on West side
Instance Condition 1 - Good
Deficiency No deficiencies recorded
Running Track Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT
Deficiency Location/Instance 132nd Avenue
Deficiency Quantity 10
Quantity Uom L.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 34 of 36
Question Response
SITE
RETAINING WALLS
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
132nd Avenue
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
SEATING Inspected
Benches Inspected
Concrete Inaccessible
Metal/Wood/Plastic Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
Bleachers Inspected
Concrete Inaccessible
Metal/Wood/Plastic Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance 132nd Avenue
Deficiency Quantity 30
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 35 of 36
Question Response
SITE
SITE WALLS (NOT RETAINING WALLS)
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
132nd Avenue
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Inspected
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2018 - 2019
Q132
PB/A&W Print Date: 6/21/2019Page 36 of 36