NREL experience and lessons learned with Remote Power Hardware-in-the-Loop Simulation 2018 IEEE PES General Meeting August 8 th , 2018 1 Przemyslaw Koralewicz NWTC/NREL Bryan Palmintier and Blake Lundstrom PSEC/NREL

NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NREL experience and lessons learned with Remote Power

Hardware-in-the-Loop Simulation

2018 IEEE PES General Meeting August 8th, 2018

1

Przemyslaw KoralewiczNWTC/NREL

Bryan Palmintier and Blake LundstromPSEC/NREL

Page 2: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

National Renewable Energy Laboratory

2

~20 miles

National Wind Technology Center (NWTC)

South Table Mountain – STM Main Campus

Page 3: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Energy Systems Integration Facility (ESIF)

3

Smart buildings & controllable loads

Power Systems IntegrationGrid Simulators - Microgrids

Energy SystemsIntegration Fuel Cells, Electrolyzers

Outdoor Test AreasEVs, Transformers, Capacitor Banks,

Voltage Regulators

Rooftop PV Energy Storage -Residential, Community

& Grid Scale StorageHigh-Performance

Computer & Data Center

Advanced Distribution

Management Systems

http://www.nrel.gov/esif

Page 4: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Siemens

2.3 MW

GE/Alstom

3 MW

GE 1.5 MW

Gamesa

2 MW

Research Turbines

2 x 600 kW

PV Array

1 MW

2.5 MW dynamometer

5 MW dynamometer,

7MVA CGI1MW / 1MWh BESS

New PV

Arrays

• Total of 12+ MW variable renewable generation currently • 7 MVA Controllable Grid Interface (CGI) • Multi-MW energy storage test facility• 2.5MW and 5 MW dynamometers (industrial motor drives)• 13.2 kV medium voltage grid

National Wind Technology Center (NWTC)

Page 5: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Power-Hardware-in-the-Loop (PHIL)?

5

Traditional PHIL:

• Hardware at power

• Fast digital simulators

• AC+DC amplifiers

With Co-simulation:

• External software for (slower) system-wide impacts

• Architectural flexibility

Page 6: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

“Sum is greater than the parts”• Combine:

– Unique test capabilities– Unique equipment– Unique expertise

• Other Multi-site advantages:– Reduce shipping– International diversity (e.g. 50/60Hz)

• Biggest?--Collaboration• Examples at NREL:

– NREL-NREL (Facility linking)– RT-SuperLab (US-EU links)– Wgrid-49 (Wind integration)– PNNL (PV-Grid Interaction)– INL (Fuel Cell-Grid)– CSIRO (PV-Battery-Grid)– TNO (Smart Home: EV, Battery, HVAC)– SDG&E (Microgrid)– CSU (Comm. Delays)

Lab-Lab Links

Page 7: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NWTC/ESIF Real-Time Interconnection

30

km

Hardware ESIF: 1MVA, NWTC: 7MVA

Model NA

Protocol GTNET SKT

Link Timestep 0.5msec oversample, GPS sync

ObjectiveLink two nearby facilities to

support large-scale multi-node

testing.

DC

AC

AC

DC

7 MVA

DC

AC13.2 kV

DC

AC

DC

AC

7 MVA

7 MVA

7 MVA

7 MVA

13.2 / 3.3 kV

Grid

13.2 kV

Controllable Grid Interface (CGI)

CGI RT Controller

RTDS HIL Model

V, I, f

ESIF RTDS CGI RTDS

GTNET SKT

GE 1.5MW

1 MW Grid Simulator

M

PV

INVERTER

Load bank

RTDS HIL Model

CGI Setpoints

ESIF

NWTC

PV Array Simulator

Distributioncircuit

10Gbps

LAN

External

colaborating

organizations

Page 8: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NREL (Colorado) ↔ PNNL (Washington State)ObjectiveUsing remote PHIL, emulate the dynamic response of 1-

ph residential 3-ph small commercial PV inverters at

NREL inside a grid model running at PNNL (located in

WA, distance of 1000 mi/1600km)

Highlights• First remotely connected power hardware-in-the-loop

demonstration within DOE national lab complex

• Included inverters connected at multiple points of

common coupling in the distribution feeder

• Various grid-support functionalities demonstrated

(Volt/Var, constant PF, etc.)

• Novel JSON-based communication protocol

• Co-simulation of IEEE 123 and 8500 node test feeders

Palmintier, Lundstrom, Chakraborty, et al., “A Power Hardware-in-the-Loop Platform

With Remote Distribution Circuit Cosimulation,” IEEE Trans. on Ind. Elect., 2015.

16

00

km

Hardware 1-2x PV inverters. Only at NREL

Model 8500 node, GridLAB-D, PNNL

Protocol JSON-link/UDP

Link Timestep 1s (limited by GridLAB-D)

Page 9: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NREL-PNNL Remote PHIL - Hardware SetupThree-

phase

Setup

Real-time System

(Opal-RT)Grid

Simulator

Single-phase

Setup

Page 10: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

• IEEE 8500-node test feeder• One 7 kVA real-inverter output scaled

up to 140 kVA in GridLAB-D simulation

• This hardware inverter was operating in VVC

• Added a large number small UPF inverters; combined output of 800 kW

• Cloud transient was implemented based on historical weather data

• The hardware inverter with VVC was capable of maintaining constant voltage on the secondary

NREL-PNNL Remote PHIL Test Case: Three-phase Inverter

12:35 12:40 12:45122

123

124

125

126

127

128

|V| m

ax

Maximum voltage magnitude on secondary system

no solar base case

distributed PF=1.0 solar

distributed PF=1.0 solar and VVC solar

12:35 12:40 12:45122

123

124

125

126

127

128

|V| m

ax

Time

Maximum voltage magnitude on secondary system

T. Williams, J. Fuller, B. Palmintier, B. Lundstrom, S. Chakraborty, “Examining Solar PV Control Systems with a

Hardware-in-the-Loop Platform,” in IEEE Photovoltaic Specialists Conference (PVSC), Denver, CO, 2014.

Page 11: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

INL-NREL Electrolyzer

75

0 k

m

Hardware NREL: 200kW Electrolyzer

Model Simplified portion of WECC

Protocol UDP

Link Timestep 2kHz (500µs)

ObjectiveExplore Transmission Grid

Interactions with a large scale

controlable load (Electrolyzer)

ESNET

Resistiveload

4 generator / 2 area test system

RTDS at INL

Interconnection point

Distribution system current

injection

RTDS at ESIF/NREL

Frequency Dependent

Voltage Source|V|

f

Φ

Electrolyzer

Time delay, Δt

Measured P,Q

Measured |V|, f, Φ

Page 12: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NREL-CSIRO Remote PHILObjectiveUsing remote PHIL, connect hardware at

CSIRO’s lab in Newcastle, NSW, Australia

and hardware at NREL in Golden, CO, USA to

multiple points on Australian and U.S. electric

distribution system models. Evaluate

coordinated control modes between the

devices.

Highlights• First trans-pacific PHIL simulation using

hardware at both sites

• Connected same hardware to both U.S.

and Australian distribution system models

• Coordinated control of the PV/batt inverter

(provided smoothing in response to PV at

both locations) and PV inverter

PRINTED:

SHEET #: 1 1of

DWG ID: CSIRO-PHILTEST-001

REVISIONNO. DATE BY CHECKED BY

0.0 ISSUED FOR PRELIMINARY DESIGN 2014-02-01 B. LUNDSTROM

1/19/2015

Power Systems Engineering Center

One-line DiagramPHIL Experimental Setup

Commonwealth Scientific and Industrial Research Organization (CSIRO)

PV SIMULATOR 1

M

SG1

Local Controller

M

SG2

Local Controller

M

Local Controller

RLC LOAD

M

PV INV 1

PV SIMULATOR 2

M

PV INV 2

BATTERY

M

BATT INV 1

Local Controller

Local Controller

Local Controller

Microgrid Controller

CSIRO NREL

PV SIMULATOR

M

MICROTURBINE

Local Controller

SUNNY TRI-POWER INVERTER

M

Local Controller

RLC LOAD

M

PV/BATT INVERTER

BATTERY

Local Controller

SYSTEM CONTROLLER

I

CONTROLLABLE GRID SOURCE (CGS)

GRID SIMULATOR

CGS CONTROLLER

REAL-TIME SIMULATOR

Australian

Dist. Sys.

Model

US

Dist. Sys.

Model

CSIRO

NREL

MLocal Controller

REIFPV

Whiteboard

LOAD BANK

I

WB CONNECTOR (WBC)

WBC

WBC

WBC

SIM. SERVER

WEB APPLICATIONSERVER

WBC

SYSTEM CONTROLLER

WBC

1.0 UPDATED BASED ON CHOSEN CONFIGURATION 2014-11-26 B. LUNDSTROM

EXAMPLE EXPERIMENT

IMPLEMENTATION VIA PHIL(NOT IDENTICAL TO EXAMPLE EXPERIMENT)

• Communications “whiteboard” for multi-point to point

real-time communication

Lundstrom, Palmintier, et. al., “Trans-oceanic Remote Power Hardware-in-the-

Loop: Multi-site Hardware, Integrated Controller, and Electric Network Co-

simulation,” IET Gen., Trans., and Dist., (Submitted). 13

,00

0 k

m

Hardware NREL: Storage+PVCSIRO: real PV

Model US & AUS feeders

Protocol Whiteboard

Link Timestep 1 sec (GridLAB-D)

Page 13: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NREL-CSIRO Remote PHIL

Lundstrom, Palmintier, et. al., “Trans-oceanic Remote Power Hardware-in-the-Loop: Multi-site Hardware, Integrated Controller, and Electric Network Co-simulation,” IET Gen., Trans., and

Dist., (Submitted).

Page 14: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NREL-SDG&E: Borrego Springs High Renewables Microgrids

DescriptionDemonstrate the viability of a microgrid to manage highamounts (up to 100%) of renewable energy to meet thecommunity load while avoiding adverse grid impacts.Advanced testing methods and a testbed that can beconfigured to utilize electrical signals from SDG&Ethrough remote hardware in the loop (HIL) will bedeveloped at ESIF.

TechnologiesPV, battery and ultracapacitor storage, microgrids

FY17 Notable OutcomeInstall and commission an integrated, multi-tech powerand controller HIL testbed to evaluate an advancedmicrogrid controller prior to deployment in the largest,highest penetration, utility-owned, microgrid in the U.S.

ImpactSuccessful implementation will prove that a community-scale, highly renewable microgrid is feasible to other utilities.

Partners

14

00

km

Hardware NREL: 500kVA PV,540kW Battery

Model Borrego Springs (Reduced)

Protocol DNP

Link Timestep 100ms

Page 15: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

• Power and Controller Hardware-in-theLoop (PHIL & CHIL) evaluation of microgrid controller for Borrego Springs community microgrid site

NREL Role: CHIL/PHIL Testing

PV Simulator

PV Inverter

Power Hardware

Virtual Model

AC Source #1

69kV Substation Bus

ESIF RTDS

High Voltage

Low Voltage

12kV Substation Bus

Ckt 172Ckt 171Ckt 170

V and I Scaling

AC Source #2

V and I Scaling

Battery Simulator

ESS Inverter

Spirae Wave Commander

AC Bus #1AC Bus #2

DieselGenset

#1

NRG PV Model

SESS #2Model

SESS #1

NarrowsGrid Tie

MG Switch

V

)(1 tv

)(1 ti

A)(11 tik I

)(11 tvkV

Fictitious Bus #1

V

Fictitious Bus #2

A

)(22 tvkV

)(22 tik I

)(2 tv)(2 ti

G

Woodward EasyGen

Woodward EasyGen

RTAC

G

Controller Hardware

To RTDSTo RTDS

Communication • CHIL: Spirae Wave microgrid controller & EasyGen diesel generator controllers

• PHIL: ESS inverter (representative Schneider 540kW) & PV inverter (actual SMA 500kW)

• Remote CHIL (RHIL): UCSD Advanced Control Technology (ACT) implemented on SEL RTAC

Page 16: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Remote CHIL

16

Virtual Model

69kV Substation Bus

ESIF DRTS

12kV Substation Bus

R&D Control Function

Implementation

Tie to Main Grid

Microgrid Switch, Point of

Interconnection

G G

UCSD Remote Hardware

PMU Data

Diesel Genset #1

Diesel Genset #2

Feeder 3

Feeder 2

Feeder 1

BESS #1

BESS #2

26MW PV

O PMU1

O PMU2

O PMU3 O PMU4

O PMU5

O PMU6 O PMU7

PQ Targets DER Dispatch

CHIL:

• UCSD Advanced Control Technology (ACT) implemented on SEL RTAC

Remote HIL (RHIL):

• RSCAD network simulation at NREL connected to controller hardware at UCSD

14

00

km

Hardware NREL: 500kVA PV,540kW Battery

Model Borrego Springs (Reduced)

Protocol DNP

Link Timestep 100ms

Page 17: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

TNO/HESI ↔ NREL/ESIF

Page 18: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Demo Setup

OPENING HESI FACILITY – 31 JANUARY 2017

NREL ESIF Facility TNO HESI Facility

Self-

Consumption

Optimizer

8,0

00

km

Hardware NREL: Air ConditionerTNO: EV Charger

Model Energy Plus (Building Simulation)

Protocol MQQT with JSON query Table

Link Timestep 1sec

Page 19: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Demo Setup

OPENING HESI FACILITY – 31 JANUARY 2017

Self-

Consumption

Optimizer

HESI-ESIF Integrated Test

8,0

00

km

Hardware NREL: Air ConditionerTNO: EV Charger

Model Energy Plus (Building Simulation)

Protocol MQQT with JSON query Table

Link Timestep 1sec

Page 20: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

TNO/HESI ↔ NREL/ESIF

Page 21: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NWTC Wind Turbines

SunEdison1 MW PV Array

Controllable Grid Interface (CGI)for Grid and Fault Simulation

Switchgear Building

XcelSubstation

1 MW / 1 MWh BESS

Controlled grid,CGI Bus

Regular grid,Xcel Bus

(7 MVA continuous / 40 MVA s.c.)

115 kV

13.2 kV tie-line

GE 1.5 MW

Siemens 2.3 MW

Alstom 3 MW

Gamesa 2 MW

DC

AC

DC

DC

DC

DC

AC

13.2 kV 13.2 kV

First Solar430 kW PV array

GE 1.25 MW / 1.25 MWh BESS

13.2 kV

Aerial view of the siteAC

AC

AC

NWTC Grid Integration Platform

Page 22: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

NWTC 7-MVA Controllable Grid Interface

Power rating• 7 MW continuous• 39 MVA short circuit capacity (for 2 sec)• 4-wire, 13.2 kVFrequency control• Fast output frequency control (3 Hz/sec) within 45-

65 Hz range• 50/60 Hz operation• Can simulate frequency conditions for any type of

power system

Voltage control (no load THD <3%)• Balanced and un-balanced voltage fault conditions

(ZVRT and 130% HVRT) – independent voltagecontrol for each phase on 13.2 kV terminals

• Response time – 1 millisecond (from full voltage tozero, or from zero back to full voltage)

• Long-term symmetrical voltage variations (+/- 10%)and voltage magnitude modulations (0-10 Hz) – SSRconditions

• Programmable impedance (strong and weak grids)

RTDS – PHIL capability

Page 23: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Communication architecture- Preferred digital optical communication

- 2Gb/s RTDS optical link - GOF

- 10Mb/s CGI-ABB proprietary link – POF

- Up to 40x16bit variables exchanged between

RTDS and CGI every 25us (40kHz)

0.2

km

Hardware NWTC 1.5MW Wind Turbine

Model RTDS 9-bus model

Protocol RTDS proprietary

Link Timestep 25us

Page 24: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

CGI-RTDS PHIL interface• Instantaneous voltage measured in model and commanded to CGI

• Very fast tracking achieved thanks to instantaneous to phasor (I2P)

algorithm

• Controllable phase delay

• Active and reactive power measured at CGI terminals is fed back to model

• P&Q is filtered to avoid PHIL experiment instability

• Current is injected back to model and synchronized using PLL

Page 25: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

• Line to line and line to ground faults simulated in RTDS –within certain electrical distance from POI

• Transient with rich harmonic content

• Zero, positive and negative sequence content

• Highly asymmetrical events

Line fault testing

Page 26: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

1 phase line to line fault

Page 27: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

PHIL tests –12% generation drop case• G4 generating 50MW before the event

• G4 CB opens

• GE 1.5MW WEC reacts with inertial response &

droop

• Frequency recovers faster with higher m

• Frequency dip was sligthly limited

m fmin[Hz]

0 59.606

3 59.608

69 59.621

100 59.625

Page 28: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

RT-SuperLab for the Futuristic GridsCollaborative research infrastructure for• Large-scale systems

• Unique (P)HIL experiments

• Cutting-edge interdisciplinary research

28

Page 29: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Global RT-SuperLab Team

29

Page 30: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Dynamic Simulations for Large Scale Power Networks in Real Time Environment using Multiple RTDS

• Collaborative research infrastructure for

– Large-scale systems

– Unique (P)HIL experiments

– Cutting-edge interdisciplinary research

RT-Super Lab

Page 31: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

RT-SuperLab Demonstration

Page 32: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Experiment Results - NREL • Frequency support from a wind turbine

– Over frequency event on account of over-generation

– Key takeaway: stability and optimal resource allocation

– Wind turbines respond based on droop settings

• Negative sign indicates import to INL from NREL

𝑷𝟏𝟓

∆𝑷(∆𝒇)

∆𝒇

Page 33: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

INL-NREL PHIL experiments

• WGRID-49 - Short-term Energy Storage and Large Motor Loads for Active Power Controls by Wind Power

• Objective: To develop and test coordinated controls using wind generation by multiple controller hardware-in-the-loop (CHIL) and NREL’s Wind Turbine as power hardware-in-the-loop (PHIL) at INL. Test and verify the functionality of the distributed wind power plant (WPP) simulation to provide grid support.

33

Page 34: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

INL-NREL Unit TestingLoopback communication tests

34

Page 35: NREL experience and lessons learned with Remote Power ...2 x 600 kW PV Array 1 MW 2.5 MW dynamometer ... • The hardware inverter with VVC was capable of maintaining constant voltage

Thank you

For more info:[email protected]

35