54
This document contains information considered proprietary and confidential to Tecnar Automation Ltd. 401010000203 Rev.A Revision date : 20130130 Page 1 of 54 LUT GAUGE Section II - OPERATION AND SOFTWARE

LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  1  of  54  

   

 

 

 

 

LUT GAUGE

Section II - OPERATION AND SOFTWARE

Page 2: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  2  of  54  

   

TABLE OF CONTENT – Section II II.1   LUT  GAUGE  OPERATION  ........................................................................................................................................  5  

II.1.1   BASIC  OPERATION  GUIDELINE  ...........................................................................................................................................  5  II.1.2   PIPE  PRESET  DATA  ..........................................................................................................................................................  5  II.1.3   FULL  START-­‐UP  PROCEDURE  .............................................................................................................................................  6  II.1.4   MAINTENANCE  START-­‐UP  PROCEDURE  ................................................................................................................................  8  II.1.5   AUTOMATIC  MEASURING  SEQUENCE  ..................................................................................................................................  8  II.1.6   MAINTENANCE  SHUTDOWN  PROCEDURE  ...........................................................................................................................  10  II.1.7   FULL  SHUTDOWN  PROCEDURE  ........................................................................................................................................  11  

II.2   LUT  GAUGE  SOFTWARE  .......................................................................................................................................  13  

II.2.1   INTRODUCTION  ............................................................................................................................................................  13  II.2.2   COMPUTER  HARDWARE  DESCRIPTION  ...............................................................................................................................  13  

II.2.2.1   Control  Unit  .....................................................................................................................................................  13  II.2.2.2   Detection  Unit  .................................................................................................................................................  13  II.2.2.3   Remote  Control  Unit  or  Viewer  .......................................................................................................................  14  II.2.2.4   Network  ...........................................................................................................................................................  14  

II.2.3   DATA  LOGGING  ............................................................................................................................................................  14  II.2.4   UPPER  SCREEN  COMMON  PART  ........................................................................................................................................  15  

II.2.4.1   Caption  bar  (A1)  ..............................................................................................................................................  15  II.2.4.2   Control  &  Status  bar  (A2)  ................................................................................................................................  15  

II.2.5   [SYSTEM  OVERVIEW]  TAB  ..............................................................................................................................................  17  II.2.5.1   [System  Active  State]  panel  (B1)  .....................................................................................................................  17  II.2.5.2   [System  Mode]  panel  (B2)  ...............................................................................................................................  17  II.2.5.3   [Pipe  Preset  Source]  panel  (B3)  .......................................................................................................................  18  II.2.5.4   [Network  Connections]  panel  (B4)  ..................................................................................................................  18  II.2.5.5   [System  Messages]  panel  (B5)  ........................................................................................................................  18  II.2.5.6   [Sub-­‐systems]  panel  (B6)  .................................................................................................................................  19  II.2.5.7   [Probe  1]  panel  (B7)  ........................................................................................................................................  21  

II.2.6   [DATA  DISPLAY]  TAB  .....................................................................................................................................................  23  II.2.6.1   [Pipe  Information]  panel  (C1)  ..........................................................................................................................  23  II.2.6.2   [Statistics]  panel  (C2)  ......................................................................................................................................  24  II.2.6.3   [Display  Layout]  panel  (C5)  .............................................................................................................................  25  

II.2.7   [PRESETS]  TAB  .............................................................................................................................................................  28  II.2.7.1   [Active  Preset]  panel  (D1)  ................................................................................................................................  29  II.2.7.2   [Operators  Presets]  list  (D2)  ............................................................................................................................  29  

II.2.8   [MAINTENANCE]  TAB  (CONTROL  UNIT  ONLY)  .....................................................................................................................  30  II.2.8.1   [Data  Recording]  panel  (E1)  ............................................................................................................................  31  II.2.8.2   [Laser  Auto-­‐Stop]  panel  (E2)  ...........................................................................................................................  31  II.2.8.3   [Probe  Activation]  panel  (E3)  ..........................................................................................................................  32  II.2.8.4   [Scanner  Maintenance]  panel  (E4)  ..................................................................................................................  32  II.2.8.5   [Probe  Maintenance]  panel  (E5)  .....................................................................................................................  32  

Page 3: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  3  of  54  

   

II.2.9   [SUB-­‐SYSTEMS]  TAB  (CONTROL  UNIT  ONLY)  ......................................................................................................................  34  II.2.9.1   [E-­‐Stops]  panel  (F1)  .........................................................................................................................................  34  II.2.9.2   [Interlocks]  panel  (F2)  .....................................................................................................................................  35  II.2.9.3   [Blower  Monitoring]  panel  (F3)  .......................................................................................................................  35  II.2.9.4   [Plant  PLC  Signals]  panel  (F4)  ..........................................................................................................................  35  II.2.9.5   [Length-­‐Meter  Temperature]  panel  (F5)  .........................................................................................................  35  II.2.9.6   [System  Monitor]  panel  (F6)  ............................................................................................................................  35  II.2.9.7   [Scanner]  panel  (F7)  ........................................................................................................................................  35  II.2.9.8   [Devices  Status  Overview]  panel  (F8)  ..............................................................................................................  35  II.2.9.9   [Detailed  Devices  Status]  panel  (F9)  ................................................................................................................  36  

II.2.10   [PROBE  “N”]  TAB  (CONTROL  UNIT  ONLY)  .....................................................................................................................  37  II.2.10.1   [Probe  Status]  panel  (G1)  ................................................................................................................................  37  II.2.10.2   [Probe  Active  state]  panel  (G2)  .......................................................................................................................  38  II.2.10.3   [Probe  Messages]  panel  (G3)  ..........................................................................................................................  38  II.2.10.4   [Chiller  Monitor]  panel  (G4)  ............................................................................................................................  38  II.2.10.5   [G-­‐Lasers]  panel  (G5)  .......................................................................................................................................  38  II.2.10.6   [G-­‐lasers  Usage]  panel  (G6)  ............................................................................................................................  38  II.2.10.7   [Probe  Temperature]  panel  (G7)  .....................................................................................................................  38  II.2.10.8   [Laser  Power]  panel  (G8)  .................................................................................................................................  38  II.2.10.9   [Detection  Unit  Interlocks]  panel  (G9)  .............................................................................................................  38  II.2.10.10   [Devices  Status  Overview]  panel  (G10)  .......................................................................................................  39  II.2.10.11   [Detailed  Devices  Status]  panel  (G11)  .........................................................................................................  39  

II.2.11   [NETWORK]  TAB  (CONTROL  UNIT  ONLY)  .......................................................................................................................  40  II.2.11.1   [Last  Preset]  panel  (H1)  ...................................................................................................................................  40  II.2.11.2   [Plant  Preset  Connection]  panel  (H2)  ..............................................................................................................  40  II.2.11.3   [Data  Logging  Connection]  panel  (H3)  ............................................................................................................  41  II.2.11.4   [Remote  &  Viewer]  panel  (H4)  ........................................................................................................................  41  

II.2.12   [CRITICAL  ERROR]  DIALOG  .........................................................................................................................................  41  

APPENDIX  1:  STATE  MESSAGE  FOR  THE  LUT  GAUGE  ........................................................................................................  43  

APPENDIX  2:  STATE  MESSAGE  FOR  THE  LUT  PROBE  .........................................................................................................  45  

APPENDIX  3:  ERRORS  AND  MESSAGES  .............................................................................................................................  46  

APPENDIX  4:  PIPE  LOGGING  DATA  FILE  ............................................................................................................................  52  

APPENDIX  5:  DATA  LOGGING  DATA  FILE  ..........................................................................................................................  53  

Page 4: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  4  of  54  

   

TABLE OF FIGURES – SECTION II Figure II. 1-2: Local command panel ......................................................................................................................... 6  

Figure II. 1-3: Remote command panel ..................................................................................................................... 7  

Figure II. 1-4: Timing from PLC. ............................................................................................................................ 10  

Figure II. 1-5: Close System option menu ............................................................................................................... 12  

Figure II. 1-6: System shutdown warning dialog box .............................................................................................. 12  

Figure II. 2-1: LUT main screen top part ................................................................................................................. 15  

Figure II. 2-2: [System Overview] tab ..................................................................................................................... 17  

Figure II. 2-3: [Message Details] dialog .................................................................................................................. 19  

Figure II. 2-4: [Sub-systems] panel .......................................................................................................................... 21  

Figure II. 2-5: [Probe 1] panel .................................................................................................................................. 22  

Figure II. 2-6: [Data Display] tab ............................................................................................................................. 23  

Figure II. 2-7: [Presets] tab ...................................................................................................................................... 28  

Figure II. 2-8: [Maintenance] tab ............................................................................................................................. 31  

Figure II. 2-9: [Sub-systems] tab .............................................................................................................................. 34  

Figure II. 2-10: [Probe] tab ...................................................................................................................................... 37  

Figure II. 2-11: [Network] tab .................................................................................................................................. 40  

Figure II. 2-12: [Critical Error] dialog ..................................................................................................................... 41  

Page 5: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  5  of  54  

   

Introduction

The  present  document  gives  a  complete  description  of  the  operation  and  software  of  the  LUT  gauge,  a  laser-­‐ultrasonic  wall  thickness  gauge  for  on-­‐line  measurement  of  hot  pipe/tube  from  Tecnar  Automation  Ltée  (TECNAR).    

II.1 LUT gauge Operation The  following  section  gives  a  step-­‐by-­‐step  description  of  the  routine  procedures  for  the  use  of  the  LUT  gauge.    

II.1.1 Basic Operation Guideline Always  read  an  entire  procedure  section  before  doing  any  operation  on  the  system.  The  LUT  gauge  is  a  complex  system  that  needs  to  be  operated  following  this  manual.  

Always  stop  the  LUT  gauge  with  the  active  command  panel  before  setting  a  security  key  or  an  e-­‐stop  on  the  system  except  in  an  emergency  situation.  The  system  is  designed  to  be  stopped  by  the  LUT  OS  software  in  a  controlled  manner.    

WARNING

Using a security key or an e-stop to stop the LUT gauge during its operation can cause permanent damage to the system.

 

II.1.2 Pipe Preset Data LUT  gauge  needs  preset  data  to  effectuate  effective  measurements.  Those  preset  data  can  be  sent  by  two  (2)  different  ways  to  the  system:  

1. Plant  preset  computer:  The  preset  data  is  sent  in  an  automatic  fashion  by  a  plant  computer  through  an  Ethernet  network.  

2. Operator:  The  preset  data  is  entered  by  the  operator  on  the  Remote  Control  computer  or  directly  on  the  control  unit.  

When  a  preset  in  sent  to  the  LUT  system,  it  remains  valid  until  a  new  preset  is  received.  The  LUT  system  will  maintain  a  measured  pipe  count  and  give  an  incremental  number  to  each  pipe  measured  in  a  batch.  This  number  will  be  reset  with  a  new  preset  data.  

Page 6: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  6  of  54  

   

II.1.3 Full Start-up Procedure The  LUT  gauge  is  a  fully  automated  gauging  system.  The  following  described  the  start-­‐up  procedure  and  automated  actions  of  the  LUT  gauge  from  a  «  cold  »  condition,  i.e.,  when  all  of  the  devices  have  been  powered  down  (for  example,  for  a  mill  shutdown  period).  

1. Activate (ON) the main breaker in the control room of the LUT gauge on the electrical distribution unit.

2. Activate (ON) the air supply unit (blower) breaker in the control room of the LUT gauge on the electrical distribution unit.

WARNING

If the blower is not ON while the LUT is measuring, the window can be damage because of dirt accumulation. The LASER can burn the dirt on the window and dramatically affect system performance.

3. Activate (ON) the cooling unit (chiller) breaker in the control room of the LUT gauge on the

electrical distribution unit. Verify that the chiller is active (powered up). If not, verify that the main switch is activate (ON) directly on the chiller unit. If the chiller is not powered up press the start button until the chiller starts. The chiller should always be activated (ON).

4. Activate (ON) the 220Vac bus in the control room of the LUT gauge inside the electrical panel. Activate (ON) the G-laser unit fan breaker, the G-laser unit breaker, the detection laser unit breaker, the detection unit breaker, the control unit breaker, the LUT inspection probe breaker, the length measuring unit breaker and the 110Vac bus breaker. Validate that all breaker in the 220Vac bus are activated (ON).

5. Enable power to the LUT gauge by turning the power key located on the LUT control unit. 6. When the LUT control unit is turned ON, the LUT OS is automatically executed after the booting

sequence of the operating system. The system should display “Connecting Devices” until all the LUT sub-systems are connected and detection unit computer is booted and connected. The [RED STATUS LIGHT] and the [WHITE SYSTEM STATUS LIGHT] will be OFF until all devices are connected.

7. Turn the [Safety switch LUT] key on the local command panel to the « unlock » position.

Figure II. 1-1: Local command panel

8. Turn the [Laser key] of the local command panel to the « unlock » position.

Page 7: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  7  of  54  

   

9. Repeat step 8 to 9 on the remote command panel.

Figure II. 1-2: Remote command panel

10. After 1-2 minutes, the pulpit screen and the system should display “System ready to be started” in the system active state window. The [RED STATUS LIGHT] and the [WHITE SYSTEM STATUS LIGHT] will be FLASHING.

11. If the [RED STATUS LIGHT] is still FLASHING, verify that all [Emergency stop] buttons are released. The emergency stop buttons are at the following location: • On  the  local  command  panel;  

• On  the  remote  command  panel  (pulpit);  

• On  the  LUT  control  unit  in  the  LUT  equipment  room;  

• On  the  LUT  detection  laser;  

• The  3  E-­‐stop  PLC  inputs  

• The  3  E-­‐stop  BNC  inputs  behind  the  control  unit  

12. If the [WHITE SYSTEM STATUS LIGHT] is FLASHING, verify that all safety interlocks are

appropriately set. The safety interlock are located: • On  the  moving  device  jib  crane  

• On  the  local  command  panel;  

• On  the  remote  command  panel  (pulpit);  

• The  3  interlock  PLC  inputs  

• The  2  interlock  inputs  behind  the  control  unit  

13. On the Local command panel, select which command panel will have control of the LUT gauge by using the 2-positions [Control] button. The yellow [Control light] is ON only for the active panel. When the [Control] button is turn to the [Local] position, the command panel in the electrical room is active while if the button is turned to the [Remote] position, the remote command panel at the production line (pulpit) is active. The [Command] button is only present on the local command panel in the electrical room. Notice that the active command panel, main or remote, can be changed with the LUT gauge in operation.

Page 8: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  8  of  54  

   

14. Turn the [Start/Stop] button of the active command panel to the « start » position and release the button. This action enables the powering of the length-meter, generation lasers and the detection laser. The LASER beacon light will turn RED. The screen of the LUT command unit will display “Waiting for System Ready”. The [SYSTEM READY LIGHT] on the command panels will be FLASHING until the system is ready to measure.

15. After the warm-up period, the system will display “System Ready”. The LUT gauge is ready for data acquisition, waiting in “Idle mode”. The [SYSTEM READY LIGHT] on the command panels will be ON.

II.1.4 Maintenance Start-up Procedure When  plant  operation  has  been  stopped  for  maintenance,  this  is  the  procedure  to  restart  the  LUT  gauge.  

1. Select the “Automatic” mode on the control unit computer.

2. Turn the [Laser key] on the active command panel to the [Unlock] position, and the [WHITE SYSTEM STATUS LIGHT] will be turn ON.

3. Insert and turn the [Safety Switch LUT] key to the [Unlock] position on both command panels. The system will display “System stopped”. The [RED STATUS LIGHT] on the command panels will be ON.

4. Turn the [Start/Stop] button of the active command panel to the “Start” position and release the button. The action enables of the length-meter, generation lasers and the detections laser. The LASER beacon light will turn RED. The system will display “Waiting for system ready”. The [SYSTEM READY LIGHT] on the command panels will be FLASHING until the system is ready to measure.

5. After the warm-up period, the system will display “System Ready”. The LUT gauge is ready for data acquisition, waiting in “idle mode”. The [SYSTEM READY LIGHT] on the command panels will be ON.

II.1.5 Automatic Measuring Sequence With  the  LUT  gauge  in  “idle  mode”,  as  described  in  the  previous  section,  the  gauge  is  an  automated  mode.  The  LUT  gauge  will  start  acquiring  data  without  any  operator  intervention.  The  following  describes  the  data  acquisition  sequence  in  “automatic  mode”.  At  the  beginning,  it  is  assumed  that  the  LUT  gauge  is  in  “idle  mode”.  

1. The mill sends an analog signal (PLC-Input 9) “Activate laser” command to the LUT command unit. The command should be sent at least thirty (30) seconds before the arrival of the pipe/tube at the measuring location of the LUT probe. This delay ensures that the LUT gauge is ready to measure BEFORE the arrival of the pipe/tube. The command should be sent for every pipe/tube to allow the LUT gauge to be in “active mode”. This way we prevent missing the measurement of a pipe/tube in the case where the LUT has automatically been place in «idle mode» because of lack of pipe/tube to inspect (see below). The system will display “Arming Lasers” and the [LASERS ARMED LIGHT] will be FLASHING.

2. After about 25 seconds, the lasers will be armed. The system will display “Lasers Armed” and the [LASERS ARMED LIGHT] will be ON.

Page 9: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  9  of  54  

   

3. Depending of the “Pipe Preset Source” selected, the LUT gauge will need one of the following action:

a. Plant Mode: The plant computer has to send one (1) preset data at least 5-10 seconds before the first pipe in batch.

b. Operator Mode: The operator has to manually enter the preset data at least 5-10 seconds before the first pipe in batch.

4. Optionally, the plant computer can send a “Pipe Info” message which contains pipe specific string identifier and number, 5-10 seconds before the target pipe.

5. An analog (PLC-Input 10) signal sends a “Pipe coming” signal to the LUT command unit. The signal is sent to indicate that a pipe/tube is present at the LUT probe location. The PLC signal must be held HIGH during the entire measuring of the pipe/tube by the LUT probe. The signal is needed for laser activation/deactivation. The signal should be raised at least two (2) seconds before the pipe/tube arrives at the LUT probe location. The delay is needed for proper activation of the generation and detection lasers. The delay should be as constant as possible. If the signal is sent a long time before the pipe actually arrives to the measure point, it is possible to add a time delay before the firing of the lasers. The delay is fixed during commissioning.

6. The LUT gauge automatically acquires the laser-ultrasonic signal and pipe temperature, length.

7. The “Pipe coming” signal drops to LOW when the pipe/tube leaves the LUT probe location. The signal should be kept HIGH for the full duration of the pipe/tube measurement under the LUT probe. The LUT gauge will stop acquiring data as soon as the signal drops to LOW. However, it is possible to add a time delay before the stop of data acquisition and lowering of the PLC signal. The delay is fixed during commissioning.

8. At the end of a processing sequence, the LUT gauge processes, stores in a single file, and sends the data of this pipe/tube through the network.

9. The sequence is repeated for the next pipe/tube.

10. If the LUT gauge has not received a “Pipe coming” command after a given time (set at commissioning, typically five (5) minutes), the LUT gauge is automatically placed back in “idle mode”. The action is done to extend the life of the flashlamps used in the LUT gauge.

Page 10: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  10  of  54  

 

Figure II. 1-3: Timing from PLC.

 

T0:  Pipe  under  LUT  position  

T1:  2-­‐5seconds  before  the  pipe  reach  the  LUT  position  

T2:  30  seconds  to  2  minutes  before  the  pipe  reach  the  LUT  position  

T3:  Should  be  kept  HIGH  for  the  full  duration  of  the  pipe/tube  traveling  under  the  LUT  probe  measure  point.  

T4:    1-­‐5  seconds  kept  high  to  be  read  by  LUT  software.  

11. When production is stopped (for maintenance or repair of the production), the LUT gauge should be deactivate following the following section.

 

II.1.6 Maintenance Shutdown Procedure When  plant  operation  is  stopped  for  maintenance,  it  is  recommended  to  shutdown  the  LUT  gauge  using  the  following  procedure.  

1. Turn and hold for one (1) second the [System start/stop] switch to the STOP position on the active control panel. (The yellow [Control light] is ON only for the active panel).

2. The system will then perform a controlled shutdown procedure. WARNING

Page 11: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  11  of  54  

 

Pressing an Emergency stop buttons or turning any of the safety keys to shutdown the LUT gauge will instantly cut the power to the components. It should never be used to perform a controlled shutdown.

3. If the lasers are armed, the system will display “Stopping Lasers” and the [LASERS ARMED

LIGHT] will be FLASHING until the lasers are stopped. 4. If the lasers were armed, the system will display briefly “System Ready” and the [LASERS ARMED

LIGHT] will be OFF. 5. The system will display “Stopping System”, indicating that the system is communicating the

shutdown command to all of the hardware components of the LUT gauge. The [SYSTEM READY LIGHT] on the command panels will be FLASHING until the system is completely stopped.

6. When the system is stopped, it will display “System stopped” and the [SYSTEM READY LIGHT] on the command panels will be OFF.

7. Turn the [Safety Switch LUT] to the [Lock] position on the active command panel and remove the key if needed to prevent anyone from restarting the system. Turn the [Laser key] on the active command panel to the « lock » position. The laser beacon light will turn GREEN and the [RED STATUS LIGHT] and the [WHITE SYSTEM STATUS LIGHT] will be FLASHING.

8. Select the “Maintenance” mode on the control unit computer.

II.1.7 Full Shutdown Procedure When  plant  operation  is  stopped  for  a  period  of  time,  it  is  recommended  to  shutdown  the  LUT  gauge  using  the  following  procedure.  

9. Turn and hold for one (1) second the [System start/stop] switch to the STOP position on the active control panel. (The yellow [Control light] is ON only for the active panel).

10. The system will then perform a controlled shutdown procedure.

WARNING

Pressing an Emergency stop buttons or turning any of the safety keys to shutdown the LUT gauge will instantly cut the power to the components. It should never be used to perform a controlled shutdown.

11. If the lasers are armed, the system will display “Stopping Lasers” and the [LASERS ARMED

LIGHT] will be FLASHING until the lasers are stopped. 12. If the lasers were armed, the system will display briefly “System Ready” and the [LASERS ARMED

LIGHT] will be OFF. 13. The system will display “Stopping System”, indicating that the system is communicating the

shutdown command to all of the hardware components of the LUT gauge. The [SYSTEM READY LIGHT] on the command panels will be FLASHING until the system is completely stopped.

14. When the system is stopped, it will display “System stopped” and the [SYSTEM READY LIGHT] on the command panels will be OFF.

15. Turn the [Safety Switch LUT] to the [Lock] position on the active command panel and remove the key if needed to prevent anyone from restarting the system. Turn the [Laser key] on the active

Page 12: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  12  of  54  

 

command panel to the « lock » position. The laser beacon light will turn GREEN and the [RED STATUS LIGHT] and the [WHITE SYSTEM STATUS LIGHT] will be FLASHING.

16. On the LUT control unit, press the “X” icon in the top right corner of the LUT engine software. Select “Power Down All LUT Hardware”.

Figure II. 1-4: Close System option menu

17. Click YES to the following prompt warning message.

Figure II. 1-5: System shutdown warning dialog box

18. Wait until the Control Unit computer is shutdown. 19. Turn the power key located on the LUT control unit to the OFF position. 20. Deactivate (OFF) the 220Vac bus in the control room of the LUT gauge inside the electrical panel.

Deactivate (OFF) the G-laser unit fan breaker, the G-laser unit breaker, the detection laser unit breaker, the detection unit breaker, the control unit breaker, the LUT inspection probe breaker, the length measuring unit breaker and the 110Vac bus breaker

21. Deactivate (OFF) the cooling unit (chiller) breaker in the control room of the LUT gauge. 22. Deactivate (OFF) the air supply unit (blower) breaker in the control room of the LUT gauge. 23. Deactivate (OFF) the main breaker on the electrical distribution unit in the control room of the LUT

gauge.

Page 13: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  13  of  54  

 

II.2 LUT gauge Software

II.2.1 Introduction The  LUT  gauge  software,  LUT  OS,  is  installed  in  the  control  unit  (LUT  Control  unit)  and  Detection  unit  (LUT  Detection  unit).  LUT  OS  has  been  designed  to  run  on  a  XP®  operating  system.  The  function  of  the  LUT  OS  is  to  provide  full  automated  control  and  data  acquisition  of  the  LUT  gauge.  All  the  programs  are  set  to  start  automatically  when  the  computers  start.  

The  LUT  OS  is  composed  of  several  independent  software  modules.  For  the  operator,  there  are  two  (3)  different  interfaces:  

1. LUT   Control   Engine:   This   is   the   main   software   component   of   the   LUT   OS   and   is   located   on   the   LUT  control  unit.  Its  function  is  to  control  the  system  operation,  maintenance,  handle  the  “Remote  Control”  and   do   the   link   between   the   LUT   gauge   and   the   plant   network   computers   (preset   and   data   logging  computers).      

2. LUT  Remote  Control:   Software   for   the  operator   to   get   the   system   status   overview,   system  messages,  data  display  and  preset  control.    

3. LUT   Remote   Viewer:   Software   for   the   operator   to   get   the   system   status   overview,   system  messages,  data  display.  The  user  can  only  visualize  the  data  with  this  software.  

All  programs  share  the  same  interface  except  for  the  four  (4)  last  tab  screens  that  are  only  available  on  the  control  unit.  

During  normal  operation  of  the  LUT  gauge,  the  “LUT  Control  Engine”,  “LUT  Remote  control”  and  “LUT  Remote  viewer”  display  the  current  status,  messages  and  data  of  the  gauge.  The  following  sections  describe  the  different  screens  of  the  LUT  Control  Engine.  

II.2.2 Computer Hardware Description The  following  sections  describe  the  different  parts  of  the  LUT  OS  computer  hardware.  

II.2.2.1 Control Unit The  main  components  of  the  LUT  software  are  installed  on  the  control  unit  of  the  LUT  gauge.  The  software  is  installed  in  the  folder  C:\LUTOS\.  The  folder  is  the  main  directory  of  the  LUT  software  on  the  control  unit  computer.  The  location  and  name  of  this  folder  should  never  be  changed  as  this  could  disable  the  LUT  gauge  operation.  The  control  engine  of  the  LUT  control  unit  computer  controls  the  Detection  unit  control  engine.      

II.2.2.2 Detection Unit Each  LUT  inspection  probe  has  its  own  control/process  computer.  This  computer  is  located  inside  the  Detection  unit.  The  detection  unit  computer  controls  the  data  acquisition,  the  detection  laser  unit,  the  generation  laser  

Page 14: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  14  of  54  

 

unit,  TWM,  and  the  LUT  inspection  probe.  The  software  is  installed  in  the  folder  C:\LUTOS\.  The  location  and  name  of  this  folder  should  never  be  changed  as  this  could  disable  the  LUT  gauge  operation.  

II.2.2.3 Remote Control Unit or Viewer The  optional  “Remote  Control”  module  of  LUT  OS  is  installed  in  the  folder  C:\LUTOS\  of  the  remote  control  computer,  located  in  the  operator  pulpit  room.  The  location  and  name  of  this  folder  should  never  be  changed  as  this  could  disable  the  LUT  gauge  operation.  

II.2.2.4 Network The  LUT  OS  makes  extensive  use  of  the  network  for  data  transfer  and  control.  The  LUT  gauge  has  its  own  internal  computer  network.  The  default  workgroup  is  [LUTGROUP].  The  LUT  network  used  the  range  of  addresses  from  192.168.1.1  to  192.168.4.255  with  subnet  mask  255.255.0.0.    

Operator  should  refrain  from  using  these  addresses  as  this  could  interfere  with  LUT  gauge  operation.  

The  LUT  system  comes  with  additional  network  adapters  that  are  configured  at  commissioning  to  connect  to  the  plant  network  system  for  data  transfer  and  for  remote  diagnostic  via  Internet.  

II.2.3 Data logging The  LUT  system  records  automatically  all  the  data  taken  by  the  system.  The  default  location  for  the  data  is  on  the  control  unit  computer:  

“D:\LUTData\”

There  are  five  (5)  default  sub-­‐folders  inside:  

1. [DataLogging]:  This  folder  contains  one  (1)  subfolder  for  each  day.  See  “Appendix  5:  Data   logging  data  file”  for  file  format  details.  

2.  [PipeLogging]:   This   folder   holds   a   log   file   of   all   the   data   taken   in   one   day.   This   file   can   be   used   to  compute  data  trends.  One  (1)  file  is  created  for  each  day  of  operation.  A  history  of  thirty  (30)  days  is  set  by   default.   This   can   be   changed   at   commissioning.   See   “Appendix   4:   Pipe   logging   data   file”   for   file  format  details.  

3.  [SavedData]:   This   folder   contains   the   saved   data   recorded   by   the   operator   during   system   operation.  One  (1)  folder  is  created  for  each  pipe  recorded.  The  data  is  reserved  for  use  by  TECNAR  personal.  

4. [TempData]:  Temporary  data  file  used  by  the  LUT  system.  This  folder  should  not  be  accessed.  

5. [ThicknessReport]:   This   folder   contains   the   reports   of   the   thickness   test   effectuated   in   maintenance  mode  in  PDF  format.  

Folder  shares  can  be  configured  at  commissioning  time  for  remote  data  access.    

Page 15: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  15  of  54  

 

II.2.4 Upper screen common part

Figure II. 2-1: LUT main screen top part

II.2.4.1 Caption bar (A1) The  caption  bar  displays  the  name  and  version  of  the  software,  the  version  and  the  current  date  and  hour.  

II.2.4.2 Control & Status bar (A2) This  part  of  the  screen  is  always  visible  and  displays  the  status  of  the  LUT  (with  LEDs)  and  two  control  buttons.    

Leds:  

• [Started]:  System  is  started(i.e.  Start  key  has  been  turn  on)  

• [Ready]:  System  is  ready  (“idle  mode”).  The  lasers  can  be  turned  on.  

• [E-­‐Stop]:   An   E-­‐stop   is   set   somewhere   on   the   system.   The   LUT   can’t   start   until   all   the   E-stops   are  pulled  off.  

• [Interlocks]:  An  interlock  is  on  somewhere  on  the  system.  The  system  can’t  operate  until  this  led  is  turn  off.  

A2  

A1  

Page 16: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  16  of  54  

 

• [Lasers  Armed]:  Lasers  are  armed  and  LUT  is  ready  to  measure  a  pipe.  

• [Measuring]:  System  is  measuring  (i.e.  Laser  are  currently  firing)  

Buttons:  

• [Stop  System]:  Stop  system  immediately  in  a  controlled  way  bypassing  the  Start/Stop  button  on  the  active  command  panel.  

• [Arm   lasers]:  Arm  Laser  button   is  only  active  when  the  system   is   ready.   It  can  be  used  to  arm  the  lasers  bypassing/replacing  the  PLC  signal   (Activate  Laser)  of  the  plant.  When  the   lasers  are  armed,  the  caption  of  the  button  becomes  “Stop  Lasers”.  At  this  moment,  the  button  can  be  used  to  stop  the  lasers  in  a  controlled  way.    

These  sections  of  the  software  are  always  visible  independently  of  which  tab  is  displayed.  It  shows  important  information  for  the  operator.    

 

Page 17: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  17  of  54  

 

II.2.5 [System Overview] Tab The  [System  Overview]  tab  displays  a  quick  overview  of  all  important  system  information  and  messages.  It  also  enables  the  operator  to  change  some  operation  mode  of  the  system.  

Figure II. 2-2: [System Overview] tab

II.2.5.1 [System Active State] panel (B1) The  [System  Active  State]  panel  (B1)  displays  the  current  state  of  operation  of  the  LUT  gauge.  The  state  message  indicates  the  current  action  being  performed  by  the  LUT  gauge.  See  Appendix  1  for  a  complete  list  and  description  of  the  states.  

II.2.5.2 [System Mode] panel (B2) The  [System  Mode]  panel  (B2)  displays  the  current  mode  of  the  system.  There  are  two  (2)  different  operation  modes.  

B2  

B1   B3  

B4  

B5  

B6   B7  

Page 18: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  18  of  54  

 

1. Automatic   Mode:   This   is   the   normal   system   operation   mode.   In   that   mode,   the   LUT   operates  automatically.   However,   some   operator   intervention   may   be   necessary   depending   of   the   preset  source.  Refer  to  the  [Pipe  Preset  Source]  panel  description  below  for  a  complete  description  of  each  different  preset  source.  

2. Maintenance   Mode:   This   mode   is   used   for   maintenance   of   the   system.   This   mode   enables   the  [Maintenance]   button   on   the   [Options   Panel].   Refer   to   the   description   of   this   panel   below   for   a  complete  description  of  the  maintenance  mode.  

II.2.5.3 [Pipe Preset Source] panel (B3) The  [Pipe  Preset  Source]  panel  (B3)  is  used  to  source  of  the  pipe  preset  information.  This  information  is  used  to  configure  the  LUT  software  for  measurement.  Two  (2)  sources  are  possible:      

1. Plant: The plant computer has to send a preset data at least 5-10 seconds before each the first pipe. The preset is valid until a new preset is received.

2. Operator: Enable the [Presets] tab. The operator has to manually enter the next pipe preset. The preset is valid until a new preset is received.

When a mode is selected, the other modes are disabled.

II.2.5.4 [Network Connections] panel (B4) The  [Network  Connections]  panel  (B4)  shows  the  actual  status  of  the  network  connections  to  the  LUT  gauge  engine.  There  are  three  (3)  different  LEDs:  

Remote  Controller:  Means  that  the  remote  software  is  connected  to  the  LUT  Control  Engine.  

Plant Computer: Means that the plant computer is connected to the LUT Control Engine

II.2.5.5 [System Messages] panel (B5) The  [System  Messages]  panel  (B5)  is  a  text  window  cumulating  the  last  one  hundred  (100)  (can  be  changed  at  commissioning  time)  system  messages  and  error  of  the  LUT  gauge.  The  messages  can  be  informative  status  messages  or  error  messages.  See  the  “Appendix  1  LUT  Errors  and  Messages”.  

The  error  messages  are  displayed  the  following  colors:  

1. Red:  Error  messages  

2. Black:  Warning  messages  

3. Blue:  Normal  messages  

In  normal  mode  the  [Messages  Details]  dialog  is  showed  on  the  right  part  of  the  [System  Messages]  panel.  This  dialog  is  used  to  get  more  information  on  the  current  message  or  error.  It  also  allows  the  operator  to  enter  some  notes  on  that  particular  message  or  error.  There  are  seven  (7)  different  fields  on  the  screen:  

1. [Timestamp]:  Gives  the  date  and  time  of  the  error  

Page 19: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  19  of  54  

 

2. [Type]:  Gives  the  type  of  message  (error,  etc)  

3. [Code]:  Gives  the  numeric  code  value  of  the  message  

4. [Message  Text]:  Gives  the  text  version  of  the  message  

5. [Extra  Information]:  Gives  any  extra  details  on  the  current  message.    

6. [Description]:  Gives  additional  description  of  the  message    

7. [User  notes]:  Field  where  the  operator  can  enter  additional  notes  or  comments  about  a  particular  message.  

 

When  the  operator  enters  new  information  in  the  [User  Notes]  field,  the  [Save  Changes]  button  becomes  enabled  and  permits  the  operator  to  save  the  new  changes.  If  the  [Close]  button  is  used,  any  change  will  be  discarded.  

Figure II. 2-3: [Message Details] dialog

II.2.5.6 [Sub-systems] panel (B6) The  [Sub-­‐systems]  panel  (B6)  gives  a  quick  overview  of  all  the  LUT  sub-­‐systems  that  are  not  included  in  the  probe:  

• [Status]  group:  

Page 20: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  20  of  54  

 

ο [Ready]   led:   Indicates   if   all   sub-­‐systems   are   ready   to   operate.   Light   green  means   that   the  sub-­‐systems  are  ready.  Dark  green  means  that  the  sub-­‐systems  are  not  ready.  

ο [Error]  led:  Indicates  if  there  is  any  error  with  the  sub-­‐systems.  Light  red  means  that  there  is  at   least   one   (1)   error   on   one   or  more   of   the   sub-­‐systems.   Dark   red  means   that   the   sub-­‐systems  are  working  well  or  that  the  status  is  not  read  yet.  

ο [Interlocks]  led:  Indicates  if  there  is  any  interlock  on  the  system,  not  related  with  the  probe  sub-­‐systems.  Light  red  means  that  there  is  at  least  one  (1)  interlock  on  the  system.  Dark  red  means  that  there  is  no  interlock  or  that  the  status  of  the  interlocks  is  not  read  yet.  

• [Blower]  group:  

ο [Fault]   led:  Indicates  if  there  is  any  error  with  the  blower.  Light  red  means  that  there  is  an  error  and  that  the  filter  needs  to  be  change.  Dark  red  means  blower  status  is  normal.    

• [Scanner]  group  (optional):  

ο [Position]   field:   Indicates   the   current   position   of   the   positioning   device   in   degrees   if  available.  

ο [Error]   led:   Indicates   if  there   is  any  error  with  the  positioning  device.  Light  red  means  that  there  is  an  error.  Dark  red  means  the  positioning  device  status  is  normal  or  that  the  status  is  not  read  yet.  

ο [Reset   Error]   button:  When   the   [Error]   led   turns   light   red,   this   button   becomes   enabled.  Pressing  this  button  will  reset  the  current  error.    

• [Length-­‐meter  Temperature]  group:  

ο [Fault]   led:   Indicates   the   length-­‐meter   box   temperature   status.   Light   red  means   that   the  length-­‐meter   box   temperature   is   too   high.   Dark   red   means   that   the   length-­‐meter   box  temperature  is  normal.  

• [Sub-­‐Systems  Details…]   button:   Open   directly   the   [Sub-­‐Systems]   tab   for  more   details   on   the   sub-­‐systems.  

Page 21: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  21  of  54  

 

Figure II. 2-4: [Sub-systems] panel

II.2.5.7 [Probe 1] panel (B7) The  [Probe  1]  panel  (B7)  shows  a  quick  overview  of  the  probe  status.    

• [Enabled] group

o [Probe]: Display the enabled state of the probe. A green check means that the probe is enabled. A red cross means that the probe is disabled.

o [Laser 1]: Display the enabled state of the generation laser 1. A green check means that the generation laser 1 is enabled. A red cross means that the generation laser 1 is disabled.

o [Laser 2]: Display the enabled state of the generation laser 2. A green check means that the generation laser 2 is enabled. A red cross means that the generation laser 2 is disabled.

• [Laser Status] group

o [Armed] Led: Indicates the “Armed” status of the probe lasers. Light red means lasers are armed. Dark red means lasers are not armed.

o [Firing] Led: Indicates the “Firing” status of the probe lasers. Light red means lasers are firing. Dark red means lasers are not firing.

o [Error] Led: Indicates an error status. Light red means lasers are in error. Dark red means lasers status is normal.

o [Reset Error] button: When the [Error] led turns light red, this button becomes enabled. Pressing this button will reset the current error.

• [Status] group:

o [Connected] Led: Indicates the probe network connection status. Light green means that the probe “Detection Engine” is remotely connected. Dark green means that the probe “Detection Engine” is not connected.

o [Ready] Led: Indicates if all the probe sub-systems are ready to operate. Light green means that the probe is ready. Dark green means that the probe is not ready.

Page 22: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  22  of  54  

 

o [Error] Led: Indicates if there is any error with the probe sub-systems. Light red means that there is at least one (1) error on one or more of the probe’s sub-systems. Dark red means that the probe sub-systems are working well or that the status is not read yet.

o [Interlocks] Led: Indicates if there is any interlock related with the probe sub-systems. Light red means that there is at least one (1) interlock on one or more of the probe’s sub-systems. Dark red means that there is no interlock or that the status of the interlocks is not read yet.

o [Temperature] Led: Indicates the probe temperature status. Light red means that the probe temperature is too high. Dark red means that the probe temperature is normal.

o [Cooling Unit] Led: Indicates the cooling unit status. Light red means that the cooling unit water temperature is too high or that the water flow is too low. Dark red means that the probe cooling group is working normally.

• [Probe Details] button: Open directly the [Probe] tab for more details on the probe status and its sub-system.

Figure II. 2-5: [Probe 1] panel

 

Page 23: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  23  of  54  

 

II.2.6 [Data Display] Tab The  [Data  Display]  tab  displays  the  last  measured  pipe  data.  The  operator  can  control  the  data  display  using  the  different  controls  on  the  screen.    

 

Figure II. 2-6: [Data Display] tab

II.2.6.1 [Pipe Information] panel (C1) The  [Pipe  Information]  panel  (C1)  displays  the  pipe  information  that  is  either  entered  by  the  operator  or  sent  by  the  plant  preset  computer.  There  are  six  (6)  different  fields:  

1. [Lot]

2. [Piece No]

3. [Alloy Code]

C1  

C2  

C3  

Page 24: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  24  of  54  

 

4. [Nominal Thickness]

5. [Nominal Diameter]

6. [Nominal Length]

7. [Nominal Temperature]

8. [position for measurement] (optional)

II.2.6.2 [Statistics] panel (C2) The  [Statistics]  panel  (C2)  displays  the  minimum,  maximum  and  average  values  of  different  configurable  measurements  of  the  displayed  pipe:  

Here  are  a  list  of  the  options  and  measurement:  

Display  Deviation  Column              

Display  Batch  Column                            

 

Display  Temperature  Statistics                          

Display  Top  Temperature  Statistics                (beginning  of  the  pipe)  

Display  Middle  Temperature  Statistics            

Display  Bottom  Temperature  Statistics          (end  of  the  pipe)  

 

Display  Cold  Thickness  Statistics                    

Display  Top  Cold  Thickness  Statistics        

Display  Middle  Cold  Thickness  Statistics    

Display  Bottom  Cold  Thickness  Statistics      

 

Display  Eccentricity  Statistics                    

Display  Top  Eccentricity  Statistics                

Display  Middle  Eccentricity  Statistics          

Display  Bottom  Eccentricity  Statistics          

Page 25: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  25  of  54  

 

 

Display  Collected  Light  Statistics                  

Display  Top  Collected  Light  Statistics          

Display  Middle  Collected  Light  Statistics    

Display  Bottom  Collected  Light  Statistics    

1. [Speed]: Speed (in meter/second) measured by the length-meter.

2. [Temperature]: Temperature (in degrees Celsius) measured by the pyrometer.

3. [Cold Thickness]: Wall thickness (in millimeter) determined by ultrasound signal and temperature.

4. [Eccentricity] (Optional): Pipe eccentricity in %. This option can be activated at commissioning time.

On  the  right  hand  side  of  the  panel,  the  operator  has  access  to  two  (2)  additional  statistics  of  the  current  pipe  and  of  the  current  batch:  

1. [Pipe Length]: Length (in meters) measured by the length-meter.

2. [Performance]: Performance of the displayed measurement. The performance led can takes three (3) different colors:

a. Green: The ultrasonic measurement was well-done.

b. Yellow: The ultrasonic measurement was valid, but with lower quality.

c. Red: The ultrasonic measurement was not valid.

The  performance  evaluation  is  done  with  several  criteria  on  the  data  acquisition  results.  

II.2.6.3 [Display Layout] panel (C5) This  panel  enables  the  operator  to  view  the  display  layout.  The  [Display]  panel  (C5)  shows  the  measurements  of  the  LUT  gauge  according  to  the  display  options.  It  is  a  real  time  viewer  of  the  last  tube  measurement.  

The  cold  thickness  profile  can  be  set  to  display  the  nominal,  minimum  and  maximum  wall  thickness  lines  depending  of  the  preset  value.  This  can  be  set  at  commissioning  time.  

Two  different  profiles  can  be  shown  on  the  display.  You  can  also  enable  the  option  to  view  the  1-­‐5  last  profiles.  Here  are  the  profile  that  you  can  get  on  the  display:  

1. Display  Mean  Thickness  Profile      

2. Display  of  the  profile              

3. Display  Eccentricity  Profile  (site  specific)                  

4. Display  Temperature  profile  

Page 26: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  26  of  54  

 

To  change  the  profile  that  are  displayed  on  the  screen  you  have  to  click  on  the  text  on  the  right  or  the  left  of  the  display  screen.    

Page 27: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  27  of  54  

 

II.2.6.3.1 [Data Display Selection] panel (C5) Three  (3)  units  for  the  X  axis  are  available:  

1. Seconds  

2. Points  

3. Meters  

The  default  options  are:  

1. Layout:  Probe  1  &  2  

2. Left  Y  Axis:  Thickness  

3. Right  Y  Axis:  Temperature  

The default display options can be configured at commissioning time.

II.2.6.3.2 [Display] panel (C5) Zoom option  

To  execute  a  zoom  action:  

• Left-­‐click   and  hold   the  mouse  button  directly   on   the   axis   you  want   to   zoom.  Be   sure   that   the  mouse  pointer  is  outside  the  grid  where  the  profiled  are  displayed.  In  other  words  click  on  where  the  number  of  the  axis  are.  

• Holding  the  mouse  button,  move  the  mouse  for  a  certain  distance  on  the  axis  you  want  to  zoom.  The  distance   that   the  mouse  will   have  been  moved  will   set   the   factor  of   the   zoom  action.   The   longer   the  distance  is,  the  higher  the  zoom/scroll  factor  will  be.  For  the  X  zoom  action,  a  left  to  right  displacement  will   do   a   positive   zoom  action.  A   right   to   left   displacement  will   do   a   negative   zoom  action.   For   the   Y  zoom  action,  a  down  to  up  displacement  will  do  a  positive  zoom  action.  An  up  to  down  displacement  will  do  a  negative  zoom/scroll  action.  

• Release  the  mouse  button  to  apply  the  new  zoom  factor.  

• Double  click  to  reset  the  display  

To  execute  a  scroll  action:  

• Left-­‐click  and  hold  the  mouse  button  directly  on  the  profile  display  in  the  grid  that  you  want  to  scroll.  Be  sure  that  the  mouse  pointer  is  inside  the  grid  and  on  the  profile  displayed.    

• If  you  left  click  between  2  profiles  you  will  scroll  both  profile.  

• Holding  the  mouse  button,  move  the  mouse  for  a  certain  distance  on  the  axis  you  want  to  scroll.  The  distance   that   the  mouse  will   have  been  moved  will   set   the   factor  of   the   scroll   action.   The   longer   the  distance  is,  the  higher  the  scroll  factor  will  be.  For  the  X  scroll  action,  a  left  to  right  displacement  will  do  a  positive  scroll  action.  A  right  to  left  displacement  will  do  a  negative  scroll  action.  For  the  Y  scroll  action,  

Page 28: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  28  of  54  

 

a  down  to  up  displacement  will  do  a  positive  zoom/scroll  action.  An  up  to  down  displacement  will  do  a  negative  scroll  action.  

• Release  the  mouse  button  to  apply  the  new  scroll  factor.  

• Double  click  to  reset  the  display  

 

II.2.7 [Presets] Tab The  [Preset]  tab  is  used  to  see  the  active  preset  and  preset  mode  and  to  manage  preset  list  for  the  “operator”  preset  mode.  The  system  operator  can  prepare  and  manage  preset  data  and  activate  them  when  needed.    

 

Figure II. 2-7: [Presets] tab

D1  

D2  

D3  

D5  D4  

Page 29: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  29  of  54  

 

II.2.7.1 [Active Preset] panel (D1) The  [Active  Preset]  panel  displays  the  active  preset  currently  in  used  for  measurement.  It  is  possible  to  manually  edit  at  all  time.The  activation  time  and  the  source  are  also  shown.  

The  second  section  show  the  plan  preset  received  from  the  process  computer.  It  cannot  be  edited.  

II.2.7.2 [Operators Presets] list (D2) The  [Available  Presets]  lists  the  available  presets  that  can  be  activated.  There  are  eleven  (11)  different  fields  needed  for  a  preset:  

1. Information:   Information   string   about   the   preset   up   to   20   characters.   This   field   can   be   used   if  additional  information  is  needed.  

2. Lot:  Lot  number  in  integer  format.  The  valid  range  is  from  0  to  4294967295.  

3. Piece:   Start   number   in   integer   format   for   the   first   pipe   in   a   batch.   The   valid   range   is   from   0   to  4294967295.  This  number  will  be  automatically  incremented  after  each  measurement.  

4. Alloy:  Material  composition  code.  This  number  is  used  to  get  the  correct  speed  of  sound  calibration  for  a  particular  alloy.  The  codes  representing  each  alloy  composition  have  to  be  set  in  the  system  at  commissioning  time.  

5. Thickness:   Nominal   wall   thickness   of   the   pipe.   Used   to   adjust   the   system   data   processing   to   get  optimal  results.  

6. Diameter:  Nominal  diameter  of  the  pipe.  Used  to  set  to  measuring  distance  of  the  system.  

7. Length:  Nominal   length  of   the  pipe.   This   value   is   used   in   case  of   failure   of   the   integrated   length-­‐meter.  

8. Speed:  Nominal  speed  of  the  pipe.  

9. Temperature:  Nominal  temperature  of  the  material.  This  number   is  used  to  calculate  the  speed  of  sound  in  the  material.    

10. Mode  (optional):  Fix  or  scan  mode  for  use  with  a  positioning  device.  

11. Angle  (optional):  Angle  of  measurement  for  use  with  a  positioning  device.  

12. Lower   thickness:   Lower   thickness   tolerance   from   the   nominal   thickness.   This   tolerance   will   be  displayed  in  the  Data  display.  

13. Upper   thickness:   Upper   thickness   tolerance   from   the   nominal   thickness.   This   tolerance   will   be  displayed  in  the  Data  display.  

14. Lower  Diameter:  Lower  Diameter  tolerance  from  the  nominal  diameter.  

15. Upper  Diameter:  Upper  Diameter  tolerance  from  the  nominal  diameter.  

16. Ovality  tolerance:  Ovality  limits  of  the  pipes  produced.  

17. Line  position:  From  1  to  3.  Use  in  the  case  the  production  line  (bottom  line)  is  moving  depending  on  the  OD  produced.  

Page 30: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  30  of  54  

 

 

The  list  is  displayed  with  different  font:  

• Active  preset  is  shown  in  bold  

• Selected  preset  is  shown  in  blue.  

• Selected  cell  that  can  be  edited  is  shown  in  light  blue.  

 

The  operator  can  effectuate  the  following  operations  on  the  preset  list:  

• Activate  a  preset:  The   [Activate]  button   (D3)   is  used   to  activate   the  selected  preset.  When  a  preset   is  activated,  it  will  be  used  for  the  next  measurement.  A  preset  can  be  activated  at  anytime.    

A  preset  can  only  be  activated  when  the  system  is  set  to  the  “Operator”  mode  

• Add  a  preset:  Use  the  [New]  button  (D4)  to  add  a  preset  at  the  end  of  the  list.  The  added  preset  will  be  copied  from  the  previous  preset  in  list.  

• Edit  a  preset:  Click  in  the  desired  cell  or  use  the  keyboard  arrows  to  bring  the  cell  selection.  The  active  preset  (shown  in  light  green)  cannot  be  edited.  

• Delete  a  preset:  [Delete]  button  (D5):  Delete  the  selected  preset  (row  shown  in  blue).  The  active  preset  cannot  be  deleted.  

 

II.2.8 [Maintenance] Tab (Control Unit only) The  [Maintenance]  tab  is  used  to  handle  system  maintenance.  It  is  only  available  in  the  “Control  Unit”  program.    The  operator  can  set  different  options  of  the  system  and  execute  some  operations  needed  with  the  system  maintenance.  

Page 31: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  31  of  54  

 

   

Figure II. 2-8: [Maintenance] tab

II.2.8.1 [Data Recording] panel (E1) The  [Data  Recording]  panel  (E1),  with  the  [Record]  button  can  be  used  to  record  up  to  5consecutive  pipes.  The  desired  pipe  number  must  be  entered  in  the  field  beside  the  button.  This  record  option  is  used  to  record  the  entire  raw  data  signal  for  diagnostic  or  calibration  purposes.  The  button  becomes  [Stop  Recording]  when  the  recording  option  is  activated.  The  button  can  be  pressed  to  stop  the  recording.  

II.2.8.2 [Laser Auto-Stop] panel (E2) The [Laser Auto-Stop] panel (E2) is used to change the maximum laser idle time. This delay is used to unarmed (stop flashing) the lasers when no pipes are coming under the LUT gauge probe. This parameter is useful to extend the flashlamps lifetime. The maximum pipe wait time parameter is used to stop firing the lasers in the case where no pipe is detected by the LUT gauge probe after the PLC signal (pipe coming) has been activated.

E1  

E2  

E3  

E4  

E5  

E7  

E8  

E6  

E9  

Page 32: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  32  of  54  

 

II.2.8.3 [Probe Activation] panel (E3) The [Probe Activation] panel (E3) is used to activate or deactivate the LUT gauge when more than one (1) gauge is present on the system. The probes that are not checked will not be in used during the LUT operation. At least one (1) probe must be active at any time.

II.2.8.4 [Scanner Maintenance] panel (E4) This panel is enabled only when the system is in maintenance mode.

The system must be started and the scanner must ready to operate to enable the controls.

Use only when the optional positioning device is installed. The [Actual Position] displays the current angular position in degrees of the positioning device.

To move the positioning device, the operator can press one of the three buttons to activate the movement.

WARNING

Always verify that the operation area is clear of any personal before enabling the positioning device. Not doing so could result in severe injury or death. Also always verify that no obstacle stands in the area of the positioning device. Any obstacle in the path could damage severely the positioning device.

II.2.8.5 [Probe Maintenance] panel (E5) The [Probe Maintenance] panel (E5) is used for all the required operation with probe maintenance. It is enabled only when the system is set to maintenance mode. The system must be in "System Ready" state to enable the controls.

II.2.8.5.1 [Probe Selection] list (E6)

The [Probe Selection] list (E6) is used to select which LUT gauge probe to use for maintenance when more than one (1) gauge is present on the system.

II.2.8.5.2 [Thickness Test] (E7)

The [Thickness Test] panel (E7) gives the operator the option to take a test measurement with the LUT gauge probe without the use of the PLC signals and the pipe detection system. The operator has to enter the material setup before executing the test:

• [Test  Material]  selection:  Shows  all  available  material  which  parameters  are  already  set   in  the  system.  Select  the  “Custom”  material  to  enter  manually  the  parameters.  

• [Custom  Test  Setup]  section:  

o Speed  of  sound:  Speed  of  sound  in  the  test  material  in  m/s.  

o Nominal  thickness:  Nominal  thickness  of  the  sample  in  mm.  

• [Start  Test]  button:  Used  to  start  the  test.  After  the  test  is  started,  this  button  becomes  the  [Stop  Test]  button  that  can  be  used  to  stop  the  test  immediately.  

Page 33: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  33  of  54  

 

• After   the   completion   of   the   test   a   PDF   file   is   generated.   The   file   can   be   found   at   this   location:  D:\LUTDATA\thicknessreport.  

II.2.8.5.3 [Laser maintenance] panel (E8)

The [Laser Maintenance] panel (E8) is used for maintenance operation on the lasers. Only one (1) laser can be use at the time. There are 2 different controls on this panel:

• [Laser  Selection]  list:  This  section  is  used  to  select  the  active  laser  on  which  the  operations  will  be  done.  There  are  3  different  choices  in  this  list:  

o [Detection Lasers]: Select to operate the command on the detection laser.

o [Generation Laser 1]: Select to operate the command on the generation laser 1.

o [Generation Laser 2]: Select to operate the command on the generation laser 2.

• [Laser  flash  count]  

o [Current  flash  count]:  Displays  the  current  flash  count  of  the  selected  laser.  

o [Reset Flash Count]: This button must be used when the selected laser flashlamps have been changed. It will reset the flashcount to 0 and assure the correct counting of the flashcount to evaluate the flashlamps life.

II.2.8.5.4 [Cold pipe thickness test] panel (E9)

The [Cold pipe thickness test] panel (E9) is used to perform a cold test on a pipe online moving exactly as a hot one.

Please contact TECNAR if you want to perform this test.

Page 34: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  34  of  54  

 

II.2.9 [Sub-Systems] Tab (Control Unit only) The  [Sub-­‐Systems]  tab  displays  the  detailed  status  of  all  the  sub-­‐systems  hardware  of  the  LUT  system.  It  is  only  available  in  the  “Control  Unit”  program.      

Figure II. 2-9: [Sub-systems] tab

The  [Sub-­‐Systems]  tab  is  a  detailed  view  of  all  the  LUT  sub-­‐systems.  

II.2.9.1 [E-Stops] panel (F1) The  [E-­‐Stops]  panel  (F1)  displays  all  the  E-­‐Stops  state  of  the  LUT  gauge.  Light  red  means  that  e-­‐stop  is  active  and  dark  red  that  the  e-­‐stop  is  not  active  or  that  its  status  is  unknown.  An  E-­‐stop  will  physically  cut  the  power  of  the  lasers,  the  length  measuring  unit  and  the  positioning  device  (option).    

F1  

F2  

F3  

F4  

F5  

F7  

F7  

F8  

F6  

Page 35: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  35  of  54  

 

II.2.9.2 [Interlocks] panel (F2) The  [Interlocks]  panel  (F2)  displays  all  the  interlocks  of  the  LUT  gauge  not  related  with  the  detection  unit.  Light  red  means  that  the  interlock  is  active  and  dark  red  that  the  interlock  is  not  active  or  that  its  status  is  unknown.    

II.2.9.3 [Blower Monitoring] panel (F3) The  [Blower  Monitoring]  panel  (F3)  shows  the  monitoring  of  the  blower’s  air  intake.  The  [Blower  Fault]  led  indicates  the  blower  monitor  status.  Light  red  means  that  the  monitor  has  detected  a  fault  and  dark  red  that  the  status  is  normal  or  unknown.    

II.2.9.4 [Plant PLC Signals] panel (F4) The  [Plant  PLC  Signals]  panel  (F4)  displays  the  PLC  signals  from  the  factory.  The  inputs  1  to  3  are  E-­‐stop  signals.  Inputs  4  to  6  are  interlock  signals.  Inputs  7  and  8  are  used  with  a  motorized  positioning  device.  The  inputs  9  and  10  are  used  in  automatic  mode  for  “Laser  On”  and  “Pipe  Coming”  signals.  Light  green  means  that  PLC  is  activated.  Dark  green  means  that  the  PLC  is  not  activated  or  that  its  status  is  unknown.  

II.2.9.5 [Length-Meter Temperature] panel (F5) The  [Length-­‐Meter  Temperature]  panel  (F5)  displays  the  temperature  inside  the  length-­‐meter  container  unit.  The  led  indicates  if  the  temperature  exceeds  the  maximum  limit  (customizable  at  commissioning).  Light  red  means  that  there  is  an  error  and  dark  red  that  the  state  is  normal  or  unknown.  

II.2.9.6 [System Monitor] panel (F6) The  [System  Monitor]  panel  (F6)  displays  the  water  temperature  and  flow  of  the  cooling  unit  and  the  temperature  inside  the  generation  unit  cabinet.  The  led  indicates  if  the  temperature  exceeds  the  maximum  limit  (customizable  at  commissioning).  Light  red  means  that  there  is  an  error  and  dark  red  that  the  state  is  normal  or  unknown.  

II.2.9.7 [Scanner] panel (F7) The  [Scanner]  panel  (F7)  displays  the  scanner  position  in  degrees  in  the  case  that  the  LUT  gauge  is  mounted  on  a  scanning  unit.  The  [Error]  led  indicates  if  there  is  an  error  with  the  scanner.  Light  red  means  that  an  error  is  signaled  and  dark  red  that  there  is  no  error.  When  an  error  happens,  the  [Reset  Error]  button  becomes  active.  It  can  be  use  to  reset  the  scanner  controller  to  try  to  clear  the  error.    

II.2.9.8 [Devices Status Overview] panel (F8) The  [Devices  Status  Overview]  panel  (F8)  displays  a  short  version  of  the  [Detailed  Devices  Status]  panel.  The  operator  can  see  in  a  glimpse  of  an  eye  when  all  the  peripheral  devices  are  ready  or  if  an  error  has  occurred.  When  the  [Details]  button  is  pressed,  the  appropriate  sub-­‐tab  window  in  the  [Detailed  Devices  Status]  panel  is  brought  to  the  front  screen.  

Page 36: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  36  of  54  

 

II.2.9.9 [Detailed Devices Status] panel (F9) The  [Detailed  Devices  Status]  panel  (F9)  displays  the  detailed  status  of  the  different  peripheral  sub-­‐systems  of  the  LUT  gauge.  The  sub-­‐system  includes:  

• The  length-­‐meter  (option),    

• The  length-­‐meter  temperature  (option),    

• the  I/O  board  control,    

• the  scanner  (option),    

• the  length-­‐meter  positioning  slide  (option),    

• the  system  monitor  (option)    

• the  Profibus  communication  system  (option).    

• Other  tab  are  available  depending  of  the  option  of  the  LUT  system.  

On  each  sub-­‐tab  of  the  [Detailed  Devices  Status]  panel,  the  operator  can  see  the  software  server  connection,  the  status  of  the  peripheral  device  and  error  text  bar  to  display  the  possible  errors.  The  operator  can  click  on  the  [History]  button  to  see  the  list  of  errors  that  occurred  with  that  device.  

Page 37: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  37  of  54  

 

II.2.10 [Probe “N”] Tab (Control Unit only) The  [Probe  “N”]  tab  displays  the  detailed  status  of  one  (1)  probe  hardware  of  the  LUT  system.  If  the  system  has  many  probes,  it  will  have  up  to  four  (4)  of  this  tab.  It  is  only  available  in  the  “Control  Unit”  program.      

Figure II. 2-10: [Probe] tab

II.2.10.1 [Probe Status] panel (G1) The  [Probe  Status]  panel  (G1)  displays  a  summary  of  the  probe  status.  There  are  four  (4)  different  fields:  

1. [Enabled] image: Indicates the “Enabled” state of the probe. A green check sign means that the probe is enabled and a red X that it is disabled.

2. [Connected] led: Indicates the connection status with the probe “Detection Engine”. Light green means that the probe is connected. Dark green means that the system is unable to connect to the probe.

3. [Powered] led: Indicates the system “Started” state. Light green means that the system is started and dark green that the system is stopped.

4. [Interlock] led: Indicates if there is any interlock local to the probe. Dark red means that there is no Interlock.

G1  

G2  

G3  

G10  

G4  

G5  

G6  

G7  

G8  

G9  

G11  

Page 38: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  38  of  54  

 

II.2.10.2 [Probe Active state] panel (G2) The  [Probe  Active  state]  panel  (G2)  displays  the  state  of  the  probe  “Detection  Engine”  software.  The  state  indicates  the  current  action  being  performed  by  the  probe.  The  following  table  describes  the  different  states.  

II.2.10.3 [Probe Messages] panel (G3) The  [Probe  Messages]  panel  (G3)  is  a  text  window  cumulating  all  the  system  messages  of  the  “LUT  Detection  Engine”.  The  messages  can  be  normal  status  messages  or  error  messages.  Please  refer  to  the  “Appendix  1:  Errors  and  Messages”  for  the  complete  list.  

II.2.10.4 [Chiller Monitor] panel (G4) The  [Chiller  Monitor]  panel  (G4)  displays  the  actual  temperature  and  flow  of  the  chiller  and  two  (2)  alarm  leds  linked  with  that  information.  Light  red  means  that  there  is  an  error  and  dark  red  that  the  state  is  normal  or  unknown.  

II.2.10.5 [G-Lasers] panel (G5) The  [G-­‐Lasers]  panel  (G5)  displays  the  error  condition  of  the  generation  lasers.  The  [Error  Condition]  led  indicates  the  error  status  of  the  G-­‐Lasers.  Light  red  means  that  there  is  an  error  and  dark  red  that  the  state  is  normal  or  unknown.  The  operator  can  reset  the  error  by  clicking  the  [Reset]  button.  

II.2.10.6 [G-lasers Usage] panel (G6) The  [G-­‐lasers  Usage]  panel  (G6)  permits  the  operator  to  choose  which  generation  laser  will  be  used  for  measurement.  Usually,  this  option  is  used  if  one  laser  is  not  operating  properly  or  if  the  system  is  in  a  maintenance  state  outside  the  LUT  probe.  In  this  case  the  LUT  gauge  will  measure  at  half  rate  instead  of  full  rate.  

II.2.10.7 [Probe Temperature] panel (G7) The  [Probe  Temperature]  panel  (G7)  displays  the  temperature  inside  the  probe.  The  [Alarm]  led  indicates  if  the  probe  temperature  exceeds  the  maximum  limit  (customizable  at  commissioning).  Light  red  means  there  is  an  error  and  dark  red  that  the  state  is  normal  or  unknown.  

II.2.10.8 [Laser Power] panel (G8) The  [Laser  Power]  panel  (G8)  displays  the  laser  power  status.  Dark  green  means  the  power  state  is  unknown,  light  that  the  power  is  normal  and  light  red  that  the  power  is  low.    

II.2.10.9 [Detection Unit Interlocks] panel (G9) The  [Detection  Unit  Interlocks]  panel  (G9)  displays  the  interlock  status  of  all  the  panels  of  the  detection  unit.  Light  red  means  that  there  is  an  interlock  detected  and  dark  red  that  the  interlock  state  is  normal  or  unknown.  

Page 39: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  39  of  54  

 

II.2.10.10 [Devices Status Overview] panel (G10) The  [Devices  Status  Overview]  panel  (G10)  displays  a  short  version  of  the  [Detailed  Devices  Status]  (G11)  panel.  The  operator  can  see  in  a  glimpse  of  an  eye  when  all  the  probe  sub-­‐systems  are  ready  or  if  an  error  has  occurred.  When  the  [Details]  button  is  pressed,  the  appropriate  sub-­‐tab  window  in  the  [Detailed  Devices  Status]  panel  is  brought  to  the  front  screen.  

II.2.10.11 [Detailed Devices Status] panel (G11) The  [Detailed  Devices  Status]  panel  (G11)  displays  the  detailed  status  of  all  the  probe  sub-­‐systems.  The  sub-­‐systems  are  both  generation  lasers,  the  detection  laser  unit,  the  ultrasound  analyzer  &  pyrometer,  the  range-­‐meter,  the  power  logger,  the  probe  temperature,  the  (TWM)  demodulation  unit,  the  IO  controller  and  the  focusing  slide  (option).  On  each  sub-­‐tab  of  the  panel,  the  operator  can  see  the  software  server  connection,  the  status  of  the  peripheral  device  and  error  text  bar  to  display  the  possible  errors.  The  operator  can  click  on  the  [History]  button  to  see  the  list  of  errors  that  occurred  with  that  particular  device.  

Page 40: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  40  of  54  

 

II.2.11 [Network] Tab (Control Unit only) The  [Network]  panel  displays  the  LUT  system  network  status  for  plant  connection.  It  is  only  available  in  the  “Control  Unit”  program.      

Figure II. 2-11: [Network] tab

II.2.11.1 [Last Preset] panel (H1) The  [Last  Preset]  panel  (H1)  indicates  the  last  pipe  parameters  and  its  time  received  from  the  plant  preset  computer.  

II.2.11.2 [Plant Preset Connection] panel (H2)

• [Network   Connection]:   Indicates   the   status   of   the   server   and   client   part   of   the   “Process   Computer”  communication.  Light  green  indicates  an  active  connection.  

• [Statistics]  section:  Indicates  statistics  with  the  “Process  Computer”  connection.  

• [Reset  Statistics]  button:  Reset  the  data  of  the  [Statistics]  section.  

H1  

H2  

H3  

H4  

Page 41: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  41  of  54  

 

II.2.11.3 [Data Logging Connection] panel (H3) • [Network  Connection]:  Indicates  the  status  of  the  server  and  client  part  of  the  “Data  Logging  Computer”  

communication.  Light  green  indicates  an  active  connection.  

• [Statistics]  section:  Indicates  statistics  with  the  “Data  Logging  Computer”  connection.  

• [Reset  Statistics]  button:  Reset  the  data  of  the  [Statistics]  section.  

II.2.11.4 [Remote & Viewer] panel (H4)

• [Remote  Connection]  led:  Light  green  indicates  that  the  “LUT  Remote  Control”  software  is  connected  to  the  “LUT  Control  Engine”.    

• [Viewer   Connection   Count]:   Indicates   how   many   “LUT   Viewer“   are   connected   to   the   “LUT   Control  Engine”  

• [Statistics]   section:   Indicates   how  many   times   the   “LUT   Remote   Control”   has   connected   to   the   “LUT  Control  Engine”.  

• [Reset  Statistics]  button:  Resets  the  data  of  the  [Statistics]  section.  

 

II.2.12 [Critical Error] Dialog  

Figure II. 2-12: [Critical Error] dialog

 

The  [Critical  Error]  dialog  will  be  displayed  if  a  critical  error  happens  on  the  system.  There  are  six  (6)  different  critical  errors:  

1. Stop  Lasers  Fire  Timeout:  An  error  happens  while  trying  to  start  the  lasers.  

Page 42: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  42  of  54  

 

2. Stop  Lasers  Timeout:  An  error  happens  while  trying  to  stop  the  lasers.  

3. Slide  movement  Timeout:  An  error  happens  while  trying  to  position  the  length-­‐meter  positioning  slide.  

4. Scanner  movement  Timeout:  An  error  happens  while  trying  to  move  the  scanner  unit.  

5. Init  data  file  timeout:  An  error  happens  while  trying  to  initialize  the  result  data  files.    

6. Close  data  file  timeout:  An  error  happens  while  trying  to  close  the  result  data  files.  

 Any  of  these  errors  will  bring  the  [Critical  Error]  dialog.  This  dialog  enables  the  operation  to  do  two  (2)  different  operations:  

1. [Reset  Error]  button:  Reset  the  error.  The  system  will  try  to  continue  its  normal  operation.  

2. [Reboot  System]  button:  If  the  [Reset  Error]  button  and  the  system  cannot  operate  correctly,  this  button  can   be   used   to   reboot   all   the   LUT   hardware   including   the   control   computer   and   probe   control  computer(s).  

Page 43: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  43  of  54  

 

Appendix 1: State message for the LUT gauge  

System State Description

Connecting Devices LUT gauge OS is attempting to connect every LUT gauge software modules and detection unit computer. There is at least one software module for each hardware component of the LUT gauge. LUT gauge OS will stay in this state until all modules are connected and operating properly.

Initializing I/O LUT gauge OS is doing input and output initialization sequence.

System Stopped LUT gauge OS is properly connected to all modules. The LUT gauge is ready to be activated (ON) and is currently in a “stop” mode.

Waiting for System Ready The LUT gauge OS has been started. LUT OS is waiting for verification of all safety interlocks and power-up of the length-meter, detection laser unit, the generation laser unit and the positioning device (optional).

Waiting Error The LUT gauge OS is scanning the system to determine the source of system errors.

Homing Scanner The LUT gauge OS is homing the positioning scanner.

System Ready The LUT gauge OS is ready for laser arming. The system’s E-stop and interlocks are all positives. The gauge is waiting for the instruction to arm the lasers.

Arming Laser The LUT gauge OS is sending the command to arm the detection laser and generation lasers to all probes. LUT OS is waiting for confirmation of the status of the lasers.

Lasers Armed The detection and generation lasers are ready to fire. The gauge is in a “laser safe” condition and laser firing is possible. The lasers are NOT firing in this state.

Positioning System The LUT gauge OS is sending a command to position the LUT probe at the focus position depending on OD value. In the case where there is a motorized positioning device, the LUT gauge OS is sending a command to place the LUT probe to its measuring position (optional).

Pipe Coming The LUT gauge OS has received « pipe coming » signal from the

Page 44: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  44  of  54  

 

plant PLC. Data acquisition is initiated in all sub-systems and probe(s) control computer.

Waiting for Pipe The LUT gauge OS is waiting for a new pipe to measure.

Measuring Pipe The LUT gauge OS has detected the presence of a pipe/tube under the LUT probe measure point and start acquiring data.

Pipe Ending The « pipe coming » signal has dropped to LOW. LUT gauge OS waits until the internal pipe detection system has detected that the pipe has left the LUT measure point.

Stopping fire and measure The LUT gauge is stopping lasers firing after the pipe has left the LUT measure point.

Processing data The LUT gauge OS has completed data acquisition for a pipe. The data is being processed, displayed, saved and transferred through the network Once those operations are done, the LUT gauge OS places the gauge in the [Lasers Armed] state.

Stopping Lasers An orderly shutdown of the LUT gauge lasers is underway.

Stopping System An orderly shutdown of the LUT gauge is underway. All electrical power will be automatically cut to the components in a few moments.

Fatal Error The LUT Control Engine was unable to start correctly. Error has to be corrected and the LUT control Engine has to be restarted.

Page 45: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  45  of  54  

 

Appendix 2: State message for the LUT probe  

System State Description

Connecting Devices LUT Detection Engine is attempting to connect every LUT probe sub-systems software modules. There is at least one software module for each hardware component of the LUT probe. LUT Detection Engine will stay in this state until all modules are connected and operating properly.

Probe Stopped LUT probe is ready to be activated (ON) and is currently in a “stop” mode.

Waiting for Probe Ready LUT probe has been started. The probe is waiting for all its sub-systems to become ready.

Probe Ready LUT probe is ready for laser arming. The probe is waiting for the instruction to arm the lasers.

Arming Laser The detection and generation lasers are being armed.

Lasers Armed The detection and generation lasers are armed.

Preparing Probe LUT probe is settings its measure position (optional).

Prepare Data Logging LUT probe is initializing data acquisition in all sub-systems

Ready to Fire LUT probe is ready to fire

Fire Laser LUT probe is actually firing its lasers

Stopping Fire LUT probe is stopping the lasers from firing

Stopping Data Logging LUT probe is stopping data logging operation

Stopping Lasers An orderly shutdown of the LUT probe lasers is underway.

Starting G-Laser Water Flow LUT probe is starting the water flow of one of its generation laser

Cycling G-Laser Water LUT probe cycling the water of one of its generation laser

Stopping G-Laser Water Flow LUT probe is stopping the water flow of one of its generation laser

Page 46: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  46  of  54  

 

Appendix 3: Errors and Messages Message

Code Message

Type Message Text Description

0 No Message or Error

No Error

1 System Message

System Stopped LUT gauge is stopped

2 System Message

System Ready to Be Started LUT system is ready to be started, all E-stop are OK and safety keys turned ON

3 System Message

Critical Error Prevents System Start

A Critical error occurs on the system: the system cannot be started until the error is cleared

4 System Message

Blower Failure Prevents System Start

The filter of the blower is blocked, clean the filter or change it to start the LUT gauge

5 System Message

E-Stop or Safety Switch Prevents System Start

An E-stop or a safety switch (key) is activated, Please correct the error to start the LUT gauge

6 System Message

Lasers Stopped on Batch End LUT gauge has stopped the lasers after receiving a "End Batch signal"

7 System Message

System Set to "Automatic" Mode

LUT gauge has been set to "Automatic Mode"

8 System Message

System Set to "Maintenance" Mode

LUT gauge has been set to "Maintenance Mode"

9 System Message

All Device Servers Connected All the LUT software server modules (sub-systems) are connected to the LUT Engine

10 System Message

System Started LUT gauge is started: all sub-systems and lasers are powered

11 System Message

Starting Manual Measurement LUT gauge is starting its measurement in manual mode (laser firing)

12 System Message

Manual Measurement Finished LUT gauge has finished its measurement in manual mode

Page 47: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  47  of  54  

 

13 System Message

System Initialization Done LUT "Control Engine" has started correctly: all parameters and required file are loaded correctly

14 System Message

Waiting for all Systems to be Connected...

LUT "Control Engine" is waiting for all the software server modules to be connected

15 System Message

System Ready LUT is powered and ready to be used. Lasers can be activated.

1001 System Error

Connection Failed One or more connection with a software server module has failed

1002 System Error

E-Stop Caused System Stop An E-stop was activated and has shutdown the system

1003 System Error

Interlock Caused System "Not Ready"

An interlock was activated and caused the LUT system to be "Not Ready"

1004 System Error

Device "Not Ready" A Software server module is not ready

1005 System Error

Unable to Change System Mode

LUT gauge was unable to change its current mode

1006 System Error

Maintenance is Required for this Operation

LUT gauge has to be in "Maintenance Mode" to perform the requested action

1007 System Error

Invalid Probe Number The selected probe number is invalid

1008 System Error

Lasers must be Stopped for this Operation

LUT gauge cannot performs the selected action while the lasers are firing

1009 System Error

Unable to Change Laser(s) Settings

LUT gauge was unable to change the laser(s) settings

1010 System Error

Invalid Laser(s) Setting The chosen setting(s) for the laser are invalid

1011 System Error

Scanner "Not Ready" for this Operation

The LUT gauge scanner cannot perform the requested operation

1012 System Error

No Pipe Detected after Pipe Signal

LUT gauge has received the "pipe is coming signal" but did not detect the pipe under the measuring position

1014 System Error

Unable to Move Scanner LUT gauge was unable to move the scanner

Page 48: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  48  of  54  

 

1015 System Error

Maximum Scanner Error reached

LUT gauge has detected an position error with the motor controller

1016 System Error

Error Moving Scanner An error happen while LUT tried to move the scanner

1017 System Error

Laser Idle Time Expired No PLC signal came from the factory after the maximum idle time period: LUT gauge has stopped the lasers

1018 System Error

Scanner not Installed The scanner option is not installed on the system. The operation cannot be completed

1019 System Error

Bad Probe Configuration Setting

An invalid probe configuration was set

1020 System Error

File Copy Error LUT gauge has got an error while trying to copy a data file

1021 System Error

Blower Fault: Please Check Blower Operation Before Restarting System

Blower Fault: The Blower filter needs to be checked

1022 System Error

Invalid Raw File Recording Setting

LUT gauge has detected an error with the RAW data acquisition settings

1023 System Error

Probe 1 Detection Engine Error

LUT "Control Engine" has detected an error with the probe 1 "Detection Engine"

1024 System Error

Probe 2 Detection Engine Error

LUT "Control Engine" has detected an error with the probe 2 "Detection Engine"

1025 System Error

Probe 3 Detection Engine Error

LUT "Control Engine" has detected an error with the probe 3 "Detection Engine"

1026 System Error

Probe 4 Detection Engine Error

LUT "Control Engine" has detected an error with the probe 4 "Detection Engine"

1027 System Error

Detection Engine not Connected

A probe "Detection Engine" is not connected to the LUT "Control Engine"

1028 System Error

Error Closing Data Files An error happen while closing the data files

1029 System Error

Error Intializating Data Files An error happen while intializating the data files

1030 System Error

Error while Stopping Laser Fire

An error happen while stopping the lasers fire

Page 49: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  49  of  54  

 

1031 System Error

Error while Stopping Lasers An error happen while stopping the lasers

1033 System Error

Stop Lasers Timeout Error A timeout error happen while stopping the lasers

1034 System Error

Stop Scanner Error An error happen while stopping the scanner

1035 System Error

Scanner Movement Error An error happen while moving the scanner

1036 System Error

Scanner Move Timeout Error A timeout error happen while starting the scanner movement

1037 System Error

Scanner Needs to be Reseted: Press "Reset" Button

An error happened during the scanner operation. The scanner needs to be reseted with the "Reset" Button

1038 System Error

Length-Meter Slide Move Timeout Error

Length-Meter Slide Move Timeout Error

1039 System Error

Unable to Move Scanner: Please Verify Scanner Contactor and Reset Error

Unable to Move Scanner: Please Verify Scanner Contactor for AC power and Reset scanner driver Error

1040 System Error

E-Stop Prevents Scanner Movement

The LUT scanner cannot move because an E-stop is activated

1041 System Error

This Operation Requires the System to be in "Ready" State

The system has to be in "Ready State" to perform the requested operation

1042 System Error

Maximum Measuring Time Expired

The maximum measure time has been reached with the current pipe: the measurement has been interrupted

1043 System Error

Arm Laser Timeout Error The maximum arm laser delay has been reached. Lasers errors should be checked

1044 System Error

Timeout During Probe Setup A timeout occurred on a multi-probe system while setting the active probe(s)

1045 System Error

Detection Laser Power Low: Flashlamp need to be Changed

The laser power output of the detection laser is too low. The flashlamp needs to be change or there is a problem with the laser

1046 System Error

Generation Laser 1 Power Low: Flashlamps need to be Changed

The laser power output of the generation laser 1 is too low. The flashlamp needs to be change or there is a problem with the laser

1047 System Generation Laser 2 Power The laser power output of the generation laser 2 is too

Page 50: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  50  of  54  

 

Error Low: Flashlamps need to be Changed

low. The flashlamp needs to be change or there is a problem with the laser

1048 System Error

Chiller Temperature Too High: Verify Chiller Operation

The water temperature of the chiller is too high. Check the LED and display status on the front of the chiller unit

1049 System Error

Chiller Water Flow Too Low: Verify Chiller Operation.

The flow of the chiller is too low. Check the LED and display status on the front of the chiller unit

1050 System Error

Generation Laser(s) Error: Verify Error Number, When Error Condition is Fixed, Use the G-Lasers "Reset Error" Button

An unexpected error occurred on a generation laser. The laser condition has to be checker and the error has to be connected. When error condition is fixed, the screen "Reset Error" button can be used to cleared the error

1051 System Error

Program Configuration File Error (*.ini)

LUT "Control Engine" has encountered an error into its configuration file ( *.ini)

1052 System Error

Device Software Not Found Cannot find the server software program file. Refer to the additional information in the "System Messages" panel

1053 System Error

Error Executing Device Software

An error occurred while starting a software server program. Refer to the additional information in the system message panel

1054 System Error

System Initialization Failed: Problem must be fixed and Program Must be Restarted

System Initialization Failed: Problem must be fixed and program must be restarted. Refer to the additional information in the "System Messages" panel

1055 System Error

Device Disconnected: Unable to Complete Operation

The device has been disconnected from the LUT "Control Engine" software: the requested operation has failed

1056 System Error

Generation Laser is Disabled The generation laser is disable and cannot be operate

1057 System Error

Probe is Disabled The probe is disabled and cannot be operate

1058 System Error

Error Setting Probe Setup An error occurred while setting the active probe configuration

1059 System Error

Measurement Failed LUT gauge measurement has failed. Refer to the additional information in the "System Messages" panel

1060 System Error

Measurement Completed with Warning(s)

LUT gauge has completed the last measurement with a warning message. Refer to the additional information in the "System Messages" panel

Page 51: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  51  of  54  

 

1061 System Error

Database Access Failed The Access to the message database has failed

1062 System Error

Alloy Code Conversion File Error

There was a problem with the Alloy code conversion file

1063 System Error

Alloy Code Not Found in Alloy Database File

The Alloy code was not found in database file

2000 Local Message

Connected to LUT Control Computer

The remote controller or viewer program has been connected to the "Control Engine" software

2001 Local Message

Disconnected from LUT Control Computer

The remote controller or viewer program was disconnected from the "Control Engine" software

3001 Local Error

Program Initialization Problem The remote controller or viewer program has detected an error during the initialization of the software

 

Page 52: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  52  of  54  

 

Appendix 4: Pipe logging data file The  pipe  logging  file  contains  the  measurement  data  for  one  (1)  day  of  operation.  One  (1)  line  is  added  for  each  new  measurement.  The  file  can  become  large  if  the  production  is  very  large  for  a  day.  

The  file  is  written  in  the  following  format:  

• Two  (2)  lines  of  heading:  

1. “Tecnar  LUT  Measurement  Log  File  version  x.x.x”  :  Display  the  version  of  the  file  to  identify  the  format  in  case  of  change.  

2. “Result   From   Computer:   LUT-­‐CTRL-­‐NNNN”:   Gives   the   name   of   the   computer   where   the   file   was  created.  

• One  (1)  line  for  the  columns  title:   “Date Time PipeInformation Lot Piece Alloy OD Nom.WT Nom.Length Nom.Speed Nom.Temp Mode Angle VeloTemp WaterFlow WaterTemp MeasureStatus TotalShots AvgGPR Length VeloStatus ScanStatus LapStatus DataValid GPR Status Shots ProcessType Avg USStatus RgmStatus PwrLogStatus AvgTemp AvgPyroCh0 AvgPyroCh1 PyroGain AvgUs Power Pump Light AvgWT AvgDistance AvgRgmChan0 AvgRgmChan1 Eccentricity DLVolts DLFC GL1Volt GL1FC GL1Energy GL1HeadTemp GL1WaterTemp GL2Volt GL2FC GL2Energy GL2HeadTemp GL2WaterTemp ProbeTemp”

• The  following  lines  are  the  results  of  the  measurement.  Here  is  an  example:  “2009-05-14 10:13:31 0041-001 70649100 1 103 0.1112 0.00360 16.14 1.90 850 FALSE 0 33.9 7.4 20.0 0 1110 83.6 16.10 0 12 12 TRUE 84 0 1110 1 1 0 0 0 721 0.17 0.19 7 0.04000 75 26 46 3.50 12.3 46 40 4.55 896 224750987 765 64083220 -1.0 0 30 750 44614555 0.0 0 33 27.9”

Page 53: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  53  of  54  

 

Appendix 5: Data logging data file The  data  logging  file  contains  a  complete  measurement  result  for  a  pipe.  One  (1)  file  is  created  for  each  measurement.    

The  file  is  written  in  the  following  format:  

-- Tecnar LUT Result File Version x.x.x -- -- System Settings -- Pipe Info 70626856 Lot No 405 Piece No 0.00390 Nominal Thickness 131 Alloy Code 0.1118 Diameter 850 Nominal Temperature 16.210 Nominal Length 1.900 Nominal Speed NO Scan Mode 0 Measure Angle 0 LUT Mode 0.000000 Laser Fire Delay YES Velocimeter Installed NO Scanner Installed 1 Number Of Probe -- Measurement Result -- 0 Processing Status 1003 Total Shots 97.1 Average GPR 0 Velocimeter Measure Status 12 Scanner Measure Status 12 LAP Measure Status -- Probe 1 Measurement Result -- YES Probe 1 Active YES Probe 1 Data Valid 0 Ultrasound & Pyrometer File Status 0 Ultrasound & Pyrometer Process Status 0 RangeMeter File Status 0 PowerLogger File Status 0 Eccentricity Process Status 0.010 Base Trigger Rate 1 Averaging Length 1 Echo Number 0.55 Minimum Correlation 0.00600 Lasers Beam Distance 7 Pyrometer Gain 717 Average Temperature 0.16 Average Signal Pyrometer Channel 1 0.15 Average Signal Pyrometer Channel 2 0.03 Average Signal Ultrasound 47.1 GPR 1003 Number of Shot -- Measurement Result Data – Shot Position Angle Temperature-1 Thickness-1 HotThickness-1 Distance-1 Light-1 Eccentricity-1 MeanThickness-1

Page 54: LUT Manual - Section II - 40101-00002-03 NEWLOGO · This!document!contains!information!considered!proprietary!and!confidential!to!Tecnar!Automation!Ltd.! 40101:00002:03!:!Rev.A! Revisiondate!:2013:01:30!

 

This  document  contains  information  considered  proprietary  and  confidential  to  Tecnar  Automation  Ltd.  40101-­‐00002-­‐03  -­‐  Rev.A   Revision  date  :  2013-­‐01-­‐30   Page  54  of  54  

 

0 0.0000 0 852 0.00000 0.00000 0.0 130.0 -1.00 0.00000 1 0.0220 0 862 0.00000 0.00000 0.0 141.0 -1.00 0.00000 2 0.0430 0 873 0.00310 0.00310 0.0 141.0 -1.00 0.00000