Modular UPS SystemS6300 20–440 kVA (n+1)
Statron’s scalable, modular 3-phase,double conversion UPS systemoffers maximum flexibility and poweravailability.
The unique system design with itsadvanced decentralized parallelarchitecture consists of fully inde-pendent and hot pluggable modules.Each module within the UPS systemconsists of a rectifier, inverter, staticbypass and its own DSP control andthus the UPS is free of commonfailure points and maximizes poweravailability.
www.statron.com
Standard features• 20 kVA or 40 kVA modules
• IGBT and MOSFET semiconductors and
DSP processors
• Input power factor 0.99
• Service friendly with hot-plug modules
• High efficiency >94%
• Input THDi <3%
• Online diagnosis and -monitoring
• Highest availability with internal redundancy
for each module
• CE mark
Options• Scalable up to 440 kVA (n+1)
• RS232 interface with MODBUS
• Monitoring software UPSMon
• Flexible communications with SNMP / LAN
• Battery monitoring
• Other options on request
The Statron S6300 UPS is developed for mission-critical applications like datacenters, computer-con-trolled industry processes, sensitive medical equipment or machines – everywhere where highest avail-ability must be provided to secure critical loads.
Power outages or other disturbances in the power grid cannot be avoided but the downtime and reco-very costs of your system can. The S6300 uninterruptible power supply (UPS) protects mission-criticalloads against all disturbances in the power grid as shown below and provides safe and clean backuppower.
Equipment connected to the S6300 UPS is protected against the following disturbances:
Voltage Phenomenon Time Example
1. Outage /blackouts >10 ms
2. Sags /brownouts <16 ms
3. Dynamic overvoltage 4 …16 ms
4. Undervoltage continuous
5. Overvoltage continuous
6. Transients / surges <4 ms
7. Voltage distorsion (burst) alternating
8. Voltage distorsion periodical
9. Frequency variations sporadic
10. Lightning strikes sporadic
Modular UPS SystemS6300 – Application Areas
Modular UPS SystemS6300 – Highest Availability
The service friendly concept is another great advantage of theS6300.Hot-plug modules and pre-configured parts guarantee easyand fast replacement, service and maintenance guaranteeingpower availability.
Key points in reducing the service and maintenance costs:
• Reduced MTTR (Mean Time to Repair) and maximizedsecured availability with hot-plug modules.
• Front access to all components.
• No need for trained personnel on site as the system isdesigned for “plug and play” integration.
• No spare parts stock on site needed. In case of a failureonly the module must be replaced.
Batteries and battery cabinets –modular technology
Multiple strings of sealed maintenance free long life lead acidbatteries in pre-configured battery trays simplify the installa-tion on site. Additional battery strings can be added while thesystem is running for additional back-up time.
External sealed maintenance free lead acid batteries or ventedlow maintenance lead acid batteries can be placed on a rack,in a special battery room or besides the UPS system.
Modular UPS SystemS6300 – Application Areas
Modular UPS SystemS6300 – Highest Availability
Modular UPS SystemS6300 – Low Service and Maintenance Cost
UPS Module
Battery string
Modular n+1 Redundancy
Real redundancy and a decentralized architecture for all critical components eliminate the“single point of failure” completely.
• Hot-plug modules up to 440 kVA (n+1).
• Every module with own inverter, recitifierand static switch. No single point of failure.
• Internal, redundant power supply.
• Internal or external batteries.
• Monitored and speed controlled fans.
Modular UPS SystemS6300 – Application Areas
Modular UPS SystemS6300 – Highest Availability
Decentralized Controller
Decentralized Bypass
Decentralized Battery
DecentralizedArchitecture
2 Modules S6300
Flexibility
The S6300 UPS is scalable up to 440 kVA (n+1) with its simple hot-plugable modules. Themodules allow flexible investments, always then when more power is required. An oversizedUPS is no longer needed.
Low operation costs
The operation costs are a key factor for every company. A modular UPS with an optimizedenergy efficiency helps to keep the operation cost as low as possible. The high efficiency of>94% even at 50% load keeps the energy consumption low.
Total cost of ownership (TCO)
Another important criteria while choosing the right UPS system is the total cost of ownership.Calculated over a full lifetime cycle the S6300 UPS has a remarkable lower TCO compared witha standard UPS system, considering key factors like investment cost, energy efficiency, lowmaintenance cost and small footprint.
Communication
State-of-the-art communication software supports themonitoring and control of the UPS, besides the displaycontrol panel.
• RS232 connection with MODBUS for monitoring.
• UPSMon control software und flexible communica-tion via SNMP and network adapter.
• The complete system can be controlled via LCDdisplay which shows an overview of the status andthe most important information.
• All alarms are shown in easy to understand text.
Modular UPS SystemS6300 – Optimized Costs with high scalability and efficiency
Modular UPS SystemS6300 – Technical Specification
Display
HTML Status monitoring
3 ph Output
Model 20 kVA Modules S6300-20 S6300-40 S6300-60 S6300-80 S6300-100 S6300-120-220
Power Rating (p.f. = 0.8 ind.) 20 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120–220 kVA
Number of power modules (n+1) 2 3 4 5 6 max. 12
Nominal output power (p.f. 1) 16 kW 32 kW 48 kW 64 kW 80 kW max. 176 kW
Dimension (mm, W2D2H) 600280021800 22600280022000
Model 40 kVA Modules S6300-40 S6300-80 S6300-120 S6300-160 S6300-200 S6300-240-440
Power Rating (p.f. = 0.8 ind.) 40 kVA 80 kVA 120 kVA 160 kVA 200 kVA 240–440 kVA
Number of power modules (n+1) 2 3 4 5 6 max. 12
Nominal output power (p.f. 1) 32 kW 64 kW 96 kW 128 kW 160 kW max. 352 kW
Dimension (mm, W2D2H) 22800280021800 …22000 22800280022000
General
Efficiency (AC-AC, online) >94% (50–100% load)
Ambient conditions 0–40 °C, <95% rh (non condensing), <1000 m a.s.l.
Audible noise <60 dB(A)
EMC compatibility IEC 62040
Protection degree IP 20 (up to IP 54 optional)
Design standards IEC / EN 62040
Input
Input voltage (3 ph + N) 32400 / 230 VAC +15% / –20%
Frequency 50 / 60 Hz ±5%
Input power factor 0.99 (>0.97 at 25% load)
Input harmonic current distortion(THDi)
<4%
DC-circuit
Number of cells (typically) 22110 – 22140 (lead acid battery)
Ripple voltage <1%
Output
Output voltage (3 ph + N) 380–415 VAC
Output frequency 50 / 60 Hz ±0.01%
Output voltage stability
– static– dynamic (0–100%–0)– unbalanced load (100%)– regulation time (±1%)
±1%±5%±2%20 ms
Overload capability 125% for 10 min150% for 1 min200% for 3 sec
500% for 100 ms (bypass)
Total harmonic distortion
– linear load– non-linear load
<2%<5%
Crest factor 3:1
Quality / Environment ISO 9001:2008; ISO 14001
Further data available on request © 2011 Statron AG, data subject to change without notice
Statron AG • Industrie Nord • CH-5506 Mägenwil • SwitzerlandPhone +41 62 887 4 887 • Fax … 888E-mail: [email protected] • www.statron.com
Modular UPS SystemS6300 – Optimized Costs with high scalability and efficiency
Modular UPS SystemS6300 – Technical Specification
Modules 20 kVA up to max. 220 kVA (n+1)Modules 40 kVA up to max. 440 kVA (n+1)