Modular UPS System S6300 20–440 kVA (n+1) Statron’s scalable, modular 3-phase, double conversion UPS system offers maximum flexibility and power availability. The unique system design with its advanced decentralized parallel architecture consists of fully inde- pendent and hot pluggable modules. Each module within the UPS system consists of a rectifier, inverter, static bypass and its own DSP control and thus the UPS is free of common failure points and maximizes power availability. www.statron.com Standard features 20 kVA or 40 kVA modules IGBT and MOSFET semiconductors and DSP processors Input power factor 0.99 Service friendly with hot-plug modules High efficiency >94% Input THDi <3% Online diagnosis and -monitoring Highest availability with internal redundancy for each module CE mark Options Scalable up to 440 kVA (n+1) RS232 interface with MODBUS Monitoring software UPSMon Flexible communications with SNMP / LAN Battery monitoring Other options on request

Modulare USV S6300 E

Embed Size (px)

DESCRIPTION

Modulare USV S6300 E

Citation preview

Page 1: Modulare USV S6300 E

Modular UPS SystemS6300 20–440 kVA (n+1)

Statron’s scalable, modular 3-phase,double conversion UPS systemoffers maximum flexibility and poweravailability.

The unique system design with itsadvanced decentralized parallelarchitecture consists of fully inde-pendent and hot pluggable modules.Each module within the UPS systemconsists of a rectifier, inverter, staticbypass and its own DSP control andthus the UPS is free of commonfailure points and maximizes poweravailability.

www.statron.com

Standard features• 20 kVA or 40 kVA modules

• IGBT and MOSFET semiconductors and

DSP processors

• Input power factor 0.99

• Service friendly with hot-plug modules

• High efficiency >94%

• Input THDi <3%

• Online diagnosis and -monitoring

• Highest availability with internal redundancy

for each module

• CE mark

Options• Scalable up to 440 kVA (n+1)

• RS232 interface with MODBUS

• Monitoring software UPSMon

• Flexible communications with SNMP / LAN

• Battery monitoring

• Other options on request

Page 2: Modulare USV S6300 E

The Statron S6300 UPS is developed for mission-critical applications like datacenters, computer-con-trolled industry processes, sensitive medical equipment or machines – everywhere where highest avail-ability must be provided to secure critical loads.

Power outages or other disturbances in the power grid cannot be avoided but the downtime and reco-very costs of your system can. The S6300 uninterruptible power supply (UPS) protects mission-criticalloads against all disturbances in the power grid as shown below and provides safe and clean backuppower.

Equipment connected to the S6300 UPS is protected against the following disturbances:

Voltage Phenomenon Time Example

1. Outage /blackouts >10 ms

2. Sags /brownouts <16 ms

3. Dynamic overvoltage 4 …16 ms

4. Undervoltage continuous

5. Overvoltage continuous

6. Transients / surges <4 ms

7. Voltage distorsion (burst) alternating

8. Voltage distorsion periodical

9. Frequency variations sporadic

10. Lightning strikes sporadic

Modular UPS SystemS6300 – Application Areas

Modular UPS SystemS6300 – Highest Availability

Page 3: Modulare USV S6300 E

The service friendly concept is another great advantage of theS6300.Hot-plug modules and pre-configured parts guarantee easyand fast replacement, service and maintenance guaranteeingpower availability.

Key points in reducing the service and maintenance costs:

• Reduced MTTR (Mean Time to Repair) and maximizedsecured availability with hot-plug modules.

• Front access to all components.

• No need for trained personnel on site as the system isdesigned for “plug and play” integration.

• No spare parts stock on site needed. In case of a failureonly the module must be replaced.

Batteries and battery cabinets –modular technology

Multiple strings of sealed maintenance free long life lead acidbatteries in pre-configured battery trays simplify the installa-tion on site. Additional battery strings can be added while thesystem is running for additional back-up time.

External sealed maintenance free lead acid batteries or ventedlow maintenance lead acid batteries can be placed on a rack,in a special battery room or besides the UPS system.

Modular UPS SystemS6300 – Application Areas

Modular UPS SystemS6300 – Highest Availability

Modular UPS SystemS6300 – Low Service and Maintenance Cost

UPS Module

Battery string

Page 4: Modulare USV S6300 E

Modular n+1 Redundancy

Real redundancy and a decentralized architecture for all critical components eliminate the“single point of failure” completely.

• Hot-plug modules up to 440 kVA (n+1).

• Every module with own inverter, recitifierand static switch. No single point of failure.

• Internal, redundant power supply.

• Internal or external batteries.

• Monitored and speed controlled fans.

Modular UPS SystemS6300 – Application Areas

Modular UPS SystemS6300 – Highest Availability

Decentralized Controller

Decentralized Bypass

Decentralized Battery

DecentralizedArchitecture

2 Modules S6300

Page 5: Modulare USV S6300 E

Flexibility

The S6300 UPS is scalable up to 440 kVA (n+1) with its simple hot-plugable modules. Themodules allow flexible investments, always then when more power is required. An oversizedUPS is no longer needed.

Low operation costs

The operation costs are a key factor for every company. A modular UPS with an optimizedenergy efficiency helps to keep the operation cost as low as possible. The high efficiency of>94% even at 50% load keeps the energy consumption low.

Total cost of ownership (TCO)

Another important criteria while choosing the right UPS system is the total cost of ownership.Calculated over a full lifetime cycle the S6300 UPS has a remarkable lower TCO compared witha standard UPS system, considering key factors like investment cost, energy efficiency, lowmaintenance cost and small footprint.

Communication

State-of-the-art communication software supports themonitoring and control of the UPS, besides the displaycontrol panel.

• RS232 connection with MODBUS for monitoring.

• UPSMon control software und flexible communica-tion via SNMP and network adapter.

• The complete system can be controlled via LCDdisplay which shows an overview of the status andthe most important information.

• All alarms are shown in easy to understand text.

Modular UPS SystemS6300 – Optimized Costs with high scalability and efficiency

Modular UPS SystemS6300 – Technical Specification

Display

HTML Status monitoring

Page 6: Modulare USV S6300 E

3 ph Output

Model 20 kVA Modules S6300-20 S6300-40 S6300-60 S6300-80 S6300-100 S6300-120-220

Power Rating (p.f. = 0.8 ind.) 20 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120–220 kVA

Number of power modules (n+1) 2 3 4 5 6 max. 12

Nominal output power (p.f. 1) 16 kW 32 kW 48 kW 64 kW 80 kW max. 176 kW

Dimension (mm, W2D2H) 600280021800 22600280022000

Model 40 kVA Modules S6300-40 S6300-80 S6300-120 S6300-160 S6300-200 S6300-240-440

Power Rating (p.f. = 0.8 ind.) 40 kVA 80 kVA 120 kVA 160 kVA 200 kVA 240–440 kVA

Number of power modules (n+1) 2 3 4 5 6 max. 12

Nominal output power (p.f. 1) 32 kW 64 kW 96 kW 128 kW 160 kW max. 352 kW

Dimension (mm, W2D2H) 22800280021800 …22000 22800280022000

General

Efficiency (AC-AC, online) >94% (50–100% load)

Ambient conditions 0–40 °C, <95% rh (non condensing), <1000 m a.s.l.

Audible noise <60 dB(A)

EMC compatibility IEC 62040

Protection degree IP 20 (up to IP 54 optional)

Design standards IEC / EN 62040

Input

Input voltage (3 ph + N) 32400 / 230 VAC +15% / –20%

Frequency 50 / 60 Hz ±5%

Input power factor 0.99 (>0.97 at 25% load)

Input harmonic current distortion(THDi)

<4%

DC-circuit

Number of cells (typically) 22110 – 22140 (lead acid battery)

Ripple voltage <1%

Output

Output voltage (3 ph + N) 380–415 VAC

Output frequency 50 / 60 Hz ±0.01%

Output voltage stability

– static– dynamic (0–100%–0)– unbalanced load (100%)– regulation time (±1%)

±1%±5%±2%20 ms

Overload capability 125% for 10 min150% for 1 min200% for 3 sec

500% for 100 ms (bypass)

Total harmonic distortion

– linear load– non-linear load

<2%<5%

Crest factor 3:1

Quality / Environment ISO 9001:2008; ISO 14001

Further data available on request © 2011 Statron AG, data subject to change without notice

Statron AG • Industrie Nord • CH-5506 Mägenwil • SwitzerlandPhone +41 62 887 4 887 • Fax … 888E-mail: [email protected] • www.statron.com

Modular UPS SystemS6300 – Optimized Costs with high scalability and efficiency

Modular UPS SystemS6300 – Technical Specification

Modules 20 kVA up to max. 220 kVA (n+1)Modules 40 kVA up to max. 440 kVA (n+1)