Light Commercial Ventilation Solutions Heat / Energy Recovery Ventilators Systemair Inc. • April, 2016 • Art. 412739 Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position. The application rendering presented in this brochure is for visual presentation purposes only. Please, contact a building professional for technical guidance. Customer Support: Canada 800.565.3548 [email protected] Send Orders: Canada 877.747.8116 [email protected] Distributed Locally by: 1250 0 SHR 14104 / SHR 14105R SHR 11004 / SHR 11005R SHR 8004 / SHR 8005R SHR 6904 / SHR 6905R 1000 1500 l/s cfm 750 500 250 0 300 50 150 600 700 450 SHR / SHR-R Series 250-1428 cfm Compact heat recovery ventilators with side connection and an aluminum heat exchanger core that transfers sensible energy between supply and exhaust air streams. All units come with low voltage control connections. Low voltage controls are sold separately. SER Series 200-1300 cfm Compact energy recovery ventilators with side connection and an energy exchanger core that transfers the heat and moisture from the supply air to the exhaust air. All units come with low voltage connections for controls that are sold separately. 1250 0 1000 1500 l/s cfm 750 500 250 0 300 50 150 600 700 450 SER 6004 SER 9504 SER 13004 Canada - Bouctouche, NB

Light Commercial Ventilation Solutions - Fantech · Light Commercial Ventilation Solutions Heat / Energy Recovery Ventilators ... incoming cooler air raising the temperature and lowering

  • Upload
    vuphuc

  • View
    229

  • Download
    1

Embed Size (px)

Citation preview

Light Commercial Ventilation SolutionsHeat / Energy Recovery Ventilators

Syst

emai

r Inc

. • A

pril,

201

6 •

Art.

412

739

Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position. The application rendering presented in this brochure is for visual presentation purposes only. Please, contact a building professional for technical guidance.

Customer Support:Canada [email protected]

Send Orders:Canada [email protected]

Distributed Locally by:

12500

SHR 14104 / SHR 14105R

SHR 11004 / SHR 11005R

SHR 8004 / SHR 8005R

SHR 6904 / SHR 6905R

1000 1500

l/s

cfm750500250

0 30050 150 600 700450

SHR / SHR-R Series 250-1428 cfm

Compact heat recovery ventilators with side connection and an aluminum heat exchanger core that transfers sensible energy between supply and exhaust air streams. All units come with low voltage control connections. Low voltage controls are sold separately.

SER Series 200-1300 cfm

Compact energy recovery ventilators with side connection and an energy exchanger core that transfers the heat and moisture from the supply air to the exhaust air. All units come with low voltage connections for controls that are sold separately.

12500 1000 1500

l/s

cfm750500250

0 30050 150 600 700450

SER 6004

SER 9504

SER 13004

Canada - Bouctouche, NB

Product Range think comfort ventilationFantech’s light commercial air handling units can be used in various applications from swimming pools and small offices to larger commercial applications. Common to all, each and every system and component has been developed with energy savings in mind. Heat exchangers, motors and fan units have all undergone extensive testing, both in the laboratory and in the field, in order to exceed current and future demands for low energy consumption.

Our products are designed for a long service life, which leads to the least amount of environmental impact over time. And, to ensure easy installation, many of our units feature control systems that are enabled for plug-and-play, i.e. simple, stress-free start-up.

Accessories

MDEHDehumidistat

RTS 3Electronic Timer

Eco-TouchTM Wall Control

EDF 1/EDF1RElectronic Control

EDF 7Electronic Dehumidistat

RTS 2Electronic Timer

IR Iris Damper

MGS Supply Grille

MGEExhaust Grille

1EFFICIENT FANS

Backward inclined motorized impellers give more airflow and better efficiency. 2ELECTRONIC

CONTROL BOARD

Superior microprocessor technology efficiently controls operation of unit. 3REVERSIBLE

DOOR PANELS

The field reversible door panel are standard on these units. Access doors can be reversed to fit requirements. 4EASE OF

MAINTENANCE

The motors and cores are mounted on a removable sliding bases for quick and easy serviceability.

Supply fan modulation defrost – 04 Models

The supply fan's speed is intermittently modulated while the exhaust fan is set to run on high speed. This allows the energy recovery core to defrost to prevent freezing.

Advantages• This is a simple and robust frost prevention system

Application noteIf you will be integrating the HRV into a central air handling unit we recommend selecting the Recirculation Defrost models since they can actively block the outdoor air port with a damper mechanism, preventing outdoor air from entering the building when not being used.

Recirculation defrost – 05R Models

When the frost conditions exist, a mechanical damper in the HRV closes the outdoor air inlet and opens a fifth duct connection. The exhaust fan shuts off while the supply fan goes on high speed. The supply fan then takes warm building air from the fifth duct connection and pulls it through the heat recovery core and delivers it back to the building. The fifth duct connection can either remain un-ducted in which case recirculation air is taken from the mechanical room where the HRV is located and used to re-energize the core. Alternatively a dedicated duct can be installed so the designer can take the recirculated air from a specific location in the building*.

Advantages• The most energy efficient and aggressive frost prevention• Ideal for higher humidity indoor conditions or colder outdoor conditions• Allows the designer to select from where recirculated air is taken• Provides a ‘recirculation’ mode that allows for the building air to be

recirculated without bringing in fresh air.

Defrost MechanismsA defrost mechanism is provided to ensure that when the outdoor air conditions are too cold, the HRV periodically re-energizes the energy exchanger

to prevent its freeze-up. When the outdoor air introduced into the HRV falls

below 23°F (-5°C), the defrost mechanism is activated and will cycle between normal operation and defrost for around 30 minutes and 5 minutes respectively,

until the outdoor air is warmer than 23°F (-5°C). Two defrost mechanisms are available on the commercial Fantech HRV.

* Recommended when HRV is used as a pre-conditioner to a central air handling unit.

SHR Series - Heat Recovery CoreThe aluminum fixed-plate, cross frow heat recovery exchanger is capable of transferring heat between airstreams. The heat recovery cores are manufactured in our facility to assure the highest level of quality.

SER Series - Energy Recovery CoreThe dense polymer membrane uses selective transfer technology to allow heat and water vapour to permeate through, while blocking contaminant compounds. The transfer is driven by temperature and humidity differentials between the airstreams.

Pool Applications SHR8005R & SHR14105RUsing a Fantech Heat Recovery Ventilator provides an economical, energy saving solution to pool ventilation and dehumidification in climates where the air is dryer outside than inside. Heat from the exhaust air is transferred to the incoming cooler air raising the temperature and lowering the load on the HVAC system. The unit is designed to reduce the occurrence of condensation in the indoor environment by first operating in the recirculation mode, moving air around the structure, keeping windows dry and eliminating troublesome cold spots, then switching to air exchange mode as needed.

Light Commercial Ventilation Solutions – HRV / ERV Ventilators Light Commercial Ventilation Solutions – HRV / ERV Ventilators Light Commercial Ventilation Solutions – HRV / ERV Ventilators