Montage- und Betriebsanleitung für Jet-Ventilatoren/Installation and Operating Instructions for Jet Fans
Jet-Ventilatoren / Jet Fans
DE
GB
Seite 2 - 21
Page 22 - 40
n Deutsche Originalversion
The data stated in these operating instructions are merely for the purpose of describing the product. Information about a certain property or suitability for a certain purpose of use cannot be derived from our information. The information does not release the user from his own assessments and examinations.Please consider the fact that our products are subject to a natural wear and ageing process.All rights are with Systemair GmbH, also for the event of applications for protective rights.Any powers of use, such as copying and forwarding rights, are with us.An exemplary configuration has been shown on the title page. The product supplied can therefore deviate from the illustration. The original operating instructions have been written in the German language.
22
1 General ...................................................................24
2 Specifications ........................................................24
2.1 Nameplate......................................................................25
2.2 FanSpecifications .........................................................25
2.3 MotorSpecifications ....................................................28
2.4 ElectricalConnections .................................................28
3 IntendedUse ..........................................................28
4 Personnel ...............................................................28
4.1 Qualifications .................................................................28
4.2 PersonalProtectiveEquipment .................................28
5 GeneralSafetyPrecautions ..................................29
6 SafetyFeatures .....................................................29
7 StructuralDesign ...................................................30
8 OperatingMode .....................................................31
9 Acceptance .............................................................31
10 Transport,Storage,Assembly ..............................31
11 CommissioningtheFan .........................................35
12 Operation ...............................................................35
13 ServiceandMaintenance .....................................36
14 Troubleshooting ....................................................36
15 Decommissioning,Disposal ..................................37
16 SpareParts .............................................................38
17 CustomerServiceCenter ......................................38
18 ECDeclarationofConformity ...............................39
Tableofcontents
23JetFans
1 General1.1 Notes on the Use of this Documentation
Forquickreferencethisdocumentincludesatableofcontents.Thepageandversiondatearenotedinthefooter.
Thefollowingsymbolsareusedtopointoutrisksortoprovideadvice:
Danger!Indicatesapossiblylife-threateningsituationorsevererisktohealth.
Caution!Indicatesriskofinjuryandpossiblepropertydamage.
Notice!Generalnotes.
2 SpecificationsThenameplateindicatesthemodeldesignation.Itincludesthefollowingdata:
Ordering Code
AJR-TR (TR) reversible
AJR / AJ8 315 - 2 (B)
300°C / 120 min.
Number of poles
Impeller diameter
Octagonal Jet Fan
Circular Jet Fan
Ordering Code
IV85-4 (F)
400°C / 120 min.
Number of poles
Size
Radial Jet Fan
300°C / 120 min.55°CIV50-4
IV50-4 (B)
24
General
2.1 NameplateThenameplateisaffixednexttotheterminalbox.
Example:
2.2 FanSpecificationsTheoperatingcharacteristicslistedonthenameplateapplyforanairdensityofP=1.2kg/m³andamaximumhumidityof80%.
Weight(kg) AJ78–95;IV102-142Typeofprotection SeedatasheetVoltage/current SeedatasheetAcousticpressure SeedatasheetPermissibleambientoperatingtemperaturerange –20°Cto+55°C(–4°Fto+131°F)Permissibletemperaturerangeforairflow –20°Cto+55°C(–4°Fto+131°F)Impellerdiameter(mm) 315,355and400Thrust(N) AJ23-55;IV14-85
25JetFans
General
ModelAJ8 k
L Lt
F E B
C
tc = sheet thickness fan casing
tm = sheet thickness mounting bracket
ts = sheet thickness silencer
H
Size H B C E F k L ts tc
315 365 550 355 635 650 476 2200 1 2
355 395 550 355 635 650 476 2200 1 2
400 445 600 380 660 700 476 2200 1 2
Alldim.inmm.
k
L
F E
C
Lt
tc = sheet thickness fan casing
ts = sheet thickness silencer
tm = sheet thickness mounting rail
H
Da
ModelAJR
Size ØDa H E C F k L ts tc
315 422 431 426.2 259 457.5 400 2200 1 2
355 462 471 444.7 280 476 400 2200 1 2
400 502 513 510 303 540 400 2200 1 2 Alldim.inmm.
26
General
ModelIV E
BC A
H
F
I
D
6x ⌀K
Size A B C D E F H I 6x⌀K
IV50 790 834 870 1248 300 370 185 210 13,5
IV85 1140 1184 1220 1900 340 420 210 230 13,5
Alldim.inmm.
ModelAJR-TR
344
L
Da HC
FE
Size Da H E C F L
315 419 430 265 235 315 1660
355 459 497 305 255 355 1820
400 504 558 350 280 400 2000
Alldim.inmm.
27JetFans
General
2.3 MotorSpecificationsPleaserefertotheoperatinginstructionssuppliedbythemotormanufacturer.
2.4 ElectricalConnectionsPleaserefertothedatasheet.
3 IntendedUse
Notice!ThemodelAJ8andAJRjetfansareintendedforinstallationinundergroundandabove-groundparkingstructures,tofacilitateventilationandsmokeextraction.
Foroptimumoperation,thejetfanmustbesuspendedhorizontallyfromtheceilinginsuchapositionthatintakeandoutletareunobstructed.
Optionaldeflectorsforcontrolofforcedairareavailableasaccessories.Thesecanbeusedtodeflecttheflowofairaroundpotentialobstructions,suchaspillars.
Thejetfanmustnotbeinstalledinhazardousareas(areaswithapotentiallyexplosiveatmosphere).Thefanisnotsuitableforintakeofmediacontainingdust,aggressivemediaormediawithadustcontentsohighthatdustdepositsontheim-pellerorfanhousingcanaffecttheoperationofthefan.
Theoperatingcharacteristicslistedonthenameplateapplyforanairdensityofp=1.2kg/m³andamaximumhumidityof80%.Thefansaresuitableforuseinanambientoperatingtemperaturerangeofupto55°C(pleasenotedataonname-plate).Thetemperatureoftheairtransportedthroughthefanmustnotbeabove55°C/131°Fnorbelow–20°C/–4°F.
Forthetemperatureresistanceofthesmokeextractingfans,whichcanalsobeusedtoextractCO,pleaserefertothenameplate(e.g.,300°C/120min).
Thestandardmotorsinthesejetfansaresuitableforoperationwithfrequencyconverters.Ifafaniscontrolledusingafrequencyconverter,thermicprotectionmustbeprovidedbyaPTCresistorinthemotor.Thisisnotincludedasstandardequipmentwiththesmoke-extractingfan(B).Forsmokeextraction,themotor-circuitswitchmustbebypassed(tobecarriedoutonsite).
Caution!Anyuseofthejetfanthatdeviatesfromtheabovedescriptionsconstitutesuseforotherthantheintendedpur-pose.Noliabilitycanbeacceptedforpersonalinjuryorpropertydamageresultingfromsuchuse.
4 Personnel
4.1 QualificationsElectricalinstallationofthefanmustbecarriedoutbyaqualifiedelectrician.
4.2 PersonalProtectiveEquipmentProtectivegloves,protectiveshoesandprotectivegogglesmustbewornbyallpersonnelperformingassembly,installation,maintenanceandinspectionworkonthefan.
28
IntendedUse
5 GeneralSafetyPrecautionsDanger!Duringassembly,commissioning,maintenanceandinspection,makesureallpartsandanyareasrequiredforpreparationareinaccessibletounauthorizedpersons
• In spite of all precautions, there will always be some element of risk that cannot be entirely excluded, whether due to human error, malfunction of the device, or force majeure. The system planner, operator or engineer must take all precautions deemed necessary, as outlined in EN 12100, to prevent a hazardous situation from arising.
• Make sure general rules and regulations for occupational safety are observed.
• Make sure the fan is accessible for servicing and maintenance.
• Assembly and electrical installation must be carried out by trained technicians working in accordance with all rele-vant regulations.
• All electrical connections must be made by a qualified electrician. Make sure the equipment is disconnected from power before any maintenance or repair work begins.
• Make sure the fan cannot be inadvertently switched on and the impeller cannot be inadvertently accessed while any work is being performed on the fan.
• The housing of the fan must not be damaged or deformed during assembly.
• Make sure there is no risk of contact with the impeller during operation of the fan. • To prevent equipment failure and to protect the motor, the motor must be disconnected from the power supply
(mains) by a built-in PTC resistor in the event of any operational disorder (for example, median temperature higher than permitted maximum) in accordance with Council Directive 94/9/EC.
• Maximum test voltage for the PTC resistor: 2.5 V.
• The motors contain triple PTC resistors. More than two PTC resistors must not be connected in series, because this can lead to undefined shutdown.
• Be sure to wear protective goggles when checking the rotation direction of the impeller.
• Parts that are relevant to safety, such as the safety guard in front of the impeller, must not be removed nor put out of operation. Furthermore, such parts must be checked for tight attachment.
• Compliance with EMC Council Directive 89/336/EEC applies to this product only if it is directly connected to the conventional electric power system (mains). If the product is integrated in a system or combined and operated with other components (such as controllers or process control modules), the manufacturer or operator of the overall system is responsible for ensuring compliance with EMC Council Directive 89/336/EEC.
• The nameplate indicates the electrical values for the optimally cooled motor approved by the notified body in the EC type examination (Declaration of Conformity).
• Prevent the intake of foreign bodies as these can damage the fan.
• Even inlet and unobstructed inlet and outlet must be ensured.
6 SafetyFeaturesThestandardmotorsareequippedwiththermicprotectionprovidedbyPTCresistors.
29JetFans
GeneralSafetyPrecautions
7 StructuralDesignTheAJR,AJ8,AJR-TRandIVfanisadirectlyoperatedaxialfan,themotorofwhichisseateddirectlyintheairstream.Thedirectionofairintakeisoverthemotor.Theexternalcasingofthefanformsanelongatedhousingmadeofhot-dipgalvanizedsheetsteelthathasapressed-onflangewithboreholes.Thefanhassilencersonboththeinletandpressuresides.Thesilencersareequippedwithretrac-tednozzlesandsafetyguardsandmadeofgalvanizedsteel.Theacousticinsulationaroundtheentirefanunitisnon-flammableinaccordancewithDIN4102asdescribedinCouncilDirective97/69EC.Thesilencermountedonthepressuresideisequippedwithacross-shapedairbaffleforstabilizationoftheaircurrent.Foroptimalguidanceoftheaircurrent,adeflectormadeofgalvanizedsheetsteel(deliveredseparately)isavailableasanaccessoryforinstallationonthepressuresidesilencer.Mountingbracketsmadeofgalvanizedsheetsteelareinstalledonthefanatthefactory.
Model AJ8 -octagonalversion AJR/AJR-TR -roundversion IV -compactverison
WithmodelAJR,thefanunitcanberemovedformaintenancepurposeswithoutdisassemblingtheentiredevice.Todothis,removethetwotensioningfastenersonthesideofthefan.
• Inthestandardversions,thefansareequippedwiththree-phasemotors(400V,50Hz)withbuilt-inPTCre-sistors.TheelectricmotorhasIP55protectionandisolationclassF,whilethesmokeextractingfanshaveIP54protectionandisolationclassH.Thetwo-speedversionisavailablewithamotorwithtappedwinding(Dahlandermotor).
• Themotorwithimpellerisfastenedtoaruggedsupportingstructuremadeofelectro-deposition-galvanizedsheetsteel.
• Theaxialfanismadeofacastaluminumalloyandisequippedwithmoldedbladesandanefficienthubratio.Thehubdesignpermitsinfiniteadjustmentofthebladeanglewhentheimpellerishalted.ThefanIVisequippedwithanaerodynamicoptimizedimpellerwithrivetedblades.ThecomponentsaredynamicallybalancedinaccordancewithISO1940T1,ClassG6.3.
• Theelectricalconnectionismadethroughaterminalboxinstalledontheoutsideofthehousing.Standardversi-on:polypropylene;protectionrating:IP65.Thesmoke-extractingfan(B)ismadeofcastaluminumalloywithIP65protection.
MainComponentsofJetFanwithAccessories
Pos.01 Diffusersystem Pos.07 MotorPos.02 Safetyguard Pos.08 MotorbaseplatePos.03 Inflowduct Pos.09 TensioningfastenersonlyAJRPos.04 Silencer,pressureside Pos.10 MountingfastenerPos.05 Terminalbox Pos.11 Silencer,intakesidePos.06 Impeller
30
StructuralDesign
8 OperatingModeThefancanbeoperatedcontinuouslywithinanambienttemperaturerangeof–20°Cto55°C(–4°Fto131°F)andwithamaximumairflowtemperatureof55°C(131°F).SmokeextractfansF300(300°/120min.)andF400(400°C/120min.)canbeoperatedwithamaximumairflowtemperatureof55°C.Themaximumairflowtemperaturefor120min.is300°Corrather400°C.Thestandardfrequencystampedonthemotormustbemaintained.
9 AcceptanceThefanissubjectedtoatestrunattheplaceofmanufacturerbeforebeingtransferredtothecustomer.Thisacceptancetestisdocumentedandthetestreportsuppliedtothecustomer.
10 Transport,Storage,Assembly
Danger!Dangerofpersonalinjuryifthefanfalls.Usesuitablehoistingdevicesandfasteningequipment.Donotstandundertheloadduringtransport.
Attention!Riskofdamagetothefanorfanparts.Donotmovethedevicebypullingonthepowercord,terminalbox,impeller,safetyguardorinflowduct.Usesuitablehoistingdevicesandfasteningequipment.
Attention!Riskofdeformationofthefan.Exercisecautionwhenloadingandunloadingthefanfortransport.Observethearrowsonthepackageindicatingthecorrectpositioningfortransport.
Pos. 01 Leitvorrichtung Pos. 05 MotorPos. 02 Schutzgitter Pos. 06 Motortrageplatte Pos. 03 Klemmkasten Pos. 07 MontagebefestigungPos. 04 Laufrad
06
02
01
07
0405
03
Pos.01 Integrateddiffuser Pos.05 MotorPos.02 Safetyguard Pos.06 MotorbaseplatePos.03 Terminalbox Pos.07 MountingfastenerPos.04 Impeller
31JetFans
OperatingMode
TransportThefanisshippedinacardboardpackage.Transportthefantotheplaceofinstallationintheoriginalpackaging.Donotmovethedevicebypullingonthepowercord,terminalbox,impeller,safetyguardorinflowduct.Exercisecautionwhenloadingandunloadingthefanfortransporttopreventdamage.Usesuitablehoistingdevices:Whenusingacrane,fastentheloadwithstrapsandensure4-pointsuspension.
Keepinmindduringtransportandloading/unloadingthatthefanweighsatleast80,86or95kg.Thefollowingtableshowsvaluesfororientation(weightswithoutaccessories):
Size Weight AJR
WeightAJR-TR
Weight AJ8
315-2/4 80kg 52kg 84kg
355-2/4 86kg 67kg 90kg
400-2/4 95kg 85kg 99kg
Notice!Attachmentpoints:mountingrail,silencersonintakeandpressuresides
Whentakingdeliveryonthefan,performavisualinspectionandchecktheequipmentsuppliedforcompleteness.
Storage
Providedtheoriginalpackagingisintactandthereisnobuild-upofcondensation,thejetfancanbestoredintheorigi-nalpackaging(polythenesheetwithgroundclearance)outofdoorsforuptoonemonth.Theunpackedfanmustnotbestoredoutofdoors.Inadry,wellventilatedroomwithoutriskofcondensationbuild-up,thejetfancanbestoredindoorsforupto6months.Storagetemperatures:–20°C(–4°F)to60°C(+140°F).
Achtung!Riskofdamagetothefan.Ifthefanisstoredlongerthanthreemonths,turntheimpellerbyhandregularly.
Assembly
Allfansaretestedatthefactorybeforeshipping.Proceedasfollowsafterremovingthepackaging:
• Checkfordamagesustainedduringtransport,•Manuallycheckwhethertheimpellerturnswithoutobstruction,and•Makesurenocondensationhasformed.
Danger!Dangerofpersonalinjuryifsafetyinstructionsarenotobserved.Makesuregeneralrulesandregulationsforoccupationalsafetyareobservedwheninstallingthefan.
Danger!Dangerofpersonalinjuryifthefanfalls.Makesureallpartsandanyareasrequiredforpreparationareinaccessibletounauthorizedpersonsduringinstal-lation.
Danger!Dangerofpersonalinjuryfromelectricalcurrent.Makesurethefanisdisconnectedfromthepowersupplybeforemakinganyelectricalconnectionsinthefan.Makesuretheelectricalpowersupplycannotbeinadvertentlyswitchedonwhileworkingonthefan.
Size 50-4 50-4/6 50-4/8 85-4 85-4/6 85-4/8
Weight IVin kg
105 102 105 140 141 142
32
Transport,Storage,Assembly
Allelectricalconnectionsinthefanmustbemadebyaqualifiedelectrician.
Danger!Dangerofpersonalinjuryfromrotatingparts.Makesurethefancannotbeinadvertentlyswitchedonandtheimpellercannotbeinadvertentlyaccessedwhileinstallationworkisbeingperformedonthefan.
Attention!Riskofdamagetothefan.Thehousingofthefanmustnotbedeformedduringinstallation.Exercisecautionwheninstallingthefan.
Attention!Riskofdamagetothefan.Turntheimpellermanuallytomakesureitisunobstructed.Donotinstallthefaniftheimpellerdoesnotturneasilyandwithoutobstruction.Notifythemanufacturer.
Attention!Riskofdamagetothefan.Makesurethefancannottakeinforeignbodies.
Notice!Riskofdamagetothefan.Iftheflowofairisimpeded,thefanmayoverheat.Ensureunobstructedandevenintakeandunobstructedoutlet.
Notice!Riskofdamagetothefan.Ifthefanisinstalledandsecuredwithoutobservingtherequiredfirerating,thefanmightworklooseofitscei-lingattachmentintheeventofafire.Makesurethesmokeextractingfanisaffixedinaccordancewiththefireratingforthecaseofoperation.
• Installthefaninsuchamannerthatitisaccessibleforserviceandmaintenanceatalltimes.• Usebothmountingrails,ormountingfeetandrequiredsafetyanchors,tofastenthefantotheceiling. Makesuretoobservethedirectionofairflowasindicatedbythearrows,andtheinformationprovidedbythemanu-facturerofthefasteningdeviceswithregardtothesizeandtypeofrawlplugsandsafetyanchorstouse.UsesteelfastenersofatleastsizeM8.
• Wheninstallingasmokeextractingfan,makesureitcannotfallfromtheceilingintheeventofafire.Useonlytestedfasteningmaterials.
• Makesureduringinstallationthatallcomponentscushionedagainstvibrationcarryanequalload.• Foroptimumoperation,installthejetfaninsuchapositionthatintakeandoutletareunobstructed.• Priortoinstallation,checktheclearancebetweenimpellerbladetipsandfanhousingagainstthevaluesinthefollowingtable:
Size Min.clearanceinmm
AJ315 2,5
AJ355/400 3,0
Donotinstallthefanifthisclearanceisnotgiven.Notifythemanufacturerwithregardtothecorrectsettingoftheclearance.
Thediffuserisnotstandardequipmentandmustbeorderedseparately.Itisshippedinaseparatepackage.
• Beforethecompleteinstallationofthejetfan,fastenthediffuseronthepressureside(seearrow)oftheoutletjetwith4self-lockingscrews,sizeM5x12(torque:4.5N).• Positionthediffuserfinssothatafterfasteningthejetfantotheceilingtheairflowisdirecteddownwardata10°angle.Whetherthefinscanbereadjustedlaterdependsonthestructureslocatedintheimmediatevicinity,suchasgirders.• Makesuretheairflowattheoutletsideisnotobstructed,e.g.bystructuralelementssuchasgirders.• Thenaffixthediffuserfinsusingself-drillingscrewssize4.2X1(torque:4.5N).
Size Min.clearanceinmm
IV50 3,0
IV85 4,0
33JetFans
Transport,Storage,Assembly
Electrical Connections
Theconnectiondiagramisdepictedinthecoverofthejunctionbox.Connectthewiresasindicated,observingalllocalregulations.Fortheelectricalspecifications,refertothenameplateortheencloseddatasheet.Groundthefanusingthegroundingterminalsontheoutsideofthefanhousing.
Makesureallmotorsareequippedwithmotor-circuitswitches(notincludedindelivery).Donotattachanythingtothefanhousing.
Danger!Dangerofpersonalinjuryfromelectricalvoltage.Checktheelectricaldataonthenameplateagainstthespecificationsofthelocalpowerconnection;forexample,inthecontrolcabinet.
Notice!Refertotheidentificationplateonthemotorforthecorrectconnectionsineachcase.
One-speed:
70 x 55 mm
3065
61
Dreiphasenmotor optional mit Thermokontakte oder KaltleiterThree phase motor with optional thermal contacts or cold conductor
Moteur triphasé avec comme option thermocontact branchéou résistance PTC
3 x 230 VD Schaltung
Delta connectionBranchement en triangle
3 x 400 VY Schaltung
Star connectionBranchement en étoile
Drehrichtungsänderung durch Vertauschen von 2 PhasenChanging of direction of rotation by interchanging of two phases
Changment de sens de rotation par inversion de deux phases
Typenschild beachten! See label! Voir plaquette! 300N
L1 L2 L3 PE TK/KL L1 L2 L3 PE TK/KL
W2 U2 V2
U1 V1 W1
W2 U2 V2
U1 V1 W1
70 x 55 mm
Dahlandermotor optional mit Thermokontakte oder KaltleiterDahlander motor with optional thermo contacts or cold conductor
Moteur Dahlander avec comme option thermocontact branchéou résistance PTC
YAnschluß für niedere Drehzahl
Connection for low speedBranchement pour vitesse à bas
Drehrichtungsänderung durch Vertauschen von 2 PhasenChanging of direction of rotation by interchanging of two phases
Changment de sens de rotation par inversion de deux phases
YYAnschluß für hohe DrehzahlConnection for high speed
Branchement pour vitesse grande
L1 L2 L3 PE TK/KL
L1 L2 L3 PE TK/KLU2 V2 W2
U1 V1 W1
U2 V2 W2
U1 V1 W1
3031
25
301N
Use M4 x M12 self-locking screw to fasten
Position fins to specified angle and secure with 4.2 x 13 self-drilling screws (DIN 7504 L)
AJ8/AJR
IV
Position fins to specified angle and secure with 4.2 x 13 self-drilling screws (DIN 7504 L)
Two-speed:
34
Transport,Storage,Assembly
Adjusting the Blade Angle
Notice!Ifthefanhastobeinstalledinadifferentlocation,withtheresultthattheangleoftheimpellerbladesmustbeadjusted,pleasecontacttheServiceDepartmentatSystemair.
Adjustingthebladeanglerequiresdetailedknowledgeofthepowerconsumptionofthemotorandthemaxi-mumpermissiblebladeangleinrelationtothemotorinstalled.
11 CommissioningtheFanDanger!Dangerofpersonalinjuryandhazardofdamagetothefan.Priortoinitialcommissioningofthefan,readtheoperationinstructionscarefullyandcheckthefollowing:
• Installationoftheequipment(mounting;potentialdeformations)•Allresiduesoftheinstallationworkremovedfromwithinthefanandtheconnectedducts• Safetyfeaturesinstalled• Tightnesstestcarriedout• Correctexecutionandcorrectconnectiontotheelectricalinstallation• Connectiondatamatchesdataonthenameplate
Beforeputtingthefanintooperation,checktheminimumclearancebetweenimpellerbladetipsandfanhousingagain.
Danger!Dangerofinjurytoeyesbyinstallationresiduesordustexpelledwhencheckingthedirectionofrotation.Besuretowearsafetygoggleswhencheckingtherotationdirectionoftheimpeller.
Iftheclearanceiscorrect,switchthedeviceonbrieflyandthenoffagaintocheckthedirectionofimpellerrotation.Theimpellermustrotateinthedirectionindicatedbythearrowonthefanhousing.Checkbylookingthroughtheinspectionwindowonthefanhousing.
Danger!Livecablesandconnections.Dangerofpersonalinjuryfromelectricalcurrent.Haveallelectricalworkperformedbyaqualifiedelectrician.
Ifthedirectionofrotationiswrong,interchangethetwophasestosetthecorrectdirectionofrotation.Assoonasyouhaveputthefanintooperation,makesureitisfunctioningproperly;checkthattheimpellerisnotobstruc-ted;measurethecurrentconsumption;checkforvibrationandnoises.
Attention!Riskofdamagetothefan.Ifthefanisoperatedoutsidethespecifiedcharacteristiccurve,thereisahazardofunstablerotationandunac-ceptablevibrations,whichcanleadtodestructionofthefan.Donotoperatethefanoutsidethespecifiedcharacteristiccurve.
Donotoperatethefanoutsidethespecifiedcharacteristiccurve.Improperoperatingcharacteristicscanresultfrompoorcurrentinfloworexcessivelyhighresistance.Thefanmustbeoperatedatthespecifiedoperatingpoint.Fillouttheenclosedcommissioningrecordformandstoreitforfuturereferenceincaseofwarrantyclaims.
12 OperationTheoperatinginstructionssuppliedbythemanufacturerofthemotormustbeobservedwhenoperatingthefan.Inspectthefanregularlyforproperfunctioning;checkthattheimpellerisnotobstructed;measurethecurrentconsumpti-on;checkforvibrationandnoises.
35JetFans
CommissioningtheFan
13 ServiceandMaintenance
Danger!Livecablesandconnections.Dangerofpersonalinjuryfromelectricalcurrent.Haveallelectricalworkperformedbyaqualifiedelectrician.
Checkthefollowingperiodicallyinaccordancewithregulatoryguidelines,andatleastonceperyear:
• Threadedconnections,inparticulartheattachmentoftheimpeller• Checkthefanwheelfordirtordustdepositsandcleanasneeded.• Checktheimpellerfordirtordustdepositsandcleanasneeded.• Properfunctioningofsafetycomponents• Properfunctioningofthecontrollersystem• Coilresistance• Operatingcurrent• Vibrations• Noisescomingfromthebearingsintheelectricmotor
Checkforproperfunctioningofthesystemandcontrol(circuitbreaker)inaccordancewiththesystem‘smaintenancebookatleastevery3months,ifmorefrequentreviewsarenotspecifiedCheckthefirstfouritemsinthislistwiththefanswitchedoff.•Theparametersfortheotheritemsmustmatchthepara-metersrecordeduponinitialinstallation.Ifthereisanydeviationinanyoftheparameters,replacethemotororthefanorhavetherelevantcomponentrepairedbythemanufacturer.Anyunauthorizedworkperformedonthefanoritscompo-nentswillvoidallclaimsunderthewarranty.Performregularserviceandmaintenanceontheelectricmotorasspecifiedinthemanufacturer‘sinstructionssuppliedwiththemotor.Filloutthemaintenancerecordattachedintheappendix.
Notice!Riskofdamagetothefanfromuseofhigh-pressurecleanerCleanthefanmanually,withavacuumcleanerorwithcompressedair.
Notice!Riskofdamagetothefan.Systemaircannotacceptliabilityfordamageresultingfromtheuseofpartssuppliedbyothermanufacturers.UseonlygenuineSystemairparts.
14 Troubleshooting
Danger!Livecablesandconnections.Dangerofpersonalinjuryfromelectricalcurrent.Haveallelectricalworkperformedbyaqualifiedelectrician.
Danger!Dangerofinjurytoeyesbyinstallationresiduesordustexpelledwhencheckingthedirectionofrotation.Besuretowearsafetygoggleswhencheckingtherotationdirectionoftheimpeller.
36
ServiceandMaintenance
Problem Solution
Fandoesnotrun Checkpowersupplyandmotor-circuitswitch.Ifproblemnotfound,checkmotor.Ifmotorhasseparatecoils,checkbothspeeds.
Volumeofairflowtoolow Checkdirectionofrotation.Ifnecessary,changemotorrotationdirectionbyinter-changingtwophases.Checkintakeareaforblockage.Checkoperatingpointandexecutionofthesystem.
Motor-circuitswitchhasbeentriggered
Checkthemotorspecifications.IfOK,checkelectricalsupply(mains)andmotor(shortcircuit,damageinstorage,impellerblockedorscraping);contactcustomerservice.
Abnormalnoises Thedevelopmentofnoiseinafandependstoagreatextentontheinstallationsituationandtheoperatingconditions.Thisiswhynogenerallyapplicabledataonnoisecanbegiven;suchdataisalwaysrelativetotheconditionsofmeasure-ment.Fordetails,pleasecheckourdatasheets.Possiblesourcesoferror:• Bearingdamageonmotor;impellerblockedorscraping• Impellerunbalancedordamaged• Impellerbladesatnon-matchingangles• Impellerrunninginthestallingrange• LoosecomponentsHavethemotoror,ifnecessary,theentirefanrepaired.
Vibrations Checkoperatingpointandexecutionofthesystem.Iftheactualoverallresistanceofthesystemishigherthanspecified,thiscancausesomefanmodelstooperateinthestallingrange.Contactthemanufacturer‘scustomerservicecenter.Changefordamageordustdepositsonimpeller.Checkweldingseamsonhousing.
Whenindoubt,contactthemanufacturer‘scustomerservicecenter.
15 Decommissioning,Disposal
Danger!Livecablesandconnections.Dangerofpersonalinjuryfromelectricalcurrent.Haveallelectricalworkperformedbyaqualifiedelectrician.
Danger!Dangerofpersonalinjuryifthefanfalls.Makesuretheareaisinaccessibletounauthorizedpersonswhiledismantlingthefan.Usesuitablehoistingdevicesandfasteningequipment.Donotstandundertheloadduringtransport.
Disconnecttheequipmentfrompowerbeforedecommissioningthefan.Putthemotoroutofserviceanddisposeofitasdescribedinthemanufacturer‘soperatinginstructions.Afterfinaldecommissioningofthefan,disposeofallmaterialsinaccordancewiththeapplicablelawsandregulations.
37JetFans
Decommissioning,Disposal
16 SparePartsAdefectivefanmustbereplacedasanentireunit.Repairsmaybecarriedoutonlybythemanufacturerandonthemanufacturer‘spremises.
17 CustomerServiceCenterYoucancontactourcustomerservicecenterasfollows:
SystemairGmbHSeehöferStr.45D-97944Windischbuch
Tel.:+49(0)7930/9272-0Fax:+49(0)7930/9273-92
E-Mail:info @systemair. de
Homepage:www .systemair. com
38
SpareParts
18 ECDeclarationofConformity
EG-KonformitätserklärungEC Declaration of Conformity
Der Hersteller: Systemair GmbHThe Manufacturer Seehöfer Str. 45 D-97944 Windischbuch Tel.: +49-79 30 / 92 72-0
erklärt hiermit, dass folgende Produkte:certified herewith that the following products:
Produktbezeichnung: Jet-Ventilatorenproduct designation Jet fans
Typenbezeichnung: AJR, AJ8; AJR (B); AJ8 (B); AJR-TR; IV type designation
Baujahr: 2011year of manufacture
allen einschlägigen Bestimmungen der Richtlinie Maschinen RL 2006/42/EG entspricht.ensure all relavant regulations of machinery directive electrical equipment RL 2006/42/EG.
Die Maschine entspricht weiterhin allen Bestimmungen der Richtlinien Elektrische Betriebsmittel (2006/95/EG) und Elektromagnetische Verträglichkeit (EMV) (2004/108/EG). The products ensure furthermore all regulations of directives electrical equipment and electromagnetic compatibility (EMC) (2004/108/EG).
Folgende harmonisierte Normen wurden angewandt:The following standards are used:
EN ISO 12100-1:2003 Sicherheit von Maschinen - Grundbegriffe, allgemeine Gestaltungsleitsätze, Teil 1: Grundsätzliche Terminologie, Methodik Safety of machinery - Basic concepts, general principles for design - Part 1: Basic terminology, methodology
EN ISO 12100-2:2003 Sicherheit von Maschinen - Grundbegriffe, allgemeine Gestaltungsleitsätze, Teil 2: Technische Leitsätze und Spezifikationen Safety of machinery - Basic concepts, general principles for design - Part 2: Technical principles
EN ISO 13857:2008 Sicherheit von Maschinen - Sicherheitsabstände gegen das Erreichen von Gefahrstellen mit den oberen und unteren Gliedmaßen Safety of machinery - Safety distances to prevent hazard zones being reached by upper and lower limbs
EN 60204-1:2006 Sicherheit von Maschinen - Elektrische Ausrüstungen von Maschinen, Teil 1: Allgemeine Anforderungen Safety of machinery - Electrical equipment of machines - Part 1: General requirements
DIN EN 61000-6-1:2007 Elektromagnetische Verträglichkeit (EMV) - Teil 6-1: Fachgrundnormen - Störfestigkeit für Wohnbereich, Geschäfts- und Gewerbebereiche sowie Kleinbetriebe Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity for residential, commercial and light-industrial environments
DIN EN 61000-6-2:2005 Elektromagnetische Verträglichkeit (EMV) - Teil 6-2: Fachgrundnormen - Störfestigkeit für Industriebereiche Electromagnetic compatibility (EMC) - Part 6-2: Generic standards - Immunity for industrial environments
Boxberg,
30.12.2010
Datum/date ppa. Harald Rudelgass, Technischer Leiter ppa. Harald Rudelgass, Technical director
39JetFans
ECDeclarationofConformity
Systemair GmbH • Seehöfer Str. 45 • D-97944 WindischbuchTel.: +49 (0)7930/9272-0 • Fax: +49 (0)7930/9273-92
info @systemair. de • www .systemair. de
3086
90•Januar201