21
HELPMAN STP Condensers Water Cooled H(C)FC models HBX, HBXV, HC, HD and HE Ammonia condensers HBN and HN Selection programme available on request 51.71 09-2000 Models HBX, HBXV, HC, HD, HE, HBN and HN

Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

  • Upload
    hadung

  • View
    241

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

HELPMANSTP Condensers

Water Cooled

n

n

n

H(C)FC models HBX, HBXV, HC, HD and HE

Ammonia condensers HBN and HN

Selection programme available on request

51.7109-2000

Models HBX, HBXV, HC, HD, HE, HBN and HN

Page 2: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers

Contents

Model Description Capacity range* Page

H(C)FC

HBX Multi purpose 32 - 5266 kW 4 - 7

HBXV Sea water (stock range) 32 - 547 kW 8 - 9

HC Small water flow 2 - 165 kW 10 - 11

HD Sea water 10 - 27 kW 12 - 13

HE Fresh water 40 - 350 kW 14 - 15

Ammonia

HBN Steel tubing ø 19/16 mm 23 - 1563 kW 16 - 18

HN Steel tubing ø 25/21 mm 636 - 6051 kW 18 - 22

* Nominal capacities at 10K lmtd

Combined Catalogue

This brochure is a collection of 7separate product leaflets. Listed inthis brochure are technical data anddimensions of the following watercooled condenser models:

H(C)FC Ammonia- HBX - HBN- HBX-V - HN- HC- HD- HE

All capacity selection data have beenleft out. For capacity selection we nowrefer to our computer selection pro-gramme, which is available on re-quest.

Individual product brochures are nolonger available.

Helpman Shell & Tube Products BV Changes possible without prior notice 2

51-7109-2000

Page 3: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers

Quality control

Strength

Strength calculations for the shellside do meet the requirements ofAD Merkblätter .The condensers are pressure testedrefrigerant side at 30 bar.

Control on dehydration

The shell side is blown through withdry compressed air and dehydratedby evacuation. The vacuum drynesstest is based on a stable pressure of10 mbar maintained for 30 minutes.

Quality assurance

Quality assurance is based onISO 9001.Dimensions of the condensers are inaccordance with the tolerance classof DIN 2800 8-E .Factory certificates and productionreports are available on request at anextra cost.

Construction and testingauthorities

Condensers can be supplied inaccordance with the rules of :

– Stoomwezen

– TÜV

– Det Norske Veritas

– Germanischer Lloyd

– Lloyd’s R.o.S.

– Bureau Veritas

– A.B.o.S.

The above rules may require modifica-tion of construction details, thereforedelivery on request only.

Operating Conditions

Unless otherwise indicated Helpmanwater cooled condensers aredesigned according to the followingoperating conditions.

Operating Operatingtemperature pressuremax. min. bar max.°C °C #14" >14"

refr. side + 100 0 23

water side + 50 1 4 2

Danger for freezing up (f.i. whenblowing off refrigerant) to be avoided.

Application outside the abovementioned areas on request .

Enquiries

It is essential that the following detailsare given when ordering or makingenquiries

– Type of refrigerant

– Duty kW

– Condensing temperature °C

– Water inlet temperature °C

– Water outlet temperature °Cor waterflow m3/h

– Fouling factor or type of water(sea water, river water etc.)

– Size of refrigerant connectionsand dimensions (if required).

Finish

Condensers are dehydrated on refrig-erant side and provided with a chargeof protection gas.Outside of condenser is blasted(quality SA 2½) and finished withprimer.

More information

For more information on the use ofwater cooled condensers we refer toour leaflet Nr. T-06-30-001(General guidelines for the use ofwater cooled condensers).

Helpman Shell & Tube Products BV Changes possible without prior notice 3

51-7109-2000

Page 4: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBX

Model indication

Example : HBX 10 - 185 - 2 ASG

HBX : Water cooled condenserwith HP-tubes ø18.9 mm

10 : Shell diameter code

185 : Effective length of tubesin cm (Nom. length)

2 : Number of passes

A : Tube material code

S : Tube plate material code

G : End cover material code

General information

Water cooled condensers type HBXform an extensive standard series forboth land and marine installations.

There are 13 shell diameters avail-able in 9 standard lengths.The condensers are suitable for allhalocarbon refrigerants.Due to application of High Perform-ance finned tubes (HP-tubes) a highduty can be reached within smalldimensions .

Duty range : 32 - 5266 kW (10 K lmtd).

For construction and testing autoritiessee page 3.

Design

Shell

Seamless steel tube for smaller con-densers (up to HBX 22).

For HBX 24 and HBX 28 welded shell,material P265 GH acc. to EN 10028-2

Tube plates

Two different types of tube plates arestandard available:

S P265 GH acc. to EN 10028-2for land installations andnon-corrosive cooling water.

I Cupro-Aluminium for sea water,brackish water and corrosivecooling water.

Cupro-Alum. is an Cu-Al-Ni-Mn-Fealloy. It contains no Zinc. This alloyoffers, for above application, an excel-lent protection against corrosion andcavitation.The holes in the tube plates aredouble grooved to give a betterresistance against thermal tension.

Tubes

For the tubes there are 3 differentstandard options :

A Aluminium-BrassHP finned tubes

C Cupro-Nickel 90/10HP finned tubes

K SF Copper HP finned tubes

Outside diameter of tubes ø18.9 mm.The tubes have plain ends ø19 mm.Tube wall according to TEMA (1988).The tubes are rolled into the tubeplate.

Helpman Shell & Tube Products BV Changes possible without prior notice 4

51-7109-2000

Page 5: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBX

HBX 6 9.4 4.7HBX 7 14.1 7.05HBX 8 23.5 11.75

HBX 10 40.0 20.0HBX 12 49.4 24.7HBX 13 61.2 30.6

HBX 14 84.7 42.35HBX 16 112.9 56.45HBX 18 136.4 68.2

HBX 20 174.0 87.0HBX 22 214.0 107.0

HBX 24 272.8 –HBX 28 392.7 –

HBX 6 - 100 32HBX 7 - 150 70HBX 8 - 150 118

HBX 10 - 185 251HBX 12 - 225 380HBX 13 - 225 471

HBX 14 - 260 761HBX 16 - 260 1015HBX 18 - 300 1424

HBX 20 - 335 2002HBX 22 - 375 2870

HBX 24 - 375 3658HBX 28 - 375 5266

End covers

Flanges according to :

DIN 2631 - for HBX 6 - HBX 22,DIN 2632 - for HBX 24 and HBX 28.

Waterflow and return connections arealways on one cover with drain andpurge connections on the oppositeend cover.Covers for 2 and 4 passes can besupplied in 3 types :

G - Cast iron,

P - Plastified cast iron,

B - Bronze.HBX 24 and 28 in bronze onlyand only 2-pass.

Covers fixed to flanges on tube plate,(see detail drawing page 7), with highgrade steel socket head bolts andsealed with O-rings.

Support plates

Intermediate supporting plates aremounted in the shell if necessary toprevent tube vibration.

Refrigerant connections

Combined soldering / welding stubs,blanked off.

Accessories

Standard with 2 refrigerant connec-tions without valves.Valves, level glasses, counter flangescan be supplied as an extra.

Supports also can be mounted as anextra.

Other material combinations

On request other materials than theabove mentioned can be selected forend covers, shell, tube plates andtubes.

Max. Waterflow m 3/h

Type 2 pass. 4 pass.

Duty kW (lmtd = 10 K)

Type Duty

Nominal Duty

The nominal duty is based on follow-ing conditions:

Refrigerant: R 22

Maximum waterflow

Fouling factor: 0.86 x 10-4 m2K/W

lmtd: 10 K

Water tubes: Aluminium-Brass

Helpman Shell & Tube Products BV Changes possible without prior notice 5

51-7109-2000

Page 6: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBX

Dimensions (mm)

Cast iron end covers (G/P)

Type 2 passes 4 passes tubes kg kg/m dm3/m

d D A B E F A B C E F numb. m2/m M N V

Bronze end covers (B)

HBX- 6 159 204 30 85 123 32 30 75 32 103 25 16 2.7 15 30 5HBX- 7 168 223 35 90 133 40 35 90 32 123 32 24 4.1 20 38 7HBX- 8 219 266 40 100 143 50 40 100 40 133 40 40 6.8 30 62 12

HBX-10 267 316 50 105 163 65 50 105 50 143 50 68 11.6 40 92 21HBX-12 298 353 55 125 193 80 50 115 60 163 65 84 14.3 50 115 26HBX-13 324 379 60 125 193 80 60 115 60 163 65 104 17.7 60 135 32

HBX-14 368 423 65 135 213 100 65 135 70 193 80 144 24.5 75 180 44HBX-16 419 481 75 140 243 125 75 140 75 193 80 192 32.6 100 245 59HBX-18 457 521 80 150 243 125 80 150 85 213 100 232 39.4 125 285 71

HBX-20 508 578 90 160 268 150 90 160 98 213 100 296 50.3 165 360 91HBX-22 559 631 180 255 268 150 100 170 110 243 125 364 61.9 270 450 112

HBX- 6 159 202 45 95 123 32 45 90 25 103 25 16 2.7 16 30 5HBX- 7 168 221 50 100 133 40 50 100 32 123 32 24 4.1 22 38 7HBX- 8 219 262 60 100 143 50 40 100 40 133 40 40 6.8 32 62 12

HBX-10 267 312 80 125 163 65 50 105 50 143 50 68 11.6 48 92 21HBX-12 298 350 90 140 193 80 55 115 60 163 65 84 14.3 63 115 26HBX-13 324 376 100 160 193 80 60 115 60 163 65 104 17.7 72 135 32

HBX-14 368 420 115 175 213 100 65 135 70 193 80 144 24.5 93 180 44HBX-16 419 476 130 195 243 125 75 140 75 193 80 192 32.6 125 245 59HBX-18 457 516 150 215 243 125 80 150 85 213 100 232 39.4 160 285 71

HBX-20 508 574 175 250 268 150 90 160 98 213 100 296 50.3 220 360 91HBX-22 559 624 180 255 268 150 100 170 110 243 125 364 61.9 270 450 112

HBX-24 610 682 205 280 318 175 464 78.9 340 500 130HBX-28 720 800 240 325 344 200 668 113.6 450 685 170

M Weight of both ends (kg)

N Weight of shell with tubes (kg/m)

V Pump down capacity (dm3/m)Pump down capacities are based on 70 %of the tubes below the liquid level.

Helpman Shell & Tube Products BV Changes possible without prior notice 6

51-7109-2000

Page 7: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBX

L + 40nom.A (B)

L nom.

F

E

H

30 30G

2-Pass

J

4-Pass

C

E

F

D d

4530

0.6 L nom.= =

Y

A

X

L + 40 mmnom. B

L nom. = Nominal length

The following details are to begiven when ordering :

Dimensions X and Y, and the size ofthe refrigerant connections.

Mounting feet (extra price)

Dimens. mm H G J

HBX- 6 160 140 14HBX- 7 170 140 14HBX- 8 190 140 14

HBX-10 215 240 18HBX-12 230 240 18HBX-13 245 240 18

HBX-14 265 240 18HBX-16 290 340 23HBX-18 310 340 23

HBX-20 335 340 23HBX-22 360 340 23

HBX-24 385 340 23HBX-28 440 390 27

Helpman Shell & Tube Products BV Changes possible without prior notice 7

51-7109-2000

Page 8: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBXV

Stock rangeAttractive pricesthrough serial production.

Model indication

Example : HBXV 8 -125 - 2 AIP

HBXV : Water cooled condenserwith HP-tubes ø18.9 mm

8 : Shell diameter code

125 : Effective length in cm(nominal length)

2 : Number of passes

A : Tube material code

I : Tube plate material code

P : End cover material code

General Information

The condensers are manufacturedwith seamless-steel-shell andCupro-Aluminium tubeplates withtubes (HP-type) of Aluminium-Brass(CuZn20Al2).Covers for 2 and 4 passes can besupplied in 3 different materials:

G - Cast iron,

P - Plastified cast iron,

B - Bronze.

This choice of material allows apply-ing for land as well as marine applica-tions.

Suitable for all halocarbon refriger-ants. Duties: from 32 up to 547 kW(10 K lmtd).

Design

In standard execution the condensersare supplied with :

– 1 Hotgas connection (welding-soldering stub).

– 2 Liquid connections (welding-soldering stub); 1 connection issufficient for the whole duty.

– 2 Connections d" NPTF, e.g. forconnecting a levelglass.

– 1 Connection 2" NPTF, e.g. forconnecting a safety valve.

– 2 Adjustable supports for mountingon floor, wall or ceiling.

Nominal Duty

The nominal duty is based on follow-ing conditions:

Refrigerant: R 22

Maximum waterflow

Fouling factor: 0.86 x 10-4 m2K/W

lmtd: 10 K

Water tubes: Aluminium-Brass

Helpman Shell & Tube Products BV Changes possible without prior notice 8

51-7109-2000

Page 9: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBXV

D d

M

100

220 P

A L B

100

Liquid (2x)

" NPTF

" NPTF (2x)Hot gas 4 Pass

C

H

2 Pass

G

F FE

Dimensions mm

Type 2 pass 4 pass Supports Weigth

d D A B A B C L M P E F kg

Water flow Nominal Connections

Type m3/h (max.) duty (kW) refrigerant water (DIN 2631)

2 pass 4 pass lmtd = 10 K hot gas liquid 2 pass G 4 pass H

HBXV 6-100 159 204 30 85 30 75 32 1040 270 600 180 35 45

HBXV 7-100 168 223 35 90 35 90 32 1040 270 600 180 35 60HBXV 7-150 168 223 35 90 35 90 32 1540 320 1100 180 35 80

HBXV 8-125 219 266 40 95 40 95 39 1290 270 850 240 30 110HBXV 8-150 219 266 40 95 40 95 39 1540 320 1100 240 30 125HBXV 8-185 219 266 40 95 40 95 39 1890 420 1450 240 30 150

HBXV 10-150 267 316 50 105 45 105 50 1540 320 1100 290 30 185HBXV 10-185 267 316 50 105 45 105 50 1890 420 1450 290 30 220

HBXV 12-185 298 353 50 120 50 115 60 1890 420 1450 320 30 275HBXV 12-225 298 353 50 120 50 115 60 2290 520 1850 320 30 325

HBXV 13-225 324 379 60 120 60 115 60 2290 520 1850 350 30 375HBXV 13-260 324 379 60 120 60 115 60 2640 620 2200 350 30 425

HBXV 6-100 9.4 4.7 32 22/27 22/27 NW 32 123 NW 25 103

HBXV 7-100 14.1 7.05 47 28/34 22/27 40 133 32 123HBXV 7-150 14.1 7.05 70 35/42 28/34 40 133 32 123

HBXV 8-125 23.5 11.75 97 42/48 28/34 50 143 40 133HBXV 8-150 23.5 11.75 118 42/48 35/42 50 143 40 133HBXV 8-185 23.5 11.75 146 54/60 35/42 50 143 40 133

HBXV 10-150 40.0 20.0 201 54/60 42/48 65 163 50 143HBXV 10-185 40.0 20.0 251 67/76 54/60 65 163 50 143

HBXV 12-185 49.4 24.75 313 67/76 54/60 80 193 65 163HBXV 12-225 49.4 24.75 380 80/89 54/60 80 193 65 163

HBXV 13-225 61.2 30.6 471 80/89 67/76 80 193 65 163HBXV 13-260 61.2 30.6 547 80/89 67/76 80 193 65 163

Helpman Shell & Tube Products BV Changes possible without prior notice 9

51-7109-2000

Page 10: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HC

Model indication

Example : HC 10 - 165 - KSG

HC : Condenser with plain tubediameter 19 mm

10 : Shell diameter code

165 : Effective length of the tubein cm (nominal length)

K : Tube material code

S : Tube plate material code

G : End cover material code

General information

The HC model water cooled condens-ers form an extensive standard seriesfor both inland and marine cooling in-stallations. There are 6 shell diame-ters in 10 standard lengths available.The condensers are suitable for allhalocarbon refrigerants for a capacityrange of 2 up to 165 kW at 10 K lmtd.

Due to the application of plain tubingthese condensers are less sensitiveto fouling. At identical capacity, therefrigerant volume of a plain tube con-denser is greater than that of a finnedtube condenser.This often makes it possible to usethe condenser as a liquid receiver.

Design

The condensers are built up of :

– seamless steel shell

– tube plates: steel orcupro-aluminium

– water tubes: plain tube ø19 mmmaterial: copper oraluminium-brass

– End covers: cast iron or plastifiedcast iron. Water connections on oneend cover. The other end cover hastwo connections G ¼" for purgingand drainage.

– Supports are available at extra cost.

– Completely coated version avail-able at extra cost.

For construction and testing autoritiessee page 3.

Material code indication

Water tubes :

K : copperA : aluminium-brass

Tube plates :

S : steelI : cupro-aluminium

End covers :

G : cast ironP : plastified cast iron

Choice of waterconnections

With the exception of the HC-6, thecondenser end covers are suitable fortwo water flows.

When less water is available the outerconnections are used for in-and outletpurposes and the central connectionmust be sealed off (single water flow).

For a higher water flow (or half thewater velocity) the outer connectionsare designed as water inlet and thecentral connection as water outlet(double water flow).

Small water volume

Large water volume

Sealed

Helpman Shell & Tube Products BV Changes possible without prior notice 10

51-7109-2000

Page 11: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HC

X

AB

Y

L . + 40 mmnom

d

o H

o Jo H

D

L nom.

L nom. + 40 A (B)

F

E

HC 6

FF

E

HC 7

F

E

G

HC 8

G

F

E

HC 10

E

HC 12

G

F

E

HC 13

Technical Data

Dimensions mm

Type A B D d E F G H J M N VBSP female BSP female kg kg/m dm3/m

HC 6 40 35 200 159 92 20 ½" 16 24 9.0HC 7 47 39 219 168 108 26 ½" ¾" 21 29 11.4HC 8 55 40 260 219 142 28 64 ¾" 1 ¼" 28 48 17.2

HC 10 56 42 308 267 162 54 84 1" 1 ¼" 42 65 24.6HC 12 63 44 345 298 220 1 ¼" 2" 54 82 30.5HC 13 65 47 372 324 220 38 113 1 ½" 2" 62 98 34.1

M Weight of endcovers (kg)

N Weight of shell (kg/m )

V Pump down capacity (dm3/m).Pump down capacities are based on 70 %of the tubes below the liquid level.

Dimensions X and Y, and the size of therefrigerant connections to be given with order.

Helpman Shell & Tube Products BV Changes possible without prior notice 11

51-7109-2000

Page 12: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HD

Model indication

Example : HD 5 - 22 - 055 - 2 CIB

HD Water cooled condenserwith low fin tubes ø12.7 mm

5 Shell diameter code

22 Number of tubes

055 Effective length in cm(nominal length)

2 Number of passes

C : Tube material code

I : Tube plate material code

B : End cover material code

General information

The HD-range of watercooled con-densers are suitable for all halocar-bon refrigerants.

The HD does have a capacity rangeform 10 up to 27 kW at 10 K lmtd.The waterside does have seawaterresistant materials, this makes thecondenser suitable for marine applica-tion and land installations with poor oraggressive water quality.

Design

Shell

seamless steel

Tube plates

copper-aluminium

Tubes

low-fin tubes ø 12.7 mm . Material:copper-nickel 90/10, tubes are rolledin the tubeplates.

Water covers

bronze with 1" BSP connections anda purge- and drain connection on thereturn cover (e" NPTF).

Refrigerant connections

inlet 22 mm O.D.S.liquid out e" O.D.S.

The condensers are supplied withmounting feet.

Construction

The materials and strength calculationfor the shell side do meet the regula-tions of : AD-Merkblätter

Condensers can be supplied inaccordance with the rules of :

– DNV

– Germanischer Lloyd

– Lloyd’s R.o.S.

– Bureau Veritas

– A.B.o.S.

The above rules may require adapta-tion of construction details, thereforedelivery and prices on request only.

Helpman Shell & Tube Products BV Changes possible without prior notice 12

51-7109-2000

Page 13: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HD

649

27 = = 42

2565

15 25

= 350 =

o10

o133

o1"

120

o 22

3232

o5/

8"

6020 20

Capacities (kW) 10 K lmtd*

Type Water velocity (m/s)

HD 0.8 1.0 1.2 1.4 1.6 1.8

5-22-055 duty kW 10.5 12.3 13.9 15.3 16.4 17.5

waterflow dm3/s 0.43 0.54 0.65 0.75 0.86 0.97

5-34-055 duty kW 16.1 18.9 21.4 23.5 25.2 26.9

waterflow dm3/s 0.67 0.83 1.00 1.17 1.33 1.50

pressure drop kPa 3.7 5.4 7.4 9.6 13.2 15.2

* Duties based on sea water with fouling factor f = 0.43 x 10-4m2K/W.

Helpman Shell & Tube Products BV Changes possible without prior notice 13

51-7109-2000

Page 14: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HE

Model indication

Example : HE 8 - 160 - 2 KSG

HE : Condenser with finnedtube, diameter ø15.9 mm

8 : Shell diameter code

160 : Effective length of the tubein cm (nominal length)

2 Number of passes

K : Tube material code

S : Tube plate material code

G : End cover material code

General information

The model HE water cooled con-denser is suitable for all halogenrefrigerants for a capacity range of40 up to 350 kW at 10 K lmtd.The series comprises 6 shell diame-ters combined with 2 standard lengths.The standard design is suitable forapplication in closed cooling systems.Application in open cooling systemsis allowed, when the correct waterquality is maintained.On request the condensers are avail-able in a sea water resistant execu-tion at an extra cost.

For construction and testing autoritiessee page 3.

Design

The condensers are built up of:

– shell: seamless steel

– tube plates : steelP265 GH acc. to EN 10028-2

– tubes:finned tube, ø15.9 mm,material: copper

– end covers:2 pass cast iron.Water connections are designedwith an internal BSP thread on con-nection cover.Purging and drainage connection¼" BSP int. on other cover.

– supports are available at an extracost.

Helpman Shell & Tube Products BV Changes possible without prior notice 14

51-7109-2000

Page 15: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HE

d Do

H

B L . + 30 mmnom

XA

Y

E

L nom.

L nom. + 30 A (B)

Technical data

Type Lnom Dimensions mm Refrigerant Weightcharge

cm A B d D E H dm3* kg

HE 5 16051 39 133 170 95 1 ½" BSP

5.4 50190 6.4 60

HE 6 16061 49 159 198 110 2" BSP

7.4 70190 8.8 85

HE 7 16066 54 194 235 120 2" BSP

11.2 100190 13.4 120

HE 8 16081 65 219 262 140 2 ½" BSP

14.0 135190 16.6 160

HE 9 16086 71 245 290 155 3" BSP

17.4 165190 20.6 195

HE 10 160102 96 273 325 155 4" BSP

24.3 200190 28.7 230

* Pump down capacity (dm3/m).Pump down capacities are based on 70 %of the tubes below the liquid level.

Dimensions X and Y, and the size of therefrigerant connections to be given with order.

Helpman Shell & Tube Products BV Changes possible without prior notice 15

51-7109-2000

Page 16: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBN

Model indication

Example : HBN 16 - 335 - 2 pass

HBN : Water cooled condenserwith plain steel tubes,ø 19 mm

16 : Shell diameter code

335 : Effective length of the tubein cm (nominal length)

2 : Number of passes

General information

The HBN model water cooled con-denser is suitable for ammonia aswell as halocarbon refrigerants.

There are 11 shell diameters avail-able in 3 standard lengths.

Capacity range of 23 up to 1563 kWat 10 K lmtd and refrigerant NH3

Design

The condensers are built up of :

– shell : seamless steel

– tube plates : P265 GH acc. toEN 10028-2

– tubes : seamless steel ø19 mmtubes rolled into tube plates

– end covers: cast iron

– water connections without counterflanges

For construction and testing autoritiessee page 3.

Operating Conditions

Refrigerant side : 23 barWater side : HBN 6-14 4 bar

HBN 16-22 2 bar

Optional extra’s

The condensers are available withvarious accessories, that can be indi-cated in your order with followingcodes.

V Connection stub ø26,9 for safetyvalve (reduced from ø42,2)

K Valves on return cover

F Steel counter flanges toDIN 2631

S Mounting feet

G Header as gas distributionheader on inlet side or as liquidcollection header on outlet side

A Drain connection with valveTAH-8 on shell

O Purge connection on shell ø21,3

Z Oilpot with drain valve TAH 8

P Coating on water side

Helpman Shell & Tube Products BV Changes possible without prior notice 16

51-7109-2000

Page 17: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBN

Technical data

Type Number Surface m2 Pump down Internal water Weight kgof capacity * capacity dm3

tubes Lnom (cm) Lnom (cm) Lnom (cm) Lnom (cm)

220 335 450 220 335 450 220 335 450 220 335 450

* Pump down capacity (dm3/m).Pump down capacities are based on 70 %of the tubes below the liquid level.

Max. Waterflow (m 3/h)

Number of passesType 2 pass. 4 pass.

HBN 6 10.4 5.2HBN 7 15.6 7.8HBN 8 26.1 13.0

HBN 10 44.3 22.1HBN 12 54.7 27.3HBN 13 67.8 33.9

HBN 14 93.8 46.9HBN 16 125.1 62.5HBN 18 151.1 75.6

HBN 20 192.8 96.4HBN 22 237.1 118.6

Nominal duty

Type Nominal duty (kW)uncoated coated

HBN 6 - 220 33.0 23.3HBN 7 - 220 49.5 35.0HBN 8 - 220 82.8 58.4

HBN 10 - 220 140.5 99.3HBN 12 - 335 266.0 187.7HBN 13 - 335 330.0 232.4

HBN 14 - 335 456.5 321.8HBN 16 - 450 824.0 579.9HBN 18 - 450 996.0 700.6

HBN 20 - 450 1271.0 893.9HBN 22 - 450 1563.0 1099.0

The nominal duty is based onfollowing conditions :

refrigerant NH3

Maximum waterflow

fouling factor :uncoated 1.72 x 10-4m2K/Wcoated 0.86 x 10-4m2K/W

lmtd : 10 K

HBN- 6 16 2.1 3.2 4.3 11 16 22 8 12 16 85 120 150HBN- 7 24 3.2 4.8 6.4 16 25 34 12 18 24 110 160 210HBN- 8 40 5.3 8.0 10.7 28 42 56 20 30 40 170 240 310

HBN-10 68 8.9 13.6 18.3 46 70 95 35 50 65 250 350 460HBN-12 84 11.0 16.8 22.6 57 87 117 40 60 80 310 440 570HBN-13 104 13.7 20.8 27.9 70 107 144 50 75 100 360 520 670

HBN-14 144 18.9 28.8 38.7 97 147 198 70 110 140 480 680 900HBN-16 192 25.2 38.4 51.6 130 198 266 95 140 180 650 950 1200HBN-18 232 30.5 46.4 62.3 156 237 320 110 170 220 800 1100 1450

HBN-20 296 38.9 59.2 79.5 200 305 410 140 210 280 1000 1400 1800HBN-22 364 47.8 72.8 97.8 246 375 505 170 260 340 1200 1750 2250

Helpman Shell & Tube Products BV Changes possible without prior notice 17

51-7109-2000

Page 18: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HBN

0.6 Lnom.

4530

= =

K

M

dD

Y O

X

A L + 40 mmnom. B

O

F

E

H

30 30G

2-Pass

J

4-Pass

C

E

F

Dimensions

Type Dimensions mm

2 passes 4 passes Oil pot Supports

d D A B E F A B C E F K M H H* G P

* With oilpot

Dimensions X and Y, and the size of therefrigerant connections to be given with order.

HBN- 6 159 204 30 85 123 32 30 75 32 103 25 115 114 160 205 140 14HBN- 7 168 223 35 90 133 40 35 90 32 123 32 120 114 170 220 140 14HBN- 8 219 266 40 100 143 50 40 100 40 133 40 125 114 190 245 140 14

HBN-10 267 316 50 105 163 65 50 105 50 143 50 125 133 215 270 240 18HBN-12 298 353 50 120 193 80 50 115 60 163 65 125 168 230 285 240 18HBN-13 324 379 60 120 193 80 60 115 60 163 65 125 168 245 300 240 18

HBN-14 368 423 65 135 213 100 65 135 70 193 80 130 168 265 325 240 18HBN-16 419 481 75 140 243 125 75 140 75 193 80 120 219 290 340 340 23HBN-18 457 521 80 145 243 125 80 145 85 213 100 125 219 310 365 340 23

HBN-20 508 578 90 160 268 150 90 160 98 213 100 125 219 335 390 340 23HBN-22 559 631 180 255 268 150 100 170 110 243 125 130 219 360 420 390 23

Helpman Shell & Tube Products BV Changes possible without prior notice 18

51-7109-2000

Page 19: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HN

Model indication

Example : HN 36 - 500 - 4 pass

HN : Condenser with plainsteel tubes 25 mm

36 : Code for shell diameter

500 : Effective length in cm(nominal length)

4 : Number of water passes

General information

The water cooled condensers typeHN are suitable for all halocarbonrefrigerants and ammonia.The range includes 24 models with6 diameters and 4 standard lengths.Each model available with 2, 4, 6 or8 pass water covers. Cooling surfacefrom 57 up to 379 m2.Duties for ammonia from 636 up to6051 kW at 10 K lmtd.

Design

Shell ø

≤ 508 : seamless steel tube: St 37.0according to DIN 1629

> 508 : welded shell, materialP265 GH acc. to EN 10028-2

Tubes

Seamless steel, ø 25 x 2 mmaccording to DIN 17.175

Tube plates

P265 GH acc. to EN 10028-2

End covers

Steel,P265 GH acc. to EN 10028-2ST 37-2 according to DIN 17.100flanges according to DIN 2633

Special design

On request available:

– mounting feet and additionalaccessories

– materials for special applicationslike low temperatures and corrosiveliquids

– coating on waterside

For construction and testing autoritiessee page 3.

Nominal duty

Type Nominal duty (kW)uncoated coated

HN 20 - 400 942 636HN 24 - 500 1605 1132HN 28 - 500 2305 1624

HN 32 - 550 3449 2320HN 36 - 600 4837 3253HN 40 - 600 6051 4069

The nominal duty is based onfollowing conditions :

refrigerant NH3

Maximum waterflow

fouling factor :uncoated 1.72 x 10-4m2K/Wcoated 0.86 x 10-4m2K/W

lmtd : 10 K

Maximum Waterflow (m 3/h)

Type 2 pass. 4 pass. 6 pass. 8 pass.

HN 20 227 113 76 57HN 24 322 161 107 80HN 28 461 231 154 115

HN 32 626 313 209 156HN 36 800 400 266 200HN 40 1004 502 335 251

Helpman Shell & Tube Products BV Changes possible without prior notice 19

51-7109-2000

Page 20: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HN

A

X

Y

L + 65 mmnom. B

d

F

D E

Technical data

Type HN 20 24 28 32 36 40

Number of tubes 182 258 370 502 641 805

Lnomcm

Cooling surface m2 400 57 81 116 158 202 253500 71 101 145 197 253 316550 79 111 160 217 278 348600 86 122 174 237 303 379

(Empty) weight kg 400 1540 2160 2750 3750 4730 5750500 1850 2600 3300 4520 5680 6910550 2000 2830 3580 4910 6160 7490600 2150 3050 3860 5290 6640 8070

Maximum*liquid capacity dm3 400 260 370 540 700 830 1060

500 330 460 670 880 1040 1330550 360 500 740 970 1140 1460600 400 550 800 1060 1240 1600

Capacity waterside dm3 400 300 430 630 850 1150 1350500 360 520 750 1020 1350 1650550 400 560 820 1110 1450 1800600 430 610 880 1200 1550 1950

* Pump down capacity (dm3/m).Pump down capacities are basedon 70 % of the tubes below theliquid level.

Dimensions in mm

Type Number of passes2 4 6 8

HN A B d D E F E F E F E F

20 130 380 508 618 310 150 344 125 344 125 370 10024 130 380 610 720 360 200 394 150 414 125 472 10028 150 400 720 830 416 250 472 200 524 150 560 125

32 150 400 820 930 468 300 554 200 608 150 636 12536 180 420 920 1030 528 350 630 200 688 200 712 15040 185 420 1020 1130 620 350 708 250 756 200 792 150

Dimensions X and Y, and the size ofthe refrigerant connections to begiven with order.

Helpman Shell & Tube Products BV Changes possible without prior notice 20

51-7109-2000

Page 21: Models HBX, HBXV, HC, HD, HE, HBN and HN - schlosser … · Water Cooled Condensers HBX Dimensions (mm) Cast iron end covers (G/P) Type 2 passes 4 passes tubes kg kg/m dm3/m dD A

Water Cooled Condensers HN

Optional extra’s

The condensers are available withvarious accessories, that can be indi-cated in your order with followingcodes.

V Connection stub ø26,9 for safetyvalve (reduced from ø42,2)

K Valves on return cover

F Steel counter flanges toDIN 2633

S Mounting feet

G Header as gas distributionheader on inlet side or as liquidcollection header on outlet side

A Drain connection with valveTAH-8 on shell

O Purge connection on shell ø21,3

Z Oilpot with drain valve TAH 8

P Coating on water side

Above mentioned optional extra'savailable at extra price.

Dimensions of supports

HN 20 24 28 32 36 40

W 450 550 650 750 850 950H 554 605 660 710 760 810

H

50 50W

o 23

0.6 L nom.

7575

= =

K S

O

150

30 AF

G

150 V

Z

o 32427

5

Helpman Shell & Tube Products BV Changes possible without prior notice 21

51-7109-2000