14
INSTALLATION & OPERATING INSTRUCTIONS for SPLIT SYSTEM HEAT PUMPS All information contained herein is subject to change without notice. 10-103E Goodman Manufacturing Company, L.P. 2550 North Loop West, Suite 400, Houston, TX 77092 www.qoodmanmfq.com ©2003-2004 Goodman Manufacturing Company, L.P. 3/04

INSTALLATION & OPERATING INSTRUCTIONS for SPLIT … · INSTALLATION & OPERATING INSTRUCTIONS for SPLIT SYSTEM HEAT PUMPS All information contained herein is subject to change without

  • Upload
    phambao

  • View
    224

  • Download
    2

Embed Size (px)

Citation preview

INSTALLATION & OPERATINGINSTRUCTIONS

for SPLIT SYSTEMHEAT PUMPS

All information contained herein is subject to change without notice.

10-103EGoodman Manufacturing Company, L.P.

2550 North Loop West, Suite 400, Houston, TX 77092www.qoodmanmfq.com

©2003-2004 Goodman Manufacturing Company, L.P.

3/04

INDEXIntroductionChecking Product Received 2Message to the Homeowner 2Before Beginning Installation 2Installing the Split System Heat Pump 2

Replacement PartsOrdering Parts 2Service Parts Department 2

Safety InstructionsRecognize Safety Symbols, Words and Labels 3

Codes and RegulationsGeneral 3EPA Regulations 3National Codes 3

Scroll CompressorsPump Down Procedures 3Crankcase Heaters 3Unbrazing System Components 3

InstallationGeneral 3Pre-lnstallation Checkpoints 3Clearance 3Location 4Elevation Limitations 4

ElectricalGeneral 4

ComponentsContactor 5Crankcase Heater 5Condenser Motor 5Compressor 5Defrost Control 5Loss of Charge Protector 5Outdoor Thermostats 5Reversing Valve Coil 5

PipingGeneral 5Line Set Installation Instructions 5

Evaporator CoilGeneral 6

Indoor CFM and Heating Capacity DeterminationAirflow Determiniation 6Airflow Test Instruments 6Temperature Rise Resistive Heat Method 6Temperature Rise Heat Pump Only Method 6

Refrigerant Charge Determination and Adjustments -CoolingWeigh In Charge Method 7Superheat Method 7Expansion Valve System Method 8

Heat Pump - Heating CycleHot Gas Method 8

Start-Up Procedure and ChecklistGeneral 8

Operation - Defrost ControlTiming 9Field Testing/Troubleshooting 9General Explanation and Guidance 9

MaintenanceGeneral 10Common Causes of Unsatisfactory Operation 11

Wiring DiagramB17244-20 12

Thermostat WiringCP/ARUF/ARPF/ARPT 13

INTRODUCTIONChecking Product ReceivedUpon receiving the unit, inspect it for damage from shipment.Claims for damage, either shipping or concealed, should befiled immediately with the shipping company. Check the unitmodel number, specifications, electrical characteristics andaccessories to determine if they are correct. In the event anincorrect unit is shipped, it must be returned to the supplierand must NOT be installed. The manufacturer assumes noresponsibility for installation of incorrectly shipped units.

Message to the HomeownerThese instructions are addressed primarily to the installer;however, useful maintenance information is included andshould be kept, after installation, for future reference.

Before Beginning InstallationCarefully read all instructions for the installation prior toinstalling unit. Make sure each step or procedure isunderstood and any special considerations are taken intoaccount before starting installation. Assemble all tools,hardware and supplies needed to complete the installation.Some items may need to be purchased locally. After decidingwhere to install unit, closely look the location over - both theinside and outside of home. Note any potential obstacles orproblems that might be encountered as noted in this manual.Choose a more suitable location if necessary.

Installing the Split System Heat PumpProper installation of the split system unit helps ensure troublefree operation. Improper installation can result in problemsranging from noisy operation to property or equipmentdamages, dangerous conditions that could result in injury orpersonal property damage and could void the warranty. Givethis booklet to the user and explain it's provisions. The usershould retain these instructions for future reference.

REPLACEMENT PARTSOrdering PartsWhen reporting shortages or damages, or ordering repairparts, give the complete unit model and serial numbers asstamped on the unit's nameplate. Replacement parts for thisappliance are available through your contractor or localdistributor. For the location of your nearest distributor, consultthe white business pages, the yellow page section of thelocal telephone book or contact:

SERVICE PARTS DEPARTMENTGOODMAN MANUFACTURING COMPANY, L.P.

2550 NORTH LOOP WEST, SUITE 400HOUSTON, TEXAS 77092

(713)861 -2500

IO-103E 3/042

IMPORTANT SAFETY INSTRUCTIONSRecognize Safety Symbols, Words, and LabelsThe following symbols and labels are used throughout thismanual to indicate immediate or potential hazards. It is theowner's responsibility to read and comply with all safetyinformation and instructions accompanying these symbols.Failure to heed safety information increases the risk ofserious personal injury or death, property damage and/orproduct damage.

DANGERIMMEDIATE HAZARDS WHICH WILL RESULT INPROPERTY DAMAGE, PRODUCT DAMAGE, SEVEREPERSONAL INJURY AND/OR DEATH.

WARNINGHAZARDS OR UNSAFE PRACTICES COULD RESULT INPROPERTY DAMAGE, PRODUCT DAMAGE, SEVEREPERSONAL INJURY AND/OR DEATH.

CAUTIONHAZARDS OR UNSAFE PRACTICES WHICH MAY RESULTIN PROPERTY DAMAGE, PRODUCT DAMAGE, AND/ORPERSONAL INJURY.

WARNINGDO NOT CONNECT TO OR USE IN CONJUNCTION WITHTHIS UNIT ANY DEVICES FOR THE PURPOSE OF SAVINGENERGY OR INCREASING OPERATING EFFICIENCIESTHAT ARE NOT DESIGN CERTIFIED FOR USE WITH THISUNIT OR HAVE NOT BEEN TESTED AND APPROVED BYGOODMAN. SERIOUS PROPERTY OR PERSONALDAMAGE, REDUCED UNIT PERFORMANCE AND/ORHAZARDOUS CONDITIONS MAY RESULT FROM THE USEOF DEVICES THAT HAVE NOT BEEN APPROVED ORCERTIFIED BY GOODMAN.

WARNINGDO NOT STORE COMBUSTIBLE MATERIALS OR USEGASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORSIN THE VICINITY OF THIS APPLIANCE SO AS TO PREVENTTHE RISK OF PROPERTY DAMAGE OR PERSONALINJURY. HAVE YOUR CONTRACTOR POINT OUT ANDIDENTIFY THE VARIOUS CUT-OFF DEVICES, SWITCHES,ETC. THAT SERVES YOUR COMFORT EQUIPMENT.

WARNINGDO NOT, UNDER ANY CIRCUMSTANCES, CONNECTDUCT WORK TO ANY OTHER HEAT PRODUCING DEVICESUCH AS FIREPLACE INSERT, STOVE, ETC.UNAUTHORIZED USE OF SUCH DEVICES MAY RESULTIN PROPERTY DAMAGE, FIRE, CARBON MONOXIDEPOISONING, EXPLOSION, PERSONAL INJURY OR DEATH.

CODES AND REGULATIONSGeneralInformation contained herein pertain only for outdoorequipment installation. NOTE: Units are not to be installedinside the structure, units are designed for Outdoor UseOnly.

IMPORTANT: THE UNITED STATES ENVIRONMENTALPROTECTION AGENCY (EPA) HAS ISSUED VARIOUSREGULATIONS REGARDING THE INTRODUCTION ANDDISPOSAL OF REFRIGERANTS IN THIS UNIT. FAILURE TOFOLLOW THESE REGULATIONS MAY HARM THEENVIRONMENT AND CAN LEAD TO THE IMPOSITION OFSUBSTANTIAL FINES. BECAUSE REGULATIONS MAY VARYDUE TO PASSAGE OF NEW LAWS, WE SUGGEST ACERTIFIED TECHNICIAN PERFORM ANY WORK DONE ONTHIS UNIT. SHOULD YOU HAVE ANY QUESTIONS PLEASECONTACT THE LOCAL OFFICE OF THE EPA.

National CodesThis product is designed and manufactured to permitinstallation in accordance with National Codes. It is theinstaller's responsibility to install the product in accordancewith National Codes and/or prevailing local codes andregulations.

SCROLL COMPRESSORSThe following should be read prior to installing units with scrollcompressors.

Pump Down ProcedureScroll equipped units should never be used to evacuate theair conditioning system. Vacuums this low can cause internalelectrical arcing resulting in a damaged or failed compressor.

Crankcase HeaterScroll equipped units do not have nor do not require acrankcase heater.

Unbrazing System ComponentsIf the refrigerant charge is removed from a scroll equippedunit by bleeding the high side only, it is sometimes possiblefor the scrolls to seal, preventing pressure equalization throughthe compressor. This may leave the low side shell and suctionline tubing pressurized. If a brazing torch is then applied tothe low side while the low side shell and suction line containspressure, the pressurized refrigerant and oil mixture couldignite when it escapes and contacts the brazing flame. Toprevent this occurrence, it is important to check both the highand low side with manifold gauge before unbrazing, or in thecase of repairing a unit on an assembly line, bleed refrigerantfrom both the high and low side.

INSTALLATIONIt is not the intent of the manufacturer that this unit equipmentbe used with components other than indicated. An impropermatch voids the warranty. Reference the Specification Sheetsfor Performance Values and Approved System Matches.

Pre-installation CheckpointsPerform pre-installation checkpoints before attempting anyinstallation. The following check points should be considered:• Structural strength of supporting members• Clearances and provision for servicing• Power supply and wiring• Air duct connections• Drain facilities and connections

ClearanceThe outdoor heat pump unit is designed to be located outsidethe building with unobstructed condenser air inlet anddischarge. Additionally, the unit must be situated to permit

IO-103E 3/043

access for service and installation. Condenser air enters fromthree sides. Air discharges upward from the top of the unit.Refrigerant tube electrical connections are made on the rightside of the unit as you face the compressor compartment.The best and most common application is for the unit to belocated 10" from back wall with the connection side facingthe wall. This "close to the wall" application minimizes exposedtubing and wiring and reduces the space for children to runaround the unit which may cause damage to the tubes orwiring.

FIGURE 1

Close to the wall application assures free, unobstructed air tothe other two sides. In more confined application spaces,such as corners provide a minimum 10" clearance on all airinlet sides. Allow 18" minimum for service access to thecompressor compartment and controls.

The top of the unit should be completely unobstructed. Ifunits are to be located under an overhang, there should be aminimum of 36" clearance and provisions made to deflect thewarm discharge air out from the overhang.

LocationConsider the affect of outdoor fan noise on conditioned spaceand any adjacent occupied space. It is recommended thatthe unit be placed so that discharge does not blow towardwindows less than 25 feet away.

The outdoor unit should be set on a solid, level foundation -preferably a concrete slab at least 4 inches thick. The slabshould be above ground level and surrounded by a graveledarea for good drainage. Any slab used as a unit's foundationshould not adjoin the building as it is possible that sound andvibration may be transmitted to the structure. For rooftopinstallation, steel or treated wood beams should be used asunit support for load distribution.

Heat pumps require special location consideration in areasof heavy snow accumulation and/or areas with prolongedcontinuous subfreezing temperatures. Heat pump unit basesare cutout under the outdoor coil to permit drainage of frostaccumulation. The unit must be situated to permit freeunobstructed drainage of the defrost water and ice. A minimum3" clearance under the outdoor coil is required in the milderclimates.

In more severe weather locations, it is recommended thatthe unit be elevated to allow unobstructed drainage and airflow. The following elevation minimums are recommended:

Design Temperature+15° and above

-5° to +14°below -5°

Suggested Minimum Elevation2 1/2"

8"12"

Elevation LimitationsIf the outdoor unit is mounted above the air handler, themaximum lift should not exceed 70' (suction line). If the airhandler is mounted above the condensing unit, the lift shouldnot exceed 50' (liquid line).

NOTE: When installing systems where the indoor - outdoorsections are separated by more than 15 feet, observe themaximum elevation separations limitations.

FIGURE 2

ELECTRICAL

WARNINGBEFORE ATTEMPTING ANY SERVICE OR ADJUSTMENTS- ENSURE THAT THE GAS AND ELECTRICAL SUPPLIESARE IN THE "OFF" POSITION. FAILURE TO FOLLOW THISWARNING MAY CAUSE PROPERTY DAMAGE, PERSONALINJURY AND/OR DEATH.

The supply power, voltage, frequency and phase mustcoincide with that on the nameplate. All wiring should becarefully checked against the manufacturer's diagrams orwith the diagram on the unit's access panel. Field wiringmust be connected in accordance with the National Code orother local codes that may apply. Make certain that theequipment is adequately grounded per local coderequirements. Use copper wire only between disconnectand unit.

Over current protection less than that recommended on theunit's "Specification Sheet" could result in unnecessary fusefailure and service call. The manufacturer bears noresponsibility for damage caused to the equipment as a resultof not using the recommended size for the protective devicesas listed on the unit's rating plate.

IO-103E 3/044

This unit has undergone a run test prior to packaging forshipment. This equipment has been started at minimum ratedvoltage and checked for satisfactory operation. Do not attemptto operate this unit if available voltage is not within theminimum and maximum shown on nameplate.

The condensing unit control wiring requires a 24 Volt minimumand a 40 VA service from the indoor transformer as shownon the wiring diagram.

CAUTIONBEFORE STARTING EQUIPMENT AFTER PROLONGEDSHUTDOWNS OR AT THE TIME OF INITIAL START UP, BESURE THAT THE CIRCUITS TO THE UNITS ARE CLOSEDFOR AT LEAST 24 HOURS.

COMPONENTSContactorThis control is activated (closed) by the room T-stat for bothheating and cooling. It is de-energized (open) duringemergency heat. The contactor has a 24 Volt coil andsupplies power to the compressor and outdoor fan motor.

Crank Case HeaterThese heaters are factory wired in such a manner that theyare in operation whenever the main power supply to the unitis "ON". It warms the compressor crankcase, preventing liquidmigration and subsequent compressor damage. It isconnected electrically to the contactor L1 and L2 terminals.

Condenser MotorThis is activated by the contactor during heating and coolingexcept during defrost and emergency heat operation.

CompressorThis is activated by the contactor for heating and coolingexcept during emergency heat. It is protected by an internaloverload.

Defrost ControlThis provides time/temperature initiation and termination ofthe defrost cycle.

Loss of Charge ProtectorIf the system loses refrigerant charge, the control will opento allow the compressor contactor to open.

Outdoor ThermostatsThese optional controls are used to prevent full electric heateroperation at varying outdoor ambient (0°F to 45°F). Theyare normally open above their set points and closed belowto permit staging of indoor supplemental heater operation.

Reversing Valve CoilThis is activated by the thermostat (system's switch) duringcooling only and during defrost. It positions the reversingvalve pilot valve for cooling operation.

PIPINGOnce located, the outdoor unit is ready to be interconnectedwith the indoor section, using the refrigeraion tubing sizesnoted in the "Long Line Application" Table. Use only-refrigeration grade (dehydrated and capped) copper tubing.

CAUTIONKEEP REFRIGERATION TUBING CLEAN AND DRY PRIORTO AND DURING INSTALLATION TO AVOID EQUIPMENTDAMAGE.

Insualation of at least 1/2" wall thickness should be used onthe vapor gas line to prevent condensation when cooling andheat loss when heating. The insulation should be installedon the tubing prior to installation and should be run the entirelength of the installed line. The end of the tubing over whichthe insulation is being slipped should be covered to insurethat no foreign material is introduced to the interior of thetubing. The outdoor units are equipped with two refrigerantline service valves, and, as shipped, the valves are in thefront-seated or "down" position.

Line Set Installation InstructionsUse the following instructions to install line sets:

1. Tubing should be cut square. Make sure it is round andfree of burrs at the connecting ends. Clean the tubing toprevent contaminants from entering the system.

2. Wrap a wet rag around the copper valve stub beforebrazing.

3. Braze or silver solder the joint.

4. After brazing, quench with a wet rag to cool the joint.Evacuate and charge the connecting lines as outlined inthese instructions.

5. Remove valve top cap. It is important to keep the cap ina clean area to assure proper sealing once replaced.

6. Using a standard L shaped Allen wrench, break open thevalve body. To expedite opening the valve body after itis broken, use a ratchet wrench with a short Allen stub.Please note that it is normal to see oil on the valve stembody once the cap is removed.

7. Replace the valve cap and tighten with a wrench makingsure that the the cap is sealed.

LONG LINE RECOMMENDATIONSREFRIGERANT LINE LENGTH (Ft)

CondUnitTons1 1/2

22 1/2

3

3 1/2

45

0-24 25-49 50-74"*Line Diameter (In. OD)

Suct5/85/83/43/4

3/4

7/87/8

Liq

1/4

1/43/8

3/8

3/83/83/8

Suct3/43/43/4*3/4"

7/8"1 1/81 1/8

Liq

3/8

3/83/83/8

3/83/8

3/8

Duct3/43/4

7/87/8

1 1/81 1/8

1 1/8

Liq

3/83/83/8

3/8

3/83/8

3/8

* 7/8" required for full ratings** 1 1/8" required for full ratings

IO-103E 3/04

EVAPORATOR COIL

CAUTIONEVAPORATOR COILS ARE SHIPPED UNDER HIGHPRESSURE. USE EXTREME CARE AND FOLLOW THEINSTALLATION INSTRUCTIONS PROVIDED WITH THEEVAPORATOR COIL TO AVOID PERSONAL INJURY.

The indoor coil is pressurized. The copper caps must bepunctured to permit a gradual escape of the pressure priorto unsweating those caps. Immediately couple the tubing tothe indoor unit to avoid exposing the coils to moisture. Aproperly sized filter drier is furnished in the condenser. Whenmaking solder connections, make sure dry nitrogen flowsthrough the lines, when heating the copper, to preventoxidization inside of the copper. Hard solder (Sil-Fos) isrecommended, to provide a more lasing joint.

INDOOR CFM AND HEATING CAPACITY DETERMINATIONPrior to using the methods described below to check thesystem's charge, it is important to verify the operating capacityof the system and that the system is delivering sufficient airacross the indoor coil (CFM). The following procedures aresuggested methods for determining the system's operatingcapacity and CFM.

Airflow Determination - Indoor CoilThe heat pump system has been designed for optimumperformance with an airflow across the indoor coil equalingapproximately 400 CFM/TON e.g. A 2 TON system shouldhave 2 x 400 CFM/TON = 800 CFM. The systems airflowcan be determined by several methods.Airflow Test InstrumentsThere are a number of readily available instruments that canbe used in the field for airflow determination such asBarometers, Volume-Aire Air Balancers, Anemometers, andVelometers. When using these devices it is important to followthe manufacture's instructions provided with them.Temperature Rise Resistive Heat MethodAlthough this method is not as accurate as the use of testequipment, a method of determining the indoor airflow in asystem employing electric resistance heat as the backup heatsource is by the Temperature Rise Method and is calculatedusing the following formula:

CFM = KWx3413TEMPERATURE RISE x 1.08

WHERE:

KW=

Volts =

Amps =

Temperature Rise =

3413 =

1.08 =

The indoor section's measured input power =Volts x Amps

The measured Volts at the Indoor Section

The measured Amps at the Indoor Section

The temperature of the supply air - thetemperature of the return air

BTU per KW

Specific Heat Air Constant

e.g. :The input power to the indoor section = 10 KWThe Temperature Rise = 20°F

CFM = 10x341320x1.08

= 1580

Refer to the Airflow Measurement Table.

NOTE: The compressor circuit (outdoor unit) must be "OFF"to insure that the Temperature Rise measured across theindoor unit is due only to the electric heat.

Use the following instructions to determine the temperaturerise across the indoor section:1. Use the same thermometer for the measuring the return

and supply air temperatures to avoid thermometer error.Measure the temperatures within 6 Feet of the indoorsection and downstream from any mixed air sourcemaking sure that the thermometer is not exposed to anyradiant heat areas.Make sure that the air temperature is stable beforemaking measurement.

2.

3.

FIGURE 3

Temperature Rise Heat Pump Only MethodThe Temperature Rise Resistive Heat Method can be used todetermine the heating capacity of the heat pump system inthe heat pump "only" mode. The results obtained using thismethod should agree within 10% of the data published in theSpecification Sheets for the combination of indoor and outdoorsection.

NOTE: When using the following procedure to determine thesystem's capacity, make sure that the indoor section's backupheat source is de-energized.1. Use the same procedure described in the Temperature

Rise Resistive Heat Method to determine the system'sCFM and temperature rise across the indoor section.

2. Determine the BTU output of the system for the measuredTemperature Rise and system CFM by using the followingformula:

BTU = CFM x TEMPERATURE x 1.08

IO-103E 3/046

REFRIGERANT CHARGE DETERMINATION ANDADJUSTMENT - HEAT PUMP - COOLING CYCLEWeigh In Charge MethodThe method to insure that the heat pump system is properlycharged is by weighing in the amount of refrigerant specifiedon the outdoor sections nameplate, with additionaladjustments for line size, line length, and other systemcomponents. Heat Pump units are supplied R-22 chargesufficiently for typical matching evaporator and approximately15 Ft. of inner-connecting tubing. Systems having more than15 ft of interconnecting refrigerant lines require an additionalcharge allowance of R22.

LINE O.D. (IN)1/43/81/25/83/47/81 1/81 3/8

LIQUID LINE0.220.581.141.86

SUCTION LINE

0.040.060.080.150.22

Superheat MethodThe following information has been developed to determine theproper charge for Goodman Heat Pump Systems that arealready in operation.

NOTE: Many field variations exist which may affect theoperating temperature and pressure readings of a heat pumpsystem. All Goodman Heat Pump Systems utilize fixed orificerefrigerant control devices. The following procedure has beendeveloped for this type of refrigerant control device.1. With both base valves fully open, connect a set of service

gages to the base valves' service port, being careful topurge the lines.

2. Allow the system to operate at least 10 minutes or untilthe pressures stabilize.

3. Temporarily install a thermometer on the suction (large)line near the condensing unit's base valve. Make surethat there is good contact between the thermometer andthe refrigerant line and wrap the thermometer and linewith insulating tape to assure accurate readings.

IO-103E 3/047

4. Determine the systems superheat as follows:a. Read the system's suction pressure.b. Using the Saturated Suction Pressure (R-22) Table,

determine the system's saturated suctiontemperature.

c. Read the suction line temperature.d. The system's superheat = the suction line

temperature - the saturated liquid temperature.

SATURATED SUCTION PRESSURE (R-22)SUCTION SATURATED SUCTION

PRESSURE PSIG TEMPERATURE °F50

53

55

58

61

63

66

69

7275

78

81

26

28

30

32

34

36

38

40

42

44

46

48

5. Adjust the charge as necessary by adding charge to lowerthe superheat or bleeding the charge to raise thesuperheat.

SYSTEM SUPERHEATAMBIENT CONDENSER INLET

TEMPERATURE °F DB

100

95

90

85

80

7570

65

60

RETURN AIR TEMPERATURE °F DB

65

55

13

17

70

55

10

14

19

25

75

5

7

10

12

17

20

26

30

80

5

7

12

17

21

25

28

32

33

85

5

9

18

20

26

29

32

35

37

CAUTIONREMOVE THE SERVICE GAUGE SET FROM THE LINESCAREFULLY. ESCAPING LIQUID REFRIGERANT CANCAUSE BURNS.

Expansion Valve System-Subcooling Charge Method1. Fully open both base valves.2. Connect service gauge manifold to base-valve service

parts making sure lines are purged. Run system at least10 minutes to allow pressure to stabilize.

3. Temporarily install the thermometer to liquid (small) linenear condensing unit. Be sure that the contact betweenthermometer and line is good. Wrap thermometer withinsulating material to ensure accurate reading.

4. Referring to the Saturated Liquid Line Temperature Table,adjust charge to obtain a temperature 12-15°F below thesaturated liquid temperature.

Example:If liquid pressure is 260 psig refer to Saturated LiquidTemperature chart, 260 psig = 120° saturated temperature.Subtract liquid line temperature obtained from thermostatconnect to liquid line. The liquid line temperature must be12° -15° cooler than the refrigeration saturation temperature.

If the liquid line temperature is warmer than 12° - 15° addcharge to decrease, if the temperature of liquid line is lowerthan 12° - 15° recover charge from the system.

SATURATED LIQUID TEMPERATURELIQUID PRESSURE

(PSIG)200

210

220

230

240

250

260

270

280

290

300

SATURATEDTEMPERATURE °F

102

105

108

111

114

117

120

123

126

128

131

HEAT PUMP - HEATING CYCLEAs in the cooling mode, the proper method of insuring thatthe system is properly charge is by weight with the additionalcharge adjustments for line size, line length, and other systemcomponents as previously indicated.

Hot Gas MethodThe following procedure can be employed as a method to checkfor system charge in the heating mode by measuring the hotdischarge gas at the compressor.1. Allow the system to operate at least 20 minutes.2. Attach and insulate an electronic thermometer's probe

to the vapor service valve (large line) at the base valve.NOTE - Make sure that the probe is well insulated fromthe outdoor air.

3. Allow the system to operate at least 10 minutes.Afterwards, use an accurate electronic thermometer tomeasure the temperature of the discharge gas at theprobe.

4. Using the electronic thermostat, measure the outdoorambient temperature.

5. For check purposes the temperature measured on thehot gas line should be equal to the outdoor ambienttemperature plus 110°F (+ or-4°F). e.g: Outdoor Ambient45°F then the temperature measured by thethermometer's probe should be 155°F for a system thatis properly charged. If the temperature measured by thethermometer's probe is higher than the outdoor ambientplus 110°F, the system charge should be adjusted byadding refrigerant to lower the temperature. If thetemperature measured is lower than the outdoor ambientplus 110°F, the system charge should be adjusted byrecovering charge to raise the temperature

NOTE: When adjusting the charge in this manner allow thesystem to operate for at least 10 minutes before taking thenext temperature reading.

STARTUP PROCEDURE AND CHECK LIST

CAUTIONTURN OFF POWER AT ALL DISCONNECTS.

1. Set first-stage thermostat heat anticipator to . 12 and turnthermostat system switch to "COOL" and fan switch to"AUTO".

IO-103E 3/048

2. Turn cooling temperature setting as high as it will go.3. Inspect all registers and set them to the normal open

position.4. Turn on the unit's electrical supply at the fused disconnect

switch, both for the indoor unit and the outdoor unit.5. Turn the fan switch to the "ON" position. The blower

should operate 10 to 15 seconds later.6. Turn the fan switch to the "AUTO" position. The blower

should stop 90 seconds later.NOTE: If outdoor temperature is below 55°F, proceed tostep 9. Do not check out in the cooling mode.

7. Slowly lower the cooling temperature until the first mercurybulb makes contact. The compressor, indoor blower, andoutdoor fan should now be running. Make sure cool air issupplied by the unit.

8. Turn system switch to "HEAT" and fan switch to "AUTO".9. Slowly raise the heating temperature setting. After the

heating first-stage mercury bulb (upper) makes contact,stop moving the lever. The compressor, indoor blowerand outdoor fan should now be running. After giving theunit time to settle out, make sure heated air is beingsupplied by the indoor unit.

10. If the outdoor ambient is above 70°F, the compressormay trip on internal overload.

11. In the event that the outdoor ambient is too high to allowa thorough heating cycle check, postpone the test untilanother day when conditions are more suitable...but —DO NOT FAIL TO TEST.

12. If unit operates properly on the heating cycle, raise theheating temperature setting high enough until the heatingsecond-stage mercury bulb (lower) makes contact.

13. Supplementary resistance heat, if installed, should nowcome on. Make sure it is operating correctly. If outdoorthermostats are installed, the outdoor ambient must bebelow the set point of these thermostats for heaters tooperate. It may be necessary to jumper these thermostatsto check heater operation if outdoor ambient is mild.

14. For thermostats with emergency heat switch, return tostartup (Step #9). The emergency heat switch is locatedat the bottom of the thermostat. Move this switch toemergency heat. The heat pump will stop, the indoorblower will continue to run, all heaters will come on andthe thermostat emergency heat light will come on.

15. If checking the unit on the heating cycle in the wintertime,when the outdoor coil is cold enough to actuate the defrostcontrol, observe at least one defrost cycle to make surethe unit defrosts properly.

16. Check to see if all supply and return air grilles are adjustedand air distribution system is balanced for the bestcompromise between heating and cooling.

17. Check for air leaks in the ductwork.18. Make sure the heat pump is free of "rattles", and the tubing

in the unit is free from excessive vibration. Also makesure tubes or lines are not rubbing against each other,sheet metal surfaces, or edges. If so, correct the trouble.

19. Set thermostat at the appropriate setting for cooling andheating or automatic changeover for normal use.

20. Be sure the owner is instructed on the unit operation,filter servicing, correct thermostat operation, etc. The

foregoing "Start-up Procedure and Check List" isrecommended to serve as an indication that the heatpump system will operate normally.

OPERATION - DEFROST CONTROLTimingWhen operating, the power to the circuit board is controlledby a temperature sensor which is clamped to a return bendon the outdoor coil. Timing periods of 30, 60, or 90 minutesmay be selected by connecting the circuit board jumper wireto 30, 60, 90 respectively. Accumulation of time for the timingperiod selected starts when the sensor closes (approximately28°F) and when the wall thermostat is calling for heat. At theend of the timing period, a defrost cycle will be initiated,provided the sensor remains closed. When the sensor opens(approximately 65°F), the defrost cycle is terminated. If thedefrost cycle is not terminated due to the sensor temperature,a 10 minute override interrupts the defrost period.

Field Testing / Trouble ShootingA. Run unit in heat mode.B. Check unit for proper charge. Note: Bands of frost indicate

low refrigerant chargeC. Shut off power to unit.D. Disconnect outdoor fan by removing the purple lead from

"DF2" on defrost control.E. Restart unit and allow frost to accumulate.F. After a few minutes of operation, the defrost thermostat

should close. To verify this, check for 24 volts between"DFT" and "C" on board. If the temperature at thethermostat is less than 28°F and the thermostat is open,replace the thermostat as it is defective.

G. When the defrost thermostat has closed, short the "test"pins on the board until the reversing valve shifts,indicating defrost. This could take up to 21 secondsdepending on what timing period the board is set on.After defrost initiation, the short must instantly be removedor the defrost period will only last 2.3 seconds.

H. After the defrost has terminated, check the defrostthermostat for 24 volts between "DFT" and "C". Thereading should indicate 0 volts (open sensor).

I. Shut off power to unit.J. Replace outdoor fan motor lead and turn on power.

General Explanation and GuidanceThe heat pump is a relatively simple device. It operates exactlyas a Summer Air Conditioning unit when it is on the coolingcycle. Therefore, all the charts and data for service that applyto summer air conditioning apply to the heat pump when it ison the cooling cycle, and most apply on the heating cycleexcept that "condenser" becomes "evaporator", "evaporator"becomes "condenser" and "cooling" becomes "heating".When the heat pump is on the heating cycle, it is necessaryto redirect the refrigerant flow through the refrigerant circuitexternal to the compressor. This is accomplished with areversing valve. Thus, the hot discharge vapor from thecompressor is directed to the inside coil (evaporator on thecooling cycle) where the heat is removed, and the vaporcondenses into liquid. It then goes through a capillary tube,or expansion valve, to the outside coil (condenser on thecooling cycle) where the liquid is evaporated, and vapor goesto the compressor.

IO-103E 3/049

When the solenoid valve is operated either from heating tocooling or vice versa, it moves the pilot valve, thus puttingsuction pressure (low pressure) on one side of the piston ofthe reversing valve, and since discharge pressure (highpressure) is on the other side of the piston, the piston slidesto the low pressure side and reverses the flow of therefrigerant in the circuit.

The following figures show a schematic of a heat pump onthe cooling cycle and the heating cycle.

Heat Pump Refrigerant Circuit

FIGURE 4

In addition to a reversing valve, a heat pump is equippedwith an expansion device and check valve for the inside coil,and similar equipment for the outside coil. It is also providedwith a defrost control system.

The expansion device performs the same function on theheating cycle as on the cooling cycle. The check valves arerequired due to the reverse flow of refrigerant when changingfrom cooling to heating or vice versa.

When the heat pump is on the heating cycle, at which timethe outdoor coil is functioning as an evaporator, thetemperature of the refrigerant in the outdoor coil must bebelow the temperature of the outdoor air in order for therefrigerant in the outdoor coil to extract heat from the air.Thus, the greater the difference in outdoor temperature andoutdoor coil temperature, the greater the heating capacity ofthe heat pump. Since this is characteristic of heat pumps, it

is good practice to provide supplementary heat for all heatpump installations in areas where the temperature dropsbelow 45°F. It is also good practice to provide sufficientsupplementary heat to handle the entire heating requirementsif there should be a failure of heat pump, such as acompressor failure, or refrigerant leak, etc.Since the temperature of the liquid refrigerant in the outdoorcoil on the heating cycle is generally below the freezing point,frost forms on the surfaces of the outdoor coil under certainweather conditions of temperature and relative humidity,Therefore, it is necessary to reverse the flow of the refrigerantto provide hot gas in the outdoor coil to melt the frostaccumulation. This is accomplished by reversing the heatpump to the cooling cycle. At the same time, the outdoor fanstops to hasten the temperature rise of the outdoor coil andlessen the time required for defrosting. The indoor blowercontinues to run and the supplementary heaters areenergized.

MAINTENANCEGeneralOutdoor units do not require a planned prevenativemaintenance program under normal operating conditions, butnot less than once each cooling season, it is recommendedthat the unit be inspected and, if necessary, cleaned.Particular attention should be given to the air inlet side of theoutdoor coil to insure that leaves, grass, etc., are not beingdrawn into the unit. Restriction to air flow across the coil willresult in loss of system capacity, high operating pressuresand excessive operating costs. If the outdoor unit is installedadjacent to a grassy area, it is suggested that lawn mowersbe routed in such a manner that the discharge of the mowerwill be directed away from the unit. There must be air filtersinstalled in the system at some point upstream to the indoorcoil. Air filters should be inspected and, if necessary, replacedand/or cleaned AT LEAST once a month.

If disposable filters are used, an adequate supply of clean,unused filters of the correct size should be kept available.

CAUTIONEQUIPMENT SHOULD NEVER BE OPERATED WITHOUTFILTERS.

Permanent type filters may be vacuumed and/or washed butshould not be reinstalled until thoroughly dry. Most air filtersare marked to indicate the direction of airflow, and this shouldbe carefully noted when they are being installed.

CAUTIONNEVER TURN A DIRTY FILTER TO ALLOW AIRFLOW INTHE OPPOSITE DIRECTION.

The blower and motor bearings are permanently lubricatedand do not require additional lubrication.

It is recommended that the owner have available at leastone set of replacement fuses of the size supplied with theoriginal equipment.

CAUTIONDO NOT REPLACE FUSES WITH SIZES OTHER THANTHOSE SUPPLIED.

IO-103E 10 3/04

Common Causes of Unsatisfactory Operation of HeatPumps on the Heating CycleA. Dirty Filters or inadequate air volume through indoor coil.

When the heat pump is on the heating cycle, the indoorcoil is functioning as a condenser; therefore, the filtersmust always be clean, and sufficient air volume mustpass through the indoor coil to prevent excessivedischarge pressure and high-pressure cutout.

B. Outside Air into Return Duct: Cold outside air should notbe introduced in the return duct of a heat pump installationon the heating cycle close enough to the indoor coil toreduce temperature of the air entering the coil below 65°F.Air below this temperature will cause low dischargepressure, thus low suction pressure and excessive defrostcycling with resultant low heating output. It may also causefalse defrosting.

C. Undercharge: Undercharge on the heating cycle willcause low discharge pressure resulting in low suctionpressure and frost accumulation on the lower part of theoutdoor coil.

D. Poor "Terminating" Defrost Thermostat contact. Defrostthermostat must make good thermal contact on return bend,otherwise it may not terminate the defrost cycle quicklyenough to prevent unit from cutting out on high dischargepressure during the defrost cycle.

If the unit is on the cooling cycle, raise discharge pressure,by restricting airflow through the outdoor coil. If the valvedoes not shift after the above attempts, cut the unit off andwait until the discharge and suction pressure equalize, andrepeat above steps. If the valve still does not shift, replace it.

IO-103E 11 3/04

E. Causes of Malfunctioning Reversing Valve:1. Solenoid not energized. In order to determine if the

solenoid is energized, touch the nut that holds thesolenoid cover in place with a screwdriver. If the nutmagnetically holds the screwdriver in the Cooling mode,the solenoid is energized.

2. No voltage to solenoid. Check the voltage and ifthere is no voltage, check the wiring circuit.

3. Valve will not shift:a. Undercharged: check for leaks.b Valve Body Damaged: Replace valve.c. Unit Properly Charged: If it is on the heating cycle,

raise discharge pressure by restricting airflowthrough the indoor coil. If the valve does not shift,tap it lightly on both ends with screwdriver handle.

CAUTIONDO NOT TAP THE VALVE BODY.

IO-103E 12 3/04

10-103E 13 3/04

NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREINARE SUBJECT TO CHANGE WITHOUT NOTICE

Quality Makes the Difference!All of our systems are designed and manufactured with the same high quality standards regardless of size orefficiency. We have designed these units to significantly reduce the most frequent causes of product failure.They are simple to service and forgiving to operate. We use quality materials and components. Finally, everyunit is run tested before it leaves the factory. That's why we know.. .There's No Better Quality.

Visit our website at www.goodmanmfg.com for information on:• Goodman products• Warranties• Customer Services• Parts• Contractor Programs and Training• Financing Options

© 2003-2004 Goodman Manufacturing Company, L.P.

IO-103E 14 3/04