North America Supplemental Manualfor

EcoMAXX® No Return Valve (EM-NRV)2020 - Second Edition - Version 0020

Page 2: North America Supplemental Manual for EcoMAXX® No Return

Page 2

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Table of Contents

Supplemental Manual Information..................................................................................................3Safety..........................................................................................................................................................3Warranty...................................................................................................................................................3Introduction............................................................................................................................................4NFPA Compliance.....................................................................................................................................4EcoMAXX® NRV Specifications (EM-NRVØ)...................................................................................5No Return Valve (NRV) Dimensions..................................................................................................6No Return Valve (NRV) Dimensions..................................................................................................6Flange and Co-Flange Dimensions....................................................................................................7EcoMAXX® Intrinsic Panel Specifications (O-EM-NRV-CP03).................................................8Receiving The EcoMAXX® EM-NRV....................................................................................................9NRV Shipment Parts and Assembly Instructions.........................................................................932”+ Assembly Instructions (Per Side).........................................................................................11Microswitch with Mounting Bolts (O-EM-NRV-MS)..............................................................13Mounting the Microswitch to the NRV......................................................................................13Dust Level Sensor with Mounting Flanges (O-EM-NRV-DLS)..............................................14Mounting the Dust Level Sensor to EcoMAXX NRV...............................................................14Dust Level Sensor -Recommended Installation Height.........................................................14General Wiring Schematic for the EcoMAXX® Intrinsic Panel..........................................15Wiring the Microswitch to the EcoMAXX® Intrinsic Panel................................................17Wiring the Dust Level Sensor to the EcoMAXX® Intrinsic Panel......................................17General Wiring Schematic for the CP04.....................................................................................18Wiring the Dust Level Sensor to the CP04.................................................................................18Wiring the Microswitch to the......................................................................................................18System interlock via the Cp04.........................................................................................................18Bypassing the Dust Level Sensor for Inspection Protocol in the CP04...........................19EcoMAXX® NRV Spare/Replacement Parts...................................................................................20EcoMAXX® NRV Control Components (All Sizes)....................................................................20EcoMAXX® NRV Replacement Parts Specific to 32” +..............................................................20Contact Information...........................................................................................................................21

Page 3: North America Supplemental Manual for EcoMAXX® No Return

Page 3

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Supplemental Manual InformationThis manual is a supplement to the Aircom installation, use and maintenance manual for no return valves. it has been compiled by Boss Products, LLC® for the North America market. The installer and end user must be famil-iar with both the Aircom Manual and the Boss Products suppliment.

Warranty1. Boss Products, LLC® warrants to the Buyer that the material sold to Buyer will be free from manufacturing

defects at the time of shipping of such material to the job site.2. Boss Products, LLC® further warrants to the Buyer that the workmanship and material supplied to the Buy-

er will be free from defects under proper usage for a period of 12 months from the shipping date so long as Buyer can demonstrate (i) that such material was installed in accordance with the National Electrical Code, NFPA guidelines, and local codes and ordinances, and (ii) that Buyer has property maintained such material as per the maintenance requirements related to such material. The warranty provided under this Section 2, shall become null and void if Buyer fails to prove proper installation and maintenance of materials provided by Boss Products, LLC®.

3. The Buyer shall be responsible for remedies to problems with material and services not provided by Boss Products, LLC®.

4. Boss Products, LLC®, at their sole discretion, will repair or replace defective material or workmanship orig-inally supplied by them. Said defective material or workmanship shall be returned to Boss Products, LLC® freight prepaid. Repaired or replaced materials will be returned to the customer freight prepaid.

There are no warranties either expressed or implied, including the implied warranties of merchant-ability and fitness for a particular purpose, which extended beyond the warranties contained in this document. Boss Products, LLC® shall not be liable for any incidental, consequential, direct,

indirect or other damages, arising under any theory of law whatsoever.

SafetyElectrical shock hazard

only qualified personell should install, maintain or work on this equipment! Always perform work with the power off.

Arc flash hazard. Appropriate PPE required!

Follow all requirements in NFPA 70E Always maintain propper conveying velocities as required by NFPA 652 & 654 for Combustible

dusts.

Warning! Do not substitute components.

Read all disclaimers in the corresponding Aircom Manual. It is the installers responsibility to verify that their installation complies

with requirements set by the authority having jurisdiction: All national, Local, NEC, and NFPA codes and/or Guidelines.

Page 4: North America Supplemental Manual for EcoMAXX® No Return

Page 4

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

IntroductionThank you for purchasing the EcoMAXX® No Return Valve (EM-NRV). The EM-NRV is an Explosion Isolation Device specifically designed to prevent deflagration propagation between connected equipment. The EM-NRV is ATEX certified and NFPA 69 compliant.Required Items for NFPA 69 Compliance:• O-EM-NRV-CP03, Intrinsically Safe Control Panel• O-EM-NRV-MS, Microswitch• O-EM-NRV-DLS, Dust Level SensorComplimentary Products:• EM-HSAG line of High Speed Abort Gates• EM-FBS line of Firebreak Shutters• EM-VQ/VD/VL line of Explosion Vents• EM-FCS Spark Detection and Extinguishment Systems• EM-IMS line of Dust Monitoring (Emissions) Systems• ECOBOSS Line of Energy Management Control Systems

NFPA ComplianceNFPA 652 – Standard on the Fundamentals of Combustible Dust -

2019 Edition• 9.7.4 – Equipment Isolation o 9.7.4.1* – Where an explosion hazard exists, isolation devices shall be provided to prevent deflagration propagation between connected equipment in accordance with NFPA 69. o 9.7.4.3 – Isolation of Upstream Work Areas. Where a dust explosion hazard exists, isolation devices shall be provided to prevent deflagration propagation from equipment through upstream ductwork to the work areas in accordance with NFPA 69.

NFPA 69 – Standard of Explosion Prevention Systems - 2019 Edition

Chapter 12 - Deflagration Control by Passive Isolationo 12.2.3 Flow Actuated Flap Valve

The EM-NRV meets all requirements of this section when installed with all options and conveying ductwork per 12.2.3.4.6

Key Points• 12.2.3.4.2 Requires a locking mechanism which is provided standard.• 12.2.3.4.3 Requires an Inspection door which is provided standard.• 12.2.3.4.4 Requires an immediate, automatic shutdown of the protected process. Accomplished with O-EM-

NRV-MS Microswitch which is an available option that mounts on the NRV locking mechanism and sends a signal upon an event.

• 12.2.3.4.5 and 12.2.3.4.5.1 requires a continuous signal to ensure valve operation is not compromised by the accumulation of a dust layer on the bottom interior of the valve and requires an immediate, automatic and orderly shutdown of the protected process. Accomplished with O-EM-NRV-DLS capacitive style Dust Level Sensor (DLS) which sends a signal when 0.15”-0.20” of dust has accumulated. The DLS is located in the air-stream and requires an intrinsically safe barrier.

• 12.2.3.5 Requires System Certification by a recognized testing organization. A.10.4.2.1 allows for European CEN ATEX certification being acceptable.

Page 5: North America Supplemental Manual for EcoMAXX® No Return

Page 5

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

EcoMAXX® NRV Specifications (EM-NRVØ) Standard Features (All Sizes)

Heavy Duty Welded Steel Construction * Epoxy Powder Coated Safety Red FinishFlanged Inlet and Outlet with Co-Flanges * Grounding Lugs * Locking Mechanism(s)

ATEX Certification

NFPA 69-2019 (A.12.2.3.4.6) STATES: The minimum design pressure for the ductwork is typically 2 x Pred because the pressure wave reflects off the closed valve. Depending on the distance between the flap valve and the

enclosure, pressure piling could further increase the expected peak pressure.** See Minimum/Maximum Distance Specifications

The NRV can be installed indoors, however the below statement from NFPA must be taken into account during the duct design process.

Page 6: North America Supplemental Manual for EcoMAXX® No Return

Page 6

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Model # Ø A B C D E F G H I LBSEM-NRV04 100mm/3.9” 7.7 6.8 15.0 8.7 9.1 3.8 3.0 0.0 0.0 40EM-NRV05 125mm/4.9” 8.7 7.8 16.0 9.6 9.6 4.3 3.3 0.0 0.0 40 EM-NRV06 160mm/6.3” 14.2 13.4 21.7 17.7 11.8 7.1 6.7 0.0 3.0 45EM-NRV07 180mm/7.1” 14.2 13.4 21.7 19.7 11.8 7.1 6.7 0.0 3.0 45EM-NRV08 200mm/7.9” 14.2 13.4 21.7 19.7 11.8 7.1 6.7 0.0 3.0 45EM-NRV10 250mm/9.8” 16.1 15.4 23.6 22.4 12.8 8.1 7.7 0.0 3.1 56EM-NRV12 300mm/11.8” 18.1 17.3 26.4 23.6 13.8 9.1 8.7 0.0 3.1 84EM-NRV14 350mm/13.8” 20.1 19.3 28.3 25.6 14.8 10.0 9.6 11.8 3.1 100EM-NRV16 400mm/15.7” 22.0 23.2 30.3 29.5 15.7 11.0 11.2 13.5 5.1 120EM-NRV18 450mm/17.7” 24.0 25.2 32.3 33.3 16.7 12.0 11.6 15.7 7.1 150EM-NRV20 500mm/19.7” 26.0 27.2 34.3 38.8 17.7 13.0 12.6 18.1 10.6 177EM-NRV22 550mm/21.7” 28.0 29.1 36.2 37.4 18.7 14.0 13.6 19.7 7.1 221EM-NRV24 600mm/23.6” 29.9 31.1 38.2 41.1 19.7 15.0 14.6 21.7 11.4 254EM-NRV26 650mm/25.6” 31.9 33.1 40.2 45.1 20.7 15.9 15.6 23.8 13.4 276EM-NRV28 700mm/27.6” 33.9 35.0 42.1 47.0 21.7 16.9 16.5 25.6 11.0 298

Model # Ø A B C D E F G H I LBSEM-NRV32 800mm/31.5” 38.6 40.4 52.5 56.5 26.0 26.0 18.9 28.1 14.2 728EM-NRV36 900mm/35.4” 42.5 44.3 44.7 60.4 28.0 28.0 20.9 28.1 14.2 860RM-NRV40 1000mm/39.4” 46.5 48.6 48.2 64.4 29.9 29.9 22.8 35.8 14.2 1000EM-NRV44 1100mm/43.3” 50.4 52.2 51.5 66.9 29.9 29.9 24.6 39.8 14.2 1135EM-NRV48 1200mm/47.2” 54.3 56.1 54.7 70.9 32.7 32.7 26.8 43.7 14.2 1275EM-NRV52 1300mm/51.2” 58.3 59.1 54.7 75.2 34.3 34.3 29.5 47.6 14.2 1425

(SIZES 4” - 16”)RATED FOR:

Class ST 2 ApplicationsKst max 270 bar m/s

Pred 0.50 bar Certification EN 16447

(SIZE 36”)RATED FOR:

Class ST 3 ApplicationsKst max 330 bar m/s

Pred 0.5 barCertification EN 16447

(SIZE 32”)RATED FOR:

Class ST 2 ApplicationsKst max 240 bar m/s

Pred 0.25 barCertification EN 16447

*NOTE: Co-flanges provided to slip over imperial sized ductwork.

*NOTE: Co-flanges provided to slip over imperial sized ductwork.

Not

Rate

d

No Return Valve (NRV) Dimensions

No Return Valve (NRV) Dimensions

(SIZES 18” - 28”)RATED FOR:

Class ST 2 ApplicationsKst max 260 bar m/s

Pred 0.50 bar Certification EN 16447

Page 7: North America Supplemental Manual for EcoMAXX® No Return

Page 7

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

• I.D. 1 Dimensions are the inner diameter dimensions of the flanges installed on EM-NRV

• I.D. 2 Dimensions are the inner di-ameter dimensions of the co-flanges provided with EM-NRV

Flange and Co-Flange Dimensions

Model # I.D. 1 I.D. 2 B.C. O.D. Holes ThicknessEB-FL04 4.01” 4.06” 5.20” 6.42” 4 @ 0.4” 0.16”EB-FL05 5.00” 5.06” 6.18” 7.42” 4 @ 0.4” 0.16”EB-FL06 6.37” 6.09” 7.6” 8.82” 6 @ 0.4” 0.16”EB-FL07 7.16” 7.125” 8.35” 9.49” 6 @ 0.4” 0.16”EB-FL08 7.95” 8.125” 9.17” 10.48” 6 @ 0.4” 0.16”EB-FL10 9.92” 10.125” 11.14” 12.48” 6 @ 0.4” 0.16”EB-FL12 11.90” 12.125” 13.35” 14.89” 8 @ 0.4” 0.20”EB-FL14 13.85” 14.125” 15.28” 16.88” 8 @ 0.4” 0.20”EB-FL16 15.78” 16.125” 17.24” 18.88” 8 @ 0.4” 0.20”EB-FL18 17.75” 18.125” 19.21” 20.88” 8 @ 0.4” 0.20”EB-FL20 19.72” 20.125” 21.18” 22.88” 12 @ 0.4” 0.20”EB-FL22 21.69” 22.125” 23.15” 24.89” 12 @ 0.5” 0.20”EB-FL24 23.66” 24.125” 25.24” 27.26” 12 @ 0.5” 0.24”EB-FL26 25.62” 26.125” 27.28” 29.26” 14 @ 0.5” 0.24”EB-FL28 27.60” 28.125” 29.25” 31.26” 14 @ 0.5” 0.24”EB-FL32 31.53” 32.09” 33.19” 34.88” 16 @ 0.5” 0.24”EB-FL36 35.48” 36.125” 37.11” 38.82” 16 @ 0.5” 0.24”EB-FL40 39.40” 40.125” 40.98” 44.06” 16 @ 0.5” 0.24”EB-FL44 43.34” 44.09” 45.39” 48.03” 18 @ 0.5” 0.24”EB-FL48 47.28” 48.12” 49.33” 52.06” 20 @ 0.5” 0.24”EB-FL52 52.13” 52.13” 53.23” 55.35” 24 @ 0.5” 0.24”

Page 8: North America Supplemental Manual for EcoMAXX® No Return

Page 8

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

4 Models Available*

• Model: O-EM-NRV-CP03 (1 NRV)• Model: O-EM-NRV-CP03X2 (Up-to 2 NRVs)• Model: O-EM-NRV-CP03X3 (Up-to 3 NRVs)• Model: O-EM-NRV-CP03X4 (Up-to 4 NRVs)• *Larger Panels are available on request

EcoMAXX® Intrinsic Panel Specifications (O-EM-NRV-CP03)All Models Feature

• NEMA 4 Enclosure• Status lights

(Green = System OK / RED = System Trouble)• Terminals for Microswitch• Intrinsic circuit with barrier and physical separation• Drawings• 120VAC Input Power *24VDC optional• UL 698A Intrinsically Safe Label

Required Sensors

• O-EM-NRV-MS - Microswitch for No Return Valve. (Shipped Loose)

• O-EM-NRV-DLS: Dust Level Sensor (Capacitive) to ensure the NRV is not compromised by a layer of dust accumulation. (Shipped Loose)

Contains O-EM-NRV-DLS (Dust Level Sensor), O-EM-NRV-MS (Microswitch) and Wiring DiagramCP03 V1 CP03 V2 CP03 V3

Page 9: North America Supplemental Manual for EcoMAXX® No Return

Page 9

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

• The EcoMAXX® EM-NRV typically ships shrink-wrapped and strapped on a wooden pallet. Custom-er must inspect the equipment for damage upon receipt. If damage is present, receiver must note damaged on the shipping documents in order to file a claim.

• All Counterweights are shipped inside the No Re-turn Valve. Sizes 7 thru 28 have 1 counter weight. Sizes 32” + Utilize 2 counterweights with patented breaking elements.

• Dependent on the size of the No Return valve, the O-EM-NRV-CP03 control panel, O-EM-NRV-MS and O-EM-NRV-DLS are shipped in a cardboard box placed on top of the valve or inside it.

Receiving The EcoMAXX® EM-NRV

NRV Shipment Parts and Assembly Instructions4”-28” Shipment Parts

Items included in NRV shipment images, not to scale**

Counter Weight Arm

Locking Mechanism

Aircom manual with metric Allen Wrenches

NRV Main Body

Page 10: North America Supplemental Manual for EcoMAXX® No Return

Page 10

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Step 1: Remove bolt on counter weight mounting shaft using provided Allen wrench.

Step 2: Slide counter weight onto mounting shaft, then re-tighten bolt using provided Allen wrench.

Step 3: Position counter weight in the locked position of the locking mechanism.

Step 4: Tighten the two bolts on counter arm to secure counter weight to mounting shaft.

For mounting the microswitch and dust level sensor, refer to pages 13, 14.

4” – 28” Assembly InstructionsNRV Shipment Parts and Assembly Instructions

Page 11: North America Supplemental Manual for EcoMAXX® No Return

Page 11

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

32”+ Shipment PartsNRV Shipment Parts and Assembly Instructions

Locking Mechanism

(2x) UpperCounter Weight Arm

(2x) LowerCounter Weight Arm

Aircom manual with metric Allen Wrenches

6x - Breaking Elements

32”+ Assembly Instructions (Per Side)

Step 1: Remove bolt and washer.

Step 2: Slide Arm on to the shaft. Note the slide key on the shaft.

Page 12: North America Supplemental Manual for EcoMAXX® No Return

Page 12

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Step 3: Secure arm in place by tightening the set screw. Note: You will need to adjust arm once locking mechanism is in place.

Step 4: Install Locking mechanism onto the mounting bracket of the EcoMAXX NRV. Note: Ensure the handle is centered in the locking mech-anism. If installed incorrectly, handle may rub or stick preventing the counter weight from locking in place during an event.

Step 5: Slide counter weight onto the shaft and insert safety pin to keep counter weight in place.

Step 6: Insert bolt and washer to secure the counterweight onto the shaft.

Step 7: With safety bolt in place and counter-weight secured, mount the breaking element to the counterweight and tighten bolts. Note: Bolts need to be snug. Do not over tighten, this may damage the breaking element.

Step 8: IMPORTANT!! Be sure to remove safe-ty pin from the counterweight. Failure to do so will cause the EcoMAXX No Return Valve to not close fast enough during an event.

Page 13: North America Supplemental Manual for EcoMAXX® No Return

Page 13

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Microswitch with Mounting Bolts (O-EM-NRV-MS)

Step 1: Secure Microswitch

Step 2: Remove screw and lever.

Step 3: Line up arrows and then insert and tighten the screw.

Mounting the Microswitch to the NRV

Step 4: Mount Microswitch to the locking mechanism using the provided bolts.

Step 5: Rotate counterweight arm into the locked position. Ensure arm is centered in the locking mechanism to avoid obstruction. If not centered, the arm may not fully close or lock during an event.

IMPORTANT!! Unlock counter weight prior to Initial Start-Up, otherwise “System Fault” will turn on and system will not start.

Page 14: North America Supplemental Manual for EcoMAXX® No Return

Page 14

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Mounting the Dust Level Sensor to EcoMAXX NRV

Step 1: Remove bolt on the bot-tom side of the NRV.

Step: 2: Install the first mounting flange onto the sensor. Note: The drawing below specifies the distances the first mounting flange should be from the top of the sensor.

Step 3: Insert sensor into the bottom side of the NRV and install second mounting flange on the sensor. Adjust height of the sensor to required height de-scribed in the drawing provided.

Dust Level Sensor -Recommended Installation Height

Dust Level Sensor with Mounting Flanges (O-EM-NRV-DLS)

Recommended Installation height of the first mounting flange. If the tip of the sensor is too close to the bottom surface of the NRV, the sen-sor will not function properly. Contrary, insert-ing the sensor too deep will result with interfer-ence from the flap valve. **26mm from the bottom surface of the NRV.

NRV Side Profile NRV Cut View

Page 15: North America Supplemental Manual for EcoMAXX® No Return

Page 15

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

General Wiring Schematic for the EcoMAXX® Cp03

NOTE: On the wiring diagram you will notice there are two options provided for connecting to the main system control panel. One is an individual alarm configuration and the other is a general alarm config-uration. Choose the one that will work with your main system control panel. You will need to refer to your main system wiring diagram to determine how the connection needs to be made. See below for an en-hanced view of the 2 options.

To wire supply power connect line, ground, and neutral wires to terminals L, GND, and N as shown in the General Wiring diagram.

Page 16: North America Supplemental Manual for EcoMAXX® No Return

Page 16

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Connect low voltage control wires to terminals 3 and 6 as shown in the General Alarm Configuration wiring diagram. Then use a jumper to connect terminals 4 and 5.

Connect low voltage control wires to terminals 3 and 4 as shown in the Individual Alarm Configuration wiring diagram. Then connect low voltage control wires to terminals 5 and 6 as shown in the Individual Alarm Configuration wiring diagram.

Page 17: North America Supplemental Manual for EcoMAXX® No Return

Page 17

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Wiring the Microswitch to the EcoMAXX® CP03

Referencing the wiring diagram on page 15, the microswitch is connected using terminals 1 and 2. When looking at the diagram, notice only the black and grey wires are used for the microswitch connection.

Wiring the Dust Level Sensor to the EcoMAXX® CP03

Connect the black wire to one of the terminals labeled 1. Then connect the grey wire to the terminal labeled 2.

**On the wiring diagrams you will notice that the Dust Level Sensor will be installed inside the physical barrier inside of the

control Panel.**

Dust level sensor wiring must be in its own conduit.

Allen Bradley ISR: Connect the brown wire to terminal 1 on the intrinsic relay barrier. Connect the blue wire to terminal 3 on the intrinsic relay barrier.

Phoenix Contact ISR: Connect the brown wire to terminal 4.1 on the intrinsic relay barrier. Connect the blue wire to terminal 4.3 on the intrinsic relay barrier.

Page 18: North America Supplemental Manual for EcoMAXX® No Return

Page 18

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

General Wiring Schematic for the Cp04 (56004-031103)

Connect the brown wire to terminal 4.1 on the intrinsic relay barrier. Connect the blue wire to terminal 4.3 on the intrinsic relay barrier.

Wiring the Dust Level Sensor to the CP04

Wiring the Microswitch to the CP04Similar to the CP03, the black wire will land in the “24V+” terminal and the gray wire will land in the “1” terminal. Disregard all other wires from microswitch. (See below)

Jumper will be required between “24V+” and “2” (See Below)

System Interlock Via CP04Terminals “U1” and “U2” will be used as a shut-down signal in the CP04. When the CP04 is “OK” the interlock contact will be closed. The contact will open if any sensor faults. (Refer to above sche-matic)

Microswitch Connections Jumper Connections(Unless Using Clean Side Vigiflap)

interlock Connections

Page 19: North America Supplemental Manual for EcoMAXX® No Return

Page 19

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Bypasssing the Dust Level Sensor for Inspection Protocol in the Cp04

In cases where an inspection protocol (NFPA 69: 2019, 12.2.3.4.5.2) is instituted in lieu of a dust level sensor for dust accumulation monitoring inside of an EcoMAXX NRV the following instructions must be followed to ensure the system remains running uninterrupted by a fault alarm.

1. Press the Up or Down arrow until your screen displays the system time and then press the “ESC” key.

2. The system menu will come up, scroll using the up and down arrows and press the “OK” key when you find “Program”.

3. Under the “Program” menu, select “Set Pa-rameter” by pressing the “OK” key.

4. Under the “Set Parameter” menu, select “By-pass DLS 1” and press the “OK” key.

5. Press the “OK” key until the word “Off ” flashes. Scroll using the up and down arrows and change to “On”. Press “ESC” when complete to exit all menus. Repeat steps 4 and 5 for DLS 2, 3, and 4 (if applicable).

Page 20: North America Supplemental Manual for EcoMAXX® No Return

Page 20

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

EcoMAXX® NRV Spare/Replacement Parts

Counter Weight AssemblyP/N: RP-EM-NRV-CWØ

NOTES:Where “Ø” is noted specify diameter of product.

Other replaceable parts not noted may be available but must discussed with Boss Products to insure integrity and functionality of the valve.

Locking Mechanism with Mounting BracketP/N: RP-EM-NRV-LMB

Flanges and Co-FlangesFlange P/N: EB-FLØCo-Flange P/N: EB-CFLØ

EcoMAXX® NRV Control Components (All Sizes)

Control PanelP/N: O-EM-NRV-CP03

Dust Level SensorP/N: O-EM-NRV-DLS

MicroswitchP/N: O-EM-NRV-MS

EcoMAXX® NRV Replacement Parts Specific to 32” +Breaking Element Part

NumberAssociated

NRV Size P-EM-NRV-BE20 32”

P-EM-NRV-BE22 36”, 40”

P-EM-NRV-BE30 44”, 48”

P-EM-NRV-BE40 52”

Page 21: North America Supplemental Manual for EcoMAXX® No Return

Page 21

NRV NA Sup. Manual 2020 - Second Edition - Version 0020Print date: 6/26/2020

Contact Information

6729 GUADA COMA DR, SUITE 100SCHERTZ, TX 78154

USA

Phone: 210-664-4200FAX: 913-620-6280

Email: [email protected]

WWW.BOSSPRODUCTSAMERICA.COM

© Boss Products, LLC 2018

Revision 20:updates to dimensions of body and flanges of nrv to match most recent documentation. Addition of CP04 to manual.