Name: Osamu TSUBOICountry: JapanRegistration No.:
Group: B5Pref. Subject: 1
Question: 7
Question 7
Non-harmonic-restraint schemes applied in Japan
2
Name: Osamu TSUBOICountry: JapanRegistration No.:
Group: B5Pref. Subject: 1
Question: 7
1. A non-harmonic-restraint scheme is selected according to the relay principle.
2. Fault current includes lower harmonic; such as 1000kV, cable transmission.
Non-harmonic-restraint schemes applied in Japan
Non-harmonic-restraint schemes are applied in the following cases:
3
Name: Osamu TSUBOICountry: JapanRegistration No.:
Group: B5Pref. Subject: 1
Question: 7
Impedance locus scheme
For preventing unwanted operation of distance protection relay
In Japan, the distance protection is generally used for a transformer backup protection
Reactance X calculated by distance protection:
varies during inrush almost fixed during fault
(for distance protection)
4
Name: Osamu TSUBOICountry: JapanRegistration No.:
Group: B5Pref. Subject: 1
Question: 7
Current remains balanced between windings of the parallel tank even during inrush
(for 1000kV transformer with parallel winding)
Parallel winding current-balance relay scheme
Serieswinding
Commonwinding
Tertiarywinding
61S
61T
61C
61: Current-balance relay
1000kV
500kV
154kV
5
Name: Osamu TSUBOICountry: JapanRegistration No.:
Group: B5Pref. Subject: 1
Question: 7
Tertiary voltage restraint scheme
Drop in transformer tertiary voltage:
small during inrush
large during internal fault
For preventing unwanted trip-lock by the harmonic restraint
(for network with lower harmonic)
Differentialrelay
Harmonicrestraint
Small drop intransformer
tertiary voltage
&
&
Trip
Trip-lockcondition