FOR ZX*(08, 09, 12, 14) ZY*(07, 08, 09, 12) SINGLE PACKAGE EQUIPMENT APPLICATIONSINCLUDING A FIELD INSTALLED HORIZONTAL POWER EXHAUST
Step 1:
Verify all unit parts in box.
2 ea. - Power Exhaust Assembly1 ea. - Hardware Bag:
16 ea. - Self-Tapping - #10 16 x ½ Screws
Figure 1
Figure 4
HORIZONTAL POWER EXHAUST ACCESSORYMODEL 2PE04704506 / 2PE04704525
2PE04704546 / 2PE04704558 INSTALLATIONINSTRUCTIONS
1073581-UAI-A-0913 (RSI FORM# YKIPH46)
Figure 2
Step 2:
Remove the control access panel. Remove the bloweraccess panel. Keep all screws for later use. See Figure 2.
Step 5:
Position the power exhaust assembies close to theopening cut in the return duct. Locate the harness markedwith the S2 connector on the power exhaust assembly withthe control box. Locate the harness marked with the P2connector on the power exhaust assembly without thecontrol box. Connect the S2 harness with the P2 harnesswithin the return duct. Secure the harness. Route thepower and control harnesses marked S1 and S11 thru thehole cut in the return duct to the return area of theeconomizer. See Figure 4.
BLOWER ACCESS PANEL
CON TROL AC CESS PANEL
RETUN DUCT
Step 3:
Remove the panel over the economizer hood (models ZX*09, ZX*12, ZX*14, ZY*08, ZY*09 and ZY*12 only).Remove the horizontal flow economizer hood. See Figure3.
Figure 3
ECONOMIZER HOOD
PANEL
HOLE IN ECONOMIZER FLOOR
HARNESS
Step 6:
Use self-tapping screws provided to mount the powerexhaust assembly over the hole cut into the return ductopening. After the power exhaust assembly is mounted tothe return duct, pull any remaining slack in the powerexhaust power and control harnesses thru the return ductinto the return area of the economizer.
WARNINGElectric shock hazard. Can cause injuryor death. Before attempting to performany service or maintenance, turn theelectrical power to unit OFF atdisconnect switch(es).
Step 4:
Cut hole in return duct 19 38" wide x 18" tall where power
exhaust is to installed. See Figure 3.
1819 3
8
19 38
6
HORIZONTAL POWER EXHAUST ACCESSORYMODEL 2PE04704506 / 2PE04704525
2PE04704546 / 2PE04704558 INSTALLATIONINSTRUCTIONS
Locate the power exhaust control harness with wirenumbers 843 (grey) and 844 (brown). Connect thisharness to the location marked EX-FAN / COM on theeconomizer controller. Secure this harness to avoiddamage during normal damper operation. See wiringdiagram for details.
Step 7:
Locate high voltage harness with black, blue and yellowwires (NOTE - yellow wire is not included with single phasepower exhaust assemblies). Route the power harnessthru the unit and along the existing harnesses in the unitback to the unit control panel as illustrated in Figure 5.Secure the power exhaust power harness to the existingharnesses throughout the unit with (field supplied) wireties.
WIRING ROUTING
Figure 5
Step 8:
Connect the power harness to the line side of contactor M1(see unit control panel component map for location ofcontactor M1). Remove and reconnect existing wires asnecessary using the pigtails provided with the powerexhaust power wires. Connect the black wire to terminal 1on contactor M1, the blue wire to terminal 2 on contactorM1 and the yellow wire to terminal 3 on contactor M1(Yellow wire only on 3 phase units). See wiring diagram.
Step 9:
Install control access panel and blower access panel using screws originally used to hold the panels in place. SeeFigure 6.
Figure 6
BLOWER ACCESS PANEL
CON TROL AC CESS PANEL
RETUN DUCT
Figure 7
PANEL
ECONOMIZER HOOD
Step 11:
Reconnect power to the unit - follow all safety instructions,rules and codes.
See unit Installation, Operation and Maintenance manualfor instructions to verify the unit controller recognizes theinstallation of the power exhaust.
Note: Once the unit is operating properly, seal anyopen joints, holes or seams with silicone caulking(field supplied), to make the power exhaustcompletely air and water tight.
1073581-UAI-A-0913 (RSI FORM# YKIPH46)
Step 10:
Install the economizer hood. Install the panel over theeconomizer hood (models ZX*09, ZX*12, ZX*14, ZY*08,ZY*09 and ZY*12 only). See Figure 7.
208-230 Volt 1 Phase Power Ex haust for2PE04704506
Notes:1. Pro vided har nesses with power ex haust, field in stalled.2. Field con nec tion to M1 ter mi nal strip, re move cur rent wires and con nect to pig tails.3. Field con nec tion to Economizer con trol ter mi nal con nec tor.
CON NEC TOR & CON TACT CON FIGU RA TIONP1 & P11 (300000292) PLUG - (30303912) PIN
P2 (30303903) PLUG - (30303912) PINS1 & S11 (300000291) CAP - (30303913) SOCKET
S2 (30303903) CAP - (30303913) SOCKET
Re vi sion Change DateWIRE COLOR CODE
BLK Black BLU BlueBRN Brown GRN GreenGRA Gray ORN Or angeRED Red VIO Vi o letWHT White YEL Yel low
HARNESS DETAIL
E# = WIRE END DESIGNATIONE2 STUD #6 18 Ga. WireE3 Female ¼ Quick Disc.E4 Male ¼ Quick Disc. InsulE6 Wire Nut Size 73B
Date: No vem ber 21, 2013
Supersedes:
Drawn by: MGL
Unit #: 80-470-46-21
Di a gram#: 804704621w
Ap proved by:
HAR NESS LEADS ARE 14 GA.WIRE WITH NO END
DES IG NA TION
C CapacitorFB Fuse BlockFM Fan MotorGRD GroundP1 Fan Plug MaleP11 Field Plug MaleM5 ContactorS1 Control Box FemaleS11 Field Cap Female
COMPONENT CODE
10
73
58
1-U
AI-A
-09
13
(R
SI F
OR
M#
YK
IPH
46
)
208-230 thru 575 Volt 3 Phase Power Ex haust for 2PE04704525 / 2PE04704546 / 2PE04704558
Notes:1. Pro vided har nesses with power ex haust, field in stalled.2. Field con nec tion to M1 ter mi nal strip, re move cur rent wires and con nect to pig tails.3. Field con nec tion to Economizer con trol ter mi nal con nec tor.
CON NEC TOR & CON TACT CON FIGU RA TIONP1 & P11 (300000292) PLUG - (30303912) PIN
P2 (30303903) PLUG - (30303912) PINS1 & S11 (300000291) CAP - (30303913) SOCKET
S2 (30303903) CAP - (30303913) SOCKET
Re vi sion Change DateWIRE COLOR CODE
BLK Black BLU BlueBRN Brown GRN GreenGRA Gray ORN OrangeRED Red VIO VioletWHT White YEL Yellow
HARNESS DETAIL
E# = WIRE END DESIGNATIONE2 STUD #6 18 Ga. WireE3 Female ¼ Quick Disc.E4 Male ¼ Quick Disc. InsulE6 Wire Nut Size 73B
Date: No vem ber 21, 2013
Supersedes:
Drawn by: MGL
Unit #: 80-470-46-23/-33/-43
Di a gram#: 8047046x3w
Ap proved by:
HAR NESS LEADS ARE 14 GA.WIRE WITH NO END
DES IG NA TION
FB Fuse BlockFM Fan MotorGRD GroundP1 Fan Plug MaleP11 Field Plug MaleM5 ContactorS1 Control Box FemaleS11 Field Cap Female