Upload
nur-adlina
View
222
Download
4
Embed Size (px)
Citation preview
MEC 2700: AEROSPACE ENGINEERING LAB 1
EXPERIMENT NO: 2
TITLE OF THE EXPERIMENT: HEAT PUMP
Date/ Day of Experiment: 11st April 2014 Due Date: 18th April 2014
Author’s Name:
Nur Adlina Binti Mat Nizam 1224256
Group Members:
Nur Aini Binti Zulkipli 1229182
Madihah Binti Mazlizam 1220020
Nur’Ain Binti Sapie 1229102
Name of Lecturer:
Dr Mirghani
OBJECTIVE
Water heat pump: To measure pressure and temperature in the circuit and in the
water reservoirs on the condenser side and the vaporizer side alternately. To calculate
energy taken up and released, also the volume concentration in the circuit and the
volumetric efficiency of the compressor.
Air-water heat pump: To measure vaporizer temperature and water bath temperature
on the condenser side under different operating conditions on the vaporizer side, ie.
natural air, cold blower and hot blower.
To determine the electric power consumed by the compressor and calculate the
coefficient of performance.
INTRODUCTION
There is no difference in principle between a heat pump (Figure 1) and a
refrigeration system (Figure 2). In a heat pump the heat which is rejected by the condenser
or heat exchanger is used for heating purposes. The condenser is therefore located within
the space to be heated, such as a room within a building. On the other hand, the evaporator
is located externally and draws its supply of heat from a source at a lower temperature than
that in the condenser. In practical, the heat source of heat pump is often the atmosphere,
but sometimes a river or soil is used instead. The only difference with air
conditioning/refrigeration system is that the heat pump system intended to cool a separate
source of heat and disposes the heat into the occupied area. Rating of heat pump is done by
the ratio of heat output to electrical input, which is called the Coefficient of Performance
(COP). Both of those systems can be summarized in figures below.
Figure 1- Heat Pump System Figure 2 - Air Conditioning/Refrigeration
System
CALCULATIONS
PART A: Water-water Heat Pump
1) Mass of water:
a) Condenser = 4.5L x 0.001m3 x 1000kg/m3
= 4.5kg
b) Vaporizer = 4.5L x 0.001m3 x 1000kg/m3
= 4.5kg
2) Graph of temperature vs time for all inlet and outlet.
Condenser
0 5 10 15 20 250
10
20
30
40
50
60
Temperature vs Time (Condenser)
θciθco
Time (min)
Tem
pera
ture
(o C
)
Vaporizer
0 5 10 15 20 250
5
10
15
20
25
30
Temperature vs Time (Vaporiser)
θviθvo
Time (min)
Tem
pera
ture
(o C
)
3) Calculations at t= 10mins
a) Vaporizer heat flow
Q̇o=c ∙mw ∙∆T 2
∆ t
¿4.187 kJkg ∙ K
×4.5kg× ¿¿
¿−0.345 kJs
b) Condenser heat flow
Q̇=c ∙mw ∙∆T2
∆ t
¿4.187 kJkg ∙ K
×4.5kg× (48+273)−(33+273)K
10m∈¿× 1min60 s
¿
¿0.471 kJs
c) Average compressor power, Pavg
Pavg=∑ P ∙∆ t
∑ ∆ t
¿ 2858.4W ∙min19min
¿150.44W
d) Performance at the condenser side
ε= Q̇Pavg
¿0.471 kJ
s0.150 kW
¿3.14
e) Volume flow at the vaporizer side
V̇=v ∙Q̇oh1−h3
*v=¿specific volume of the water at vaporizer
¿0.04348 m3
kg
¿0.04348 m3
kg×
0.345 kJs
406.61 kJkg
−219.03 kJkg
¿0.0800×10−3m3
s
f) Geometrical volume flow
Given
Vg = 5.08 cm3
f = 1450 min-1
V̇ g=V g ∙ f
¿5.08cm3×1450min−1× 1m3
1×106cm3×1min60 s
¿0.123×10−3m3
s
g) Volumetric efficiency of the compressor
λ= V̇V̇ g
¿0.0800×10−3 m3
s
0.123×10−3 m3
s
¿0. 650
PART B: Air-water Heat Pump
1. Graph of temperature versus time for all the results.
2. The average vaporizer temperature:
Natural air
T avg=∑T ∙∆ t
∑ ∆ t
¿ 101℃ ∙min20min
¿5.05℃ Hot blower
0 5 10 15 20 250
10
20
30
40
50
60
Temperature vs Time
natural air θ1hot blower θ1cold blower θ1
Time (min)
Tem
pera
ture
(o C
)
T avg=∑T ∙∆ t
∑ ∆ t
¿ 286℃∙min18min
¿15.89℃
Cold blower
T avg=∑T ∙∆ t
∑ ∆ t
¿ 217℃∙min20min
¿10.85℃
3. Condenser heat flow:
Natural Air
Q̇=c ∙mw ∙∆T∆ t
¿4.187 kJkg ∙ K ×4.5kg×
(32+273 )−(20+273)K20min × 1min
60 s
¿0.188 kJs
Hot blower
Q̇=c ∙mw ∙∆T∆ t
¿4.187 kJkg ∙ K ×4.5kg×
( 48+273 )−(20+273)K18min × 1min
60 s
¿0.488 kJs
Cold blower
Q̇=c ∙mw ∙∆T∆ t
¿4.187 kJkg ∙ K ×4.5kg×
( 43+273 )−(20+273)K20min × 1min
60 s
¿0.361 kJs
4. The performance:
Natural Air
ε= Q̇Pavg
¿0.188 kJ
s0.0907 kW
¿2.073
Hot blower
ε= Q̇Pavg
¿0.488 kJ
s0.133 kW
¿3.669
Cold blower
ε= Q̇Pavg
¿0.361 kJ
s0.121kW
¿2.983
DISCUSSION
Heat pump cycle is based on thermodynamic theory, which states that heat moves from
low pressure cold air to high pressure hot air. The benefit of using heat pump is its
effectiveness in heating cold air in short interval of time. The effectiveness in heating
depends on how well the heat pump transfer the hot air to cold air and the power required
to do so. The refrigeration cycle uses a fluid known as refrigerant. The purpose of using this
fluid is to transfer heat from one place to another. The refrigerant boils at much lower
temperature than water at the same pressure. The heat pump and refrigerant cycles are
through compression, condensation, evaporation and expansion. Both system can run
effectively if the temperature difference is higher and the heat lost to surrounding
considerably low.
Based on the experiment we were conducted, this experiment is divided into two parts,
part A for water-water heat pump and part B for air-water heat pump.
In part A, we used two water reservoirs, one at the condenser side while the other one at
the vaporizer side. Then, we have to record the power reading, pressure and temperature
for both sides. Based on the plotted graph, for condenser side, it shows increasing trend as
time increases while decreasing trend as time increases for vaporizer side. Next, we
calculated the vaporizer heat flow from equation Q̇o=c ∙mw ∙∆T 2
∆ t and condenser heat flow
from equation Q̇=c ∙mw ∙∆T2
∆ t. Then, the average compressor power (1), performance at the
condenser side (2), volume flow at the vaporizer side (3), geometrical volume flow (4) and
volumetric efficiency of the compressor (5) from these equations:
Pavg=∑ P ∙∆ t
∑ ∆t ---- (1) ε=
Q̇Pavg
----(2) V̇=v ∙Q̇oh1−h3
-----(3) V̇ g=V g ∙ f ----(4)λ=V̇V̇ g
----(5)
In part B, we only used one water reservoir but in three conditions, by natural air, hot
blower and cold blower. From this experiment, we obtained power reading and
temperature at the vaporizer outlet and the condenser water temperature. Then, from the
plotted graph, we can conclude that the temperature is directly proportional to time for all
conditions. As time increase, the temperature also increase. Next, we calculate the average
vaporizer temperature by using this equation T avg=∑T ∙∆ t
∑ ∆ t for all conditions. The condenser
heat flow is then calculated using the equation Q̇=c ∙mw ∙∆T∆ t and ε=
Q̇Pavg
is used to find the
performance. From the calculation, hot blower shows the highest temperature at vaporizer
outlet, condenser and performance compares to the two, which are natural air and cold
blower. This shows that when air is blown, the effect on heat pump process is less compared
to static air regardless of their hotness and coolness.
There are some errors encountered during the experiment, the first one is parallax error
during the recording of temperature from thermometer since the eyes are not in line with
the thermometer. Next, the power reader machine produce unconstant result, the value
keep on changing.
CONCLUSION
As the conclusion, the objectives of this experiment are achieved. We are able to
measure pressure and temperature in the circuit and in the water reservoirs on the
condenser side and the vaporizer side alternately and energy taken up and released, also
the volume concentration in the circuit and the volumetric efficiency of the compressor.
Next, we are also able to measure vaporizer temperature and water bath temperature on
the condenser side under different operating conditions on the vaporizer side ( natural air,
cold blower and hot blower). And lastly, the electric power consumed by the compressor
and calculate the coefficient of performance are determined from this experiment.