Instrumentation Cable ApplICAtIons• Predominantly used in utility substations
• Can be installed indoors or outdoors, direct burial, free air, raceways, encased in concrete, open trays, troughs, or continuous rigid cable support
• Other Uses • Class 1 remote-control and signaling
circuits
• Class 1, Division 2 hazardous locations
• Conductor operating temperatures are not to exceed 90°C wet or dry
• Rated 600 Volts
ConstRUCtIon DEtAIls•Conductors
• 18 or 16 AWG, 7 Strand, Annealed Bare Copper
•Insulation
• Tough, Heat and Moisture Resistant Polyvinyl Chloride (PVC)
• Color Code:(Pairs – Black, White, and Numbered) & (Triads – Black, White, Red, and Numbered)
• Conductor Jacket:Clear Nylon (polyamide)
•Assembly
• Color-coded twisted pairs or triads; group of pairs or triads with numeric print identification on the groups
• Overall aluminum polyester foil with 100% coverage, tinned drain wire
•OverallJacket
• Heat, Moisture and Sunlight Resistant Black Polyvinyl Chloride (PVC)
• PAiRS: SOUTHWiRe X PR OAS XXAWG SHielDeD (Ul) TyPe TC 600V THHN/TFFN SUN ReS DiR BURiAl ROHS (MONTH/DAy/yeAR) SeqUeNTiAl FOOTAGe MARkS
• TRiADS: SOUTHWiRe X TR OAS XXAWG SHielDeD (Ul) TyPe TC 600V THHN/TFFN SUN ReS DiR BURiAl ROHS (MONTH/DAy/yeAR) SeqUeN-SeqUeNTiAl FOOTAGe MARkS
spECIFICAtIonsSouthwire’sSubstationInstrumentationCablemeetsorexceeds:• All Applicable ASTM Specifications
• Ul 83
• Ul1277
• Ul1581
• Ul 1685
• ieee 1202
• iCeA T-30-520
• RoHS Compliant
optIons• Unshielded Pairs or Triads, with Overall
Shield
• XlP insulated Conductors
• Rip Cord
• Also Available in 300V Construction Upon
Request
SUBSTATIONINSTRUMENTATIONCABLE
ConDUCtoR tYpE18 – 16 AWG COPPeR
InsUlAtIon tYpE PVC/NylON
JACKEt tYpE PVC
ConstRUCtIonAt A GlAnCE
37
1
2
3
32
1
SUBSTATIO
NIN
STRUM
ENTATIO
NCA
BLEIN
STRUM
ENTATIO
NCA
BLE
38
Dimensions and weights shown above are nominal and subject to industry tolerances.
SectionB
Size Numberof InsulationThickness
InsulationJacket
Thickness
OverallJacketThickness
NominalCoreDiameter
NominalOverall
Diameter
ApproximateWeight
AWGorkcmil
Pairs Triads inches mm inches mm inches mm inches mm inches mm lbs/1000ft
kg/km
18 1 - 0.015 0.38 0.004 0.1 0.045 1.14 0.167 4.2 0.26 6.6 38 57
18 - 1 0.015 0.38 0.004 0.1 0.045 1.14 0.181 4.6 0.28 7.1 47 70
16 1 - 0.015 0.38 0.004 0.1 0.045 1.14 0.191 4.9 0.29 7.4 49 73
16 - 1 0.015 0.38 0.004 0.1 0.045 1.14 0.206 5.2 0.30 7.6 61 91
18 2 - 0.015 0.38 0.004 0.1 0.045 1.14 0.377 9.6 0.48 12.2 84 125
16 2 - 0.015 0.38 0.004 0.1 0.045 1.14 0.429 10.9 0.53 13.5 106 158
18 4 - 0.015 0.38 0.004 0.1 0.045 1.14 0.471 12.0 0.57 14.5 131 195
16 4 - 0.015 0.38 0.004 0.1 0.045 1.14 0.536 13.6 0.64 16.3 173 257
18 8 - 0.015 0.38 0.004 0.1 0.060 1.50 0.630 16.0 0.76 19.3 245 365
16 8 - 0.015 0.38 0.004 0.1 0.060 1.50 0.717 18.2 0.85 21.6 327 487
18 12 - 0.015 0.38 0.004 0.1 0.060 1.50 0.770 19.6 0.90 22.9 339 504
16 12 - 0.015 0.38 0.004 0.1 0.060 1.50 0.876 22.2 1.01 25.7 459 683