Notes21 Protection

Embed Size (px)

Citation preview

  • 7/29/2019 Notes21 Protection

    1/22

    Notes 21: Protection

    21.0 Introduction

    Distribution system protection involves

    using current interrupting devices to de-

    energize faulted portions of the network so

    that the associated high fault currents will

    not flow. Otherwise, continued high faultcurrent that is not interrupted can cause

    significant heat, resulting in damaged

    equipment (e.g., line burn-downs,

    transformer loss of life) and in the worst

    case fires and explosions. In addition, faultscan sometimes expose people to live

    conductors, resulting in a safety hazard.

    In addition, the coordination of protective

    devices can be done in such a way so as to

    minimize interruptions and interruptiondurations as seem by customer, thus

    improving their overall reliability levels.

    1

  • 7/29/2019 Notes21 Protection

    2/22

    In this document, we will briefly survey the

    field of protection for distribution systems.

    This should be viewed as an introductiononly. Students desiring more in-depth

    treatment of the subject should refer to one

    of the four very good references listed in the

    bibliography of this document.

    21.1 Basic principles

    Directional relays are unnecessary in radial

    distribution systems that do not have any

    distributed generation. So almost all

    distribution protection devices are simply

    non-directional, overcurrent devices.

    (Exceptions are, however, when the

    distribution system has multiple feeds and/or

    when it contains generation).

    2

  • 7/29/2019 Notes21 Protection

    3/22

    The four most basic requirements for an

    overcurrent interrupting device is that

    1.

    Do not operate for highest load current.2. Do operate for minimum fault current.

    3. Must be capable of interrupting the

    maximum fault current.

    4. Interrupt more severe faults more

    quickly.

    21.1.1 Maximum load current

    The load currents of concern are those

    highest in magnitude which therefore may

    appear to the protective device as a fault

    current. An interrupting device should

    obviously never open for any load current.

    The highest load current is typically the

    current that occurs just as the system is re-

    energized following an outage. This currentis commonly referred to as the cold-load

    pickup current.

    3

  • 7/29/2019 Notes21 Protection

    4/22

    The cold-load pick-up current can be

    significantly higher than the normal peak

    load current because of two main reasons.

    Current in-rush: Cold-load pickup currents

    can be affected during the first second or so

    following energization by current inrush,

    which is the tendency of magnetic loads

    (e.g., transformers and motors) to draw highcurrents during the initial transient period as

    a result of the difference between the

    residual magnetization of the iron and the

    initial phase applied across the device.

    Simultaneous operation: Cold-load pickup is

    also affected by the fact that following an

    outage, on re-energizing, many devices that

    normally do not run simultaneously will

    switch on instantaneously, and

    simultaneously. This is particularly true ofdevices that perform temperature control,

    e.g., air conditioners, furnaces, water

    heaters, refrigerators.

    4

  • 7/29/2019 Notes21 Protection

    5/22

    Cold-load pickup currents can range from 2-5 times normal peak load currents during the

    first few seconds following re-energization

    and [2].

    21.1.2 Minimum fault current

    The minimum fault current is determined by

    the least severe fault within the protection

    zone of the device.

    The protection zone is defined by the reach

    of the device. The reach is the maximum

    distance from the device to a fault for which

    the protective device is supposed to operate.

    As the fault moves further from the source,

    the impedance between source and faultincreases and the fault current decreases.

    5

  • 7/29/2019 Notes21 Protection

    6/22

    So the reach of an overcurrent device

    increases as the current interruption setting

    decreases.

    Observation: Location of the maximum

    distance fault depends only on the current

    setting and not on the device location.

    So basic procedure is that one identifies theleast severe fault type, computes the fault

    current for the maximum distance fault. This

    fault current is the minimum fault current

    and the device should be set to operate at a

    level

    Significantly higher than the maximum

    load current and

    Significantly lower than the minimum

    fault current

    What happens when this is not possible?

    Is it ever the case that it is not possible?

    6

  • 7/29/2019 Notes21 Protection

    7/22

    Fact: There always exist faulted conditions

    for which the fault current is less than the

    maximum load current!!!

    How can this be?

    Consider the single-line-to-ground (SLG)

    fault. In notes20, we found that the

    connection for a SLG fault was as in Fig. 1:

    0

    faI

    2

    faI

    1

    faI

    1.0

    Z1

    Z2

    Z0

    Fig. 1

    Sequence fault currents are:

    021

    021 0.1

    ZZZIII fafafa (1)

    And the phase a fault current Ifa=3I1

    fa.

    7

  • 7/29/2019 Notes21 Protection

    8/22

    However, this is for a so-called bolted fault,

    which means that the fault is a pure short-

    circuit with no fault impedance.

    For a SLG fault through an impedance Zf,

    the fault impedance shows up in all three

    sequence networks, so that the sequence

    network connection is as in Fig. 2.

    0

    faI

    2

    faI

    1

    faI

    1.0

    Z1

    Z2

    Z0

    3Zf

    Fig. 2

    Then the sequence fault currents are:

    f

    fafafa

    ZZZZ

    III

    3

    0.1

    021

    021

    (2)

    Again we have that Ifa=3I1fa.

    8

  • 7/29/2019 Notes21 Protection

    9/22

    The difference between this case and the

    bolted fault case is that the 3Zf term is in the

    denominator, so that the fault current isdecreased. If Zf is large, the fault current can

    be decreased significantly.

    What can Zf be? Consider the case where an

    overhead conductor crossing a street breaks

    and falls to the pavement. In this case, theimpedance between the conductor and

    ground is going to be very high. Then,

    clearly, the fault current is going to be very

    low.

    Such a situation is quite dangerous because

    the protection device will not trip.

    It is for this reason that a distribution

    substation transformer is almost never

    connected in ungrounded Y, because then,the zero sequence circuit is open, which is

    equivalent to Zf=, and no fault current

    flows!

    9

  • 7/29/2019 Notes21 Protection

    10/22

    So we see that, because of the variability of

    Zf, there will always be some faults that

    result in currents that are below themaximum load current.

    Therefore, it is typical to define the

    minimum fault current as that which would

    flow for a SLG fault through a fault

    impedance of 30 or 40 ohms.

    21.1.3 Time to operate

    The heating effect of a fault current is

    depends on the energy dissipated. The

    energy dissipated depends on two things:

    Power and

    Time

    Since the power is given by I2R, and since R

    is fixed, we see that the variable parameters

    for a particular faulted condition are thesquare of the current and the time or

    duration of the fault.

    10

  • 7/29/2019 Notes21 Protection

    11/22

    So I2t is an important parameter in

    determining the severity of a fault.

    In order to protect equipment and people,

    protection should be designed so that it

    avoids exceeding a certain value of I2t.

    So we see that a good design for a protection

    device is one that operates faster (smaller t)for higher values of current (larger I).

    This thinking results in the so-called time-

    inverse characteristic of a protection device,

    shown in Fig. 3.

    I

    t

    Fig. 3

    11

  • 7/29/2019 Notes21 Protection

    12/22

    21.2 Types of protection devices

    There are four basic types of protectiondevices used in distribution systems. These

    are

    1. Fuses

    2. Automatic circuit reclosers

    3. Sectionalizers

    4. Circuit breakers and relays

    We will discuss each of these briefly.

    21.2.1 Fuses

    Fuses have elements that melt if enough

    current flows through it for enough time.

    They are inexpensive, and they can open

    very fast for high currents.

    The most common type of fuse is the

    expulsion type within a cue out, illustrated

    in Fig. 4.

    12

  • 7/29/2019 Notes21 Protection

    13/22

    Fig. 4

    The purpose of the cutout is to support thefuse and enable efficient replacement when

    it is blown. One often sees these devices.

    The fuse is called expulsion because, when

    the fusible element, located within a fuse

    tube, melts under high current, an arcremains. The arc causes a rapid pressure

    buildup, which forces the ionized gas out of

    the bottom of the cutout, which helps to

    prevent reigniting. Fig. 5 shows operation of

    an expulsion fuse, which suggests that they

    should not be placed where a blast of hot

    ionized gas could cause a flashover on

    another phase.

    13

  • 7/29/2019 Notes21 Protection

    14/22

    Fig. 5 [2]

    Industry standards specify two types of

    expulsion fuses.

    K type: fast fuse with speed ratio of 6-8

    T-type: slower fuse with speed ratio 10-13

    The speed ratio is the ratio of

    The melting current at 0.1 second to

    The melting current at X seconds, where Xis 300 for fuse ratings below 100 amps and

    X is 600 for fuse ratings above 100 amps.

    14

  • 7/29/2019 Notes21 Protection

    15/22

    The current rating is the level of current the

    fuse can safely carry for an indefinite period

    of time.

    For example, a typical K-type fuse would

    have ratio (using 600 seconds) of

    200/30=6.7.

    21.2.2 Circuit breakers and relays

    21.2.3 Automatic circuit reclosers

    ACRs are essentially circuit breakers with

    increased capacity both in terms of

    interrupting capacity and normal load

    carrying capacity.

    They are less expensive than circuit breakers

    but less accurate.

    ACRs are motivated by the fact that 60-80%

    of all overhead distribution faults are

    temporary and last only a few cycles or a

    15

  • 7/29/2019 Notes21 Protection

    16/22

    few seconds. For example, a branch may

    blow against a circuit and then fall to the

    ground.

    As a result, it becomes very attractive to

    reclose following an initial opening of the

    protection device.

    So the basic operation of an ACR is to Sense the overcurrent

    Time and interrupt the overcurrent

    Reclose to re-energize the circuit

    An ACR can reclose as many as 3-4 times

    before locking out.

    The first reclose is generally done

    instantaneously which means there is no

    intentional time delay embedded in the first

    reclose. Typical timing sequences used in

    the industry include

    0-15-30 seconds

    0-30-60-90 seconds

    16

  • 7/29/2019 Notes21 Protection

    17/22

    5-45 seconds

    But most ACRs can be set for any

    combination of instantaneous operations ortime delayed operations.

    21.2.4 Sectionalizers

    Sectionalizers are switches. The main

    difference between a switch an all otherdevices described previously is that all the

    other devices can detect and interrupt a

    short-circuit fault current, but a switch can

    do neither.

    It is typically applied together with an ACR

    or a circuit breaker to isolate faulted sections

    of the distribution system.

    So how does a sectionalizer operate?

    It counts the number of operations of thebackup device

    After a pre-set number of interruptions, it

    opens while the backup device is open.

    17

  • 7/29/2019 Notes21 Protection

    18/22

    Then the backup device can reclose to

    restore service to remaining circuits.

    Advantage relative to fuse is it is

    unnecessary to replace it.

    Advantage relative to circuit breaker or

    ACR is it is less expensive.

    Clear disadvantage is that it is a switch.

    21.3 Coordination

    The basic issue in coordinating multiple

    devices in a distribution feeder is that we

    want to ensure that only the minimum

    number of customers are interrupted for a

    specific fault, given the devices that we have

    in place.

    18

  • 7/29/2019 Notes21 Protection

    19/22

    We use the terms protected device

    (upstream) and protecting device

    (downstream).

    Important coordinating principles:

    1. The protecting device must clear a fault

    before the protected device interrupts the

    circuit (fuse) or operates to lockout.

    2. Outages caused by permanent faultsmust be restricted to the smallest section

    of the system for the shortest time.

    Figure 6 shows an example of system

    coordination where a substation receives

    power flow a high voltage transmission line

    and steps the voltage down.

    Protective devices in this illustration are

    located at the coordinating points. Device A

    is at the substation. Devices C and H are inthe feeder. Device B is at the branch tap off

    the feeder.

    19

  • 7/29/2019 Notes21 Protection

    20/22

    Device D is on the transformer primary and

    devices E, F, and G are service entrance

    fuses on the transformer secondary. Alldevices must be selected to carry normal

    load current and respond properly to a fault.

    Fig. 6 [1]

    20

  • 7/29/2019 Notes21 Protection

    21/22

    With respect to device H, device C is the

    protected device. For a fault at point 1,

    device C must not open and device H mustinterrupt.

    With respect to device A, device C is the

    protecting device and must interrupt

    permanent fault current at point 2 before

    device A operates to lockout. Device B isalso a protecting device for A and must

    operate similar to device C for a fault at

    point 3. Only device A functions when a

    fault occurs between A and C, such as at

    point 4. For a transformer fault at point 5,

    device D is expected to interrupt current and

    permit normal load current to flow in the

    remainder of the system. For an overload on

    the secondary tap of transformer at point 6,

    device E should interrupt the circuit,

    permitting power to the transformer to becontinued so that customers on other

    secondary taps will receive service.

    21

  • 7/29/2019 Notes21 Protection

    22/22

    References

    [1] McGraw-Edison Power Systems,Distribution system protection manual.

    [2] T. Short, Electric power distribution

    handbook, CRC press, 2004.

    [3] T. Gonen, Electric Power Distribution

    System Engineering, McGraw-Hill, 1986.

    [4] J. Blackburn and G. Rockefeller,Applied Protective Relaying,

    Westinghouse Corporation.

    [5] J. Blackburn, Protective Relaying:

    Principles and Applications, 2nd edition,

    Marcel-Dekker, New York, 1998.

    [6] P. Anderson, Power system protection,

    McGraw-Hill, 1999.