Display 571 Universal Display Units with Impulse Inputs 0.571.012.E90: Display with analogue output 0.571.011.E00: Display with two presets and outputs 0.571.012.E05: Display with serial interface Operation modes: Tachometer, frequency meter Counter for positions and events Baking time, processing time (reciprocal speed) Timer, stopwatch Speed display from delay between a Start and a Stop input Additional Functions: Linearization, Brightness Control, Digital Filter etc. Operating Instructions Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Display 571

Universal Display Units withImpulse Inputs

0.571.012.E90: Display with analogue output0.571.011.E00: Display with two presets and outputs0.571.012.E05: Display with serial interface

Operation modes: Tachometer, frequency meter

Counter for positions and events

Baking time, processing time (reciprocal speed)

Timer, stopwatch

Speed display from delay between a Start and a Stop input

Additional Functions: Linearization, Brightness Control, Digital Filter etc.

Operating Instructions

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 2: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Safety Instructions

This manual is an essential part of the unit and contains important hints aboutfunction, correct handling and commissioning. Non-observance can result indamage to the unit or the machine or even in injury to persons using theequipment!

The unit must only be installed, connected and activated by a qualified electrician

It is a must to observe all general and also all country-specific and application-specific safety standards

When this unit is used with applications where failure or maloperation could causedamage to a machine or hazard to the operating staff, it is indispensable to meeteffective precautions in order to avoid such consequences

Regarding installation, wiring, environmental conditions, screening of cables andearthing, you must follow the general standards of industrial automation industry

- Errors and omissions excepted –

Version: Description01/wb/sb/April 0202/wb/sb/July 03 Supplements for 571 serial interface03/wb/sb/Jan. 04 Range extensions and supplements for serial code04/wb/sb/Jan. 07 Version with 3 keys, A5 brochure08c/wb/sb/Feb.08 Corrections: Scrolling to negative values, Auto-Reset/Set08d/wb/sb/Jan.09 Correction: Decimal point with Parameter "Gain"08e/wb/Dec.11 Chapter 5 supplemented by “Response time of analogue output”09c/wb/May 12 Extended functions: Linearization, Printer Mode

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 3: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Table of Contents

1. Electrical Connections................................................................................. 4

1.1. Power supply .........................................................................................................51.2. Aux. voltage output ...............................................................................................51.3. Inputs A, B and Reset ............................................................................................51.4. Adjustable analogue output (0.571.012.E90 only) ................................................61.5. Optocoupler (transistor) outputs (0.571.011.E00 only)..........................................61.6. Serial RS232 / RS485 interface (0.571.012.E05 only)...........................................7

2. How to Operate the Keys ............................................................................ 8

3. Basic Settings............................................................................................. 9

4. Operational registers ................................................................................ 10

4.1. RPM, operation as tachometer or frequency counter .........................................104.2. Time, display of baking or processing time (reciprocal speed)...........................114.3. Timer, stopwatch.................................................................................................124.4. Count, Counter mode...........................................................................................134.5. Speed from differential time between a Start and a Stop input ........................144.6. Linearization points .............................................................................................14

5. Additional Settings for Units with Analogue Output (0.571.012.E90)........ 15

6. Additional settings for Units with Presets (0.571.011.E00) ........................ 17

7. Additional settings for Units with serial interface (0.571.012.E05) ............ 19

7.1. Printer-Mode .......................................................................................................21

8. Special Functions...................................................................................... 22

8.1. Linearization ........................................................................................................228.2. Manual Input or „Teaching“ of the Interpolation Points.....................................24

9. Set all register to “Default“ ...................................................................... 26

10. Dimensions............................................................................................... 26

11. Technical Data.......................................................................................... 27

12. Parameter List........................................................................................... 28

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 4: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

1. Electrical Connections0.571.012.E90: Display with analogue output

GN

D17

-30V

CD

IN

1 2 3 4 5 6 7 8 9 10

INPU

TA

INPU

TB

RES

ET(C

)G

ND

+24V

DC

OU

TG

ND

ANAL

OG

+/-1

0VAN

ALO

G0/

4-20

mA

ANAL

OG

PEG

ND

23

0V

AC

11

5V

AC

0V

AC

0.571.011.E00: Display with two presets and outputs

GN

D17

-30V

CD

IN

1 2 3 4 5 6 7 8 9 10

INPU

TA

INPU

TB

RES

ET(C

)G

ND

+24V

DC

OU

TC

OM

+O

UT

1O

UT

2

PEG

ND

23

0V

AC

115

VA

C

0V

AC

0.571.012.E05: Display with serial interface

GN

D17

-30V

CD

IN

1 2 3 4 5 6 7 8 9 10

INP

UT

AIN

PU

TB

RE

SE

T(C

)

+24V

DC

OU

T

TXD

/B

(-)R

XD

/A

(+)

PE

GN

D

GN

D

23

0V

AC

11

5V

AC

0V

AC

GN

D

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 5: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

1.1. Power supplyThe unit accepts DC supply from 17V to 30V when using terminals 1 and 2, and theconsumption depends on the level of the supply voltage (typical 80mA at 30V or 150mA at 17V,plus current taken from aux. output).For AC supply, terminals 0 VAC, 115 VAC or 230 VAC can be used. The total AC powerconsumption is 7.5 VA.

The diagrams show a dotted line for grounding to PE. This connection is not really necessary,neither for safety nor for EMC. However, for some applications, it can be useful to ground thecommon potential of all signal lines.

When using this earthing option, please observe:

All terminals and potentials marked “GND“ will be earthed.

Please avoid multiple earthing, e.g. when you use a DC power supplywhere the Minus is already connected to earth etc.

1.2. Aux. voltage outputTerminal 7 provides an auxiliary output of 24VDC/150mA max. for supply of sensors andencoders.

1.3. Inputs A, B and ResetIn the basic setup menu, these inputs can be configured to PNP (signal must switch to +) orto NPN (signal must switch to -). This configuration is valid for all three inputs at a time. Thefactory setting is always PNP.

Please note:

Independent of your setting, all functions of the unit are “active HIGH“and the unit triggers to positive transitions (rising edge). Because, withNPN setting, open or unused inputs are HIGH, you must tie the Reset lineto GND for operation. Otherwise, your unit will be in a continuous RESETstate and cannot work.

Where your use 2-wire NAMUR type sensors, please select NPN, connectthe negative wire of the sensor to GND and the positive wire to thecorresponding input.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 6: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Typical input circuit:

PNP

4,7k

GND GND

+24V int.

Input

4,7k

GND

Input

+24V int.NPN

Counting inputs A and B are designed for input frequencies up to 100 KHz with all countermodes, and up to 25 kHz with all other operating modes.The minimum pulse duration on the Reset input must be 500 µsec.All inputs are designed to receive impulses from an electronic impulse source. Whereexceptionally you need to use mechanical contacts, please connect an external capacitorbetween GND (-) and the corresponding input (+). With a capacity of 10 µF, the maximum inputfrequency will reduce to 20 Hz and miscounting due to contact bouncing will be eliminated.

1.4. Adjustable analogue output (0.571.012.E90 only)A voltage output is available, operating in a range of 0...+10V or –10V....+10V according tosetting. At the same time, a current output 0/4 – 20mA is available. Both outputs refer to theGND potential and the polarity changes with the sign in the display. The outputs provide a14 bits resolution and the response time to changes of the measuring value value depends onmode of operation. For details please see chapter 5.The maximum current of the voltage output is 2 mA, and the load on the current output can varybetween 0 and max. 270 Ohms.

1.5. Optocoupler (transistor) outputs (0.571.011.E00 only)The outputs provide programmable switching characteristics and are potential-free. Pleaseconnect terminal 8 (COM+) to the positive potential of the voltage you like to switch (range5V....35V). You must not exceed the maximum output current of 150mA. Where you switchinductive loads, please provide filtering of the coil by means of an external diode.

Opto Opto 33 R

(8)

(9)

(10)

Com+ (5 ... 35 V)

Output 1 (max. 150 mA)

Output 2 (max. 150 mA)33 R

Preset 2 Preset 1

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 7: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

1.6. Serial RS232 / RS485 interface (0.571.012.E05 only)Ex factory the unit is set to RS232 communication. This setting can be changed to RS485(2-wire) by means of an internal DIL switch. To access the DIL switch, you must remove thescrew terminal connectors and the backplane. Then pull the print to the rear to remove the PCBfrom the housing.

ON DIP

DIL-Switch

Removal of the back plane Location of the DIL switch

RS232:

ON

89

10RxD

TxD

GND

RS485:

ON

89

10A (+)

B (-)

GND

Warning!

Never set DIL switch positions 1 and 2 or DIL switch positions 3 and 4 to ONat the same time!

After setting the switch, shift the print carefully back to the housing, inorder not to damage the front pins for connection to the front keypad plate.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 8: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

2. How to Operate the KeysThere are three keys on the front of the unit. The left key p provides the “ENTER“ functionand the center key (SET) is used to scroll.

The right key is used for “Teaching” the interpolation points of the linearization function.Details please see chapter 8.2.

To start the menu, keep the ENTER key down for at least 3 seconds.

Use the SET key to scroll from one menu text to the next. Select the menu text byENTER . Scroll through the settings and confirm your choice by ENTER again.

Where you get to numeric entries, the low order digit will blink. Keep the SET key downto increment this digit to the figure desired. When you release the SET key, the next digit willblink for editing etc. After setting the high order digit, the low order digit will blink again andyou are free to make corrections

With registers using a sign, the most significant digit scrolls first from “0” to “9” (positivesettings) and then continues to “-1” and “-“ (negative settings).

As soon as you have set all digits to the desired value, press ENTER to store the setting.This will also change over to the next parameter text.

To exit the menu, keep again “ENTER“ down for at least 3 seconds.

When you do not touch any key for about 10 seconds, the “time-out“ routine will switch back tothe previous menu level and finally to normal display operation. All changes that have not beenconfirmed by ENTER at this time will not be saved.

All counting functions remain disabled while you are using the menu!

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 9: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

3. Basic SettingsThe subsequent settings are of unique nature and must only be made upon the very first setup.Sections 3. and 4. describe all parameters of the “display only“ and supplementary settings foroptional outputs and interfaces are explained later.

The basic setup selects the desired operation mode of the unit, the input characteristicsPNP/NPN and the desired brightness of the LED display.

To access the basic setup, press ENTER and SET at a time

for at least 3 seconds.

Menu Selection Text Description

Type Operation Mode

RPM tachometer, frequency meter (4.1)

Time baking/processing time (4.2)

Timer stopwatch

Count position or event counter (4.4)

Speed speed from differential time

Char Characteristics of input

NPN switch to “-“

PNP switch to “+“

Bright brightness of display 20%, 40%, 60%, 80%,100%

Code Code locking of the keypad

No keys enabled all the time

ALL keys disabled for all functions

P_FrEE keys disabled, except for access to Preset valuesPres 1 and Pres 2 (0.571.011.E00 only)

LrnodE Linearization Mode is only available in RPM undCount mode (Details please see chapter 8)

No The linearization is switch off.

1-9UA Linearization settings for the positive range only(negative values will appear as a mirror).

4-9UA Linearization over the full numeric range.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 10: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

4. Operational registersAfter the basic setup, you can access the operational parameters by pressing ENTER for atleast 3 seconds. You will only find the parameters that are relevant for your mode of operation.

To exit the menu, keep again ENTER down for at least 3 seconds, or just wait for the time-out.

When the code locking of the keypad has been switched on, any key access first results indisplay of

To access the settings, within 10 seconds you must now press the key sequence

otherwise the unit automatically will return to the normal display mode.

4.1. RPM, operation as tachometer or frequency counter(Input A = frequency input, Input B not in use; for exceptions please see chapter 5)

Menu Selection Text Description

Frequency Set a typical operating frequency for yourapplication. Range 1 Hz to 25 000 Hz

Display Set the value you would like to see on your displaywith above frequency at the input.

Decimalpoint

Select the desired position like shown in thedisplay

Wait Define a “waiting time“, this is the time inseconds that the unit will wait from one inputpulse to the next, before it sets the display to zero.When you enter “0“, the unit will wait forever andshow the last result until it receives the next input.

Filter Selectable average filter to suppress unstabledisplay with unsteady input frequencies.

OFF No filtering

2, 4, 8, 16 = number of floating average cycles.

Units of version 0.571.012.E90 allow displaying speed also with a sign for the direction ofrotation. See section 5.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 11: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

4.2. Time, display of baking or processing time (reciprocal speed)(Input A = frequency input, Input B not in use)

Menu Selection Text Description

Display-Format:

Select between seconds, minutes, minutes andseconds or minutes with two decimal positions.This will also automatically set your decimal pointto the proper place.

Frequency Set a typical operating frequency for yourapplication. Range 1 Hz to 25 000 Hz.

Display Set the value you would like to see on your displaywith above frequency at the input.

Wait Define a “waiting time“, this is the time inseconds that the unit will wait from one inputpulse to the next, before it sets the display to zero.When you enter “0“, the unit will wait forever andshow the last result until it receives the next input.

Filter Selectable average filter to suppress unstabledisplay with unsteady input frequencies.No filtering2, 4, 8, 16 = number of floating average cycles.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 12: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

4.3. Timer, stopwatchPlease note that open NPN inputs are always “HIGH“ and open PNP inputs are always “LOW“.

Menu Selection Text Description

Base Select the time base (resolution) for yourapplication.Milliseconds

1/100 seconds

1/10 seconds

integer seconds

minutes with two decimals

minutes with one decimal

minutes : seconds

Start High_Low: Time count active while input A isHIGH

Start_Stop Rising edge on input A starts count. Rising edgeon input B stops count

A_StSP Period time measurement. Repeating display ofthe time between two rising edges on input A

Reset: no Time count cumulates with every new start. Noautomatic Reset. Use the Reset input to set zero.

YES Every start initializes a new count starting fromzero.

Latch: no Real time display, count visible.

YES Display freezes final count result after every Stop.Timer counts in the background

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 13: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

4.4. Count, Counter mode

Menu Selection Text Description

Mode:A_Bdir

A_Bdir: Input A counts and input B selects thecounting direction (LOW = increment, HIGH =decrement)

A u B Summing mode, count = A + B

A - B Differential count A – B

A_B.1 Quadrature up/down counter A/B with single edgecount (x1)

A_B.2 Quadrature up/down counter A/B with doubleedge count (x2)

A_B.4 Quadrature up/down counter A/B with (x4) edgecount.

Factor Impulse scaling factor 0.0001 – 9.9999.Example: setting 1.2345 results in display of12 345 after 10 000 input pulses.

Set Every Reset input will set your display to the valueentered here. Range –199 999....0....999 999.

ResetN0

Select, how to set/reset the counter.no: No set/reset possible

Front Set/reset by the front SET key

Extern Set reset by remote signal to the Reset input.

Fr u E Set/reset by front SET key and external input.

Dpoint Sets your decimal point to the desired place.

The counting range of the unit is limited from -199999 to 999999. In case of

underflow or overflow the unit will display

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 14: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

4.5. Speed from differential time between a Start and a Stop inputInput A operates as a start input and input B operates as a Stop input. The differential timebetween start and stop will be converted into the speed of the passing object.

Menu Selection Text Description

Time Enter a typical delay time you expect betweenstart and stop. Range 0.001 sec to 999.999 sec.

Displ Enter the speed you would like to see in thedisplay when an object passes with above time.

Dpoint Sets your decimal point to the desired place.

Wait How long should the last result remain in thedisplay before it returns to zero? Set the desiredwaiting time. With setting “0” the display willfreeze and wait until to the next measuring cycle.

4.6. Linearization pointsThe linearization points will only appear with Operation Modes "RPM" or "Count" whenLinearization is enabled.

Menu Selection Text Description

P01_X X value of the first interpolation point.Range -199999 to 999999.

P01_Y Y value of the first interpolation point.Range -199999 to 999999.

: :: :

P16_X X value of the 16. interpolation point.Range -199999 to 999999.

P16_Y Y value of the 16. interpolation point.Range -199999 to 999999.

For more details about linearization please refer to section 8.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 15: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

5. Additional Settings for Units withAnalogue Output (0.571.012.E90)

This version uses the following additional parameters in the basic setup:

Menu Selection Text Description

A-Char Analogue Characteristics. Select between+/- 10V (positive and negative output)0...+10V (positive output only)0 - 20mA

4 - 20mA.

Offset Set this register to “0” when your output rangeshould begin at zero (or 4mA) If you desire anotherinitial output value, set this registercorrespondingly. Setting 5.000 means your outputwill start at 5 Volts instead of zero.

Gain Set the analogue stroke you desire: Setting 10.00means 10 Volts or 20 mA. Setting 2.00 reduces thestroke to 2 Volts or 4 mA.Full scale output = Offset + Gain.

Where you set the output to +/- 10 Volts, your input signals A/B must be of quadrature typewith phase displacement. The polarity of the output follows the sign in the display (operationas a counter or as a speed display with detection of direction of rotation).

Menu Selection Text Description

Anabeg In the operational menus you will find twoadditional parameters: Anabeg sets the displayvalue where the analogue output should begin andAnaend sets the display value for full scale output.Where you set Anabeg to -1500 and Anaend to2100, your output will generate the start value(like defined before) at a display of -1500 and thefull scale value at a display value of 2100.

Anaend

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 16: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Response time of the analogue output:

Operation mode Response time analogue outputTachometer, frequency meter (4.1.) 330ms at f >3Hz

1/f at f < 3HzBaking time / processing time indicator (4.2.) 330ms at f >3Hz

1/f at f < 3HzTimer, Stopwatch (4.3.) 7 ms

(With latch function after every measurement)Counter for position or event (4.4.) Counter value + 7msSpeed calculation from differential transitiontime (4.5.)

Runtime + 7ms

The analogue output behaves like the display output.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 17: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

6. Additional settings for Units with Presets(0.571.011.E00)

The basic setup menu provides the following additional parameters. Where you programimpulse outputs, the impulse duration will always be 300msec (factory adjustable only).

The settings “Char 1“ and “Char2” select the switching characteristics of output 1 andoutput 2 according to the following table.

Parameters “Hyst1” and “Hyst2” allow assigning a switching hysteresis to each of the twooutputs.

Hysteresis settings are only active with the operation modes RPM (tachometer) andTime (baking time)

The direction of operation of the hysteresis depends on the selected switching characteristics“GE” or “LE” as explained in the drawing below.

Menu Selection Text Description

GE Greater/Equal: static ”ON” signal when displayvalue is greater or equal preset.

LE Lower/Equal: static ”ON” signal when displayvalue is lower or equal preset

GE Greater/Equal: Impulse output when displayoverpasses preset

LE Lower/Equal: Impulse output when displayunderpasses preset

PresetHyst

OFF

ON

GE = Greater/Equal LE = Lower/Equal

Hinweis "Anlaufüberbrückung":Wenn Sie Preset1 in der Betriebsart RPM oder TIMEzur Überwachung eines Minimum-Wertes benutzen(Charakterist ik LE), dann arbeitet Ausgang1 mit einerautomatischen Anlaufüberbrückung und wird erst dannaktiv, wenn nach Neueinschaltung der Vorwahlwerterstmals überschritten wurde.Hint "Start-up-delay":When you use Preset1 for monitoring a minimum value(LE characteristics) with operation modes RPM or TIME,then output1 will provide an automatic start-up delay andswitch on only after the measuring value has overpassedthe preset for the first time after power up.

Hint for Start-up-delay:When you use Preset 1 with LE modeto monitor the minimum value, operationmodes RPM and TIME automaticallyprovide a start-up-delay.After power-up the output will switch ononly when the measuring value hasbeen overpassing the preset forat least one time.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 18: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Menu Selection Text Description

Res**) Impulse output and automatic Reset to zero whendisplay reaches preset 1.

Set**) Impulse output and automatic setting to preset 1when display reaches zeroSee Char 1

See Char 1

See Char 1

See Char 1

Output switches ON when display reaches thevalue of Preset 1 – Preset 2 *).Impulse output when display reaches the value ofPreset 1 – Preset 2 *)

*) Serves for generation of an anticipation signal with a fixed distance to the preset 1 signal.The anticipation automatically follows the setting of preset 1 (trailing preset).

**) Auto-Set and Auto-Reset operation will limit the counting frequency to 1 kHz

Menu Selection Text Description

Pres_1 Setting of the preset values uses the texts Pres1and Pres2 which appear first of all parameterswhen accessing the menu.

Pres_2

Indication of the switching states of the outputs1_2off During normal operation, it is possible to check for

the actual states of the outputs. To do this, pressshortly the ENTER key. For about 2 seconds, thedisplay will then show one of the adjoiningmessages.

1_2on

1 on

2on

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 19: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

7. Additional settings for Units with serial interface(0.571.012.E05)

The basic setup menu contains the main parameters of the serial interface configuration, likeBaud Rate, Data Format and Unit Number. The factory settings are shown in parenthesis

Menu Selection Text Description

S-Unit Serial Unit Number (11):You can assign any address number between 11and 99 to your unit.The address must not contain a “0“ because thesenumbers are reserved for collective addressing.

Serial data format (7 E 1):The first character indicates the number of databits. The second character specifies Parity “Even”or “Odd” or “none” and the third characterindicates the number of Stop bits.

Baud rate (9600):The following Baud rates shown beside can beselected:

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 20: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Menu Selection Text Description

S-tim Serial Timer (0.100): When the subsequentparameter is set to “Print1” or “Print2” mode, thistimer generates automatic transmission cyclesevery x.xxx seconds. The string consists of thefollowing sequence of ASCII characters: Detailsplease see chapter 7.1

Menu Selection Text Description

PC Serial mode: PC: Communication according to theDrivecom standard protocol ISO 1745*

Print1 Details see above and in chapter 7.1

Print2 Details see above and in chapter 7.1

S-Code Serial register code (101):Specifies the code number of the register thatshould appear in the data string. For readout of theactual measuring value the code number is 101,which with PC mode is represented by the ASCIIcharacters “:” and “1”

* The protocol uses the following string to request for data. The example shows how torequest unit number 11 for the content of the register with register code 101(actual display value)

EOT AD1 AD2 C1 C2 ENQ...

(04) (31) (31) (3A) (31) (05)

(EOT) (1) (1) (:) (1) (ENQ)

Hex-Code

ASCII-Code

0000 0100 0011 0001 0011 0001 0011 1010 0011 0001 0000 0101 Binary

EOT: Control character

AD1: Unit address, high byte

AD2: Unit address, low byte

C1: Register code, high byte

C2: Register code, low byte

ENQ: Control character

When in our example the measuring data xxxx would have a value of „-180“, the unit wouldrespond with the following string:

C1 C2

(3A) (31) Hex-Code

ASCII-Code

Binary

STX x x x x ETX BCC

(02) (2D) (31) (38) (30) (03)

(STX) (:) (1) (-) (1) (8) (0) (ETX)

0011 00010000 0010 0011 1010 0010 1101 0011 0001 0011 1000 0011 0000 0000 0011 0001 1100

(1C)

Leading zeros will not be transmitted.BCC represents a „Block Check Character“ which results from the Exclusive-OR of all charactersbetween C1 and ETX (inclusively).

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 21: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

With incorrect request strings, the unit only responds STX C1 C2 EOT or just NAK.

Units with serial link also allow setting or resetting the counter by serial command (similar tothe external input or front key function). To use the Reset command, you must write the data“1” to the register code “60” to activate Reset, and “0” to release the Reset command again.

The following strings show how to reset a unit with unit No. 11:

Reset ON :

Reset OFF :

7.1. Printer-ModeThe Printer Mode allows cyclic or manual activation of transmissions of the specified registerdata. The corresponding register can be specified by means of parameter „S-Code“.Another parameter named „S-mod“ allows selection between two different string types:

„S-mod“ Transmission String Type

„Print1“ Space Sign Data Linefeed

Carriagereturn

+/- X X X X X X LF CR

„Print2“ Sign Data Carriagereturn

+/- X X X X X X CR

EOT AD1 AD2 STX C1 C2 Dat ETX BCC...

(04) (31) (31) (02) (36) (30) (31) (03) (34)(EOT) (1) (1) (STX) (6) (0) (1) ETX (4)

0000 0100 0011 0001 0011 0001 0000 0010 0011 0110 0011 0000 0011 0001 0000 0 011 0011 0100

HEXASCIIBIN

EOT AD1 AD2 STX C1 C2 Dat ETX BCC...

(04) (31) (31) (02) (36) (30) (30) (03) (35)(EOT) (1) (1) (STX) (6) (0) (0) ETX (5)

0000 0100 0011 0001 0011 0001 0000 0010 0011 0110 0011 0000 0011 0000 0000 0 011 0011 0101

HEXASCIIBIN

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 22: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

The mode of activation of serial transmissions can be determined as follows:

Cyclic (timed)transmissions:

Set the Serial Timer to any value ≥ 0.010 sec.Select the desired string type by parameter "S-mod"

After exit from the menu the timed transmissions willstart automatically

Manual activation oftransmissions

Set the Serial Timer to 0.000.Select the desired string type by parameter "S-mod"

After exit from the menu a transmission can be activated at any timeby shortly pressing the ENTER key

8. Special Functions8.1. LinearizationThis function allows converting a non-linear input signal into a linear presentation or vice-versa. There are 16 interpolation points available, which can be freely arranged over the wholemeasuring range in any distance. Between two points the unit automatically will interpolatestraight lines.

It is advisable to set many points into areas with strong bending, and to use only a few pointsin areas with little bending. „Linearization Mode“ has to be set to either „1-quA“ or „4-quA“ toenable the linearization function (see subsequent drawing).

Parameters P01_x to P16_x select 16 x- coordinates, representing the display values which theunit would normally show in the display. With parameters P01_y to P16_y you can specify,which values you would like to display instead of the corresponding _x values.

This means e.g. that the unit will replace the previous P02_x value by the new P02_y value.

With respect to the consistency of the linearization, the x- registers have to use continuouslyincreasing values, e.g. the x- registers must conform to the constraintP01_X < P02_X < … < P15_X < P16_X.

Independent of the selected linearization mode, the possible setting range of all registersP01_x, P01_y,…, P16_x, P16_y is always -199999 … 999999

With measuring values lower than P01_x the display will always be P01_y

With measuring values higher than P16_x, the display will always be P16_y.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 23: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

x

y

P1(x)= 0P1(y)= 0

Linearization Mode = 1_quA

x

y

Linearization Mode = 4_quA

P1(x)= -1000P1(y)= 900

P8(x)= 0P8(y)= 750

P16(x)= +1000P16(y)= - 600

*)

P16(x)= 1000P16(y)= 800

*) Mirror of positive range

Application Example:The picture below shows a Watergate where the opening is picked up by means of anincremental encoder. We would like to display the clearance of the gate "d", but the existingencoder information is proportional to the angular information φ.

d

φ

(1-cos )φ

Incremental Encoder

d = d0Display value

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 24: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

P01

_x

P05

_x

P16

_x

P01_y

P05_y

P16_y

P03

_x

P03_y

P07_y

P07

_xEncoder Position ( )φ

Display (d)

P15_y

P15

_x

8.2. Manual Input or „Teaching“ of the Interpolation PointsInterpolation points to form the linearization curve can be entered one after each other, usingthe same procedure as for all other numeric parameters. This means you will have to enter allparameters P01_x to P16_x and P01_y to P16_y manually by keypad.

During manual input of interpolation points the unit will not examine the settingsP01_x to P16_x. Therefore the operator is responsible for observation of the constraintP01_X < P02_X < … < P15_X < P16_X.

In most cases it should however be much more convenient to use the Teach function.For this method we have to move the encoder, step by step, from one interpolation point to thenext. Every time we enter the desired display value by keypad.

How to use the Teach Function:

Please select the desired range of linearization (see chapter 3.0).

Hold down the “Cmd” key for 3 seconds, until the display shows “tEACh”. Nowthe unit has switched over to the Teach mode. To start the teach procedure please pressagain “Cmd” within the next 10 seconds. The display will then show “P01_X”.

With respect to the consistency required for linearization, all parameters from P01_X toP16_Y will first be overwritten by suitable initial values. Initial values for „P01_X“ and„P01_Y“ are -199999 and all other values will start with 999999.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 25: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Press once more “Cmd” to display the actual encoder position. Then move theencoder to the first of the desired interpolation points

When you read the x-value of your first interpolation point in the display, press “Cmd”again. This will automatically store the actual display value to the P01_x register. Forabout 1 second you will read “P01_y “ on the display, followed by the same readingagain that has been stored previously

This display value now can be edited like a regular parameter, and you can change it tothe desired P01_y value

When you read the desired P01_y value in your display, store it by pressing “Cmd”again. This will automatically cycle the display to the next interpolation point P02_x.

Once we have reached and stored the last interpolation points P16_x/y, the routine willrestart with P01_x again. You are free to double-check your settings once more or tomake corrections.

To conclude the Teach procedure, keep ENTER down for about 2 seconds. In the displayyou will read “StOP” for a short time, and then the unit returns to the normal operation.At the same time all linearization points have been finally stored.

The unit will examine the constraint valid for the x-values of interpolation points. Everyinterpolation point must be higher than its preceding point. Where this constraint isbreached, all 6 decimal points will blink automatically as a warning. Pressing the CMD keywill not store the illegal value, but result in an error text "E.r.r.-.L.O."

To exit the teach mode again, you have the following two possibilities:

1. Press the enter key for 2 seconds. On the display you will read “StOP” for a short time,and then the unit will switch back to the normal mode.

2. Just do nothing. After 10 seconds the unit will switch back to the normal modeautomatically.

In both cases the parameters of linearization P01_X to P16_Y will not change.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 26: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

9. Set all register to “Default“

At any time you can return all settings to the factory default values.

To do this:

switch power off

press the ENTER key on the front

keep ENTER down while you power up again.

This action will reset all parameters to factory default values and your ownsettings will be lost. You will have to repeat your individual setup procedure.Factory default values are shown in the subsequent parameter tables.

10. Dimensions

96,0 (3.780’’)

110,0 (4.331’’)

44,0

(1.7

32)

10,0

(.394

)

8,0

(.315

)

91,0 (3.583)

9,0 (.345) 129,0 (5.079)140,5 (5.531)

48,0

(1.8

90)

Panel cut out: 91 x 44 mm (3.583 x 1.732’’)

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 27: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

11. Technical Data

Supply voltage AC : 115/230 V (+/- 12,5 %)

Supply voltage DC : 24V (17 – 30V)

Consumption (without sensor) : 18V : 120mA, 24V : 95 mA, 30V : 80mA

AC Power : 7,5 VA

Aux. output for sensors : 24V DC, +/- 15%, 150mA ( AC + DC supply)

Inputs : 3 (PNP/NPN/Namur), A/B = Impulse, C = Reset

Input currents : 5,1 mA / 24V (Ri = 4,7 kOhms)

Input level HTL : Low: 0...3,5V, High: 9...35V

Max. input frequency : Counter modes: 100 kHzAll other operating modes: 25 kHzReset input C: 1kHz (minimum pulse duration 500 µsec)

Accuracy : +/- 1 ppm +/- 1 Digit

Analogue output : Current: 0/4...20mA (load 0 – 270 ohms)(0.571.012.E90) Voltage: 0...+/- 10V (max. 2 mA)

Resolution analogue : 14 Bits + Sign

Accuracy analogue : 0.1%

Analogue response time : Depends on mode of operation. For details please seechapter 5.

Ambient temperature : Operation: 0° - 45°C ( 32 – 113°F)Storage: -25° - +70°C (-13 – 158°F)

Housing : Norly UL94 – V-0

Display : 6 Digit, LED, high- efficiency orange, 15mm

Protection class : Front IP65, Rear IP20

Terminals : Signals max. 1.5 mm², AC power max. 2.5 mm²

Switching outputs (0.571.011.E00) : PNP, max. 35 volts, max. 150 mA

Conformity and Standards : EMC 2004/108/EC: EN 61000-6-2EN 61000-6-3

LV 2006/95/EC: EN 61010-1

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 28: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

12. Parameter ListDescription Text

Min -Value

Max -Value

Settingsbold = default

Pos. CharSer.Code

Selection

Basic settings

Operating mode tYPE 0 4 0 1 0 00 rpm1 time2 timer3 count4 speed

NPN / PNP CHAr 0 1 0 1 0 01 npn1 pnp

Brightness briGht 0 4 0 1 0 02 1001 802 603 404 20

Keypad locking Code 0 2 0 1 0 03 no1 all2 Preset free

RPM, operation as Tachometer or frequency meter

Frequency FrEqu 1 25000 1000 5 0 04

Display value diSPL 1 99999 1000 5 0 05

Decimal point dPoint 0 5 3 1 0 06 0.000

Wait time to zero WAit 0,1 99,9 1,0 3 1 07

Average filter FiLtEr 0 4 0 1 0 08 off1 22 43 84 16

Time, display of backing and processing time

Display format diSFor 0 3 0 1 0 09 sec1 min2 min-sec3 min-h

Frequency FrEqu 1 25000 100 5 0 10

Display value diSPL 1 999999 100 6 0 11

Wait time to zero WAit 0,1 99,9 5,0 3 1 12

Average filter FiLtEr 0 4 0 1 0 13 off

1 2

2 4

3 8

4 16

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 29: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Description TextMin -Value

Max -Value

Settingsbold = default

Pos. CharSer.Code

Selection

Timer, stopwatch

Resolution bASE 0 6 0 1 0 14 sec - 0001 sec - 002 sec - 03 sec4 min - 005 min - 06 hr.min.s

Start / Stop StArt 0 2 0 1 0 15 hi - lo1 st – sp2 ast - sp

Auto-Reset rESEt 0 1 0 1 0 16 no1 yes

Display latch LAtcH 0 1 0 1 0 17 no1 yes

Count, counter operation

Counter mode modE 0 5 0 1 0 18 A-B div1 A+B2 A-B3 A_B-14 A_B-25 A_B-4

Scaling factor FActor 0,0001 9,9999 1,0000 5 4 19

Set value SEt -199999 +999999 0 +/- 6 0 20

Reset / Set rESEt 0 3 0 1 0 21 no

1 Front2 E_tErn3 FruE

Decimal point dPoint 0 5 0 1 0 22

Speed from differential time

Delay time timE 1 999999 1000 6 0 23

Display with delaytime

diSPL 1 999999 1000 6 0 24

Decimal point dPoint 0 5 0 1 0 25

Wait time to zero WAit 0,0 99,9 10,0 3 1 26

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 30: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Description TextMin -Value

Max -Value

Settingsbold = default

Pos. CharSer.Code

Selection

Linearization

LinearizationMode

LrnodE 0 2 0 1 0 D2

P1(x) P01_H -199999 999999 999999 +/- 6 0 A0

P1(y) P01_Y -199999 999999 999999 +/- 6 0 A1

P2(x) P02_H -199999 999999 999999 +/- 6 0 A2

P2(y) P02_Y -199999 999999 999999 +/- 6 0 A3

P3(x) P03_H -199999 999999 999999 +/- 6 0 A4

P3(y) P03_Y -199999 999999 999999 +/- 6 0 A5

P4(x) P04_H -199999 999999 999999 +/- 6 0 A6

P4(y) P04_Y -199999 999999 999999 +/- 6 0 A7

P5(x) P05_H -199999 999999 999999 +/- 6 0 A8

P5(y) P05_Y -199999 999999 999999 +/- 6 0 A9

P6(x) P06_H -199999 999999 999999 +/- 6 0 B0

P6(y) P06_Y -199999 999999 999999 +/- 6 0 B1

P7(x) P07_H -199999 999999 999999 +/- 6 0 B2

P7(y) P07_Y -199999 999999 999999 +/- 6 0 B3

P8(x) P08_H -199999 999999 999999 +/- 6 0 B4

P8(y) P08_Y -199999 999999 999999 +/- 6 0 B5

P9(x) P09_H -199999 999999 999999 +/- 6 0 B6

P9(y) P09_Y -199999 999999 999999 +/- 6 0 B7

P10(x) P10_H -199999 999999 999999 +/- 6 0 B8

P10(y) P10_Y -199999 999999 999999 +/- 6 0 B9

P11(x) P11_H -199999 999999 999999 +/- 6 0 C0

P11(y) P11_Y -199999 999999 999999 +/- 6 0 C1

P12(x) P12_H -199999 999999 999999 +/- 6 0 C2

P12(y) P12_Y -199999 999999 999999 +/- 6 0 C3

P13(x) P13_H -199999 999999 999999 +/- 6 0 C4

P13(y) P13_Y -199999 999999 999999 +/- 6 0 C5

P14(x) P14_H -199999 999999 999999 +/- 6 0 C6

P14(y) P14_Y -199999 999999 999999 +/- 6 0 C7

P15(x) P15_H -199999 999999 999999 +/- 6 0 C8

P15(y) P15_Y -199999 999999 999999 +/- 6 0 C9

P16(x) P16_H -199999 999999 999999 +/- 6 0 D0

P16(y) P16_Y -199999 999999 999999 +/- 6 0 D1

Appears only with modes "RPM" and "Count" when the linearization function has been enabled

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 31: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Description TextMin -Value

Max -Value

Settingsbold = default

Pos. CharSer.Code

Selection

Presets (0.571.011.E00)

Preset 1 PrES 1 -199999 +999999 10000 +/- 6 0 27

Preset 2 PrES 2 -199999 +999999 5000 +/- 6 0 28

Mode Preset 1 CHAr 1 0 0 0 1 0 29 GE

1 LE2 GE3 LE

4 RES5 SET

Mode Preset 2 CHAr 2 0 5 0 1 0 30 GE1 LE2 GE

3 LE4 1-25 1-2

Hysteresis 1 HYSt1 0 99999 0 5 0 31

Hysteresis 2 HYSt2 0 99999 0 5 0 32

Analogue output (0.571.012.E90)

Analogue begin An-bEG" -199999 999999 0 +/-6 0 33

Analogue end An-End -199999 999999 10000 +/-6 0 34

Analogue mode A-CHAr 0 3 0 1 0 35 10 V1 0 ... 10V2 0 ... 20 mA3 4 ... 20 mA

Offset OFFSEt -9,999 9,999 0,000 +/- 4 3 36

Gain GAin 00,00 99,99 10,00 4 2 37

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Page 32: Kuebler 571 LED Multifunction Preset Counter Operating ...The right key is used for “Teaching” the interpolation points of the linearization function. Details please see chapter

Description TextMin -Value

Max -Value

Settingsbold = default

Pos. CharSer.Code

Selection

Serial interface (0.571.012.E05)

Serial format S-Form 0 9 0 1 0 92 0 = 7E11 1 = 7E22 2 = 7013 3 = 7024 4 = 7N015 5 = 7N026 6 = 8E17 7 = 8018 8 = 8N019 9 = 8N02

Baud rate S-bAUd 0 6 0 1 0 91 0 = 96001 1 = 48502 2 = 24003 3 = 12004 4 = 6005 5 = 192006 6 = 38400

Unit address S-Unit 0 99 11 2 0 90

Serial timer S-tim 10 9999 100 4 3 38

Serial mode S-mod 0 1 0 1 0 39 0 = PC1 1 = print

Code for print S-CodE 100 120 101 3 0 40