33
Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM ---9000CFM Midea ® reserves the right to improve the product and technology without prior notice.

Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

  • Upload
    hadien

  • View
    228

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

Midea Air Handling Unit

Floor mounted

3000CFM ---25000CFM

Vertical mounted

3000CFM ---25000CFM

Ceiling suspended

1000CFM ---9000CFM

Midea® reserves the right to improve the product and technology without prior notice.

Page 2: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

2

General

With years of design and manufacturing experience, Midea carried out the new 2nd generation

Air Handling Unit (MKSII Series) with a series of improvements and innovations to meet market

demand. As comfort air-conditioning, it can be widely used in hotels, theaters, shopping malls,

office buildings, schools and other places; as for industrial use air conditioning, it can also meet

the electronics, chemical, medical, pharmaceutical, cigarettes, food, light industry and other

industries needs.

The standard MKSII Series AHU can be divided into 3 types which are suspended, horizontal

and vertical types. The air volume is from 2000 m3/h to 40,000 m3/h (1170 to 23,500CFM).

Page 3: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

3

Features Cold-bridge Free(Thermal break) Design

Both the framework and panels are designed to be isolated. And the cavity of the framework and panels

are filled with high-density polyurethane foam (density ≥ 50kg/m3) to cut off cold bridge completely,

which can effectively prevent cooling capacity loss and external condensate.

Multiple-seal to Prevent Air Leakage

Units using multiple “ladder-style” structure, both inside and outside ladder are with closed measures.

Coupled with the negative pressure design, can ensure that the units of air leakage rate is a low air leakage

rate ≤ 0.29%, only the provisions of the national standard 1 / 10, more no danger of water leakage.

Lower Noise Running

Famous-brand fan is in use. The professional selection software makes sure the optimum working point

and outlet velocity to guarantee the smooth & low noise air flow in the duct.

Page 4: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

4

More compact size, Space saving

The dimensions of the units are optimized and the performance is maintained. The units with more

compact size save the installation space rapidly.

Optimized water pass, Higher heat transferring efficiency

The coil uses windowed high-quality aluminum fin staggered arrangement, coupled with a wide range of

flow path design optimization, which is taking into account the higher heat transferring efficiency and

lower liquid side resistance.

Better appearance, Anti-corrosion and anti-damage

Fillet corner, beautiful color steel with protection film that can against rust, corrosion and damage while

transportation.

Page 5: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

5

Assembled structure, Easier maintenance

Assembled structure is easy for assembly and maintenance at site , also it’s suitable for CKD

transportation.

Page 6: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

6

How to Read the Model No.?

MKSII 080 D A — Z

Connection Direction: Z—Left,Y—Right

Rows: A — 4 Rows, B — 6 Rows

C — Other, 8 Rows etc.

Type: D — Ceiling Suspended

W — Horizontal

L — Vertical

Nominal Air Volume: ( 80×100 m3/h)

Midea 2nd generation AHU

Pipe Connection Direction

Face the air inlet (along the air flow direction),

If the connection pipes and maintenance access is left side, then the unit is left-connection unit,

Otherwise is the right-connection unit.

Air inlet

Air outlet

It is left-connection unit

Page 7: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

7

SPECIFICATIONS

Ceiling Suspended (Recycling Air)

Model No. Nominal Air Volume

Cooling Capacit

y

Heating Capacity

Chilled Water STD ESP

STD Motor Power

Noise N.W. ESP

RangeDimensions L×W×H Flow

rate Resista

nce MKSII-D m3/h kW kW L/s kPa Pa kW dB(A) kg Pa mm

020 4R

2000 12.1 14.9 0.58 10.4

120 0.37 56.2 98 80

~ 200

900*850*525 6R 14.2 18.5 0.68 12.5 57.1 110

030 4R

3000 17.1 20.5 0.82 15.2

130 0.37 57.4 122 80

~ 200

1010*970*5556R 20.1 26.5 0.96 20.4 57.5 140

040 4R

4000 23.1 27.7 1.10 12.6

130 0.55 58.2 162 80

~ 300

1010*1300*5556R 28.4 35.2 1.36 18.5 60.1 173

050 4R

5000 30.5 36.8 1.46 14.4

130 1.1 59.5 196 80

~ 300

1010*1360*6056R 37.1 43.9 1.77 15.2 61.5 218

060 4R

6000 34.8 43.6 1.66 21.1

170 1.1 60.2 215 100

~ 350

1010*1550*6056R 42.8 52.5 2.05 25.8 61.5 242

070 4R

7000 42.9 51.5 2.05 25.0

180 1.5 62.1 232 100

~ 350

1010*1600*6806R 50.5 60.6 2.42 27.4 63.5 260

080 4R

8000 49.2 60.1 2.35 28.3

180 1.5 63.4 251 100

~ 350

1050*1800*6806R 60.2 72.2 2.88 30.4 63.5 275

100 4R

10000 58.5 70.2 2.80 27.5

190 2.2 63.5 310 100

~ 400

1100*1900*7856R 71.5 84.6 3.42 32.5 65.2 340

120 4R

12000 70.7 84.8 3.38 34.5

210 2.2 65.5 335 100

~ 450

1100*1950*8856R 89.5 108.6 4.28 38.6 67.1 370

150 4R

15000 89.2 111.0 4.27 21.4

260 3.0 66.4 402 150

~ 500

1250*2350*9106R 112.5 138.9 5.38 23.5 68.2 445

Note:

Stand Conditions Entering Air DB(℃) Entering Air WB(℃) Entering Water T(℃) Water ΔT(℃)

Recycling Air Cooling 27 19.5 7 5

Recycling Air Heating 21 — 60 —

◎ Noise data is the average noise pressure of which is got at 1 meter from each surface of the unit, while the unit is running with the

duct connected and without water going though the coil;

◎ If you need a nonstandard ESP, please make a special comment on the order. We recommend you could choose the ESP within the

ESP range showed for the best effect.

◎ If the entering air conditions, entering water conditions or the ESP are different from the standard, the specifications will change.

Page 8: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

8

SPECIFICATIONS Ceiling Suspended (Fresh Air)

Model No. MKSII-D

Nominal Air

Volume

Cooling Capacity

Heating Capacity

Water STD ESP

STD motor Power

Noise N.W. ESP

RangeDimensions L×W×H Flow rate Resistance

m3/h kW kW L/s kPa Pa kW dB(A) kg Pa mm

020 4R

2000 29.0 34.8 1.39 20.5

120 0.37 56.2 98 80~

200 900×850×5256R 36.0 43.2 1.72 30.4 57.1 110

030 4R

3000 42.3 50.7 2.02 30.6

130 0.37 57.4 122 80~

200 1010×970×5556R 51.4 61.7 2.46 45.4 57.5 140

040 4R

4000 50.3 60.4 2.41 25.3

130 0.55 58.2 162 80~

300 1010×1300×

555 6R 67.6 81.2 3.23 40.2 60.1 173

050 4R

5000 65.7 78.8 3.14 35.1

130 1.1 59.5 196 80~

300 1010×1360×

605 6R 84.2 101.0 4.03 35.5 61.5 218

060 4R

6000 77.8 93.5 3.72 25.4

170 1.1 60.2 215 100~

350 1010×1550×

605 6R 99.8 119.8 4.77 38.6 61.5 242

070 4R

7000 91.9 110.3 4.40 32.5

180 1.5 62.1 232 100~

350 1010×1600×

680 6R 115.6 138.7 5.53 40.5 63.5 260

080 4R

8000 107.1 128.5 5.12 42.4

180 1.5 63.4 251 100~

350 1050×1800×

680 6R 134.4 161.2 6.43 46.4 63.5 275

100 4R

10000 122.8 147.4 5.87 45.3

190 2.2 63.5 310 100~

400 1100×1900×

785 6R 144.5 173.4 6.91 45.4 65.2 340

120 4R

12000 144.9 173.9 6.93 55.4

210 2.2 65.5 335 100~

450 1100×1950×

885 6R 183.7 220.5 8.79 55.4 67.1 370

150 4R

15000 185.0 222.0 8.85 50.4

260 3.0 66.4 402 150~

500 1250×2350×

910 6R 233.3 279.9 11.16 60.6 68.2 445

Note:

Stand Conditions Entering Air DB(℃) Entering Air WB(℃) Entering Water T(℃) Water ΔT(℃)

Fresh Air Cooling 35 28 7 5

Fresh Air Heating 7 — 60 —

◎ Noise data is the average noise pressure of which is got at 1 meter from each surface of the unit, while the unit is running with the

duct connected and without water going though the coil;

◎ If you need a nonstandard ESP, please make a special comment on the order. We recommend you could choose the ESP within the

ESP range showed for the best effect.

◎ If the entering air conditions, entering water conditions or the ESP are different from the standard, the specifications will change.

Page 9: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

Dimensions: Ceiling Suspended

Model MKSII

Outline Installation C D

Air Inlet G J K

Air Outlet P Q R

Pipe X L W H A B 4R 6R E F M N 4R 6R

020D 900 850 525 826 946 66 110 25 416 766 152 292 / 267 236 164 86 103 DN40 DN40 030D 1010 970 555 936 1066 66 110 25 446 886 127 343 / 306 270 164 86 103 DN40 DN40 040D 1010 1300 555 936 1396 66 110 25 446 1216 152 343 176 240 270 164 86 103 DN40 DN40 050D 1010 1360 605 936 1456 66 110 25 496 1276 152 394 176 240 270 164 86 103 DN40 DN40 060D 1010 1550 605 936 1646 66 110 25 496 1466 127 394 236 306 270 164 86 103 DN50 DN50 070D 1010 1600 680 969 1696 66 110 50 546 1516 177 444 206 273 297 189 111 103 DN50 DN50 080D 1050 1800 680 1009 1896 66 110 50 546 1716 177 444 256 339 297 189 111 103 DN50 DN50 100D 1100 1900 785 1059 1996 66 110 50 651 1816 205 546 316 403 349 189 111 103 DN50 DN65 120D 1100 1950 885 1059 2046 66 110 50 651 1866 205 648 316 403 349 189 111 103 DN50 DN65 150D 1250 2350 910 1209 2446 104 173 50 776 2266 205 620 286 385 412 189 111 112 DN65 DN65

Page 10: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

Horizontal (Recycling Air)

Model No. MKSII-W

Nominal Air

Volume

Cooling Capacity

Heating Capacity

Water STD ESP

STD motor Power

Noise N.W. ESP

RangeDimensions L×W×H Flow rate Resistance

m3/h kW kW L/s kPa Pa kW dB(A) kg Pa mm

050 4R

5000 30.5 36.8 1.46 10.5

150 0.75 59.5 205 80~

300 1120×1060×

780 6R 37.1 43.9 1.77 14.6 61.2 221

060 4R

6000 34.8 43.6 1.66 9.4

180 1.1 60.3 220 100~

350 1120×1230×

780 6R 42.8 52.5 2.05 12.6 61.4 249

080 4R

8000 49.2 60.1 2.35 18.2

180 1.5 63.1 260 100~

350 1150×1370×

880 6R 60.2 72.2 2.88 20.5 63.5 283

100 4R

10000 58.5 70.2 2.80 24.4

250 2.2 63.5 318 150~

350 1200×1650×

890 6R 71.5 84.6 3.42 28.2 65.2 346

150 4R

15000 89.2 111.0 4.27 25.4

260 3.0 66.1 405 150~

500 1200×1940×

1155 6R 112.5 138.9 5.38 30.6 68.2 4G50

200 4R

20000 122.5 150.8 5.86 16.5

310 5.5 70.4 552 150~

600 1350×2350×

1155 6R 145.2 160.7 6.95 21.5 71.6 590

250 4R

25000 141.5 183.0 6.77 35.1

410 7.5 70.2 610 200~

600 1350×2350×

1395 6R 181.8 218.2 8.70 36.6 71.5 645

300 4R

30000 198.5 243.0 9.49 34.2

410 11 73.3 690 250~

650 1450×2730×

1475 6R 222.0 266.4 10.62 37.1 73.5 730

350 4R

35000 216.2 268.2 10.34 29.3

500 2×5.573.8 781 250~

650 1830×2710×

1635 6R 245.8 294.9 11.76 31.4 74.2 838

400 4R

40000 241.5 299.2 11.55 32.2

550 2×7.576.2 1010 300~

650 1830×3050×

1635 6R 264.4 317.2 12.65 39.4 77.5 1095

Note:

Stand Conditions Entering Air DB(℃) Entering Air WB(℃) Entering Water T(℃) Water ΔT(℃)

Fresh Air Cooling 27 19.5 7 5

Fresh Air Heating 21 — 60 —

◎ Noise data is the average noise pressure of which is got at 1 meter from each surface of the unit, while the unit is running with

the duct connected and without water going though the coil;

◎ If you need a nonstandard ESP, please make a special comment on the order. We recommend you could choose the ESP within

the ESP range showed for the best effect.

◎ If the entering air conditions, entering water conditions or the ESP are different from the standard, the specifications will

change.

Page 11: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

11

Horizontal (Fresh Air)

Model No. MKSII-W

Nominal Air

Volume

Cooling Capacity

Heating Capacity

Water STD ESP

STD motor Power

Noise N.W. ESP

RangeDimensions L×W×H Flow rate Resistance

m3/h kW kW L/s kPa Pa kW dB(A) kg Pa mm

050 4R

5000 65.7 78.8 3.14 30.4

150 0.75 59.5 205 80~

300 1120×1060×

780 6R 84.2 101.0 4.03 34.4 61.1 221

060 4R

6000 77.8 93.5 3.72 21.2

180 1.1 60.2 220 100~

350 1120×1230×

780 6R 99.8 119.8 4.77 22.6 61.4 249

080 4R

8000 107.1 128.5 5.12 28.7

180 1.5 63.0 260 100~

350 1150×1370×

880 6R 134.4 161.2 6.43 30.1 63.5 283

100 4R

10000 122.8 147.4 5.87 25.2

250 2.2 63.2 318 150~

350 1200×1650×

890 6R 144.5 173.4 6.91 35.3 65.4 346

150 4R

15000 185.0 222.0 8.85 62.4

260 3.0 66.3 405 150~

500 1200×1940×

1155 6R 233.3 279.9 11.16 65.3 68.1 450

200 4R

20000 269.0 322.8 12.87 40.5

310 5.5 70.5 552 150~

600 1350×2350×

1155 6R 299.9 359.9 14.35 45.2 71.6 590

250 4R

25000 329.4 395.24 15.76 75.1

410 7.5 70.5 610 200~

600

1350×2350×1395 6R 403.6 484.3 19.31 82.3 71.5 645

300 4R

30000 433.4 520.0 20.73 70.4

410 11 73.2 690 250~

650 1450×2730×

1475 6R 492.8 591.4 23.57 72.2 73.5 730

350 4R

35000 478.3 573.9 22.88 65.2

500 2×5.573.4 781 250~

650 1830×2710×

1635 6R 540.8 640.9 25.87 70.6 74.3 838

400 4R

40000 533.7 640.5 25.53 60.4

550 2×7.576.4 1010 300~

650 1830×3050×

1635 6R 581.7 698.0 27.82 71.2 77.5 1095

Note:

Stand Conditions Entering Air DB(℃) Entering Air WB(℃) Entering Water T(℃) Water ΔT(℃)

Fresh Air Cooling 35 28 7 5

Fresh Air Heating 7 — 60 —

◎ Noise data is the average noise pressure of which is got at 1 meter from each surface of the unit, while the unit is running with

the duct connected and without water going though the coil;

◎ If you need a nonstandard ESP, please make a special comment on the order. We recommend you could choose the ESP within

the ESP range showed for the best effect.

◎ If the entering air conditions, entering water conditions or the ESP are different from the standard, the specifications will

change.

Page 12: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

12

Dimensions: Horizontal

Model MKSII

Outline C D

Air Inlet G J K

Air OutletP Q R

Pipe X L W H 4R 6R E F M N 4R 6R

050W 1120 1060 780 66 110 40 656 976 104 475 / 317 349 179 101 103 DN40 DN50

060W 1120 1230 780 66 110 40 656 1146 104 475 / 403 349 179 101 103 DN50 DN50

080W 1150 1370 880 66 110 40 756 1286 116 576 / 479 412 179 101 103 DN50 DN50

100W 1200 1650 890 66 110 50 756 1566 116 576 / 479 412 189 111 103 DN50 DN50

150W 1200 1940 1155 104 173 50 1021 1856 381 840 286 381 412 189 111 112 DN65 DN65

200W 1350 2350 1155 104 173 50 1021 2266 215 840 335 438 486 189 111 112 DN65 DN65

250W 1350 2350 1395 104 173 50 1261 2266 445 1080 335 438 486 189 111 112 DN65 DN65

300W 1450 2730 1475 104 173 50 1341 2646 525 1160 450 565 486 189 111 112 DN80 DN80

350W 1830 2710 1635 104 173 50 1501 2626 685 1320 788 565 486 189 111 112 DN80 DN80

400W 1830 3050 1635 104 173 50 1501 2966 685 1320 828 565 486 189 111 112 DN80 DN80

Page 13: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

Vertical (Recycling Air)

Model No. MKSII-L

Nominal Air

Volume

Cooling Capacity

Heating Capacity

Water STD ESP

STD motor Power

Noise N.W. ESP

RangeDimensions L×W×H Flow rate Resistance

m3/h kW kW L/s kPa Pa kW dB(A) kg Pa mm

030 4R

3000 17.1 20.5 0.82 15.2

130 0.55 57.1 135 80~

200 650×1000×

1150 6R 20.1 26.5 0.96 20.1 57.5 160

040 4R

4000 23.1 27.7 1.10 12.4

150 0.75 58.2 195 80~

300 670×1250×

1200 6R 28.4 35.2 1.36 18.5 60.3 206

050 4R

5000 30.5 36.8 1.46 14.4

150 1.1 59.5 225 80~

300 750×1150×

1440 6R 37.1 43.9 1.77 15.7 61.2 242

060 4R

6000 34.8 43.6 1.66 10.1

190 1.1 60.4 249 80~

350 750×1250×

1440 6R 42.8 52.5 2.05 17.8 61.1 272

080 4R

8000 49.2 60.1 2.35 23.4

190 1.5 63.2 272 100~

350 840×1300×

1740 6R 60.2 72.2 2.88 26.4 63.6 295

100 4R

10000 58.5 70.2 2.80 30.2

250 2.2 63.5 338 150~

350 840×1525×

1740 6R 71.5 84.6 3.42 34.6 65.4 361

150 4R

15000 89.2 111.0 4.27 25.1

270 4.0 66.3 450 150~

500 860×1930×

1880 6R 112.5 138.9 5.38 30.4 68.4 485

200 4R

20000 122.5 150.8 5.86 16.5

320 5.5 70.5 580 150~

600 1000×2350×

2040 6R 145.2 160.7 6.95 21.7 71.2 625

250 4R

25000 141.5 183.0 6.77 35.7

410 7.5 70.7 645 200~

600 1000×2500×

2200 6R 181.8 218.2 8.70 36.9 71.3 693

300 4R

30000 198.5 243.0 9.49 34.2

410 11 73.1 725 250~

650 1000×2780×

2300 6R 222.0 266.4 10.62 37.9 73.5 816

350 4R

35000 216.2 268.2 10.34 29.1

500 2*5.573.6 810

250~650

1000×3200×2300 6R 245.8 294.9 11.76 31.1 74.2 921

400 4R

40000 241.5 299.2 11.55 36.4

550 2*7.576.2 1050

300~650

1000×3310×2300 6R 264.4 317.2 12.65 46.2 77.5 1180

Note:

Stand Conditions Entering Air DB(℃) Entering Air WB(℃) Entering Water T(℃) Water ΔT(℃)

Fresh Air Cooling 27 19.5 7 5 Fresh Air Heating 21 — 60 —

◎ Noise data is the average noise pressure of which is got at 1 meter from each surface of the unit, while the unit is running with

the duct connected and without water going though the coil;

◎ If you need a nonstandard ESP, please make a special comment on the order. We recommend you could choose the ESP within

the ESP range showed for the best effect.

◎ If the entering air conditions, entering water conditions or the ESP are different from the standard, the specifications will

change.

Page 14: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

14

Vertical (Fresh Air)

Model No. MKSII-L

Nominal Air

Volume

Cooling Capacity

Heating Capacity

Water STD ESP

STD motor Power

Noise N.W. ESP

RangeDimensions L×W×H Flow rate Resistance

m3/h kW kW L/s kPa Pa kW dB(A) kg Pa mm

030 4R

3000 42.3 50.7 2.02 30.2

130 0.55 57.1 135 80~

200 650×1000×

1150 6R 51.4 61.7 2.46 45.3 57.5 160

040 4R

4000 50.3 60.4 2.41 25.7

150 0.75 58.4 195 80~

300 670×1250×

1200 6R 67.6 81.2 3.23 40.8 60.3 206

050 4R

5000 65.7 78.8 3.14 30.2

150 1.1 59.6 225 80~

300 750×1150×

1440 6R 84.2 101.0 4.03 34.7 61.4 242

060 4R

6000 77.8 93.5 3.72 21.2

190 1.1 60.1 249 80~

350 750×1250×

1440 6R 99.8 119.8 4.77 22.8 61.4 272

080 4R

8000 107.1 128.5 5.12 28.7

190 1.5 63.4 272 100~

350 840×1300×

1740 6R 134.4 161.2 6.43 30.9 63.7 295

100 4R

10000 122.8 147.4 5.87 25.8

250 2.2 63.6 338 150~

350 840×1525×

1740 6R 144.5 173.4 6.91 35.7 65.3 361

150 4R

15000 185.0 222.0 8.85 62.4

270 4.0 66.4 450 150~

500 860×1930×

1880 6R 233.3 279.9 11.16 65.1 68.2 485

200 4R

20000 269.0 322.8 12.87 40.5

320 5.5 70.4 580 150~

600 1000×2350×

2040 6R 299.9 359.9 14.35 45.9 71.7 625

250 4R

25000 329.4 395.2 15.76 75.2

410 7.5 70.4 645 200~

600 1000×2500×

2200 6R 403.6 484.3 19.31 82.6 71.8 693

300 4R

30000 433.4 520.0 20.73 70.4

410 11 73.1 725 250~

650 1000×2780×

2300 6R 492.8 591.4 23.57 72.2 73.5 816

350 4R

35000 478.3 573.9 22.88 65.8

500 2*5.573.6 810

250~650

1000×3200×2300 6R 540.8 640.9 25.87 70.1 74.4 921

400 4R

40000 533.7 640.5 25.53 60.7

550 2*7.576.2 1050

300~650

1000×3310×2300 6R 581.7 698.0 27.82 71.9 77.5 1180

Note:

Stand Conditions Entering Air DB(℃) Entering Air WB(℃) Entering Water T(℃) Water ΔT(℃)

Fresh Air Cooling 35 28 7 5 Fresh Air Heating 7 — 60 —

◎ Noise data is the average noise pressure of which is got at 1 meter from each surface of the unit, while the unit is running with

the duct connected and without water going though the coil;

◎ If you need a nonstandard ESP, please make a special comment on the order. We recommend you could choose the ESP within

the ESP range showed for the best effect.

◎ If the entering air conditions, entering water conditions or the ESP are different from the standard, the specifications will

change.

Page 15: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

Dimensions: Vertical Type

Model MKSII

Outline G

Air Outlet Air Inlet Pipe X

L W H A B E C D 4R 6R

030L 650 1000 1150 60 270 306 / 480 916 DN40 DN40

040L 670 1250 1200 60 297 339 / 480 1166 DN40 DN40

050L 750 1150 1440 60 349 403 / 683 1066 DN40 DN50

060L 750 1280 1440 60 349 403 / 683 1196 DN50 DN50

080L 860 1300 1740 60 412 479 / 886 1216 DN50 DN50

100L 860 1525 1740 60 412 479 / 886 1441 DN50 DN50

150L 860 1980 1880 63 412 381 286 1046 1896 DN65 DN65

200L 1000 2350 2040 63 486 438 335 1046 2266 DN65 DN65

250L 1000 2500 2200 63 486 438 335 1206 2416 DN65 DN65

300L 1000 2780 2300 80 486 565 450 1286 2696 DN80 DN80

350L 1000 3200 2300 80 486 565 592 1286 3116 DN80 DN80

400L 1000 3310 2300 80 486 565 592 1286 3226 DN80 DN80

Page 16: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

Capacity Correction at Non-standard Conditions

Calculation Formula:

Q = F1×F2×F3×Q0

Legend: Q0 --- Cooling capacity at standard conditions, refer to the specifications

F1--- Temperature correction factor of cooling coil

F2--- Water ΔT correction factor, refer to Fig.1

F3--- Water flow velocity correction factor, refer to Fig.2. According to the average flow

velocity of Midea coils, we take F3≈1.02

Temperature Correction Factor of Cooling Coil F1

EWT

EWB

Entering Water Temperature ℃

4 5 6 7 8 9 10

,En

teri

ng Air Wet Bulb ℃

17 0.978 0.890 0.801 0.711 0.626 0.523 0.423

18 1.093 1.001 0.915 0.823 0.731 0.635 0.538

19 1.213 1.124 1.032 0.940 0.846 0.750 0.652

19.5 1.274 1.184 1.093 1.000 0.906 0.809 0.711

20 1.337 1.246 1.155 1.061 0.967 0.869 0.770

21 1.464 1.373 1.281 1.186 1.090 0.993 0.893

22 1.597 1.504 1.411 1.316 1.219 1.121 1.020

23 1.733 1.641 1.547 1.450 1.352 1.252 1.151

24 1.874 1.781 1.685 1.589 1.490 1.389 1.287

26 2.172 2.076 1.978 1.879 1.779 1.676 1.571

28 2.489 2.391 2.291 2.189 2.086 1.981 1.874

30 2.824 2.725 2.623 2.519 2.414 2.306 2.196

Page 17: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

17

Fig 1. Water ΔT Correction Factor F2 Fig 2. Water Flow Velocity Correction Factor F3

WDT, ℃ WFV, m/s

Note: F1, F2 and F3 are only approximate value for your reference.

3.0 4.0 5.0 6.0 7.00.90

0.95

1.00

1.05

1.10

8.00.90

1.00.4

0.95

1.00

1.05

1.10

1.5 1.9

1.067

F2 F3

Page 18: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

18

Optional

Air Volume The specifications show the standard units with standard air volume. Also the units with different air

volume from 1000 m3/h to 40000 m3/h can be customized as required, such as 1500 m3/h, 13500 m3/h,

27000 m3/h and etc.

Exhaust Direction Suspended Unit

Standard:Lower horizontal, Code FB (Recommended) Optional: Upper horizontal, Code FT

Suspended Unit

Standard:Lower horizontal, Code FT (Recommended) Optional: Upper horizontal, Code FB

Vertical Unit

Standard:Front Up, Code UF (Recommended) Optional: Back Up, Code UR

Page 19: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

19

Optional

Coil Rows

Standard Coil: 4 Rows (A) and 6 Rows (B). 2 Rows (T) and 8 Rows (C) can be customized as required.

The standard working pressure of all the coils is 1.6MPa.

Filter

The standard filter is panel type aluminum washable pre-filter which efficiency is G3. They are installed

in the track on the air inlet frame and can be drawn out from both sides for check and maintenance. Also

the other prefilter and the middle-efficiency filters are optional, which efficiency is G2, G4, F5 and F6.

Humidifier

Line-style wet film humidifier is optional. The thickness of the film is 50-200mm.

Electrical Heater

Beside the coil, the unit can be equipped with a certain power electrical heater for heating.

Page 20: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

20

Optional Water Drop Eliminator

Wet deck drop eliminator is optional as required to stop the water drops.

Power Source

The standard power source is “3¢-415V-50Hz”. The others are optional.

Control

If detailed control requirement is given, we can provide some control cabinet such as step-down starter

and inverter.

Other Accessories

UV germicidal lamp, 24V maintenance lamp, view window, water proof seal and etc.

Note:

The optional items may change the specifications, dimensions, cost and prices, delivery time of the standard units.

Page 21: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

21

3D Exploded View

1—Base; 2—Bottom Panel; 3—Pipe Seal; 4—Panel with Hole; 5—Wiring Box; 6—Quadrangle Aluminum Frame; 7—Handle; 8—Access Panel; 9—Pentagon Aluminum Frame; 10—3-way Connector; 11—Air Outlet Panel; 12—Air Outlet Flange; 13—Fan Supporter; 14—Fan Assembly; 15—Top Panel; 16—Coils; 17—Drain Pan; 18—Up Air Baffler; 19—Side Panel; 20—Prefilter; 21—Right Air Baffler; 22—Air Inlet Flange; 23—Left Air Baffler; 24—Supporter of Drain Pan

Note:

The upper picture is only for reference while assembling.

Page 22: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

22

Modular Air Handling Units

(Air Volume Range 5,000 m3/h to 100,000m3/h) A comfortable indoor climate is an important factor for all people. Midea® modular, high-end air handling unit is designed to regulate and control temperatures, humidity and air quality in hotels, office buildings, hospital, airport–or anywhere else where the well-being of the occupants is a priority.

• Flexibility: Through Modular Design to Cater to All kinds of Occasions. • IAQ (Indoor Air Quality) Focused to Meet Tough Standards of Schools, Air Port, Hospitals, and Other Commercial Buildings. • Accessibility for Ease of Installation and Maintenance. • Quiet Operation for Sound Sensitive Applications. • Durable and Weather tight cabinet for long work life.

Page 23: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

23

■ Sturdy framework with box-section steel frame members. ■ Solid Aluminum, powder-coated corner pieces with a stable construction. ■ 30 mm or 50mm thick double-skin, flush-fitting panels without sharp edge. ■ Non-hygroscopic, rigid sheet, mineral PU insulation with a density of 50 kg/m3. ■ Fully enclosed panels with 20-gauge galvanized and pre-painted steel. ■ Fully demountable casing. ■ Multi-section blocks to reduce site assembly time. ■ Stainless steel casing and drain pan available as a standard alternative.

Page 24: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

24

HOW TO READ THE MODELS? MKZII 0710 A Z 1 A 01

Design Code: 【From 01~99】

Series Code: 【From A~Z】

Discharge Direction Code: 【1---Top Front Discharge;4---Upper Horizontal Discharge】

Pipe Connection Code: 【Z---Left;Y---Right】

【Face the returning air direction】

Rows of Coils: 【A---4 Rows;B---6 Rows;C---8 Rows】

Modular Code: 【The first 2 numbers means Height Modular, the last 2numbers means Width Modular】 【Each modular = 100mm】 【Midea 2nd generation Modular AHU】

Page 25: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

25

Quick Selection Table

M o d e l Nominal Air Flow

Section Dimension Air Flow in Different Velocity (m3/h)

Fan Diameter

Fan Performance

H W 2.25 m/s

2.5 m/s

2.75 m/s

3.0 m/s

3.25 m/s

3.5

m/s Max. TSP

STD Motor Power

MKZⅡ m3/h mm mm m3/h m3/h m3/h m3/h m3/h m3/h mm Pa kW

0710 5000 1045 745 4050 4500 5198 5400 5850 6300 280 220 2.2

0712 6000 1245 745 5022 5580 6138 6696 7254 7812 280 250 2.2

0812 7000 1245 845 5589 6210 7173 7452 8073 8694 315 290 3

0814 8000 1445 845 6480 7200 8216 8640 9360 10080 315 310 3

0915 10000 1545 945 8019 8910 10291 10692 11583 12474 355 310 3

1118 15000 1845 1145 12069 13410 15489 16092 17433 18774 450 350 5.5

1418 20000 1845 1445 15876 17640 20374 21168 22932 24696 500 410 7.5

1620 25000 2045 1645 19845 22050 25468 26460 28665 30870 560 410 11

1623 30000 2345 1645 23571 26190 30249 31428 34047 36666 630 420 11

1826 40000 2645 1845 30375 33750 39724 40500 43875 47250 710 510 15.

2127 50000 2745 2145 37989 42210 49681 50652 54873 59094 800 510 22

2131 60000 3145 2145 43578 48420 58523 58104 62946 67788 800 560 22

2631 70000 3145 2645 54432 60480 71850 72576 78624 84672 900 640 30

2635 80000 3545 2645 60264 66960 80285 80352 87048 93744 1000 640 37

3136 100000 3645 3145 74682 82980 99493 99576 107874 116172 1000 680 45

Note: 【1】Some of the model have not full listed; 【2】The height of the foundation and air outlet are not including to the total height of the unit; 【3】The section dimension is measured under the air flow ≤40000m3/h, 25mm dual skin panel;under the air flow ≥70000m3/h, 50mm dual skin panel,other 35mm 【4】The total static pressure is max pressure under the rated air flow. 【5】Coil face velocity is lower than 2.7m/s,or a breakwater should be used to prevent the water blower to the other function section.

Page 26: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

26

Cooling Performance Table(Recycling Air) Model

Nominal

Air Flow

ESP(Ⅰ) ESP(Ⅱ) Cooling Capacity

Heating Capacity

Water Flow rate

Water Resistance Pipe

ESP Motor

Power ESP

Motor

Power

MKZⅡ- m3/h Pa kW Pa kW kW kW L/s kPa DN

0710 4 Rows

5000 220 2.2 350 2.2

28.0 52.6 1.34 43.8 40

6 Rows 35.0 63.1 1.67 45.2 40

8 Rows 42.0 68.8 2.01 63.2 50

0712 4 Rows

6000 250 2.2 400 3

35.0 65.5 1.67 36.7 50

6 Rows 47.0 78.6 2.25 36.7 50

8 Rows 52.0 86.5 2.48 54.7 50

0812 4 Rows

7000

280 3 450 3

40.0 78.7 1.91 47.8 50

6 Rows 53.0 94.4 2.53 47.8 50

8 Rows 62.0 103.8 2.96 65.8 50

0814 4 Rows

8000

310 3 510 4

50.0 86.4 2.39 49.2 50

6 Rows 65.0 103.7 3.10 29.4 50

8 Rows 70.0 113.1 3.31 47.4 50

0915 4 Rows

10000

310 3 510 5.5

62.0 109.9 2.96 71.5 50

6 Rows 78.0 131.8 3.73 43.8 50

8 Rows 89.0 142.4 4.25 61.8 65

1118 4 Rows

15000 350 5.5 550 7.5

90.0 149.1 4.30 46.9 65

6 Rows 120.0 175.9 5.73 57.2 65

8 Rows 132.0 190.0 6.31 75.2 65

1418 4 Rows

20000 410 7.5 620 11

128.0 210.3 6.11 46.5 65

6 Rows 165.0 250.3 7.88 56.7 65

8 Rows 175.0 275.3 8.36 74.7 80

1620 4 Rows

25000

410 11 620 11

158.0 279.2 7.55 55.7 65

6 Rows 200.0 332.2 9.55 41.7 65

8 Rows 215.0 365.5 10.27 59.7 80

1623 4 Rows

30000

420 11 650 15

186.0 297.2 8.88 46.5 80

6 Rows 245.0 347.7 11.70 46.5 80

8 Rows 255.0 379.0 12.18 64.5 80

1826 4 Rows

40000

510 15 750 18.5

255.0 459.8 12.18 58.7 80

6 Rows 310.0 551.76 14.81 36.3 80

8 Rows 341.0 612.5 16.29 54.3 80

2127 4 Rows

50000 510 22 750 30

298.0 566.3 14.23 68.8 65

6 Rows 415.0 679.6 19.82 68.8 65

8 Rows 430.0 754.3 20.54 86.8 80

2131 4 Rows

60000 560 22 810 37

375.0 606.8 17.91 77.5 65

6 Rows 490.0 746.4 23.41 57.2 65

8 Rows 525.0 835.9 25.08 75.2 80

2631 4 Rows

70000 640 30 900 45

440.0 797.7 21.02 83.7 65

6 Rows 554.0 973.2 26.46 50.6 65

8 Rows 616.0 1099.7 29.42 68.6 80

2635 4 Rows

80000

640 37 900 45

464.0 906.1 22.16 52.4 80

6 Rows 616.0 1087.3 29.42 64.2 80

8 Rows 690.0 1228.7 32.96 82.2 80

3136

4 Rows

100000 680 45 1000 55

610.0 1177.8 29.14 56.2 80

6 Rows 765.0 1436.9 36.54 68.8 80

8 Rows 834.0 1595.0 39.84 86.8 80

Page 27: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

27

Cooling Performance Table(Fresh Air) Model

Nominal

Air Flow

ESP(Ⅰ) ESP(Ⅱ) Cooling Capacity

Heating Capacity

Water Flow rate

Water Resistance Pipe

ESP Motor

Power ESP

Motor

Power

MKZⅡ- m3/h Pa kW Pa kW kW kW L/s kPa DN

0710 4 Rows

5000 220 2.2 350 2.2

70.0 78.2 2.73 5.95 40

6 Rows 86.0 92.2 3.39 61.5 40

8 Rows 91.0 104.2 4.05 85.8 50

0712 4 Rows

6000 250 2.2 400 3

80.0 86.4 3.41 49.8 50

6 Rows 98.0 100.2 4.56 49.8 50

8 Rows 115.0 118.2 5.02 74.3 50

0812 4 Rows

7000

290 3 450 3

92.0 112.1 3.90 64.9 50

6 Rows 117.0 139.0 5.14 64.9 50

8 Rows 131.0 161.2 5.98 89.4 50

0814 4 Rows

8000

310 3 510 4

115.0 139.8 4.87 65.5 50

6 Rows 135.0 160.8 6.30 68.5 50

8 Rows 145.0 184.9 6.75 70.5 50

0915 4 Rows

10000

310 3 510 5.5

135.0 187.1 6.04 70.5 50

6 Rows 175.0 217.0 7.56 72.5 50

8 Rows 189.0 260.4 8.59 82.3 65

1118 4 Rows

15000 350 5.5 550 7.5

200.0 274.8 8.77 63.7 65

6 Rows 260.0 324.3 11.64 77.6 65

8 Rows 285.0 372.9 12.74 89.6 65

1418 4 Rows

20000 410 7.5 620 11

275.0 334.1 12.47 63.2 65

6 Rows 345.0 394.2 16.00 77.0 65

8 Rows 375.0 457.3 16.89 95.4 80

1620 4 Rows

25000

410 11 620 11

330.0 416.7 15.40 65.6 65

6 Rows 440.0 500.0 19.39 71.5 65

8 Rows 485.0 590.0 20.75 80.6 80

1623 4 Rows

30000

420 11 650 15

390.0 462.9 18.12 63.2 80

6 Rows 510.0 555.5 23.76 63.2 80

8 Rows 575.0 655.5 24.60 87.6 80

1826 4 Rows

40000

510 15 750 18.5

500.0 702.5 24.85 71.5 80

6 Rows 660.0 814.9 30.06 72.4 80

8 Rows 750.0 945.3 32.90 79.5 80

2127 4 Rows

50000 510 22 750 30

640.0 838.6 29.04 92.9 65

6 Rows 840.0 969.6 40.24 92.9 65

8 Rows 955.0 1147.9 41.49 101.7 80

2131 4 Rows

60000 560 22 810 37

800.0 1037.8 36.54 95.6 65

6 Rows 985.0 1203.8 47.51 99.5 65

8 Rows 1155.0 1396.5 50.66 100.6 80

2631 4 Rows

70000 640 30 900 45

985.0 1229.3 42.88 96.4 65

6 Rows 1155.0 1450.5 53.72 97.8 65

8 Rows 1265.0 1682.7 59.44 102.6 80

2635 4 Rows

80000

640 37 900 45

998.0 1383.7 45.21 97.6 80

6 Rows 1255.0 1632.8 59.73 99.5 80

8 Rows 1478.0 1894.0 66.58 102.6 80

3136

4 Rows

100000 680 45 1000 55

1305.0 1756.3 59.44 98.6 80

6 Rows 1625.0 2072.4 74.18 102.6 80

8 Rows 1864.0 2404.0 80.47 103.6 80

Page 28: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

28

Heating Performance Table

Note: 【1】Some of the model have not full listed; 【2】Entering heat water temperature is 60℃,Leaving temperature is 50℃; 【3】Heating condition: Fresh air : 7℃,Recycling air: 21℃; 【4】The coil is copper tube abounded with aluminum fins.

Model Nominal Air

Flow

1 Row 2 Row

Recycling air Fresh air Recycling air Fresh air

Heating

Water

Flow

Rate

Water Resistance Pipe Heating

Water

Flow

Rate

Water Resistance Pipe Heating

Water

Flow

Rate

Water Resistance Pipe Heating

Water

Flow

Rate

Water Resistance Pipe

MKZⅡ m3/h kW L/s kPa DN kW L/s kPa DN kW L/s kPa DN kW L/s kPa DN

0710 5000 16.0 0.38 6.2 40 28.0 0.67 7.4 40 28.0 0.67 0.76 40 48.0 1.15 8.9 40

0712 6000 21.0 0.50 7.8 40 35.0 0.84 9.4 40 35.0 0.84 0.95 40 60.0 1.43 11.2 40

0812 7000 23.0 0.55 8.2 40 38.0 0.91 9.8 40 37.0 0.88 1.14 40 65.0 1.55 11.8 40

0814 8000 27.0 0.64 8.5 40 46.0 1.10 10.2 40 46.0 1.10 1.26 40 77.0 1.84 12.2 40

0915 10000 35.0 0.84 9.4 40 61.0 1.46 11.3 40 58.0 1.39 1.6 40 98.0 2.34 13.5 40

1118 15000 53.0 1.27 12.4 50 90.0 2.15 14.9 50 90.0 2.15 2.17 50 151.0 3.61 17.9 50

1418 20000 71.0 1.70 13.2 50 119.0 2.84 15.8 50 118.0 2.82 3.06 50 198.0 4.73 19.0 50

1620 25000 92.0 2.20 14.6 50 155.0 3.70 17.5 50 154.0 3.68 4.06 50 255.0 6.09 21.0 50

1623 30000 108.0 2.58 15.8 65 173.0 4.13 19.0 65 181.0 4.32 4.32 65 305.0 7.28 22.8 65

1826 40000 142.0 3.39 16.4 65 229.0 5.47 19.7 65 235.0 5.61 6.68 65 410.0 9.79 23.6 65

2127 50000 181.0 4.32 17.6 50 289.0 6.90 21.1 50 305.0 7.28 8.23 50 485.0 11.58 25.3 50

2131 60000 215.0 5.13 18.4 50 364.0 8.69 22.1 50 355.0 8.48 8.82 50 598.0 14.28 26.5 50

2631 70000 245.0 5.85 19.7 50 418.0 9.98 23.6 50 415.0 9.91 11.59 50 690.0 16.48 28.4 50

2635 80000 275.0 6.57 20.6 65 475.0 11.34 24.7 65 470.0 11.23 13.17 65 795.0 18.99 29.7 65

3136 100000 325.0 7.76 21.5 65 578.0 13.80 25.8 65 585.0 13.97 17.12 65 1015.0 24.24 31.0 65

Page 29: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

29

Standard Units Dimension

Model Nominal Air

Flow 25mm panel 35mm panel 50mm panel

MKZⅡ m3/h W(mm) H(mm) W(mm) H(mm) W(mm) H(mm)

0710 5000 1045 745 - - - -

0712 6000 1245 745 - - - -

0812 7000 1245 845 - - - -

0814 8000 1445 845 - - - -

0915 10000 1545 945 - - - -

1118 15000 1845 1145 - - - -

1418 20000 1845 1445 - - - -

1620 25000 2045 1645 - - - -

1623 30000 2345 1645 - - - -

1826 40000 - - 2645 1845 - -

2127 50000 - - 2745 2145 - -

2131 60000 - - 3145 2145 - -

2631 70000 - - - - 3145 2645

2635 80000 - - - - 3545 2645

3136 100000 - - - - 3645 3145

Note: 【1】The base height and air outlet are not accounted to the unit dimension listed above; 【2】Units with the air flow less than 8000m3/h are equipped with a base that is 50mm high.

Units with the air flow larger than 40000m3/h are equipped with a base that is 80mm high. others are 63mm; 【3】MKZII unit feature 3-D modulus design. 1M=100mm; Unit Length= Length modulus*100+Number of Delivered sections*Q

Unit Width= Width modulus*100+Q Unit Height= Height modulus*100+ Q

Q:45mm for 25mm units;60mm for 35mm units;90mm for 50mm units

Page 30: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

30

Typical Unit Arrangement

Page 31: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

31

Page 32: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

32

AHU Selection Software

1. The products of this selection software contain Fan Coil Unit, standard Air

Handling Unit and Modular Air Handling Unit 2. You can make selections under varies entering air conditions, entering water

conditions and different fan speed settings. 3. The interface is much visualized, which makes the operation is very easy. 4. Powerful project management function.

Page 33: Midea Air Handling Unit - Zen Ac SKIN AHU-SPECS(NEW).pdf · Midea Air Handling Unit Floor mounted 3000CFM ---25000CFM Vertical mounted 3000CFM ---25000CFM Ceiling suspended 1000CFM

33

Main Interface

AHU Selection Interface

Menu Project Operation Area Selection Button Product Operation Area

Unit Settings

Selection Result (Equipment List) Simple Report (Specifications)