John Rodkey, MA HI Lic.727, ASHI Gold Certified 250412, US Gov. E-Quip Favorable
JM Rodkey, Co., InspectionsHome Inspection Report
Cover Page
Renovated Victorian from the 1890's, Northampton MA, 01060Inspection prepared for:
Inspection Date: 5/25/2011 Time: 12:30pm-2:30om Age: Abt. 1900 Size: 3,070 sq.ft
Weather: 81 degrees, clear, previous day rain
SAMPLE REPORT of a RENOVATED VICTORIAN
Inspector: John RodkeyAmherst, MA
Phone: 413-259-6969Email: [email protected]
www.JMRodkey.com
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 1 of 38
OBJECTIVES and METHODS of INSPECTION The home inspection is conducted to give you an objective profile of the property as to the best of our ability, and withinthe Massachusetts Standards of Practice for Home Inspections. For a good understanding, you should read the entirereport, including the written material, maintenance suggestions and comments on each page. It is expected that you willevaluate the information based herein based on your specific situation and needs, and make decisions accordingly. The information in this report is based on the visual inspection of the property on the day of the inspection as allowed bythe Standards of Practice of Massachusetts home inspections. This is a visual, non destructive investigation. Homes arecomplex constructions with infinite variables that can and will affect its performance in ways we cannot predict. However,we expect this report to give you a profile of its behavior based on the visual inspection, There is no destructive probing or dismantling of any components or systems. We cannot see through walls, enter crawlspaces, attics or other areas that are not designed for safe passage. We cannot fully determine how the property, itssystems or components will respond in all situations. The inspection cannot predict the future life expectancy, or suddenfailure of any components. The inspection is not an insurance policy, a home warranty or guarantee of performance. Be aware that this is not an assessment of building or electrical codes. Each municipality establishes their own buildingcodes. These entities should be consulted if there is a questions of code compliance. We are not responsible for repairsnecessary to bring a building into compliance with local building codes. This report does not guarantee the absence of wood boring insects. It is a visual, non destructive investigation forevidence of past or present wood boring insect activity. We are not responsible for insect damage that was concealed ornot accessible at the time of the inspection. No evaluation will be made regarding air, soil, lead, water, asbestos, formaldehyde, lead paint, molds, radon, pipingoutside the foundation or gas fittings or regulators. Only those components specifically mentioned in this report have been inspected and any other components notinspected are not part of this report and as such we make no statement regarding the condition of these inspected areas. You should evaluate and act on any comments before continuing with the purchase and sale of the property. This report is exclusive to you and is not transferable. JM Rodkey, Co. will retain the report if the inspection fee has not been paid at the time of the inspection or otherarrangements for payment have not been agreed upon. Legend:S = Component use is consistent with its original purpose but may show signs of normal wear or deterioration.A= May require replacement or repair within a few yearsU= Component requires repair now.NA = Does not apply to this inspectionH= Component is not visible using reasonable effort. Basis of inspection:This report is based on observations of the condition of the inspected building and components at the listed date andtime of the inspection. JM Rodkey, Co or Friendly Inspection Services does not give any warranty or guaranty. Thisreport is made using the best of our ability and judgment. Recommended action:All categories listed as “U” should be evaluated by trades people, repaired, or acted upon before the completion of thesale.
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 2 of 38
Roof
.
1. Roof ConditionS A U N/A H
XType of Roof: Gable • SpireMaterials: Slate shingles
• Visual/Binocular inspection from ground• Debris should be removed from roof
Debris should be removed from roof Debris should be removed from roof
2. Chimney ConditionS A U N/A H
XType: BrickVisual/binocular inspection from ground
3. Roof PenetrationsS A U N/A H
XType: Chimney • Plumbing vent • SkylightVisual/Binocular inspection from the ground
• Skylight viewed from inside as well.
4. Roof FlashingS A U N/A H
XAreas Flashed: Chimney, Plumbing stack, SkylightObservations:• Visual/binocular inspection from ground• Irregular installation of wall flashing above porch. Customarily flashing is tucked under theshingles.• Consult a roofing contractor
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 3 of 38
Exterior Areas
Irregular installation of wall flashing above porch.
5. SkylightsS A U N/A H
X
6. Gutters/DownspoutS A U N/A H
XGutter type: Galvanized
• Bent creating inverted slope
Bent creating inverted slope
1. Siding ConditionS A U N/A H
XSiding type: Wood clapboard • Wood shakes
• Missing sections• Consult a licensed contractor
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 4 of 38
Missing sections
2. WallsS A U N/A H
XObservations:• Appear true and plumb
3. Eaves & FaciaS A U N/A H
X
4. SoffitsS A U N/A H
X
5. Corner Boards and TrimS A U N/A H
X
6. PaintS A U N/A H
XBlistered
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 5 of 38
Blistered
7. Exterior FaucetsS A U N/A H
XFreeze-resistant faucet observed; remove hose in winter to facilitate proper drainage.
Freeze-resistant faucet observed
8. Exterior ElectricalS A U N/A H
X
9. Exterior LightingS A U N/A H
X
10. Entryway Doors & WindowsS A U N/A H
X
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 6 of 38
11. Stairs and railingsS A U N/A H
XLocation & type:• Front of house has concrete steps• Front of house has wooden steps• Rear of house has wood steps• Side of house has wooden steps
• Not child safe, should have proper railings• Concrete steps are damaged and missing part of the tread. Use caution.• Consult a licensed contractor
Concrete steps are damaged and missing part of the tread. Use caution.
12. Window wellsS A U N/A H
XType: Metal
13. Bulkhead HatchS A U N/A H
XWater is penetrating bulkhead
Water is penetrating bulkhead
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 7 of 38
Grounds
14. Exhaust VentsS A U N/A H
XMaterials: Bathroom vent • Dryer vent • Furnace vent • Kitchen vent • Ait intake vent
1. Driveway / walkwayS A U N/A H
XDriveway: AsphaltWalkways: Brick, Concrete
• Walkway somewhat uneven in area.
Walkway somewhat uneven in area.
2. Retaining wallsS A U N/A H
XType: ConcreteDamaged • Cracks observed • Leaning retaining wall • Consult a licensed contractor
Damaged
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 8 of 38
Decks and Porches
3. GradingS A U N/A H
X
4. PlantingsS A U N/A H
XObservations:• Clearance should be provided between plantings and house
Clearance should be provided between plantings and house
5. PatioS A U N/A H
XType: Patio block, Gravel
1. Deck/porch LocationLocation: Front of house • Left side of house • Rear of house
2. DeckingS A U N/A H
XMaterials: Wood
3. FramingS A U N/A H
XMaterials: Pressure Treated Wood
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 9 of 38
Image of front porch construction
4. PostsS A U N/A H
XMaterials: Pressure treated wood • Steel
5. Connection to StructureS A U N/A H
XMaterials: Nails • Lag Screws
6. Stairs and RailingsS A U N/A H
X • Railing/guardrails low. Customary for the period of the home.• Stair stringers are in contact with soil. This will shorten the useful life of the stairs.• No railing system on side and rear deck.• Earth in contact with wood. Recommend clearing dirt away.
Railing/guardrails low. Customary for the period of thehome.
No railing system on rear deck.
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 10 of 38
Balconies
Garage Detatched
Earth in contact with wood. Recommend clearing dirt away. No railing system on side deck.
1. Balcony LocationLocation: Front of house
2. DeckingS A U N/A H
XMaterials: Wood
3. FramingS A U N/A H
XObservations:• Unable to determine method of expelling water from the balcony. There were severalmethods used in this period to move the water off balconies without a visual interferencewith the design of the home. Which, if any, are employed here could not be determined.
1. Garage typeType of garage: Detached
2. Roof ConditionS A U N/A H
XMaterials: Asphalt shingles
3. Siding ConditionS A U N/A H
XSiding type: Wood clapboard
• Deteriorated corner board.• Earth in contact with siding or trim. Recommend clearing away.
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 11 of 38
Earth in contact with siding or trim. Recommend clearingaway.
Deteriorated corner board.
Earth (gravel) in contact with siding.
4. Foundation & floorS A U N/A H
XFoundation wall type: Concrete
5. SillsS A U N/A H
XWood sills
6. Walls, ceilings / firewallsS A U N/A H
XType: Wood frame walls
7. Garage WindowS A U N/A H Type: Double hung
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 12 of 38
Basement/Foundation
8. ElectricalS A U N/A H
XUnprotected electrical wiring. • Consult a licensed electrician
Unprotected electrical wiring.
9. Garage doors & openerS A U N/A H
XType of door: Automatic door opener present, Manual doors presentNo controls available to inspect the automatic door opener. • Manual door operated fine. •No eye beam system present • Consult with home owner for proper operation.
No controls available to inspect the automatic door opener.
10. Rafters & CeilingS A U N/A H
X
1. Foundation wallsS A U N/A H
XType of foundation: Brick, Stone
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 13 of 38
2. Basement floorS A U N/A H
XFloor type: Concrete
• Hole in floor• Unfinished at water service closet
3. Basement windowsS A U N/A H
X • Hopper
4. ColumnsS A U N/A H
XType: Brick
5. GirdersS A U N/A H
XType: Wood
6. SillsS A U N/A H
XType of sills: Wood
• Mostly hidden by insulation
7. Floor joistsS A U N/A H
XType of joists: Wood
• Cut floor joist to accomodate drain pipe. Questionable support post has been connectedbeneath it. Consult with a licensed contractor and/or structural engineer for the suitability ofthis arrangement.
Cut floor joist to accomodate drain pipe. Questionable support post has been connected beneath it. Consult with alicensed contractor and/or structural engineer for the suitability of this arrangement.
8. SubfloorS A U N/A H
XType of subfloor: Wood boards
• Sign of previous water damage
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 14 of 38
9. Interior chimneyS A U N/A H
XChimney type: Brick
10. Bulkhead Foundation & DoorS A U N/A H
X • signs of moisture penetration
11. Water Penetration and DampnessS A U N/A H
XWater Penetration? Yes • Current water penetration observedEffloresence? YesObservations:• Efflorescence is usually an indicator of moisture penetration• Basement was damp at time of inspection• Evidence of active water penetration• Evidence of previous water penetration
Evidence of active water penetration
12. Sump Pump and DehumidifierS A U N/A H
XSump Pump Present? NoDehumidifier Present? Yes
13. MoldS A U N/A H
XPresence of Mold? Organic-like growth observedObservations:• Mold-like growth observed on ceiling tiles in unfinished front room.• Recommend that mold and air quality be evaluated by a professional
14. ElectricalS A U N/A H
X • Open electrical box• Unsecured wires in contact with furnace exhaust duct.• Hot & neutral reversed• Unsecured electrical box• Consult a licensed electrician
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 15 of 38
Utility Shut-offs
Open electrical box Unsecured wires in contact with furnace exhaust duct.
Unsecured electrical box Hot & neutral reversed
15. Unfinished Area InsulationS A U N/A H
XUninsulated against conditioned space
It is helpful to know where the shut-off are for all utilities so you can quickly cut power, water or fuel at its source if aproblem develops.
1. Electrical Shut-offS A U N/A H
XLocation: At electrical service panel
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 16 of 38
Insulation
Electric shut off for main and sub panels
2. Water Shut-offS A U N/A H
XLocation: At water meter
Water shut off
3. Fuel Shut-offS A U N/A H
XLocation: At gas meter
While insulation levels have no immediate health and safety effects, it will impact the cost and comfort of a home.Missing or ineffective air/vapor barriers and ventilation do effect health and safety by governing the building’s ability toget rid of moisture without damaging the structure. .
1. Attic InsulationS A U N/A H
XType: Blown cellulose insulation • Fiberglass batts • Polyisocyanurate Foam BoardThickness and Vapor Barrier: Vapor retarder present against conditioned surface • 10"Observations:• Unable to observe or determine insulation above ceilings.• Mostly hidden by interior finish
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 17 of 38
Electrical Service
2. Basement Area InsulationS A U N/A H
XType: None
• Rim joist bays have fiberglass insulation
3. Wall InsulationS A U N/A H
XType: Blown cellulose
• Hidden; unable to inspect.• Indications of blown wall insulation is seen in the attic behind the 3rd floor bath, and in thejoist bays in the basement. The completeness and R-value can not be determined.
Indications of blown wall insulation in the joist bays in the basement.
1. Service Entry CableS A U N/A H
XType of Service:• Overhead service• Inspected overhead wire, weatherhead, drip loop and meter boxType of Cable: Multi-strand aluminumObservations:• Corrosion inhibitor observed at service panel connection
2. Main Service PanelS A U N/A H
XCapacity: 200 amp • 120 / 240 voltLocation:• Basement
• Aluminum cable rated panel
3. Main Panel Breakers/FusesS A U N/A H
XType: Circuit breakersAmperage: 15 Amp, 20 Amp, 50 Amp, 100 amp, GFCI
• Aluminum wire rated
4. Main Panel Number of Breakers/fusesS A U N/A H
X28 breakers
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 18 of 38
Heat/AC
5. Main Panel Branch Circuit WiringS A U N/A H
XConductor materials: BX • NMWiring type: Copper: solid • Copper: Multi-strand • Aluminum: Multi-strandCorrosion inhibitor observed
6. Sub-PanelS A U N/A H
XLocation: AtticCapacity: 100 Amps • 110/220 volts • Sub-panel disconnect at main panel
• Aluminum wire rated• Corrosion inhibitor observed• Multi-strand aluminum
7. Sub-Panel Breakers/fusesS A U N/A H
XType: BreakersRatings: 15 amp • 20 amp
8. Sub-Panel Number of Breakers10
9. System GroundS A U N/A H
X
1. Heating systemS A U N/A H
XHeating system type: Gas fired hot water boiler was tested satisfactorilyDistribution method: Black iron pipe, Copper piping
• The distribution pipes from an old steam system have been incorporated into the currentsystem.
2. Flue Pipe and DamperS A U N/A H
X • "Z" type flue pipe• Vented through the wall.
3. OtherS A U N/A H
XObservations:• Gas line improperly supported.
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 19 of 38
Plumbing
Water Heater
Gas line improperly supported.
1. Water Supply PipingS A U N/A H
XWater Supply: Copper water serviceType of Branch Pipe: Copper
2. Waste Pipe and VentS A U N/A H
XWaste Pipe: Copper • Cast Iron • PlasticVent Pipe: Cast IronObservations:• Improperly pitched waste pipe
Improperly pitched waste pipe
1. MakeMake: HydroJet
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 20 of 38
Fireplaces/Alt Fuel
Interior Spaces
2. Water CapacityRated capacity: 50 Gallons
3. Water HeaterS A U N/A H
XType: Indirect firedLocation: Basement
4. T&P Valve and Vacuum BreakerS A U N/A H
X • T & P valve and vacuum breaker observed in place
5. Heater EnclosureS A U N/A H
X
6. Discharge PipeS A U N/A H
XType: Copper
1. FireplaceS A U N/A H
XType: Masonry • MetalObservations:• Recommend a chimney sweep clean and inspect the chimney before using.• Creosote flakes falling from damper.
2. Fireplace Vent, Flue, ChimneyS A U N/A H
XMaterials: Consult a chimney technician and/or a chimney cleaner before using.Observations:• Visual inspection only
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 21 of 38
Kitchen
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. ElectricalS A U N/A H
X
8. Exterior doorS A U N/A H
X
9. Basement stairsS A U N/A H
X • Narrow
10. Stairs & HandrailS A U N/A H
X
11. Smoke DetectorsS A U N/A H
XSmoke and carbon monoxide detectors will be inspected by fire dept. prior to transfer ofproperty
12. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 22 of 38
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. Water temperatureS A U N/A H
XWater temperature: 135 degrees
8. Sink observationsS A U N/A H
X
9. PlumbingS A U N/A H
X
10. CountersS A U N/A H
X
11. CabinetsS A U N/A H
X
12. ElectricalS A U N/A H
XLoose receptacle
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 23 of 38
Loose receptacle
13. GFCIS A U N/A H
X • GFCI resets for located in the electric service panel
14. HVACS A U N/A H
XHeat source: Radiator
15. Cook top conditionS A U N/A H
X
16. Oven & RangeS A U N/A H
X
17. Vent ConditionS A U N/A H
XType: None
18. DishwasherS A U N/A H
XDrain loop needs to be elevated to counter height • Consult a licensed plumber
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 24 of 38
Living Room
Drain loop needs to be elevated to counter height
19. Garbage grinderS A U N/A H
X
20. RefrigeratorS A U N/A H
X
21. Exterior doorS A U N/A H
X
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 25 of 38
Dining Room
Family Room
5. DoorsS A U N/A H
X
6. ElectricalS A U N/A H
X
7. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ElectricalS A U N/A H
X
7. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 26 of 38
1st Floor Bath
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
5. ElectricalS A U N/A H
X
6. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Tile
4. Window ConditionS A U N/A H
XType of window: Double hung • Stationary
5. DoorsS A U N/A H
X
6. SinksS A U N/A H
XWater temperature: 139 degrees
• Recommend lowering temperature for safety and economy
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 27 of 38
2nd Floor Bath
7. PlumbingS A U N/A H
X
8. CountersS A U N/A H
X
9. CabinetsS A U N/A H
X
10. Tub / ShowerS A U N/A H
XWater temperature: 139 degrees
• Temperature at tub / shower should not excceed 111 degrees• Consult a licensed plumber to balance the water temperature in the home
11. Shower wallsS A U N/A H
XType: Tile tub walls
12. ToiletsS A U N/A H
X
13. ElectricalS A U N/A H
X
14. GFCIS A U N/A H
X
15. Exhaust FanS A U N/A H
X
16. HVACS A U N/A H
X
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 28 of 38
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Tile
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. SinksS A U N/A H
XWater temperature: 138 degrees
• Recommend lowering temperature for safety reasons
7. PlumbingS A U N/A H
X
8. CountersS A U N/A H
X
9. CabinetsS A U N/A H
X
10. Tub / ShowerS A U N/A H
XWater temperature: 138 degrees
• Temperature at tub / shower should not excceed 111 degrees• Consult a licensed plumber to balance the water temperature in the home
11. Shower wallsS A U N/A H
XType: Tile tub walls
12. ToiletsS A U N/A H
X
13. ElectricalS A U N/A H
X
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 29 of 38
3rd Floor Bath
14. GFCIS A U N/A H
X
15. Exhaust FanS A U N/A H
X
16. HVACS A U N/A H
X
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Tile
4. Window ConditionS A U N/A H
XType of window: None
5. DoorsS A U N/A H
X
6. SinksS A U N/A H
XWater temperature: 115 degreesRecommend lowering temperature for safety reasons
7. PlumbingS A U N/A H
X
8. CountersS A U N/A H
X
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 30 of 38
9. CabinetsS A U N/A H
X
10. Tub / ShowerS A U N/A H
XWater temperature: 115 degreesTemperature at tub / shower should not excceed 111 degrees • Consult a licensed plumberto balance the water temperature in the home
11. Shower wallsS A U N/A H
XType: Tile shower walls
12. EnclosureS A U N/A H
X
13. ToiletsS A U N/A H
XMissing closet bolt covers
Missing closet bolt covers
14. ElectricalS A U N/A H
X
15. Exhaust FanS A U N/A H
X
16. HVACS A U N/A H
XHeat source: Electric wall heater
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 31 of 38
2nd Floor Front Bedroom
2nd Floor Rear Bedroom
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. ElectricalS A U N/A H
X
8. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 32 of 38
2nd Floor Left Middle Bedroom
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. ElectricalS A U N/A H
X
8. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 33 of 38
2nd Floor Right Middle Bedroom
3rd Floor Front Bedroom
7. ElectricalS A U N/A H
X
8. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Wood
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. ElectricalS A U N/A H
X
8. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 34 of 38
3rd Floor Rear Bedroom
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Carpet
4. Window ConditionS A U N/A H
XType of window: Double hung
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. ElectricalS A U N/A H
X
8. HVACS A U N/A H
XHeat source: Radiator
1. Ceiling ConditionS A U N/A H
XType of ceiling: Gypsum wallboard
2. Wall ConditionS A U N/A H
XType of walls: Gypsum wallboard
3. Floor ConditionS A U N/A H
XType of flooring: Carpet
4. Window ConditionS A U N/A H
XType of window: Double hung
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 35 of 38
Attic
5. DoorsS A U N/A H
X
6. ClosetsS A U N/A H
X
7. ElectricalS A U N/A H
X
8. HVACS A U N/A H
XHeat source: Radiator
1. AccessS A U N/A H
XType of access: Through door
2. Attic ElectricS A U N/A H
XAttic Light Yes
3. Attic structureS A U N/A H
XFraming type: Rafter, Ceiling joistsSheathing material: Wood boards
• Mostly hidden and inaccessible.
4. Attic PlumbingS A U N/A H
X
5. VentilationS A U N/A H
XType: Exhaust fan
• Slate roof construction creates a nature ventilation.
6. Whole house fanS A U N/A H
X
7. ChimneyS A U N/A H
X • Hidden by interior finish
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 36 of 38
8. Mold like materialS A U N/A H
X • None observed
9. Water penetrationS A U N/A H
X • None visible or accessible
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 37 of 38
Report SummaryReport Summary
RoofPage 2 Item: 1 Roof Condition • Debris should be removed from roof
Page 3 Item: 4 Roof Flashing • Irregular installation of wall flashing above porch. Customarily flashing istucked under the shingles.• Consult a roofing contractor
Page 3 Item: 6 Gutters/Downspout • Bent creating inverted slope
Exterior AreasPage 4 Item: 1 Siding Condition • Missing sections
• Consult a licensed contractorPage 5 Item: 6 Paint • Blistered
Page 6 Item: 11 Stairs and railings • Not child safe, should have proper railings• Concrete steps are damaged and missing part of the tread. Use caution.• Consult a licensed contractor
Page 6 Item: 13 Bulkhead Hatch • Water is penetrating bulkhead
GroundsPage 7 Item: 2 Retaining walls • Damaged • Cracks observed • Leaning retaining wall • Consult a licensed
contractorPage 8 Item: 4 Plantings • Clearance should be provided between plantings and house
Decks and PorchesPage 10 Item: 6 Stairs and Railings • Stair stringers are in contact with soil. This will shorten the useful life of
the stairs.• No railing system on side and rear deck.• Earth in contact with wood. Recommend clearing dirt away.
Garage DetatchedPage 11 Item: 3 Siding Condition • Earth in contact with siding or trim. Recommend clearing away.
Page 12 Item: 8 Electrical • Unprotected electrical wiring. • Consult a licensed electrician
Page 12 Item: 9 Garage doors &opener
• No eye beam system present • Consult with home owner for properoperation.
Basement/FoundationPage 13 Item: 2 Basement floor • Hole in floor
• Unfinished at water service closetPage 13 Item: 7 Floor joists • Cut floor joist to accomodate drain pipe. Questionable support post has
been connected beneath it. Consult with a licensed contractor and/orstructural engineer for the suitability of this arrangement.
Page 14 Item: 11 Water Penetrationand Dampness
• Evidence of active water penetration• Evidence of previous water penetration
Page 14 Item: 13 Mold • Mold-like growth observed on ceiling tiles in unfinished front room.• Recommend that mold and air quality be evaluated by a professional
Page 15 Item: 14 Electrical • Open electrical box• Unsecured wires in contact with furnace exhaust duct.• Hot & neutral reversed• Unsecured electrical box• Consult a licensed electrician
Heat/ACPage 19 Item: 3 Other • Gas line improperly supported.
PlumbingPage 19 Item: 2 Waste Pipe and
Vent• Improperly pitched waste pipe
JM Rodkey, Co., Inspections Renovated Victorian from the 1890's,Northampton, MA
Page 38 of 38
Fireplaces/Alt FuelPage 20 Item: 1 Fireplace • Creosote flakes falling from damper.
KitchenPage 23 Item: 12 Electrical • Loose receptacle
Page 24 Item: 18 Dishwasher • Drain loop needs to be elevated to counter height • Consult a licensedplumber
1st Floor BathPage 26 Item: 6 Sinks • Recommend lowering temperature for safety and economy
Page 27 Item: 10 Tub / Shower • Temperature at tub / shower should not excceed 111 degrees• Consult a licensed plumber to balance the water temperature in thehome
2nd Floor BathPage 28 Item: 6 Sinks • Recommend lowering temperature for safety reasons
Page 28 Item: 10 Tub / Shower • Temperature at tub / shower should not excceed 111 degrees• Consult a licensed plumber to balance the water temperature in thehome
3rd Floor BathPage 29 Item: 6 Sinks • Recommend lowering temperature for safety reasons
Page 30 Item: 10 Tub / Shower • Temperature at tub / shower should not excceed 111 degrees • Consult alicensed plumber to balance the water temperature in the home
Page 30 Item: 13 Toilets • Missing closet bolt covers