38
Liebert TVSS: The First Liebert TVSS: The First Line of Defense Line of Defense - - Product Overview Product Overview Jim Tiesi

Liebert TVSS: The First Line of Defense - Product Overvie · Liebert TVSS: The First Line of Defense - Product Overview Jim Tiesi. INTERCEPTOR ... Motorola R56 Version Hybrid Advantage

  • Upload
    vunhan

  • View
    224

  • Download
    0

Embed Size (px)

Citation preview

Liebert TVSS: The First Liebert TVSS: The First Line of Defense Line of Defense --Product OverviewProduct OverviewJim Tiesi

INTERCEPTORINTERCEPTORSURGE SUPPRESSIONSURGE SUPPRESSION

3Company ConfidentialJanuary 21, 2005

Board Meeting

True modular design

Low impedance copper conduction plates

Best in class performance

Real-time status

Built-in test capability

Stringent third party testing

Warranty: 10 year

Overall DesignOverall DesignOverall Design

4Company ConfidentialJanuary 21, 2005

Board Meeting

NEMA 4 w/status mounted behind protected window

Black, textured paint, silk-screened

Status label includes pushbutton to operate Audible, Push to Test, BIT, and Counter Reset

EnclosureEnclosureEnclosure

5Company ConfidentialJanuary 21, 2005

Board Meeting

Copper InteriorCopper InteriorCopper InteriorLow impedance copper

conduction plates

Copper back plane

Maximizes surface area

High mechanical strength

Heavy duty tin plated copper lugs

Conductor sizes to # 1/0AWG

6Company ConfidentialJanuary 21, 2005

Board Meeting

Rotary Disconnect (Fused)Rotary Disconnect (Fused)Rotary Disconnect (Fused)Lock off-able safety feature

Extremely low impedance

Heavy duty industrial quality

Tin plated copper lugs and conductor surfaces

True “through door” disconnect for NEMA 4 rating

7Company ConfidentialJanuary 21, 2005

Board Meeting

CapacitorsCapacitorsCapacitors30 microfarad total capacitance;

highest in industry

Great ring-wave attenuation

EMI / RFI filtering

–100kHz: 41 dB

–10MHz: 35 dB

–1 MHz: 31 dB

–100MHz: 53 dB

8Company ConfidentialJanuary 21, 2005

Board Meeting

Surge ModuleSurge ModuleSurge ModuleMOV

Custom, Durez coated, 25 mm MOVs

– MOV surge capability 18 kA

Array of 7 MOVs per module matchedto +/- 1 volt

Fusing

Component level, coordinated fusing

99.9% pure, silver link fuse

200 kAIC rating

individual fuse links w/ monitoring on all modes

9Company ConfidentialJanuary 21, 2005

Board Meeting

Protection RedundancyProtection RedundancyProtection Redundancy

Industry Typical Phase Conductor

NEUTRAL / GROUND

30 kA 18 kA 18 18 18 18 18 18 kA

Reality 30 kA 125 kA Reality

18 18 18 18 18 18 18 kA 18 18 18 18 18 18 18 kA

Fuse Link

MOV

WEAK

No Weak Links

10Company ConfidentialJanuary 21, 2005

Board Meeting

Surge ModuleSurge ModuleSurge ModuleSurge Ratings

80 kA, 100 kA, and 125 kA modules

Independent surge current testing by R&B Labs

Flexible per phase kA ratings from 160 kA to 1000 kA

Endurance testing / 15,000 category C3 impulses < 1.5% degradation

Approved for direct bus connections

11Company ConfidentialJanuary 21, 2005

Board Meeting

Internal and external LEDsAudible alarmForm C contactsBuilt-in-Test feature

Self check logic bussTests each fuse/MOV in every

module L-N, L-G, N-G% protection per phase

Undervoltage detectionPhase loss monitoring

Unit StatusUnit StatusUnit Status

12Company ConfidentialJanuary 21, 2005

Board Meeting

NEMA LS 1 Test PackageNEMA LS 1 Test PackageNEMA LS 1 Test PackageHigh current abnormal over-voltage test (AIC Rating)

Maximum continuous operating voltage (MCOV)

Surge current test

UL 1449 suppressed voltage rating (SVR)

Frequency response curve

UL 1449 authorization

Endurance testing

13Company ConfidentialJanuary 21, 2005

Board Meeting

SIxxxyyyYARSE

Surge Rating016 (160kA)025 (250kA)032 (320kA)040 (400kA)050 (500kA)060 (600kA)075 (750kA)

100 (1000kA)

N = Single Phase L-NL = Single Phase L-LS = Split PhaseD = 3-Phase DeltaY = 3-Phase WyeH = 3-Ph Delta Hi-leg

SourceConfiguration

ProtectionModesA = All

Connection OptionsR = With DisconnectN = Wire Lug

Voltage120208220230240277480

Monitoring OptionsS = StdC = 1 CounterD = Dual Counter

Enclosure OptionsE = NEMA 4(Std)N = Caseless

Liebert Interceptor II Series Model NumberLiebert Interceptor II Series Model Liebert Interceptor II Series Model NumberNumber

14Company ConfidentialJanuary 21, 2005

Board Meeting

UL 1449, UL 1283, CE, and CUL

UL rated 200kAIC fuse network

160 kA to 1,000 kA /Phase surge capacity

Independent Test Pkg. Nema LS1

Unmatched levels of redundancy

Summary: Liebert Interceptor II Series Summary: Liebert Interceptor II Series Summary: Liebert Interceptor II Series

Ideal protection for service entrance and distribution

15Company ConfidentialJanuary 21, 2005

Board Meeting

Protection for service entrances less than 1200 amperes and distribution

panelsUL 1449, UL 1283, OWHX and CUL Listed

ACV models offer 65 kA per mode/ 130kA/ phase surge current capacity

ACVII models offer 80 kA per mode/ 160kA/ phase surge current capacity

UL Rated 200 kAIC fuse network

NEMA LS 1

Liebert AccuVar SeriesLiebertLiebert AccuVarAccuVar SeriesSeries

16Company ConfidentialJanuary 21, 2005

Board Meeting

Life cycle rating Category C3 Impulses ACV 6,000 per mode/12,000/ phase ACVII 8,000 per mode/16,000/ phase

Compact module design - easily retrofits on panelboards

Flush mount kit

On-line monitoring in all modes

EMI/RFI filtering option

Any modes of protection available

Enclosure NEMA 4X

Warranty: 10 year

Liebert AccuVar SeriesLiebertLiebert AccuVarAccuVar SeriesSeries

17Company ConfidentialJanuary 21, 2005

Board Meeting

ACVxxxY101RKE

ACV = 65 kA ModulesACVII = 80 kA Modules

Voltage120240277208480

N = Single PhaseS = Split PhaseD = 3-Phase DeltaY = 3-Phase Wye

SourceConfiguration

Surge Protection Modes1xx = L-L or L-Nx1x = L-Gxx1 = N-GAnd Number of Modulese.g. 201

OptionsR = Red/Green LEDK = Form C ContactE = EMI Filter

Liebert AccuVar Series Model NumberLiebert Liebert AccuVarAccuVar Series Model NumberSeries Model Number

Note: Note: New RatingsNew Ratings

18Company ConfidentialJanuary 21, 2005

Board Meeting

Designed specifically for the needs of the telecommunications

industryTrue hybrid - integrates response time of SAD’s

with the high-energy capability of the Interceptor MOV design

Industry’s only Active Disconnect System Surge

Surge current ratings from 50 kA to 750 kA per phase

Liebert Interceptor Hybrid AdvantageLiebert Interceptor Hybrid AdvantageLiebert Interceptor Hybrid Advantage

19Company ConfidentialJanuary 21, 2005

Board Meeting

Interceptor Hybrid AdvantageInterceptor Hybrid AdvantageInterceptor Hybrid Advantage

Source Load

Ground Neutral

Control Circuit

Control Circuit

Current Diverter Module

Current Diverter Module

ElectronicDisconnectElectronicDisconnect

Current Diverter Module

Current Diverter Module

Current Diverter Module

Current Diverter Module

SADSAD

ImpedanceImpedance

20Company ConfidentialJanuary 21, 2005

Board Meeting

MOV & SAD Clamping Characteristics

0.0

100.0

200.0

300.0

400.0

500.0

600.0

0 2500 5000 7500 10000

Surge Current (Amperes)

Cla

mpi

ng V

olta

ge (V

olts

)

MOV

SAD

MOV & SAD CLAMPING CHARACTERISTICSMOV & SAD CLAMPING CHARACTERISTICSMOV & SAD CLAMPING CHARACTERISTICS

21Company ConfidentialJanuary 21, 2005

Board Meeting

SAD Hybrid Interceptor Surge Current Sharing DataH2120Y222R-01

0.010.020.030.040.050.060.070.080.090.0

100.0

0 5000 10000 15000 20000 25000 30000

Total Surge Current (Amperes)

Perc

enta

ge o

f Sur

ge C

urre

nt (%

)

Interceptor MOV ModuleHybrid SAD Module

Interceptor Hybrid AdvantageInterceptor Hybrid AdvantageInterceptor Hybrid Advantage

22Company ConfidentialJanuary 21, 2005

Board Meeting

All components are computer tested and matched

SAD’s within ± 1%, MOVs within 1 volt

Matched low impedance buss system for SAD and MOV modules

Primary stage joule ratings:

“H1” modules 250 joules

“H2” modules 500 joules

UL rated 200 kAIC fuse network

Options audible alarm, transient counters, test set, NEMA 3R, 4, 4X enclosures

Warranty: 10 Year

Interceptor Hybrid AdvantageInterceptor Hybrid AdvantageInterceptor Hybrid Advantage

23Company ConfidentialJanuary 21, 2005

Board Meeting

H1xxxY111R

H1 = 250 Joule SADH2 = 500 Joule SAD

Surge Current Ratings111 Series 250kA/Phase222 Series 320kA/Phase333 Series 400kA/Phase444 Series 750kA/Phase

R = With Disconnect

Voltage120240277208480

S = Split PhaseD = 3-Phase DeltaY = 3-Phase Wye

SourceConfiguration

Interceptor Hybrid Advantage Model NumberInterceptor Hybrid Advantage Model Interceptor Hybrid Advantage Model NumberNumber

24Company ConfidentialJanuary 21, 2005

Board Meeting

Motorola R56 Standards & Guidelines for Communication Sites

CompetitionTranstectorA-C DataNorthern Tech

Motorola R56 Version Interceptor & Hybrid AdvantageMotorola R56 Version Motorola R56 Version Interceptor & Hybrid AdvantageInterceptor & Hybrid Advantage

25Company ConfidentialJanuary 21, 2005

Board Meeting

Source Load

Normal Mode (L-N, L-L) Neutral

MOVCurrent Diverter

Module

MOVCurrent Diverter

Module

MotorolaInterceptor Hybrid Advantage Type 1 & 1AMotorolaMotorolaInterceptor Hybrid Advantage Type 1 & 1AInterceptor Hybrid Advantage Type 1 & 1A

SADSAD

ImpedanceImpedance

26Company ConfidentialJanuary 21, 2005

Board Meeting

Type 1A– Protection for facilities located

where the level of exposure is high

Primary SAD module: 500 J / phaseSecondary MOV module: 5000 J / phaseL-N suppression only330 volt protection levelPulse life requirements

(40) 20 kV / 10 kA(360) 6 kV / 3 kA

NEMA 4XWarranty: 10 Year

Motorola R56 Version Hybrid AdvantageMotorola R56 Version Hybrid AdvantageMotorola R56 Version Hybrid Advantage

27Company ConfidentialJanuary 21, 2005

Board Meeting

Type 2

– Protection for specific applications

MOV modules: 5000 J / phase

L-N suppression only

400 volt protection level

6 kV / 3 kA per UL 1449 Edition 2

Pulse life requirements

(400) 6 kV / 3 kA

NEMA 4X

Warranty: 10 Year

Motorola R56 Version InterceptorMotorola R56 Version InterceptorMotorola R56 Version Interceptor

28Company ConfidentialJanuary 21, 2005

Board Meeting

Transmits transients generated by lightning and switching

Minimal voltage drops

Patented coaxial cables

Minimizes inductance through a reduced coaxial aspect ratio

Extremely low impedance (2-10 Ω)

Losses are under 4.2 V / ft / kA

Especially valuable in cases where SPD cannot be installed close to the point of protection (> 5 ft)

Liebert AccuGuideLiebertLiebert AccuGuideAccuGuide

29Company ConfidentialJanuary 21, 2005

Board Meeting

JacketOuter BraidInner Braid

Primary & SecondaryInsulation

Conductor

l Conventional conductor voltage losses exceed 16V/ft/kA

l AccuGuide coax voltage losses are less than 4.2V/ft/kA

l AccuGuide provides 400% improved performance

AccuGuide Coax ConstructionAccuGuideAccuGuide Coax ConstructionCoax Construction

30Company ConfidentialJanuary 21, 2005

Board Meeting

0

500

1000

1500

2000

2500

3000

3500

0 7.5 16.5 26 33 43

Distance Feet

Cla

mpi

ng V

olta

ge

AccuGuide 3kA PerformanceAccuGuideAccuGuide 3kA Performance3kA Performance#10 AWGAccuGuide

31Company ConfidentialJanuary 21, 2005

Board Meeting

Liebert LM Series®Liebert LM SeriesLiebert LM Series®®

“Competitive Grade” product for competitor controlled specifications

Modular design

120 kA to 500 kA per phase surge current capacity

UL rated 200kAIC fuse network

All modes of protection

Internal and external LEDs, Form C Contacts, & Audible Alarm

Service entrances and distribution panel applications

32Company ConfidentialJanuary 21, 2005

Board Meeting

Liebert LM Series®Liebert LM SeriesLiebert LM Series®®

EMI / RFI filtering

Complete Testing/Certifications:

UL 1449, UL 1283, and CSA Listed

NEMA LS1 (up to LM200)

5 year parts warranty

Options: disconnect, counter, test set, enclosures - NEMA 3r, 4 & 4X

33Company ConfidentialJanuary 21, 2005

Board Meeting

LM 1 - 2 - 3 - 4 - 5- 6 - 7

1 Surge Level per Mode : 060, 080, 100, 125, 150, 200, 225, 250, 300

2 Voltage: 120, 208, 220, 230, 240, 277, 347, 480, 600

3 Phase Configuration: N (1 ph L-N), L (1 ph L-L), S (split), Y (Wye), D (Delta), H (Delta Hi-Leg), X (Wye no neutral)

4 Modes of Protection: A (All)

5 Disconnect: N (no disconnect), R (disconnect)

6 Options: S (standard: LEDs, form C, AA), C (Counter)

7 Enclosure: E (standard 12), R (3R), T (4), X (4X)

Ex: LM080120YARSEModel # designation - LM SeriesModel # designation Model # designation -- LM SeriesLM Series

34Company ConfidentialJanuary 21, 2005

Board Meeting

Liebert PowerSure Medium Exposure

Non modular TVSS

Ideal for 800 Amp panels or less

Surge Current Ratings: 100kA, 160kA

Fault tested to 65 kAICDimensions:

100kA - 6.0”x4.0”x3.0” , 160kA-8.0”x6.0”x4.0”

EMI/RFI Noise Attenuation

Status Indication: LED, Form CCertifications: UL 1449, CUL

Warranty: 5 Years

35Company ConfidentialJanuary 21, 2005

Board Meeting

LPM - 1 - 2 - 3 EX: LPM277Y160

1 - Voltage: 120, 208, 240, 277, 480

2 - Phase Configuration: N (1 ph L-N), L (1 ph L-L), S (split), Y (Wye), D (Delta), H (Delta Hi-Leg), X (Wye no neutral)

3 - Surge Capacity:

160 (160 kA per ph/ 80 kA per mode)

100-2 (100 kA L-N, N-G)

Model # designation - PowerSure Medium ExposureModel # designation Model # designation -- PowerSurePowerSure Medium Medium ExposureExposure

36Company ConfidentialJanuary 21, 2005

Board Meeting

Non modular TVSSIdeal for 400 Amp panels or less

Surge Current Ratings: 25kA, 50kA, 100kA

Fault Tested to 14 kAIC

Dimensions: 4.72”x4.72”x2.36”EMI/RFI Noise Attenuation

Status Indication: LED, Form C Contacts

Certifications: UL 1449, CUL

Warranty: 5 Years

Liebert PowerSure Low Exposure

37Company ConfidentialJanuary 21, 2005

Board Meeting

LPL - 1 - 2 - 3 Ex: LPL120S25-21 - Voltage: 120, 208, 240, 277, 480

2 - Phase Configuration: N (1 ph L-N), L (1 ph L-L), S (split), Y (Wye), D (Delta), H (Delta Hi-Leg), X (Wye no neutral)

3 - Surge Capacity:

100 (100 kA per ph/ 50 kA per mode)

50 (50 kA per ph/25 kA per mode)

25-2 (25 kA L-N, N-G)

Model # designation - PowerSure Low ExposureModel # designation Model # designation -- PowerSurePowerSure Low Low ExposureExposure

38Company ConfidentialJanuary 21, 2005

Board Meeting

l MOV / SAD Matching - Every MOV / SAD is voltage matched to allow complete current sharing

l Component Level Fusing - Every MOV/SAD is individually fused and monitored

l 200 kAIC Silver Fuse Network - Allows rated surge current to pass without fuse operation

l NEMA LS 1 complete documentation package

l Modular and non-modular devices/power, data, and telecom

l Broadest range of ratings 25 kA to 1000 kA

Why LIEBERT TVSS?Why LIEBERT TVSS?Why LIEBERT TVSS?