M-2001D Tapchanger Control Quick Start Guide
Death or severe electrical shock can occur.WARNING: In no case should the line current circuit be interrupted with the regulator or transformer energized. Do not remove auxiliary current transformers without shorting the current inputs.Exercise care during installation, operation and maintenance proceduresThe equipment described in this manual contains voltages high enough to cause serious injury or death. Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all personnel safety procedures are carefully followed. Exercise due care when operating or servicing alone.WARNING:Remove Fuses Before Service.
WARNING: When an adapter panel is not used, automatic shorting ofCT inputs is not provided by the M2001D/M-2050; the customer mustprovide a method for shorting the CT's before the control is disconnected.
24-Pin Connector (P2)
Voltage Input (Polarity)
Neutral
Load Current (Return)
Load Current (Polarity)
Circulating Current (Polarity)
Circulating Current (Return)
Tapchanger Raise Output
Motor Power Input
Voltage Reduction Step #2 orContact KeepTrack 1R1L/1N Input
Contact "Wetting"Supply + 12 Vdc
Operations Counter/Switch Status Input #1Operations Counter/
Switch Status Input #2Input 1 Motor Seal-in/
Switch StatusNeutral Position Detector #1
Neutral Position Detector #2
Tapchanger Lower Output
Non-Sequential Operation/AutoTap Inhibit Input/SCADA Cutout
Voltage Reduction Step #1 orContact KeepTrack 1R1L/1N Input
Motor Seal-in Disconnect Output
User-Programmable Alarm
Self-Test Alarm
User-Programmable Alarm
Non-InterruptablePwr Supply Input
Self-Test Alarm
P3
Source Voltage Input
Aux Output
Aux Input A1Or DVAr2 Disable Input
Aux Input A2
Aux Input A3
1
2
3
4
5
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Fuse ¼ AmpVoltage Input (Polarity)
Load Current (Return) See Note 2
Voltage Input (Return) See Note 2
Load Current (Polarity) 0.2 A
Circulating Current (Polarity) 0.2A
Circulating Current (Return)
Self-Test Alarm(Return) See Note 4
User-ProgrammableAlarm (Return)
Self-Test Alarm(Input) See Note 4
User-ProgrammableAlarm (Input)
Motor Seal-in
Note 3
AUTO
OFF
OFF
RAISE
LOWER
RAISELS
LOWERLS
ALINTERLOCK
ARINTERLOCK
AUX LOWER (AL)
AUX RAISE (AR)
AL AR MOTOR
FUSE 6 A
MOTOR POWER 120/240 VSee Note 1
R L
NOTES: 1. Motor voltage may be 120 or 240 V to neutral, or 240 V phase-to-phase.
2. The customer is to provide an earth ground connection to the CT/VT’s neutral connection, external to the control. 3. To Motor Power Seal-In board.
4. If the M-2001D is configured for the SCAMP pushbutton Auto/Manual Switch type, then the Self-Test Alarm relay is NOT available.
TX
Bottom View
Top View
Front
Fiber Optic V-PinConnector(optional)
Fiber Optic STConnector
RJ-45 Ethernet overCopper (optional)
Control PowerBackup Input
BlueTooth
Ethernet over FiberOptic (optional)
RS-485
RS-232 DE9S
In-Line, 6-Pin Connectorfor the M-2025B, C or DCurrent Loop Module
24-Pin Blue Connector forM-2000 Series Adapter
Panels or Direct Connection
Source Voltage InputOne Aux Output
Three Aux Inputs
LCD SCREEN Pressing any pushbutton will wake up the LCD and display the heading corresponding to the “Hot Button” label inside the pushbutton - WAKE, MNTR, SETP, CNFG, COMM, UTIL, or VR.
EXIT/WAKE Pushbutton The EXIT WAKE Pushbutton wakes the LCD from sleep mode and begins scrolling through a list of user programmed metered/calculated values.
While navigating through the different HMI menus the EXIT pushbutton is used to: - Exit a level to the next higher level - Cancel data entry - Clear the screen when at the header level
VR Pushbutton Activates the user defined Voltage Reduction Steps.
Shortcuts/ArrowsSETP Access to the Setpoints Screens.
MNTR Access to the Monitoring Screens.
ENT/UTL Pushbutton Access to the Utilities screens and ENTER button.
While navigating through the different HMI menus the ENT pushbutton is used to: - Enter the edit mode of a screen - Store a setpoint or condition in memory - Enter the sub heading data level - Reset certain monitoring screens
CNFG Access to the Configuration Screens.
COMM Access to the Communication Screens.
RAISE LED Out of Band Low Voltage.
LOWER LED Out of Band High Voltage.
REV PWR LED Indicates reverse power flow.
OK LED Illuminates to indicate the micro controller is functioning properly and is extinguished when a Motor Seal-in Failure Block is in effect.
COM1 TX/RX LEDS Indicates when control is transmitting and/or receiving data.
ALARM LED Indicates any of the programmable alarms are activated.V/RED LED Indicates voltage reduction has been invoked. - Continuous illumination and one periodic
flash indicates Level 1 Voltage Reduction. - Continuous illumination and two periodic
flashes indicates Level 2 Voltage Reduction. - Continuous illumination and three periodic
flashes indicates Level 3 Voltage Reduction.
MANUAL LED Indicates automatic control is disabled and in manual mode.
LOCAL LED Indicates control is switched into Local mode. Cannot command control to raise or lower via SCADA.
USB Port Used for Direct TapTalk® Communications Connection.
Smart FlashCard Slot Used for loading and saving setpoints, saving Datalog files, SOE files, OSC files, Clone save and load, load and save DNP files, Firmware Update, save Wake-up Screens, save ALL Metering Parameters and can be utilized as an Access Code Key.
Scan this QR Code for direct access to product software and support documents.
Press ENT to view Tapchanger Status
Press ENT to view Alarm Status
Press ENT to view Input Status
Press ENT to viewOutput Status
Peak RMS Currx.x mA (x.x) T
Avg RMS Currx.x mA (x.x) T
Profile DurationXXXX.Xms(xxxx.x)T
Peak Motor Current Ex.x mA
Voltage % THDx.x %
Current % THDxx.x %
Press ENT to viewVoltage Harmonics
Press ENT to viewCurrent Harmonic
Status Motor Current Harmonics
MONITORUTIL SETP
Tap Information Present Demand Demand History Energy Metering
Tap Position/CalDISABLE
Drag Hands EL= 0 N R= 0 N
Definite TimerRaise xxs Lower xxs
Intertap Timerxxx %
Operation Counterx
Resettable Counter Ex
Neutral Sw Counterx
Lower Counter x
Raise Counter x
Press ENT to viewspecific Tap Stats
Press ENT to clear Tap Statistics
RTN Success Counterxxxxx
RTN StatusDISABLED
Count to RTN Activexxxxx
Demand Intervalxx Min
Demand Load Voltagexxx.x Volts
Demand Pri. Currentxxx.x Amps
Demand Pri. Wattsx.xx MW
Demand Pri. VArsx.xx MVArs
Demand Pri. VA x.xx MVA
Demand Intervalxx Min
Min Load Voltage Ex.x Volts
Max Load Voltage Exxx.x Volts
Max Pri.Current Exxx.x Amps
Max Primary Watts Ex.xx MW
Max Primary VArs Ex.xx MVAr
Max Primary VA Ex.xx MVA
PF @ Max VA Ex.xxx PF
Press ENT to resetDemand History
Press ENT to performMaster Reset
Watt Hours FwdE
x kWh
Lagging VAr Hours E x kVArh
Watt Hours Rev E xx kWh
Leading VAr Hours E x kVArh
Press ENT to resetEnergy Metering
Press ENT to perform Master Reset
If DVAr enabled
Metering
Load Voltagexxx.x Volts
Meter Out Voltagexxx.x Volts
Source Voltagedisabled
Load Currentx.x mA Lead/Lag
Circulating Currentx.x mA LEAD/LAG
DVar Currentx.x mA LEAD/LAG
Compensated Voltagexxx.x Volts
Primary Voltagex.xx kV
Primary Src Voltagedisabled
Primary Currentxxx.x Amps
Primary Wattsx.xx MW
Primary VArsx.xx MVArs
Primary VAx.xx MVA
Power Factorx.xxx LEAD/LAG
Frequencyxx.x Hz
Load Voltagexxx.x Volts
Watt Hours Fwd E x.xxx MWh
Press ENT to view Tapchanger Status
Press ENT to view Alarm Status
Press ENT to view Input Status
Press ENT to viewOutput Status
Peak RMS Currx.x mA (x.x) T
Avg RMS Currx.x mA (x.x) T
Profile DurationXXXX.Xms(xxxx.x)T
Peak Motor Current Ex.x mA
Voltage % THDx.x %
Current % THDxx.x %
Press ENT to viewVoltage Harmonics
Press ENT to viewCurrent Harmonic
Status Motor Current Harmonics
MONITORUTIL SETP
Tap Information Present Demand Demand History Energy Metering
Tap Position/CalDISABLE
Drag Hands EL= 0 N R= 0 N
Definite TimerRaise xxs Lower xxs
Intertap Timerxxx %
Operation Counterx
Resettable Counter Ex
Neutral Sw Counterx
Lower Counter x
Raise Counter x
Press ENT to viewspecific Tap Stats
Press ENT to clear Tap Statistics
RTN Success Counterxxxxx
RTN StatusDISABLED
Count to RTN Activexxxxx
Demand Intervalxx Min
Demand Load Voltagexxx.x Volts
Demand Pri. Currentxxx.x Amps
Demand Pri. Wattsx.xx MW
Demand Pri. VArsx.xx MVArs
Demand Pri. VAx.xx MVA
Demand Intervalxx Min
Min Load Voltage Ex.x Volts
Max Load Voltage Exxx.x Volts
Max Pri.Current Exxx.x Amps
Max Primary Watts Ex.xx MW
Max Primary VArs Ex.xx MVAr
Max Primary VA Ex.xx MVA
PF @ Max VA Ex.xxx PF
Press ENT to resetDemand History
Press ENT to performMaster Reset
Watt Hours FwdE
x kWh
Lagging VAr Hours Ex kVArh
Watt Hours Rev Exx kWh
Leading VAr Hours Ex kVArh
Press ENT to resetEnergy Metering
Press ENT to perform Master Reset
If DVAr enabled
Metering
Load Voltagexxx.x Volts
Meter Out Voltagexxx.x Volts
Source Voltagedisabled
Load Currentx.x mA Lead/Lag
Circulating Currentx.x mA LEAD/LAG
DVar Currentx.x mA LEAD/LAG
Compensated Voltagexxx.x Volts
Primary Voltagex.xx kV
Primary Src Voltagedisabled
Primary Currentxxx.x Amps
Primary Wattsx.xx MW
Primary VArsx.xx MVArs
Primary VAx.xx MVA
Power Factorx.xxx LEAD/LAG
Frequencyxx.x Hz
Load Voltagexxx.x Volts
Watt Hours Fwd Ex.xxx MWh
* Power Flow Reverse setting screens are only available when the "Reverse Power Operation" selection under "Common Settings" is selected to either: REGULATE REVERSE,REG. R MEASURED SRC, DISTRIBUTED GENERATION, AUTO DETERMINE orAUTO DETERMINE MEASURED. If Distributed Generation is selected, then only LDC values can be set.
Selecting BLOCK, IGNORE or RETURN TO NEUTRAL disables the Power Flow Reverse setting screens.
Active Setpoint Profile or Setpoint Profile Selected for Editing
Limits 1
Profile Settings Common Settings 1
Block Raise Voltagexxx.x Volts
Block Lower Voltagexxx.x Volts
Runup Deadbandx.x Volts
Current Block Limit xxx mA
Runback Deadbandx.x Volts
Runup Enable/Disabledisable
Active Profile1
Edit Profile 1 Name"Empty"
Profile to Edit1
Repeats for Profiles 2-4
LDC SelectionRX
Timer ResetINTEGRATING
Timer CharacteristicDEFINITE
Power Direction BiasNONE
Rev Power OperationBLOCK *
Bandcenter Fwdxxx.x Volts
LDC X Fwd x Volts
Bandwidth Fwdx.x Volts
LDC Z Fwdx Volts
With LDC R,X
With LDC Z
Bandcenter Revxxx.x Volts
Bandwidth Revx.x Volts
LDC X Fwd x Volts
LDC Z Fwdx Volts
With LDC R,X
With LDC Z
VAr Bias 1
Disable on Rev Pwrdisable
Set VAr Bias MethodStep
Set VAr Bias Methoddisable (Step, Linear)
Fwd Max Cap Bnk Size 12000 KVAr
Rev Max Cap Bnk Size 12000 KVAr
Lead % Pickup 75
Lag % Pickup 75
VAr Bias Volt Step1.0 Volts
Max VAR Bias Time300 mins
Curr Mult Base Value x
Disable on Rev Pwrdisable
Set VAr Bias MethodLinear
Linear V Bias -X x Volts
Normlzd Lin V Bias -X x.x Volts
Linear V Bias -X Lmtx.x Volts
Linear V Bias +X x Volts
Normlzd Lin V Bias +X x.x Volts
Linear V Bias +X Lmt x.x Volts
To Profile Settings
To VAr Bias
Voltage Reduction 1
VRed Turnoff Time x Min
Smart VRdisable
Save VR at Power OffDON"T SAVE
Standard VRdisable
Reduction Step 1 % 2.5
Reduction Step 3 %7.5
Reduction Step 2 %5.0
LDC R Fwd x Volts
Definite(Inverse) Delay Fwd xx Sec
Power Flow Rev 1Power Flow Fwd 1
LDC R Fwd x Volts
Definite (Inverse) Delay Fwd xx Sec
SETPOINTSMNTR CNFG
Sheet 2 of 4800-M-2001D-QSG-08 (03-17)
At any menu screen:
Press EXIT to go to the Menu Header.
Press either to move sideways to the adjacent Menu Header.
COMMUNICATIONCNFG UTIL
CONFIGURATIONSETP COMM
UTILITIESCOMM MNTR
To Harmonics
To Tap Information
CONFIGURATIONSETP COMM
Tap SettingsTapchanger TypeRemote Voltage Bias
Enable/Disabledisable
RVB HB Timerx Secs
RVB Scale Factorx.x
Rev RVB Scale Factorx.x
Run Through Neutral
Enable/Disabledisable
Reset RTN Succ CtrPress ENT to begin
Max Allowed Tapsx
Max RTN Standby Ops xx
Taps Between Runsxxxx
Max Load Current xx mA
Nameplate
Auto/Man Sw TypeSCAMP SWITCH
Scamp Init PwrupAUTO MODE
Auto/Man Sw TypeNONE/TOGGLE
Comm Block AutoDON'T SAVE
CT Multiplier xxxx X
Load VT ConfigLINE_TO_GROUND
Aux Curr Transformerxxx mA
CT/Load VT Phasingx Deg
Load VT Multiplierxx.x X
Load VT Correction x.x Volts
CT/Source VT Phasingx Deg
Source VT Multiplierxx.x X
Source VT Correctionx.x Volts
Norm. VT. Multiplierx.xx
Power Display OptionSINGLE_PHASE
Fast Volt Recoverydisable
Fast Volt R Settingx.x V
Auto/Man Switch Type set to SCAMPin Nameplate
Programmable Alarm
Prog Alarm Function–<0000000000000000
Prog Alarm FunctionNORMAL/AS DEADMAN OUT
Op Count Signal Alrmx
Clear Sealin AlarmReady Press ENTER
Clr Low Current BlkReady Press ENTER
Clr RTN Fail To OprReady Press ENTER
System Clock
Set Date and Timexx/xx/xx xx:xx:xx
Daylight Savingsdisable
Input Selection
Input Selection 1SWITCH STATUS
Input Selection 2NONSEQ INPUT
Input Selection 3VOLTAGE RED 2
Mtr Current Profile
Peak RMS % Changexxx
Average RMS % Changexxx
Duration % Changexxx
Init. Motor CurrentPress ENT to reset
CBEMA Setup Harmonics Setup Data Logging
Data Log Select111111111111111
Data Log Intervalx mins
Press ENT to clearData Log Records
Regulator TypeTYPE A
Output SelectionCONTINUOUS
Output Pulsex.x Sec
Low Current Blockdisable
Paralleling
Tap Limits ENABLED
Not settable unless an external source of Tap
Position is selected
Tap Position/Cal DISABLE
Tap Informationdisable
Tap Block Raise xx
Tap Block Lower–xx
Highest Tap xx
Lowest Tap–xx
Intertap Delayx Sec
Seal-in Fail BlockENABLE
Op Counter Config1 X / 2 X/
COUNT WINDOW/CAM FOLLOWER
Cam Followerdisable
X Mode Delay xx ms
Op Counter Preset xxxxxx
Ntrl Counter Presetxxxxxx
Lower Counter Presetxxxxxx
Tapchanger TypeLTC
Regulator VendorDefault
Counter Time Window x.x Sec
Raise Counter Presetxxxxxx
Maximum Tap Wearxxxxx
IndTapWear Alrm Set100 %
Cooper Quick Drivedisable
Op Ctr = Count Window Op Ctr = 1X/2X
Paralleling TypeDISABLE
Paralleling TypeDELTA VAR #1
Paralleling TypeCIRCULATING I
Paralleling TypeDISABLE
Paralleling TypeDELTA VAR #2orDELTA VAR #2 (KT)
DVAR2 Sensitivityx.x
DVAR2 Reac I Lmtxxx mA
DVAR2 I Ratiox.xx
Paralleling TypeMASTER/FOLLOWER
MASTER/FOLLOWERNONE
Paralleling Addressxx
Num. Devicesx
T.P.R. Timeoutxxxxx
Breaker Optionxxxxxx
Tap Differencex
Clear Lockout AlarmReady Press ENTER
Paralleling TypePEER2PEER DELTAVAR
P2P DVar Sensitivityx.x
DVAR2 Reac I Lmtxxx mA
TopologySingle Bus
Paralleling Addressxx
Num. Devicesx
P2P Update Speedxxxxx
Clear Lockout AlarmReady Press ENTER
Load Side Brk ConfigNot Used
Right Tie Brk ConfigNot Used
Left Tie Brk ConfigNot Used
MVA Ratingx.x
I Multi Correctionxxx %
Min I Thresh. ENABLED
Use TapTalk ForCBEMA in SOE or OSC
Event 1ENABLE
Event1 Sag Pickupxx %
Event1 Sag Dropoutxx %
Event1 Sag Min Dur1 cycles (xx ms)
Repeats forEvents 2 thru 4
Clear All CountersReady Press ENTER
V 2-16 Har. Alarm011101111111111
V 17-31 Har. Alarm000000000000001
V Alarm Thresholdx.x %
I 2-16 Har. Alarm011101011111111
I 17-31 Har. Alarm000000000000001
I Alarm Thresholdxx %
Min I Thresh. EnableENABLE
Min Fund I Thresholdxx mA
Harmonic Alarm Delayxx s
Normal Voltagexxx.x Volts
Tap Limitsdisable/ENABLE
Tap Info ENABLED
To Data Logging
CONFIGURATIONSETP COMM
Tap SettingsTapchanger TypeRemote Voltage Bias
Enable/Disabledisable
RVB HB Timerx Secs
RVB Scale Factorx.x
Rev RVB Scale Factorx.x
Run Through Neutral
Enable/Disabledisable
Reset RTN Succ CtrPress ENT to begin
Max Allowed Tapsx
Max RTN Standby Opsxx
Taps Between Runsxxxx
Max Load Currentxx mA
Nameplate
Auto/Man Sw TypeSCAMP SWITCH
Scamp Init PwrupAUTO MODE
Auto/Man Sw TypeNONE/TOGGLE
Comm Block AutoDON'T SAVE
CT Multiplierxxxx X
Load VT ConfigLINE_TO_GROUND
Aux Curr Transformerxxx mA
CT/Load VT Phasingx Deg
Load VT Multiplierxx.x X
Load VT Correctionx.x Volts
CT/Source VT Phasingx Deg
Source VT Multiplierxx.x X
Source VT Correctionx.x Volts
Norm. VT. Multiplierx.xx
Power Display OptionSINGLE_PHASE
Fast Volt Recoverydisable
Fast Volt R Settingx.x V
Auto/Man Switch Type set to SCAMPin Nameplate
Programmable Alarm
Prog Alarm Function–<0000000000000000
Prog Alarm FunctionNORMAL/AS DEADMAN OUT
Op Count Signal Alrm x
Clear Sealin AlarmReady Press ENTER
Clr Low Current BlkReady Press ENTER
Clr RTN Fail To OprReady Press ENTER
System Clock
Set Date and Timexx/xx/xx xx:xx:xx
Daylight Savingsdisable
Input Selection
Input Selection 1SWITCH STATUS
Input Selection 2NONSEQ INPUT
Input Selection 3VOLTAGE RED 2
Mtr Current Profile
Peak RMS % Changexxx
Average RMS % Changexxx
Duration % Changexxx
Init. Motor CurrentPress ENT to reset
CBEMA Setup Harmonics Setup Data Logging
Data Log Select111111111111111
Data Log Intervalx mins
Press ENT to clearData Log Records
Regulator TypeTYPE A
Output SelectionCONTINUOUS
Output Pulsex.x Sec
Low Current Blockdisable
Paralleling
Tap Limits ENABLED
Not settable unless anexternal source of Tap
Position is selected
Tap Position/CalDISABLE
Tap Informationdisable
Tap Block Raisexx
Tap Block Lower–xx
Highest Tapxx
Lowest Tap–xx
Intertap Delayx Sec
Seal-in Fail BlockENABLE
Op Counter Config1 X / 2 X/
COUNT WINDOW/CAM FOLLOWER
Cam Followerdisable
X Mode Delay xx ms
Op Counter Preset xxxxxx
Ntrl Counter Presetxxxxxx
Lower Counter Presetxxxxxx
Tapchanger TypeLTC
Regulator VendorDefault
Counter Time Windowx.x Sec
Raise Counter Presetxxxxxx
Maximum Tap Wearxxxxx
IndTapWear Alrm Set100 %
Cooper Quick Drivedisable
Op Ctr = Count Window Op Ctr=1X/2X
Paralleling TypeDISABLE
Paralleling TypeDELTA VAR #1
Paralleling TypeCIRCULATING I
Paralleling TypeDISABLE
Paralleling TypeDELTA VAR #2orDELTA VAR #2 (KT)
DVAR2 Sensitivityx.x
DVAR2 Reac I Lmtxxx mA
DVAR2 I Ratiox.xx
Paralleling TypeMASTER/FOLLOWER
MASTER/FOLLOWERNONE
Paralleling Address xx
Num. Devicesx
T.P.R. Timeout xxxxx
Breaker Optionxxxxxx
Tap Difference x
Clear Lockout AlarmReady Press ENTER
Paralleling TypePEER2PEER DELTAVAR
P2P DVar Sensitivity x.x
DVAR2 Reac I Lmt xxx mA
TopologySingle Bus
Paralleling Addressxx
Num. Devices x
P2P Update Speedxxxxx
Clear Lockout AlarmReady Press ENTER
Load Side Brk ConfigNot Used
Right Tie Brk ConfigNot Used
Left Tie Brk ConfigNot Used
MVA Rating x.x
I Multi Correction xxx %
Min I Thresh. ENABLED
Use TapTalk ForCBEMA in SOE or OSC
Event 1ENABLE
Event1 Sag Pickupxx %
Event1 Sag Dropoutxx %
Event1 Sag Min Dur1 cycles (xx ms)
Repeats forEvents 2 thru 4
Clear All CountersReady Press ENTER
V 2-16 Har. Alarm011101111111111
V 17-31 Har. Alarm000000000000001
V Alarm Thresholdx.x %
I 2-16 Har. Alarm011101011111111
I 17-31 Har. Alarm000000000000001
I Alarm Thresholdxx %
Min I Thresh. EnableENABLE
Min Fund I Thresholdxx mA
Harmonic Alarm Delayxx s
Normal Voltagexxx.x Volts
Tap Limitsdisable/ENABLE
Tap Info ENABLED
CONFIGURATIONSETP COMM
Tap SettingsTapchanger TypeRemote Voltage Bias
Enable/Disabledisable
RVB HB Timerx Secs
RVB Scale Factorx.x
Rev RVB Scale Factorx.x
Run Through Neutral
Enable/Disabledisable
Reset RTN Succ CtrPress ENT to begin
Max Allowed Tapsx
Max RTN Standby Opsxx
Taps Between Runsxxxx
Max Load Currentxx mA
Nameplate
Auto/Man Sw TypeSCAMP SWITCH
Scamp Init PwrupAUTO MODE
Auto/Man Sw TypeNONE/TOGGLE
Comm Block AutoDON'T SAVE
CT Multiplierxxxx X
Load VT ConfigLINE_TO_GROUND
Aux Curr Transformerxxx mA
CT/Load VT Phasingx Deg
Load VT Multiplierxx.x X
Load VT Correctionx.x Volts
CT/Source VT Phasingx Deg
Source VT Multiplierxx.x X
Source VT Correctionx.x Volts
Norm. VT. Multiplierx.xx
Power Display OptionSINGLE_PHASE
Fast Volt Recoverydisable
Fast Volt R Settingx.x V
Auto/Man Switch Type set to SCAMPin Nameplate
Programmable Alarm
Prog Alarm Function–<0000000000000000
Prog Alarm FunctionNORMAL/AS DEADMAN OUT
Op Count Signal Alrmx
Clear Sealin AlarmReady Press ENTER
Clr Low Current BlkReady Press ENTER
Clr RTN Fail To OprReady Press ENTER
System Clock
Set Date and Timexx/xx/xx xx:xx:xx
Daylight Savingsdisable
Input Selection
Input Selection 1SWITCH STATUS
Input Selection 2NONSEQ INPUT
Input Selection 3VOLTAGE RED 2
Mtr Current Profile
Peak RMS % Change xxx
Average RMS % Changexxx
Duration % Change xxx
Init. Motor CurrentPress ENT to reset
CBEMA Setup Harmonics Setup Data Logging
Data Log Select111111111111111
Data Log Intervalx mins
Press ENT to clearData Log Records
Regulator TypeTYPE A
Output SelectionCONTINUOUS
Output Pulsex.x Sec
Low Current Blockdisable
Paralleling
Tap Limits ENABLED
Not settable unless anexternal source of Tap
Position is selected
Tap Position/CalDISABLE
Tap Informationdisable
Tap Block Raisexx
Tap Block Lower–xx
Highest Tapxx
Lowest Tap–xx
Intertap Delayx Sec
Seal-in Fail BlockENABLE
Op Counter Config1 X / 2 X/
COUNT WINDOW/CAM FOLLOWER
Cam Followerdisable
X Mode Delay xx ms
Op Counter Preset xxxxxx
Ntrl Counter Presetxxxxxx
Lower Counter Presetxxxxxx
Tapchanger TypeLTC
Regulator VendorDefault
Counter Time Windowx.x Sec
Raise Counter Presetxxxxxx
Maximum Tap Wearxxxxx
IndTapWear Alrm Set100 %
Cooper Quick Drivedisable
Op Ctr = Count Window Op Ctr=1X/2X
Paralleling TypeDISABLE
Paralleling TypeDELTA VAR #1
Paralleling TypeCIRCULATING I
Paralleling TypeDISABLE
Paralleling TypeDELTA VAR #2orDELTA VAR #2 (KT)
DVAR2 Sensitivityx.x
DVAR2 Reac I Lmtxxx mA
DVAR2 I Ratiox.xx
Paralleling TypeMASTER/FOLLOWER
MASTER/FOLLOWERNONE
Paralleling Addressxx
Num. Devicesx
T.P.R. Timeoutxxxxx
Breaker Optionxxxxxx
Tap Differencex
Clear Lockout AlarmReady Press ENTER
Paralleling TypePEER2PEER DELTAVAR
P2P DVar Sensitivityx.x
DVAR2 Reac I Lmtxxx mA
TopologySingle Bus
Paralleling Addressxx
Num. Devicesx
P2P Update Speedxxxxx
Clear Lockout AlarmReady Press ENTER
Load Side Brk ConfigNot Used
Right Tie Brk ConfigNot Used
Left Tie Brk ConfigNot Used
MVA Ratingx.x
I Multi Correctionxxx %
Min I Thresh. ENABLED
Use TapTalk ForCBEMA in SOE or OSC
Event 1ENABLE
Event1 Sag Pickup xx %
Event1 Sag Dropout xx %
Event1 Sag Min Dur 1 cycles (xx ms)
Repeats for Events 2 thru 4
Clear All CountersReady Press ENTER
V 2-16 Har. Alarm 011101111111111
V 17-31 Har. Alarm 000000000000001
V Alarm Thresholdx.x %
I 2-16 Har. Alarm 011101011111111
I 17-31 Har. Alarm 000000000000001
I Alarm Threshold xx %
Min I Thresh. EnableENABLE
Min Fund I Threshold xx mA
Harmonic Alarm Delayxx s
Normal Voltagexxx.x Volts
Tap Limitsdisable/ENABLE
Tap Info ENABLED
ToNameplate
Sheet 3 of 4800-M-2001D-QSG-08 (03-17)
At any menu screen:
Press EXIT to go to the Menu Header.
Press either to move sideways to the adjacent Menu Header.
COMMUNICATIONCNFG UTIL
MONITORUTIL SETP
SETPOINTSMNTR CNFG
UTILITIESCOMM MNTR
If Memory Card is present, the first menu displayed under Communication is the
Memory Card menu, otherwise the Memory Card menu is not displayed.
If IEC 61850 is purchased
COMMUNICATIONCNFG UTIL
Memory Card
Load SetpointsPress ENT to begin
Save SetpointsPress ENT to begin
Save DatalogPress ENT to begin
Save seq. of eventsPress ENT to begin
Save oscillographPress ENT to begin
Clone savePress ENT to begin
Clone loadPress ENT to begin
Load DNP ConfigPress ENT to begin
Save DNP ConfigPress ENT to begin
Save Metering DataPress ENT to begin
Firmware UpdatePress ENT to begin
Load IEC configPress ENT to begin
Save IEC ConfigPress ENT to begin
SD Quick CapturePress ENT to begin
Comm Settings
Comm1 Port TypeRS485
Comm2 Port TypeRS232
Comm ProtocolDNP3.0
DNP ConfigurationM2001D DNP DEFAULT
CID File IDM2001D DEFAULT
Src Addr Validationdisable
Substation AddressDNP x
Feeder AddressDNP x
Comm AddressDNP x Mdbus x
Baud Rate9600
ParityNONE
Stop BitsONE STOPBIT
Sync Time x mS
Output Pulsex.x Sec
Comm Access Securitydisable
Comm Access timeoutxx sec
TX Delayxx ms
Heartbeat OptionDisabled
ProtocolMODBUS
Baud Rate115200
ParityNONE
Stop BitsTWO STOPBITS
Sync Time xx mS
RS232
Bluetooth EnableENABLE
Bluetooth ResetReady Press ENTER
Bluetooth ProtocolMODBUS
Authenticationdisable
Friendly NameM2001D-1
Bluetooth Pass ResetReady Press ENTER
Control BT DeviceXX:XX:XX:XX:XX:XX
Bluetooth ModeMODE0
Bluetooth
Set LCD Contrast: E************
User Line 1 EBeckwith Electric
User Line 2 EM-2001D
Level 1 Access CodePress ENT to change
Level 2 Access CodePress ENT to change
Clear Osc RecordsReady Press ENTER
Oscillograph MessageENABLE
HMI
DHCP EnableENABLE
IP Address0.0.0.0
Net Mask0.0.0.0
Gateway0.0.0.0
Enter Modbus Port 502
Enter DNP Port20000
Auto NegotiationENABLE
Keepalive time7200 sec
Ethernet
Radius Server 1 IPx. x. x. x
Radius Server 2 IPx. x. x. x
Radius 1 Auth. Port 1812
Radius 2 Auth. Port1814
Radius Secret CodePress ENT to change
IEEE 1686 Standardnot used/Authen with Encryp*
Radius 1 Acc. Port 1813
Radius 2 Acc. Port 1815
Radius En./Dis.disable
IPSEC En./Dis.disable
Load User configPress ENT to begin
Load IPsec configPress ENT to begin
SNTP Enabledisable
SNTP Server Address0.0.0.0
Time Zone GMT–5 Hr
UTILITIESCOMM MNTR
Bias Voltage Status/Test Mode
Load VoltageXXX.X Volts
Voltage OffsetX
Volt Cal Coefficient32767 X
Volt RMS Coefficient 32762 X
Control Load Ix.x mA Lag/Lead
Curr Cal Coefficient 32767 X
Power Factorx.xxx Lag/Lead
I Sin Coefficient0 X
I Cos Coefficient8192 X
Motor Currentx.xx mA
Mtr Cal. Coefficient 8192 X
Mtr Sin Coefficient 0 X
Mtr Cos Coefficient 8192 X
Calibration/Test
Mtr RMS Coefficient 8192 X
Circ Cal. Coefficien 32767 X
Circ Sin Coefficient0 X
Circ Cos Coefficient 8192 X
LED Scroll TestPress ENT to begin
Input TestPress ENT to Begin
Output TestPress ENT to test
Button Input TestPress ENT to Begin
Change Src Input press ENTER.
Watchdog resets: xTotal resets: xx
Clear reset countersPress ENT to begin
X1 Duration0 ms, Avg: 0 ms
Alarm ActivityPress ENT to Begin
About
Serial Numberxxxxx
Firmware VersionD-0214VXX.XX.XX
EE ChecksumXxXXXx
Last Loaded File CRCx.x
Hardware Number x
Comm Options En/Dis11101111111111
Sheet 4 of 4800-M-2001D-QSG-08 (03-17)
CONFIGURATIONSETP COMM
SETPOINTSMNTR CNFG
MONITORUTIL SETP
© 2011 Beckwith Electric Co. All Rights Reserved
Technical Supportwww.beckwithelectric.com / 727 544-2326
Email Support: [email protected]
*NOTE: Once IEEE 1686 Standard cyber security is enabled, the user must enter a valid User Name and Password toaccess any menus other than the "Utilities/About" menu. Thisselection cannot be changed to "not used" without enteringa valid User Name and Password.
At any menu screen:
Press EXIT to go to the Menu Header.
Press either to move sideways to the adjacent Menu Header.