M-2001D Tapchanger Control Quick Start Guide Death or severe electrical shock can occur. WARNING: In no case should the line current circuit be interrupted with the regulator or transformer energized. Do not remove auxiliary current transformers without shorting the current inputs. Exercise care during installation, operation and maintenance procedures The equipment described in this manual contains voltages high enough to cause serious injury or death. Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all personnel safety procedures are carefully followed. Exercise due care when operating or servicing alone. WARNING: Remove Fuses Before Service. WARNING: When an adapter panel is not used, automatic shorting of CT inputs is not provided by the M2001D/M-2050; the customer must provide a method for shorting the CT's before the control is disconnected. 24-Pin Connector (P2) Voltage Input (Polarity) Neutral Load Current (Return) Load Current (Polarity) Circulating Current (Polarity) Circulating Current (Return) Tapchanger Raise Output Motor Power Input Voltage Reduction Step #2 or Contact KeepTrack 1R1L/1N Input Contact "Wetting" Supply + 12 Vdc Operations Counter/ Switch Status Input #1 Operations Counter/ Switch Status Input #2 Input 1 Motor Seal-in/ Switch Status Neutral Position Detector #1 Neutral Position Detector #2 Tapchanger Lower Output Non-Sequential Operation/Auto Tap Inhibit Input/SCADA Cutout Voltage Reduction Step #1 or Contact KeepTrack 1R1L/1N Input Motor Seal-in Disconnect Output User-Programmable Alarm Self-Test Alarm User-Programmable Alarm Non-Interruptable Pwr Supply Input Self-Test Alarm P3 Source Voltage Input Aux Output Aux Input A1 Or DVAr2 Disable Input Aux Input A2 Aux Input A3 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Fuse ¼ Amp Voltage Input (Polarity) Load Current (Return) See Note 2 Voltage Input (Return) See Note 2 Load Current (Polarity) 0.2 A Circulating Current (Polarity) 0.2A Circulating Current (Return) Self-Test Alarm (Return) See Note 4 User-Programmable Alarm (Return) Self-Test Alarm (Input) See Note 4 User-Programmable Alarm (Input) Motor Seal-in Note 3 AUTO OFF OFF RAISE LOWER RAISE LS LOWER LS AL INTERLOCK AR INTERLOCK AUX LOWER (AL) AUX RAISE (AR) AL AR MOTOR FUSE 6 A MOTOR POWER 120/240 V See Note 1 R L NOTES: 1. Motor voltage may be 120 or 240 V to neutral, or 240 V phase-to-phase. 2. The customer is to provide an earth ground connection to the CT/VT’s neutral connection, external to the control. 3. To Motor Power Seal-In board. 4. If the M-2001D is configured for the SCAMP pushbutton Auto/Manual Switch type, then the Self-Test Alarm relay is NOT available. T X Bottom View Top View Front Fiber Optic V-Pin Connector (optional) Fiber Optic ST Connector RJ-45 Ethernet over Copper (optional) Control Power Backup Input BlueTooth Ethernet over Fiber Optic (optional) RS-485 RS-232 DE9S In-Line, 6-Pin Connector for the M-2025B, C or D Current Loop Module 24-Pin Blue Connector for M-2000 Series Adapter Panels or Direct Connection Source Voltage Input One Aux Output Three Aux Inputs LCD SCREEN Pressing any pushbutton will wake up the LCD and display the heading corresponding to the “Hot Button” label inside the pushbutton - WAKE, MNTR, SETP, CNFG, COMM, UTIL, or VR. EXIT/WAKE Pushbutton The EXIT WAKE Pushbutton wakes the LCD from sleep mode and begins scrolling through a list of user programmed metered/calculated values. While navigating through the different HMI menus the EXIT pushbutton is used to: - Exit a level to the next higher level - Cancel data entry - Clear the screen when at the header level VR Pushbutton Activates the user defined Voltage Reduction Steps. Shortcuts/Arrows SETP Access to the Setpoints Screens. MNTR Access to the Monitoring Screens. ENT/UTL Pushbutton Access to the Utilities screens and ENTER button. While navigating through the different HMI menus the ENT pushbutton is used to: - Enter the edit mode of a screen - Store a setpoint or condition in memory - Enter the sub heading data level - Reset certain monitoring screens CNFG Access to the Configuration Screens. COMM Access to the Communication Screens. RAISE LED Out of Band Low Voltage. LOWER LED Out of Band High Voltage. REV PWR LED Indicates reverse power flow. OK LED Illuminates to indicate the micro controller is functioning properly and is extinguished when a Motor Seal-in Failure Block is in effect. COM1 TX/RX LEDS Indicates when control is transmitting and/or receiving data. ALARM LED Indicates any of the programmable alarms are activated. V/RED LED Indicates voltage reduction has been invoked. - Continuous illumination and one periodic flash indicates Level 1 Voltage Reduction. - Continuous illumination and two periodic flashes indicates Level 2 Voltage Reduction. - Continuous illumination and three periodic flashes indicates Level 3 Voltage Reduction. MANUAL LED Indicates automatic control is disabled and in manual mode. LOCAL LED Indicates control is switched into Local mode. Cannot command control to raise or lower via SCADA. USB Port Used for Direct TapTalk ® Communications Connection. Smart FlashCard Slot Used for loading and saving setpoints, saving Datalog files, SOE files, OSC files, Clone save and load, load and save DNP files, Firmware Update, save Wake-up Screens, save ALL Metering Parameters and can be utilized as an Access Code Key. Scan this QR Code for direct access to product software and support documents.

M-2001D Tapchanger Control Quick Start · PDF fileprogrammable alarms are activated. ... x.xx MW Demand Pri. VArs x.xx MVArs Demand Pri. VA x.xx MVA ... x.x mA Lead/Lag Circulating

Embed Size (px)

Citation preview

Page 1: M-2001D Tapchanger Control Quick Start · PDF fileprogrammable alarms are activated. ... x.xx MW Demand Pri. VArs x.xx MVArs Demand Pri. VA x.xx MVA ... x.x mA Lead/Lag Circulating

M-2001D Tapchanger Control Quick Start Guide

Death or severe electrical shock can occur.WARNING: In no case should the line current circuit be interrupted with the regulator or transformer energized. Do not remove auxiliary current transformers without shorting the current inputs.Exercise care during installation, operation and maintenance proceduresThe equipment described in this manual contains voltages high enough to cause serious injury or death. Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all personnel safety procedures are carefully followed. Exercise due care when operating or servicing alone.WARNING:Remove Fuses Before Service.

WARNING: When an adapter panel is not used, automatic shorting ofCT inputs is not provided by the M2001D/M-2050; the customer mustprovide a method for shorting the CT's before the control is disconnected.

24-Pin Connector (P2)

Voltage Input (Polarity)

Neutral

Load Current (Return)

Load Current (Polarity)

Circulating Current (Polarity)

Circulating Current (Return)

Tapchanger Raise Output

Motor Power Input

Voltage Reduction Step #2 orContact KeepTrack 1R1L/1N Input

Contact "Wetting"Supply + 12 Vdc

Operations Counter/Switch Status Input #1Operations Counter/

Switch Status Input #2Input 1 Motor Seal-in/

Switch StatusNeutral Position Detector #1

Neutral Position Detector #2

Tapchanger Lower Output

Non-Sequential Operation/AutoTap Inhibit Input/SCADA Cutout

Voltage Reduction Step #1 orContact KeepTrack 1R1L/1N Input

Motor Seal-in Disconnect Output

User-Programmable Alarm

Self-Test Alarm

User-Programmable Alarm

Non-InterruptablePwr Supply Input

Self-Test Alarm

P3

Source Voltage Input

Aux Output

Aux Input A1Or DVAr2 Disable Input

Aux Input A2

Aux Input A3

1

2

3

4

5

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

Fuse ¼ AmpVoltage Input (Polarity)

Load Current (Return) See Note 2

Voltage Input (Return) See Note 2

Load Current (Polarity) 0.2 A

Circulating Current (Polarity) 0.2A

Circulating Current (Return)

Self-Test Alarm(Return) See Note 4

User-ProgrammableAlarm (Return)

Self-Test Alarm(Input) See Note 4

User-ProgrammableAlarm (Input)

Motor Seal-in

Note 3

AUTO

OFF

OFF

RAISE

LOWER

RAISELS

LOWERLS

ALINTERLOCK

ARINTERLOCK

AUX LOWER (AL)

AUX RAISE (AR)

AL AR MOTOR

FUSE 6 A

MOTOR POWER 120/240 VSee Note 1

R L

NOTES: 1. Motor voltage may be 120 or 240 V to neutral, or 240 V phase-to-phase.

2. The customer is to provide an earth ground connection to the CT/VT’s neutral connection, external to the control. 3. To Motor Power Seal-In board.

4. If the M-2001D is configured for the SCAMP pushbutton Auto/Manual Switch type, then the Self-Test Alarm relay is NOT available.

TX

Bottom View

Top View

Front

Fiber Optic V-PinConnector(optional)

Fiber Optic STConnector

RJ-45 Ethernet overCopper (optional)

Control PowerBackup Input

BlueTooth

Ethernet over FiberOptic (optional)

RS-485

RS-232 DE9S

In-Line, 6-Pin Connectorfor the M-2025B, C or DCurrent Loop Module

24-Pin Blue Connector forM-2000 Series Adapter

Panels or Direct Connection

Source Voltage InputOne Aux Output

Three Aux Inputs

LCD SCREEN Pressing any pushbutton will wake up the LCD and display the heading corresponding to the “Hot Button” label inside the pushbutton - WAKE, MNTR, SETP, CNFG, COMM, UTIL, or VR.

EXIT/WAKE Pushbutton The EXIT WAKE Pushbutton wakes the LCD from sleep mode and begins scrolling through a list of user programmed metered/calculated values.

While navigating through the different HMI menus the EXIT pushbutton is used to: - Exit a level to the next higher level - Cancel data entry - Clear the screen when at the header level

VR Pushbutton Activates the user defined Voltage Reduction Steps.

Shortcuts/ArrowsSETP Access to the Setpoints Screens.

MNTR Access to the Monitoring Screens.

ENT/UTL Pushbutton Access to the Utilities screens and ENTER button.

While navigating through the different HMI menus the ENT pushbutton is used to: - Enter the edit mode of a screen - Store a setpoint or condition in memory - Enter the sub heading data level - Reset certain monitoring screens

CNFG Access to the Configuration Screens.

COMM Access to the Communication Screens.

RAISE LED Out of Band Low Voltage.

LOWER LED Out of Band High Voltage.

REV PWR LED Indicates reverse power flow.

OK LED Illuminates to indicate the micro controller is functioning properly and is extinguished when a Motor Seal-in Failure Block is in effect.

COM1 TX/RX LEDS Indicates when control is transmitting and/or receiving data.

ALARM LED Indicates any of the programmable alarms are activated.V/RED LED Indicates voltage reduction has been invoked. - Continuous illumination and one periodic

flash indicates Level 1 Voltage Reduction. - Continuous illumination and two periodic

flashes indicates Level 2 Voltage Reduction. - Continuous illumination and three periodic

flashes indicates Level 3 Voltage Reduction.

MANUAL LED Indicates automatic control is disabled and in manual mode.

LOCAL LED Indicates control is switched into Local mode. Cannot command control to raise or lower via SCADA.

USB Port Used for Direct TapTalk® Communications Connection.

Smart FlashCard Slot Used for loading and saving setpoints, saving Datalog files, SOE files, OSC files, Clone save and load, load and save DNP files, Firmware Update, save Wake-up Screens, save ALL Metering Parameters and can be utilized as an Access Code Key.

Scan this QR Code for direct access to product software and support documents.

Page 2: M-2001D Tapchanger Control Quick Start · PDF fileprogrammable alarms are activated. ... x.xx MW Demand Pri. VArs x.xx MVArs Demand Pri. VA x.xx MVA ... x.x mA Lead/Lag Circulating

Press ENT to view Tapchanger Status

Press ENT to view Alarm Status

Press ENT to view Input Status

Press ENT to viewOutput Status

Peak RMS Currx.x mA (x.x) T

Avg RMS Currx.x mA (x.x) T

Profile DurationXXXX.Xms(xxxx.x)T

Peak Motor Current Ex.x mA

Voltage % THDx.x %

Current % THDxx.x %

Press ENT to viewVoltage Harmonics

Press ENT to viewCurrent Harmonic

Status Motor Current Harmonics

MONITORUTIL SETP

Tap Information Present Demand Demand History Energy Metering

Tap Position/CalDISABLE

Drag Hands EL= 0 N R= 0 N

Definite TimerRaise xxs Lower xxs

Intertap Timerxxx %

Operation Counterx

Resettable Counter Ex

Neutral Sw Counterx

Lower Counter x

Raise Counter x

Press ENT to viewspecific Tap Stats

Press ENT to clear Tap Statistics

RTN Success Counterxxxxx

RTN StatusDISABLED

Count to RTN Activexxxxx

Demand Intervalxx Min

Demand Load Voltagexxx.x Volts

Demand Pri. Currentxxx.x Amps

Demand Pri. Wattsx.xx MW

Demand Pri. VArsx.xx MVArs

Demand Pri. VA x.xx MVA

Demand Intervalxx Min

Min Load Voltage Ex.x Volts

Max Load Voltage Exxx.x Volts

Max Pri.Current Exxx.x Amps

Max Primary Watts Ex.xx MW

Max Primary VArs Ex.xx MVAr

Max Primary VA Ex.xx MVA

PF @ Max VA Ex.xxx PF

Press ENT to resetDemand History

Press ENT to performMaster Reset

Watt Hours FwdE

x kWh

Lagging VAr Hours E x kVArh

Watt Hours Rev E xx kWh

Leading VAr Hours E x kVArh

Press ENT to resetEnergy Metering

Press ENT to perform Master Reset

If DVAr enabled

Metering

Load Voltagexxx.x Volts

Meter Out Voltagexxx.x Volts

Source Voltagedisabled

Load Currentx.x mA Lead/Lag

Circulating Currentx.x mA LEAD/LAG

DVar Currentx.x mA LEAD/LAG

Compensated Voltagexxx.x Volts

Primary Voltagex.xx kV

Primary Src Voltagedisabled

Primary Currentxxx.x Amps

Primary Wattsx.xx MW

Primary VArsx.xx MVArs

Primary VAx.xx MVA

Power Factorx.xxx LEAD/LAG

Frequencyxx.x Hz

Load Voltagexxx.x Volts

Watt Hours Fwd E x.xxx MWh

Press ENT to view Tapchanger Status

Press ENT to view Alarm Status

Press ENT to view Input Status

Press ENT to viewOutput Status

Peak RMS Currx.x mA (x.x) T

Avg RMS Currx.x mA (x.x) T

Profile DurationXXXX.Xms(xxxx.x)T

Peak Motor Current Ex.x mA

Voltage % THDx.x %

Current % THDxx.x %

Press ENT to viewVoltage Harmonics

Press ENT to viewCurrent Harmonic

Status Motor Current Harmonics

MONITORUTIL SETP

Tap Information Present Demand Demand History Energy Metering

Tap Position/CalDISABLE

Drag Hands EL= 0 N R= 0 N

Definite TimerRaise xxs Lower xxs

Intertap Timerxxx %

Operation Counterx

Resettable Counter Ex

Neutral Sw Counterx

Lower Counter x

Raise Counter x

Press ENT to viewspecific Tap Stats

Press ENT to clear Tap Statistics

RTN Success Counterxxxxx

RTN StatusDISABLED

Count to RTN Activexxxxx

Demand Intervalxx Min

Demand Load Voltagexxx.x Volts

Demand Pri. Currentxxx.x Amps

Demand Pri. Wattsx.xx MW

Demand Pri. VArsx.xx MVArs

Demand Pri. VAx.xx MVA

Demand Intervalxx Min

Min Load Voltage Ex.x Volts

Max Load Voltage Exxx.x Volts

Max Pri.Current Exxx.x Amps

Max Primary Watts Ex.xx MW

Max Primary VArs Ex.xx MVAr

Max Primary VA Ex.xx MVA

PF @ Max VA Ex.xxx PF

Press ENT to resetDemand History

Press ENT to performMaster Reset

Watt Hours FwdE

x kWh

Lagging VAr Hours Ex kVArh

Watt Hours Rev Exx kWh

Leading VAr Hours Ex kVArh

Press ENT to resetEnergy Metering

Press ENT to perform Master Reset

If DVAr enabled

Metering

Load Voltagexxx.x Volts

Meter Out Voltagexxx.x Volts

Source Voltagedisabled

Load Currentx.x mA Lead/Lag

Circulating Currentx.x mA LEAD/LAG

DVar Currentx.x mA LEAD/LAG

Compensated Voltagexxx.x Volts

Primary Voltagex.xx kV

Primary Src Voltagedisabled

Primary Currentxxx.x Amps

Primary Wattsx.xx MW

Primary VArsx.xx MVArs

Primary VAx.xx MVA

Power Factorx.xxx LEAD/LAG

Frequencyxx.x Hz

Load Voltagexxx.x Volts

Watt Hours Fwd Ex.xxx MWh

* Power Flow Reverse setting screens are only available when the "Reverse Power Operation" selection under "Common Settings" is selected to either: REGULATE REVERSE,REG. R MEASURED SRC, DISTRIBUTED GENERATION, AUTO DETERMINE orAUTO DETERMINE MEASURED. If Distributed Generation is selected, then only LDC values can be set.

Selecting BLOCK, IGNORE or RETURN TO NEUTRAL disables the Power Flow Reverse setting screens.

Active Setpoint Profile or Setpoint Profile Selected for Editing

Limits 1

Profile Settings Common Settings 1

Block Raise Voltagexxx.x Volts

Block Lower Voltagexxx.x Volts

Runup Deadbandx.x Volts

Current Block Limit xxx mA

Runback Deadbandx.x Volts

Runup Enable/Disabledisable

Active Profile1

Edit Profile 1 Name"Empty"

Profile to Edit1

Repeats for Profiles 2-4

LDC SelectionRX

Timer ResetINTEGRATING

Timer CharacteristicDEFINITE

Power Direction BiasNONE

Rev Power OperationBLOCK *

Bandcenter Fwdxxx.x Volts

LDC X Fwd x Volts

Bandwidth Fwdx.x Volts

LDC Z Fwdx Volts

With LDC R,X

With LDC Z

Bandcenter Revxxx.x Volts

Bandwidth Revx.x Volts

LDC X Fwd x Volts

LDC Z Fwdx Volts

With LDC R,X

With LDC Z

VAr Bias 1

Disable on Rev Pwrdisable

Set VAr Bias MethodStep

Set VAr Bias Methoddisable (Step, Linear)

Fwd Max Cap Bnk Size 12000 KVAr

Rev Max Cap Bnk Size 12000 KVAr

Lead % Pickup 75

Lag % Pickup 75

VAr Bias Volt Step1.0 Volts

Max VAR Bias Time300 mins

Curr Mult Base Value x

Disable on Rev Pwrdisable

Set VAr Bias MethodLinear

Linear V Bias -X x Volts

Normlzd Lin V Bias -X x.x Volts

Linear V Bias -X Lmtx.x Volts

Linear V Bias +X x Volts

Normlzd Lin V Bias +X x.x Volts

Linear V Bias +X Lmt x.x Volts

To Profile Settings

To VAr Bias

Voltage Reduction 1

VRed Turnoff Time x Min

Smart VRdisable

Save VR at Power OffDON"T SAVE

Standard VRdisable

Reduction Step 1 % 2.5

Reduction Step 3 %7.5

Reduction Step 2 %5.0

LDC R Fwd x Volts

Definite(Inverse) Delay Fwd xx Sec

Power Flow Rev 1Power Flow Fwd 1

LDC R Fwd x Volts

Definite (Inverse) Delay Fwd xx Sec

SETPOINTSMNTR CNFG

Sheet 2 of 4800-M-2001D-QSG-08 (03-17)

At any menu screen:

Press EXIT to go to the Menu Header.

Press either to move sideways to the adjacent Menu Header.

COMMUNICATIONCNFG UTIL

CONFIGURATIONSETP COMM

UTILITIESCOMM MNTR

To Harmonics

To Tap Information

Page 3: M-2001D Tapchanger Control Quick Start · PDF fileprogrammable alarms are activated. ... x.xx MW Demand Pri. VArs x.xx MVArs Demand Pri. VA x.xx MVA ... x.x mA Lead/Lag Circulating

CONFIGURATIONSETP COMM

Tap SettingsTapchanger TypeRemote Voltage Bias

Enable/Disabledisable

RVB HB Timerx Secs

RVB Scale Factorx.x

Rev RVB Scale Factorx.x

Run Through Neutral

Enable/Disabledisable

Reset RTN Succ CtrPress ENT to begin

Max Allowed Tapsx

Max RTN Standby Ops xx

Taps Between Runsxxxx

Max Load Current xx mA

Nameplate

Auto/Man Sw TypeSCAMP SWITCH

Scamp Init PwrupAUTO MODE

Auto/Man Sw TypeNONE/TOGGLE

Comm Block AutoDON'T SAVE

CT Multiplier xxxx X

Load VT ConfigLINE_TO_GROUND

Aux Curr Transformerxxx mA

CT/Load VT Phasingx Deg

Load VT Multiplierxx.x X

Load VT Correction x.x Volts

CT/Source VT Phasingx Deg

Source VT Multiplierxx.x X

Source VT Correctionx.x Volts

Norm. VT. Multiplierx.xx

Power Display OptionSINGLE_PHASE

Fast Volt Recoverydisable

Fast Volt R Settingx.x V

Auto/Man Switch Type set to SCAMPin Nameplate

Programmable Alarm

Prog Alarm Function–<0000000000000000

Prog Alarm FunctionNORMAL/AS DEADMAN OUT

Op Count Signal Alrmx

Clear Sealin AlarmReady Press ENTER

Clr Low Current BlkReady Press ENTER

Clr RTN Fail To OprReady Press ENTER

System Clock

Set Date and Timexx/xx/xx xx:xx:xx

Daylight Savingsdisable

Input Selection

Input Selection 1SWITCH STATUS

Input Selection 2NONSEQ INPUT

Input Selection 3VOLTAGE RED 2

Mtr Current Profile

Peak RMS % Changexxx

Average RMS % Changexxx

Duration % Changexxx

Init. Motor CurrentPress ENT to reset

CBEMA Setup Harmonics Setup Data Logging

Data Log Select111111111111111

Data Log Intervalx mins

Press ENT to clearData Log Records

Regulator TypeTYPE A

Output SelectionCONTINUOUS

Output Pulsex.x Sec

Low Current Blockdisable

Paralleling

Tap Limits ENABLED

Not settable unless an external source of Tap

Position is selected

Tap Position/Cal DISABLE

Tap Informationdisable

Tap Block Raise xx

Tap Block Lower–xx

Highest Tap xx

Lowest Tap–xx

Intertap Delayx Sec

Seal-in Fail BlockENABLE

Op Counter Config1 X / 2 X/

COUNT WINDOW/CAM FOLLOWER

Cam Followerdisable

X Mode Delay xx ms

Op Counter Preset xxxxxx

Ntrl Counter Presetxxxxxx

Lower Counter Presetxxxxxx

Tapchanger TypeLTC

Regulator VendorDefault

Counter Time Window x.x Sec

Raise Counter Presetxxxxxx

Maximum Tap Wearxxxxx

IndTapWear Alrm Set100 %

Cooper Quick Drivedisable

Op Ctr = Count Window Op Ctr = 1X/2X

Paralleling TypeDISABLE

Paralleling TypeDELTA VAR #1

Paralleling TypeCIRCULATING I

Paralleling TypeDISABLE

Paralleling TypeDELTA VAR #2orDELTA VAR #2 (KT)

DVAR2 Sensitivityx.x

DVAR2 Reac I Lmtxxx mA

DVAR2 I Ratiox.xx

Paralleling TypeMASTER/FOLLOWER

MASTER/FOLLOWERNONE

Paralleling Addressxx

Num. Devicesx

T.P.R. Timeoutxxxxx

Breaker Optionxxxxxx

Tap Differencex

Clear Lockout AlarmReady Press ENTER

Paralleling TypePEER2PEER DELTAVAR

P2P DVar Sensitivityx.x

DVAR2 Reac I Lmtxxx mA

TopologySingle Bus

Paralleling Addressxx

Num. Devicesx

P2P Update Speedxxxxx

Clear Lockout AlarmReady Press ENTER

Load Side Brk ConfigNot Used

Right Tie Brk ConfigNot Used

Left Tie Brk ConfigNot Used

MVA Ratingx.x

I Multi Correctionxxx %

Min I Thresh. ENABLED

Use TapTalk ForCBEMA in SOE or OSC

Event 1ENABLE

Event1 Sag Pickupxx %

Event1 Sag Dropoutxx %

Event1 Sag Min Dur1 cycles (xx ms)

Repeats forEvents 2 thru 4

Clear All CountersReady Press ENTER

V 2-16 Har. Alarm011101111111111

V 17-31 Har. Alarm000000000000001

V Alarm Thresholdx.x %

I 2-16 Har. Alarm011101011111111

I 17-31 Har. Alarm000000000000001

I Alarm Thresholdxx %

Min I Thresh. EnableENABLE

Min Fund I Thresholdxx mA

Harmonic Alarm Delayxx s

Normal Voltagexxx.x Volts

Tap Limitsdisable/ENABLE

Tap Info ENABLED

To Data Logging

CONFIGURATIONSETP COMM

Tap SettingsTapchanger TypeRemote Voltage Bias

Enable/Disabledisable

RVB HB Timerx Secs

RVB Scale Factorx.x

Rev RVB Scale Factorx.x

Run Through Neutral

Enable/Disabledisable

Reset RTN Succ CtrPress ENT to begin

Max Allowed Tapsx

Max RTN Standby Opsxx

Taps Between Runsxxxx

Max Load Currentxx mA

Nameplate

Auto/Man Sw TypeSCAMP SWITCH

Scamp Init PwrupAUTO MODE

Auto/Man Sw TypeNONE/TOGGLE

Comm Block AutoDON'T SAVE

CT Multiplierxxxx X

Load VT ConfigLINE_TO_GROUND

Aux Curr Transformerxxx mA

CT/Load VT Phasingx Deg

Load VT Multiplierxx.x X

Load VT Correctionx.x Volts

CT/Source VT Phasingx Deg

Source VT Multiplierxx.x X

Source VT Correctionx.x Volts

Norm. VT. Multiplierx.xx

Power Display OptionSINGLE_PHASE

Fast Volt Recoverydisable

Fast Volt R Settingx.x V

Auto/Man Switch Type set to SCAMPin Nameplate

Programmable Alarm

Prog Alarm Function–<0000000000000000

Prog Alarm FunctionNORMAL/AS DEADMAN OUT

Op Count Signal Alrm x

Clear Sealin AlarmReady Press ENTER

Clr Low Current BlkReady Press ENTER

Clr RTN Fail To OprReady Press ENTER

System Clock

Set Date and Timexx/xx/xx xx:xx:xx

Daylight Savingsdisable

Input Selection

Input Selection 1SWITCH STATUS

Input Selection 2NONSEQ INPUT

Input Selection 3VOLTAGE RED 2

Mtr Current Profile

Peak RMS % Changexxx

Average RMS % Changexxx

Duration % Changexxx

Init. Motor CurrentPress ENT to reset

CBEMA Setup Harmonics Setup Data Logging

Data Log Select111111111111111

Data Log Intervalx mins

Press ENT to clearData Log Records

Regulator TypeTYPE A

Output SelectionCONTINUOUS

Output Pulsex.x Sec

Low Current Blockdisable

Paralleling

Tap Limits ENABLED

Not settable unless anexternal source of Tap

Position is selected

Tap Position/CalDISABLE

Tap Informationdisable

Tap Block Raisexx

Tap Block Lower–xx

Highest Tapxx

Lowest Tap–xx

Intertap Delayx Sec

Seal-in Fail BlockENABLE

Op Counter Config1 X / 2 X/

COUNT WINDOW/CAM FOLLOWER

Cam Followerdisable

X Mode Delay xx ms

Op Counter Preset xxxxxx

Ntrl Counter Presetxxxxxx

Lower Counter Presetxxxxxx

Tapchanger TypeLTC

Regulator VendorDefault

Counter Time Windowx.x Sec

Raise Counter Presetxxxxxx

Maximum Tap Wearxxxxx

IndTapWear Alrm Set100 %

Cooper Quick Drivedisable

Op Ctr = Count Window Op Ctr=1X/2X

Paralleling TypeDISABLE

Paralleling TypeDELTA VAR #1

Paralleling TypeCIRCULATING I

Paralleling TypeDISABLE

Paralleling TypeDELTA VAR #2orDELTA VAR #2 (KT)

DVAR2 Sensitivityx.x

DVAR2 Reac I Lmtxxx mA

DVAR2 I Ratiox.xx

Paralleling TypeMASTER/FOLLOWER

MASTER/FOLLOWERNONE

Paralleling Address xx

Num. Devicesx

T.P.R. Timeout xxxxx

Breaker Optionxxxxxx

Tap Difference x

Clear Lockout AlarmReady Press ENTER

Paralleling TypePEER2PEER DELTAVAR

P2P DVar Sensitivity x.x

DVAR2 Reac I Lmt xxx mA

TopologySingle Bus

Paralleling Addressxx

Num. Devices x

P2P Update Speedxxxxx

Clear Lockout AlarmReady Press ENTER

Load Side Brk ConfigNot Used

Right Tie Brk ConfigNot Used

Left Tie Brk ConfigNot Used

MVA Rating x.x

I Multi Correction xxx %

Min I Thresh. ENABLED

Use TapTalk ForCBEMA in SOE or OSC

Event 1ENABLE

Event1 Sag Pickupxx %

Event1 Sag Dropoutxx %

Event1 Sag Min Dur1 cycles (xx ms)

Repeats forEvents 2 thru 4

Clear All CountersReady Press ENTER

V 2-16 Har. Alarm011101111111111

V 17-31 Har. Alarm000000000000001

V Alarm Thresholdx.x %

I 2-16 Har. Alarm011101011111111

I 17-31 Har. Alarm000000000000001

I Alarm Thresholdxx %

Min I Thresh. EnableENABLE

Min Fund I Thresholdxx mA

Harmonic Alarm Delayxx s

Normal Voltagexxx.x Volts

Tap Limitsdisable/ENABLE

Tap Info ENABLED

CONFIGURATIONSETP COMM

Tap SettingsTapchanger TypeRemote Voltage Bias

Enable/Disabledisable

RVB HB Timerx Secs

RVB Scale Factorx.x

Rev RVB Scale Factorx.x

Run Through Neutral

Enable/Disabledisable

Reset RTN Succ CtrPress ENT to begin

Max Allowed Tapsx

Max RTN Standby Opsxx

Taps Between Runsxxxx

Max Load Currentxx mA

Nameplate

Auto/Man Sw TypeSCAMP SWITCH

Scamp Init PwrupAUTO MODE

Auto/Man Sw TypeNONE/TOGGLE

Comm Block AutoDON'T SAVE

CT Multiplierxxxx X

Load VT ConfigLINE_TO_GROUND

Aux Curr Transformerxxx mA

CT/Load VT Phasingx Deg

Load VT Multiplierxx.x X

Load VT Correctionx.x Volts

CT/Source VT Phasingx Deg

Source VT Multiplierxx.x X

Source VT Correctionx.x Volts

Norm. VT. Multiplierx.xx

Power Display OptionSINGLE_PHASE

Fast Volt Recoverydisable

Fast Volt R Settingx.x V

Auto/Man Switch Type set to SCAMPin Nameplate

Programmable Alarm

Prog Alarm Function–<0000000000000000

Prog Alarm FunctionNORMAL/AS DEADMAN OUT

Op Count Signal Alrmx

Clear Sealin AlarmReady Press ENTER

Clr Low Current BlkReady Press ENTER

Clr RTN Fail To OprReady Press ENTER

System Clock

Set Date and Timexx/xx/xx xx:xx:xx

Daylight Savingsdisable

Input Selection

Input Selection 1SWITCH STATUS

Input Selection 2NONSEQ INPUT

Input Selection 3VOLTAGE RED 2

Mtr Current Profile

Peak RMS % Change xxx

Average RMS % Changexxx

Duration % Change xxx

Init. Motor CurrentPress ENT to reset

CBEMA Setup Harmonics Setup Data Logging

Data Log Select111111111111111

Data Log Intervalx mins

Press ENT to clearData Log Records

Regulator TypeTYPE A

Output SelectionCONTINUOUS

Output Pulsex.x Sec

Low Current Blockdisable

Paralleling

Tap Limits ENABLED

Not settable unless anexternal source of Tap

Position is selected

Tap Position/CalDISABLE

Tap Informationdisable

Tap Block Raisexx

Tap Block Lower–xx

Highest Tapxx

Lowest Tap–xx

Intertap Delayx Sec

Seal-in Fail BlockENABLE

Op Counter Config1 X / 2 X/

COUNT WINDOW/CAM FOLLOWER

Cam Followerdisable

X Mode Delay xx ms

Op Counter Preset xxxxxx

Ntrl Counter Presetxxxxxx

Lower Counter Presetxxxxxx

Tapchanger TypeLTC

Regulator VendorDefault

Counter Time Windowx.x Sec

Raise Counter Presetxxxxxx

Maximum Tap Wearxxxxx

IndTapWear Alrm Set100 %

Cooper Quick Drivedisable

Op Ctr = Count Window Op Ctr=1X/2X

Paralleling TypeDISABLE

Paralleling TypeDELTA VAR #1

Paralleling TypeCIRCULATING I

Paralleling TypeDISABLE

Paralleling TypeDELTA VAR #2orDELTA VAR #2 (KT)

DVAR2 Sensitivityx.x

DVAR2 Reac I Lmtxxx mA

DVAR2 I Ratiox.xx

Paralleling TypeMASTER/FOLLOWER

MASTER/FOLLOWERNONE

Paralleling Addressxx

Num. Devicesx

T.P.R. Timeoutxxxxx

Breaker Optionxxxxxx

Tap Differencex

Clear Lockout AlarmReady Press ENTER

Paralleling TypePEER2PEER DELTAVAR

P2P DVar Sensitivityx.x

DVAR2 Reac I Lmtxxx mA

TopologySingle Bus

Paralleling Addressxx

Num. Devicesx

P2P Update Speedxxxxx

Clear Lockout AlarmReady Press ENTER

Load Side Brk ConfigNot Used

Right Tie Brk ConfigNot Used

Left Tie Brk ConfigNot Used

MVA Ratingx.x

I Multi Correctionxxx %

Min I Thresh. ENABLED

Use TapTalk ForCBEMA in SOE or OSC

Event 1ENABLE

Event1 Sag Pickup xx %

Event1 Sag Dropout xx %

Event1 Sag Min Dur 1 cycles (xx ms)

Repeats for Events 2 thru 4

Clear All CountersReady Press ENTER

V 2-16 Har. Alarm 011101111111111

V 17-31 Har. Alarm 000000000000001

V Alarm Thresholdx.x %

I 2-16 Har. Alarm 011101011111111

I 17-31 Har. Alarm 000000000000001

I Alarm Threshold xx %

Min I Thresh. EnableENABLE

Min Fund I Threshold xx mA

Harmonic Alarm Delayxx s

Normal Voltagexxx.x Volts

Tap Limitsdisable/ENABLE

Tap Info ENABLED

ToNameplate

Sheet 3 of 4800-M-2001D-QSG-08 (03-17)

At any menu screen:

Press EXIT to go to the Menu Header.

Press either to move sideways to the adjacent Menu Header.

COMMUNICATIONCNFG UTIL

MONITORUTIL SETP

SETPOINTSMNTR CNFG

UTILITIESCOMM MNTR

Page 4: M-2001D Tapchanger Control Quick Start · PDF fileprogrammable alarms are activated. ... x.xx MW Demand Pri. VArs x.xx MVArs Demand Pri. VA x.xx MVA ... x.x mA Lead/Lag Circulating

If Memory Card is present, the first menu displayed under Communication is the

Memory Card menu, otherwise the Memory Card menu is not displayed.

If IEC 61850 is purchased

COMMUNICATIONCNFG UTIL

Memory Card

Load SetpointsPress ENT to begin

Save SetpointsPress ENT to begin

Save DatalogPress ENT to begin

Save seq. of eventsPress ENT to begin

Save oscillographPress ENT to begin

Clone savePress ENT to begin

Clone loadPress ENT to begin

Load DNP ConfigPress ENT to begin

Save DNP ConfigPress ENT to begin

Save Metering DataPress ENT to begin

Firmware UpdatePress ENT to begin

Load IEC configPress ENT to begin

Save IEC ConfigPress ENT to begin

SD Quick CapturePress ENT to begin

Comm Settings

Comm1 Port TypeRS485

Comm2 Port TypeRS232

Comm ProtocolDNP3.0

DNP ConfigurationM2001D DNP DEFAULT

CID File IDM2001D DEFAULT

Src Addr Validationdisable

Substation AddressDNP x

Feeder AddressDNP x

Comm AddressDNP x Mdbus x

Baud Rate9600

ParityNONE

Stop BitsONE STOPBIT

Sync Time x mS

Output Pulsex.x Sec

Comm Access Securitydisable

Comm Access timeoutxx sec

TX Delayxx ms

Heartbeat OptionDisabled

ProtocolMODBUS

Baud Rate115200

ParityNONE

Stop BitsTWO STOPBITS

Sync Time xx mS

RS232

Bluetooth EnableENABLE

Bluetooth ResetReady Press ENTER

Bluetooth ProtocolMODBUS

Authenticationdisable

Friendly NameM2001D-1

Bluetooth Pass ResetReady Press ENTER

Control BT DeviceXX:XX:XX:XX:XX:XX

Bluetooth ModeMODE0

Bluetooth

Set LCD Contrast: E************

User Line 1 EBeckwith Electric

User Line 2 EM-2001D

Level 1 Access CodePress ENT to change

Level 2 Access CodePress ENT to change

Clear Osc RecordsReady Press ENTER

Oscillograph MessageENABLE

HMI

DHCP EnableENABLE

IP Address0.0.0.0

Net Mask0.0.0.0

Gateway0.0.0.0

Enter Modbus Port 502

Enter DNP Port20000

Auto NegotiationENABLE

Keepalive time7200 sec

Ethernet

Radius Server 1 IPx. x. x. x

Radius Server 2 IPx. x. x. x

Radius 1 Auth. Port 1812

Radius 2 Auth. Port1814

Radius Secret CodePress ENT to change

IEEE 1686 Standardnot used/Authen with Encryp*

Radius 1 Acc. Port 1813

Radius 2 Acc. Port 1815

Radius En./Dis.disable

IPSEC En./Dis.disable

Load User configPress ENT to begin

Load IPsec configPress ENT to begin

SNTP Enabledisable

SNTP Server Address0.0.0.0

Time Zone GMT–5 Hr

UTILITIESCOMM MNTR

Bias Voltage Status/Test Mode

Load VoltageXXX.X Volts

Voltage OffsetX

Volt Cal Coefficient32767 X

Volt RMS Coefficient 32762 X

Control Load Ix.x mA Lag/Lead

Curr Cal Coefficient 32767 X

Power Factorx.xxx Lag/Lead

I Sin Coefficient0 X

I Cos Coefficient8192 X

Motor Currentx.xx mA

Mtr Cal. Coefficient 8192 X

Mtr Sin Coefficient 0 X

Mtr Cos Coefficient 8192 X

Calibration/Test

Mtr RMS Coefficient 8192 X

Circ Cal. Coefficien 32767 X

Circ Sin Coefficient0 X

Circ Cos Coefficient 8192 X

LED Scroll TestPress ENT to begin

Input TestPress ENT to Begin

Output TestPress ENT to test

Button Input TestPress ENT to Begin

Change Src Input press ENTER.

Watchdog resets: xTotal resets: xx

Clear reset countersPress ENT to begin

X1 Duration0 ms, Avg: 0 ms

Alarm ActivityPress ENT to Begin

About

Serial Numberxxxxx

Firmware VersionD-0214VXX.XX.XX

EE ChecksumXxXXXx

Last Loaded File CRCx.x

Hardware Number x

Comm Options En/Dis11101111111111

Sheet 4 of 4800-M-2001D-QSG-08 (03-17)

CONFIGURATIONSETP COMM

SETPOINTSMNTR CNFG

MONITORUTIL SETP

© 2011 Beckwith Electric Co. All Rights Reserved

Technical Supportwww.beckwithelectric.com / 727 544-2326

Email Support: [email protected]

*NOTE: Once IEEE 1686 Standard cyber security is enabled, the user must enter a valid User Name and Password toaccess any menus other than the "Utilities/About" menu. Thisselection cannot be changed to "not used" without enteringa valid User Name and Password.

At any menu screen:

Press EXIT to go to the Menu Header.

Press either to move sideways to the adjacent Menu Header.