Upload
alexander-martin
View
216
Download
0
Embed Size (px)
Citation preview
7/29/2019 Notes21 Protection
1/22
Notes 21: Protection
21.0 Introduction
Distribution system protection involves
using current interrupting devices to de-
energize faulted portions of the network so
that the associated high fault currents will
not flow. Otherwise, continued high faultcurrent that is not interrupted can cause
significant heat, resulting in damaged
equipment (e.g., line burn-downs,
transformer loss of life) and in the worst
case fires and explosions. In addition, faultscan sometimes expose people to live
conductors, resulting in a safety hazard.
In addition, the coordination of protective
devices can be done in such a way so as to
minimize interruptions and interruptiondurations as seem by customer, thus
improving their overall reliability levels.
1
7/29/2019 Notes21 Protection
2/22
In this document, we will briefly survey the
field of protection for distribution systems.
This should be viewed as an introductiononly. Students desiring more in-depth
treatment of the subject should refer to one
of the four very good references listed in the
bibliography of this document.
21.1 Basic principles
Directional relays are unnecessary in radial
distribution systems that do not have any
distributed generation. So almost all
distribution protection devices are simply
non-directional, overcurrent devices.
(Exceptions are, however, when the
distribution system has multiple feeds and/or
when it contains generation).
2
7/29/2019 Notes21 Protection
3/22
The four most basic requirements for an
overcurrent interrupting device is that
1.
Do not operate for highest load current.2. Do operate for minimum fault current.
3. Must be capable of interrupting the
maximum fault current.
4. Interrupt more severe faults more
quickly.
21.1.1 Maximum load current
The load currents of concern are those
highest in magnitude which therefore may
appear to the protective device as a fault
current. An interrupting device should
obviously never open for any load current.
The highest load current is typically the
current that occurs just as the system is re-
energized following an outage. This currentis commonly referred to as the cold-load
pickup current.
3
7/29/2019 Notes21 Protection
4/22
The cold-load pick-up current can be
significantly higher than the normal peak
load current because of two main reasons.
Current in-rush: Cold-load pickup currents
can be affected during the first second or so
following energization by current inrush,
which is the tendency of magnetic loads
(e.g., transformers and motors) to draw highcurrents during the initial transient period as
a result of the difference between the
residual magnetization of the iron and the
initial phase applied across the device.
Simultaneous operation: Cold-load pickup is
also affected by the fact that following an
outage, on re-energizing, many devices that
normally do not run simultaneously will
switch on instantaneously, and
simultaneously. This is particularly true ofdevices that perform temperature control,
e.g., air conditioners, furnaces, water
heaters, refrigerators.
4
7/29/2019 Notes21 Protection
5/22
Cold-load pickup currents can range from 2-5 times normal peak load currents during the
first few seconds following re-energization
and [2].
21.1.2 Minimum fault current
The minimum fault current is determined by
the least severe fault within the protection
zone of the device.
The protection zone is defined by the reach
of the device. The reach is the maximum
distance from the device to a fault for which
the protective device is supposed to operate.
As the fault moves further from the source,
the impedance between source and faultincreases and the fault current decreases.
5
7/29/2019 Notes21 Protection
6/22
So the reach of an overcurrent device
increases as the current interruption setting
decreases.
Observation: Location of the maximum
distance fault depends only on the current
setting and not on the device location.
So basic procedure is that one identifies theleast severe fault type, computes the fault
current for the maximum distance fault. This
fault current is the minimum fault current
and the device should be set to operate at a
level
Significantly higher than the maximum
load current and
Significantly lower than the minimum
fault current
What happens when this is not possible?
Is it ever the case that it is not possible?
6
7/29/2019 Notes21 Protection
7/22
Fact: There always exist faulted conditions
for which the fault current is less than the
maximum load current!!!
How can this be?
Consider the single-line-to-ground (SLG)
fault. In notes20, we found that the
connection for a SLG fault was as in Fig. 1:
0
faI
2
faI
1
faI
1.0
Z1
Z2
Z0
Fig. 1
Sequence fault currents are:
021
021 0.1
ZZZIII fafafa (1)
And the phase a fault current Ifa=3I1
fa.
7
7/29/2019 Notes21 Protection
8/22
However, this is for a so-called bolted fault,
which means that the fault is a pure short-
circuit with no fault impedance.
For a SLG fault through an impedance Zf,
the fault impedance shows up in all three
sequence networks, so that the sequence
network connection is as in Fig. 2.
0
faI
2
faI
1
faI
1.0
Z1
Z2
Z0
3Zf
Fig. 2
Then the sequence fault currents are:
f
fafafa
ZZZZ
III
3
0.1
021
021
(2)
Again we have that Ifa=3I1fa.
8
7/29/2019 Notes21 Protection
9/22
The difference between this case and the
bolted fault case is that the 3Zf term is in the
denominator, so that the fault current isdecreased. If Zf is large, the fault current can
be decreased significantly.
What can Zf be? Consider the case where an
overhead conductor crossing a street breaks
and falls to the pavement. In this case, theimpedance between the conductor and
ground is going to be very high. Then,
clearly, the fault current is going to be very
low.
Such a situation is quite dangerous because
the protection device will not trip.
It is for this reason that a distribution
substation transformer is almost never
connected in ungrounded Y, because then,the zero sequence circuit is open, which is
equivalent to Zf=, and no fault current
flows!
9
7/29/2019 Notes21 Protection
10/22
So we see that, because of the variability of
Zf, there will always be some faults that
result in currents that are below themaximum load current.
Therefore, it is typical to define the
minimum fault current as that which would
flow for a SLG fault through a fault
impedance of 30 or 40 ohms.
21.1.3 Time to operate
The heating effect of a fault current is
depends on the energy dissipated. The
energy dissipated depends on two things:
Power and
Time
Since the power is given by I2R, and since R
is fixed, we see that the variable parameters
for a particular faulted condition are thesquare of the current and the time or
duration of the fault.
10
7/29/2019 Notes21 Protection
11/22
So I2t is an important parameter in
determining the severity of a fault.
In order to protect equipment and people,
protection should be designed so that it
avoids exceeding a certain value of I2t.
So we see that a good design for a protection
device is one that operates faster (smaller t)for higher values of current (larger I).
This thinking results in the so-called time-
inverse characteristic of a protection device,
shown in Fig. 3.
I
t
Fig. 3
11
7/29/2019 Notes21 Protection
12/22
21.2 Types of protection devices
There are four basic types of protectiondevices used in distribution systems. These
are
1. Fuses
2. Automatic circuit reclosers
3. Sectionalizers
4. Circuit breakers and relays
We will discuss each of these briefly.
21.2.1 Fuses
Fuses have elements that melt if enough
current flows through it for enough time.
They are inexpensive, and they can open
very fast for high currents.
The most common type of fuse is the
expulsion type within a cue out, illustrated
in Fig. 4.
12
7/29/2019 Notes21 Protection
13/22
Fig. 4
The purpose of the cutout is to support thefuse and enable efficient replacement when
it is blown. One often sees these devices.
The fuse is called expulsion because, when
the fusible element, located within a fuse
tube, melts under high current, an arcremains. The arc causes a rapid pressure
buildup, which forces the ionized gas out of
the bottom of the cutout, which helps to
prevent reigniting. Fig. 5 shows operation of
an expulsion fuse, which suggests that they
should not be placed where a blast of hot
ionized gas could cause a flashover on
another phase.
13
7/29/2019 Notes21 Protection
14/22
Fig. 5 [2]
Industry standards specify two types of
expulsion fuses.
K type: fast fuse with speed ratio of 6-8
T-type: slower fuse with speed ratio 10-13
The speed ratio is the ratio of
The melting current at 0.1 second to
The melting current at X seconds, where Xis 300 for fuse ratings below 100 amps and
X is 600 for fuse ratings above 100 amps.
14
7/29/2019 Notes21 Protection
15/22
The current rating is the level of current the
fuse can safely carry for an indefinite period
of time.
For example, a typical K-type fuse would
have ratio (using 600 seconds) of
200/30=6.7.
21.2.2 Circuit breakers and relays
21.2.3 Automatic circuit reclosers
ACRs are essentially circuit breakers with
increased capacity both in terms of
interrupting capacity and normal load
carrying capacity.
They are less expensive than circuit breakers
but less accurate.
ACRs are motivated by the fact that 60-80%
of all overhead distribution faults are
temporary and last only a few cycles or a
15
7/29/2019 Notes21 Protection
16/22
few seconds. For example, a branch may
blow against a circuit and then fall to the
ground.
As a result, it becomes very attractive to
reclose following an initial opening of the
protection device.
So the basic operation of an ACR is to Sense the overcurrent
Time and interrupt the overcurrent
Reclose to re-energize the circuit
An ACR can reclose as many as 3-4 times
before locking out.
The first reclose is generally done
instantaneously which means there is no
intentional time delay embedded in the first
reclose. Typical timing sequences used in
the industry include
0-15-30 seconds
0-30-60-90 seconds
16
7/29/2019 Notes21 Protection
17/22
5-45 seconds
But most ACRs can be set for any
combination of instantaneous operations ortime delayed operations.
21.2.4 Sectionalizers
Sectionalizers are switches. The main
difference between a switch an all otherdevices described previously is that all the
other devices can detect and interrupt a
short-circuit fault current, but a switch can
do neither.
It is typically applied together with an ACR
or a circuit breaker to isolate faulted sections
of the distribution system.
So how does a sectionalizer operate?
It counts the number of operations of thebackup device
After a pre-set number of interruptions, it
opens while the backup device is open.
17
7/29/2019 Notes21 Protection
18/22
Then the backup device can reclose to
restore service to remaining circuits.
Advantage relative to fuse is it is
unnecessary to replace it.
Advantage relative to circuit breaker or
ACR is it is less expensive.
Clear disadvantage is that it is a switch.
21.3 Coordination
The basic issue in coordinating multiple
devices in a distribution feeder is that we
want to ensure that only the minimum
number of customers are interrupted for a
specific fault, given the devices that we have
in place.
18
7/29/2019 Notes21 Protection
19/22
We use the terms protected device
(upstream) and protecting device
(downstream).
Important coordinating principles:
1. The protecting device must clear a fault
before the protected device interrupts the
circuit (fuse) or operates to lockout.
2. Outages caused by permanent faultsmust be restricted to the smallest section
of the system for the shortest time.
Figure 6 shows an example of system
coordination where a substation receives
power flow a high voltage transmission line
and steps the voltage down.
Protective devices in this illustration are
located at the coordinating points. Device A
is at the substation. Devices C and H are inthe feeder. Device B is at the branch tap off
the feeder.
19
7/29/2019 Notes21 Protection
20/22
Device D is on the transformer primary and
devices E, F, and G are service entrance
fuses on the transformer secondary. Alldevices must be selected to carry normal
load current and respond properly to a fault.
Fig. 6 [1]
20
7/29/2019 Notes21 Protection
21/22
With respect to device H, device C is the
protected device. For a fault at point 1,
device C must not open and device H mustinterrupt.
With respect to device A, device C is the
protecting device and must interrupt
permanent fault current at point 2 before
device A operates to lockout. Device B isalso a protecting device for A and must
operate similar to device C for a fault at
point 3. Only device A functions when a
fault occurs between A and C, such as at
point 4. For a transformer fault at point 5,
device D is expected to interrupt current and
permit normal load current to flow in the
remainder of the system. For an overload on
the secondary tap of transformer at point 6,
device E should interrupt the circuit,
permitting power to the transformer to becontinued so that customers on other
secondary taps will receive service.
21
7/29/2019 Notes21 Protection
22/22
References
[1] McGraw-Edison Power Systems,Distribution system protection manual.
[2] T. Short, Electric power distribution
handbook, CRC press, 2004.
[3] T. Gonen, Electric Power Distribution
System Engineering, McGraw-Hill, 1986.
[4] J. Blackburn and G. Rockefeller,Applied Protective Relaying,
Westinghouse Corporation.
[5] J. Blackburn, Protective Relaying:
Principles and Applications, 2nd edition,
Marcel-Dekker, New York, 1998.
[6] P. Anderson, Power system protection,
McGraw-Hill, 1999.