Make the most of your energySM
Improve your process and energy management with the Modicon™ M340™ PAC
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
When you need to achieve your energy and productivity improvement objectives by delivering innovative solutions throughout your enterprise, to create a single environment to measure energy usage, process data, asset utilization and machine performance, turn to Schneider Electric!
Our innovative PLC solutions allow you to:• Reduceengineering,operationsandmaintenancecosts
• Maximizeplantandproductionefficiency
• Improveproductionquality
• Protectpeople,plantassetsandtheenvironment
• Supportproductionandbusinessdecisions
2
Smart Instrumentation Smart Instrumentation
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
Extremely powerful, rugged and compactThe Modicon M340 programmable automation controller (PAC) provides cutting-edge features and high-end performance in a mid-range processor. Using commercial integrated circuit technology, the M340 PAC utilizes modern data networking to interact with distributed inputs/outputs (I/O), drives, other PAC devices and enterprise-type entities. It also uses the same Unity™ Pro application development software as the Modicon Quantum™ and Premium™ equipment, making it easy to quickly select, program and implement the controller to optimally manage simple to complex applications.
3
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
Advantages for your applicationTheModiconM340PACprovidesnumerouscostandperformanceadvantagesovercomparablypricedPACsby:
•Requiringnobattery,whichhelpstominimizemaintenancecostsandhelpstoeliminateprogramlossasaresultofapowerfailure.
•Offeringacompactsize(4in.heightby3.7in.depth),whichreducespanelsizeandcosts.
•Utilizinghigh-density64pointdiscreteI/Ocardsthatareonly1.25in.wideandprovidetheabilitytomanagelargeamountsofI/Oinaverycompactspace.
•Utilizinghigh-density8-channelanalogI/Oforvoltageorcurrent.
•Offeringpre-terminatedcableswithflyingleadsorTelefast™connectionstoreducewiringtime.
•UsingenhancedEtherNet/IP4-portswitchthatsupportsbothEtherNet/IPandModbus™TCP/IPandcanconnectI/Oinadaisy-chainarchitecture.
•UsingCANopennetworkstoreducefieldwiringandlowerinstallationcosts.
•ProvidingRTUmodulethatsupportsDNP3.0andIEC60870-5serialorModbusTCP/IPconnections.
•UtilizingUSBconnectionsforprogrammingratherthanproprietarynetworks,therebypromotingopenstandards.
•ExceedingIECrequirementsforshockandvibration.
Integrate Modicon M340 PACs into your plant control system and boost your return on investment
4
Enhance power and speedTheModiconM340PACenhancesprocessingpowerwith4MbofinternalRAM,upto128MbofadditionalmemoryonanSDflashmemorycardandanexecutionspeedofupto8.1Kinstructions/ms.
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
5 IntegratedUSBport •Foraprogrammingterminalor
human/machineinterface
6 Twocommunicationports •ChooseModbus,EthernetorCANopen
7 Adaptabletoharshenvironments
•Conformallycoatedtowithstand harshenvironments
•Extendedtemperature:-25°Cto70°C
8 RTUmodule •Dataloggingwithtimestampinginside
theRTUmoduleSDcard
•E-mail/SMSforalarmandreportnotifications
•WebserverforRTUProtocolssetup, diagnosticsandmonitoring
1
2
4
6
3
85
7
1 Compactness •Height:100mmor3.937in.
•Depth:93mmor3.661in.forintegration in150mmor5.906in.enclosures
2 Adaptablerack •4,6,8or12modules
•Extensibleupto4racks
• “HotSwap”functionforeasymaintenance
3 HighdensityI/Omodules •DiscreteI/Omoduleshave16,32or
64channels
•AnalogI/Omoduleshave2,4,6(4in/2out) or8channels
4 Widepowersupplychoice •24...48Vdc
•24Vdc/0.9Asensorsupplyoutput
•100...240Vac
5
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
Get more with an integrated and cost effective solution for water, wastewater, oil and gas applications
The Modicon M340 PAC offers extensive features and modularity suitable for RTU and telemetry applications including:
•Thein-rackRTUmodulethatsupportsIEC60870-5-101(Serial–MasterorSlave)andIEC60870-5-104*(overIP–ClientorServer)andDNP3protocols(DNP3Serial–MasterorSlave,DNP3IP–ClientorServer)
•FullrangeofCPUandI/Omodulesforoperationinextendedtemperaturesandharshenvironments(conformalcoating)
•Specializedfunctionsblocksforflowcalculations(AGA3-7,8,9-5and11)
•Expandablerack-basedmodularI/OconfigurationsanddistributedI/Ocapabilities
•HighdensityI/Omodules(discrete,analogand125Vdc)
•SerialandEthernetcommunicationsportsarebuilt-intotheCPUandothermodules
•SupportsModbus,ModbusTCP(ClientandServer),CANopen,ASiandEtherNet/IP
Built-in functions include:• DataloggingwithtimestampinginsidetheRTUmoduleSDcard
• E-mail/SMSforalarmandreportnotifications
• WebserverforRTUProtocolssetup,diagnosticsandmonitoring
6
*IEC60870-5-101(IEC101)isaninternationalstandardforpowersystemmonitoring,controlandassociatedcommunicationsfortelecontrol,teleprotectionandassociatedtelecommunicationsforelectricpowersystems.IEC60870-5-104(IEC104)protocolisanextensionofIEC101withthechangesintransport,network,linkandphysicallayerservicestomeetthecompletenetworkaccessrequirements.
In-rackM340RTUmodule
•HV/MVsubstations
•Sitedistribution
•MV/LVsubstations
•Reclosers
•Monitoring
•Measurement
•Tankfarms
•Compressorstations
•Pipelines
•Distribution
•Measurement
•Treatment
•Smalltreatment
•Largepumping
•Smallpumping
•Reservoirs
•Monitoring
•Measurement
•Tunnels
•Machines
•Generators
•Windmills
•Telecom
•Monitoring
•Measurement
Power Oil and Gas Water wastewater Other INFRA
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
It’s rugged and reliableTheModiconM340PACrequiresnobatteriesandexceedsIECrequirementsforshockandvibrationstandards.Thistranslatesintomoremountingoptions,continuousoperationsatremotelocationsandtheknowledgethatprogrammingwon’tbelostduringpoweroutagesasaresultofadeadbattery.
It’s smartTheModiconM340PACallowsyouto“HotSwap”moduleswithoutrebootingthePACforfasteraccessandresponsiveness.Inaddition,4Mbofmemoryimprovesthesharingofdatabystoringdrawings,billsofmaterialsandcutsheetsrightinsidethePAC’smemory,aswellasusingfaultydevicereplacement(FDR)tostoreconfigurationsandloadthemintoreplacementdevicessuchasdrives.There’salsoanSDflashmemorycardwithupto128Mbavailableforapplicationbackupincludingtheexecutableprogram,sourcecodeandcommentsanddata.
It’s web friendlyTheModiconM340PACfeaturesanembeddedwebbrowser,whichutilizesSchneiderElectric’sTransparentReady™web-basedconnectivityplatformforremotemonitoringandtroubleshooting.Thisalsoenablesuserstomaintainanaccuraterecordofequipmentlifeandschedulepredictivemaintenancebasedonknownvariablesandmilestones.
It’s connectableImplementationandconnectivityhaveneverbeeneasierastheModiconM340PACembedsModbusMasterserialprotocolandEthernetonthesameprocessor.Inaddition,installationcostsandwiringerrorsarereducedbyutilizingaCANopennetwork,FCN/HE10connectors,preterminatedcableswithflyingleadsandstandardUSBcablingtolinktoyourprogrammingPC.
More of what you need!
8
Numerous certificationsTheModiconM340platformconformstointernationalstandardsandmarineclassifications.
Certifications
Internationalstandards
CE
UL
CSA,CSAClass1Div2
C-Tick
GostR
Marinecertifications
ABS
DNV
RMRS
BV
GL
LR
RINA
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
It countsThecountingofferonModiconM340PACprogrammablecontrollersincludes:
•Twomodules:2x60kHzchannelsand8x10kHzchannels,highperformancewith32-bitcounting,cycletime1µs,twocaptureregistersandreflexactionswithresponsetimedownto200µs
•Configurableadvancedservicesofferingafilteroneachinput,awidechoiceofreflexactions,pulsegenerator,mechanicalplayreducer
•Countingandmeasurementmodeconfigurablefunctions
It positionsTheModiconM340PACofferspositioningsolutionsthatareintegrated,flexibleandhighlyeconomicalforapplicationsimplementingindependentandmaster/slavelinkedaxes.Noaxismoduleneedstobeaddedtotheconfigurationbecausethesolutionisbasedonamotionfunctionblock(MFB)libraryconformingtoPACopenstandard.VariablespeeddriveandservomotorcontrolisbyMFBcommandsviaCANopen.
It controlsAlibraryofcontrolloopfunctionsisintegratedasstandardinUnityProsoftware.IEC61131-3functionblockdiagramlanguageenablescompletelygraphicandhighlyflexibleprogramming.Youthereforeoptimizeyourcontrolloopalgorithmandkeepcontroloftheoperation.
InadditiontoPIandPIDcontrollers,thelibraryintegratesnumerousadvancedblocks:
•PIDautomaticadjustment(autotune)
• Integratorwithlimitation,firstandsecondordervariationlimiter
•Two-orthree-positioncontroller,PIhot/cold,PIPandPPIcascade
•Functiongenerator
•PD/PIregulatorstructureswitching
•Durationpulsemodulation
Counting
Positioning
Control Loop
Counting
Positioning
Control Loop
Counting
Positioning
Control Loop
9
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
SustainableTheUnityProdevelopmentsoftwareistheonlyprogrammingtoolyouneedtofullydevelop,test,debugandmanageyourapplicationsthatleveragethecurrentModiconlineofindustrialcontrollers.Itsversatility,ease-of-useandbuilt-inlibraryofpre-testedapplicationfunctionblocksallowuserswithmulti-processorapplicationstoshareideasandinformationvisually,soindividualsandteamscanbenefitfromtheircollectiveexperienceandworktogethermoreeffectively.Asaresult,yousavetimeandmoneybyreducingon-sitedevelopment,installationtimesanddebuggingacrossyourapplication’sentirelifecycle.
Reduce your development costs
Choose your languageTheUnityProsoftwareoffersfiveIEC61131-3languagesasstandard.Eachsectionofcodecanbeprogrammedinthelanguageofyourchoice,adaptedtoeachprocessingoperation.Alledit,debuggingandoperationtoolsareaccessiblewhateverthelanguageused.
•LD:ladderdiagram
• IL:instructionslist
•ST:structuredtext
•SFC:sequentialfunctionchart
•FBD:functionblockdiagram
10
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
Operates in severe environments
IEC Modicon M340Mechanicalconstraints IEC60068-2-x —
Shock 15gn 30gn
Vibration 1gn 3gn
Electricalimmunity IEC61000-4-x —
Electromagneticfield 10V/m 15V/m
Electrostaticcontactdischarge 4kV 6kV
Environmentalimmunity IEC60068-2-x —
Temperature -25°Cto70°C -25°Cto70°C
Altitude 2000m 4000m
Standard processor High performance processorBMX P34 1000 BMX P34 2000 BMX P34 2010 BMX P34 2020 BMX P34 2030
Executiontime
Booleaninstruction 0.18μs 0.12µs 0.12μs 0.12μs 0.12μs
Numericalinstruction 0.26μs 0.17µs 0.17μs 0.17μs 0.17μs
Internalmemory
UserRAMmemory 2048kB 4096kB 4096kB 4096kB 4096kB
ProgramKinstructions 35Kinst. 70Kinst. 70Kinst. 70Kinst. 70Kinst.
Userdata 128kB 256kB 256kB 256kB 256kB
SDcardmemory
Filestorage — 128MB 128MB 128MB 128MB
Applicationbackup 8MB 8MB 8MB 8MB 8MB
Webserver 2MB 2MB 2MB 2MB 2MB
Communication
IntegratedUSBport 1 1 1 1 1
IntegratedTCP/IPEthernet — — — 1 1
IntegratedCANopen — — 1 — 1
IntegratedModbus 1 1 1 1 —
Applicationexpertise
Counting yes yes yes yes yes
Positioning — yes yes — yes
Controlloop yes yes yes yes yes
Flexibility and performance
11
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com
SchneiderElectricUSA,Inc.
AutomationandControlCenterofExcellence8001KnightdaleBlvd.Knightdale,NC27545Tel:919-266-3671www.schneider-electric.us
DocumentNumber8000BR1107 March2011lh
Thisdocumenthasbeenprintedonrecycledpaper
SchneiderElectricCanada,Inc.
19WatermanAvenueToronto,ONM4B1Y2Tel:1-800-565-6699
©2
011
Sch
neid
erE
lect
ric.A
llR
ight
sR
eser
ved.
Talk to someone you can trustWhenweintroducedthefirstprogrammablecontroller,wewererespondingtotheneedsofourcustomersforbetter,moreeffectivemachinecontrol.Morethan40yearslater,wecontinuetolistenandworkwithyoutopioneerinnovativenewwaysofdeliveringvalue,efficiencyandperformance.
Thiscommitmenthasearnedusareputationfordependability,innovationandreliabilitythatisthedefiningcharacteristicofSchneiderElectricteammembersfromaroundtheworld.Thisincludesproductspecialists,industryexperts,distributors,partnersandthecountlessothermembersoftheSchneiderElectricfamily.
FormoreinformationonhowtoputSchneiderElectrictoworkforyou,orabouttheModiconM340PAC,visitwww.schneider-electric.us/go/plcorcontactyourSchneiderElectricsalesrepresentativeordistributor.
Provided by N
ortheast Pow
er System
s, Inc. w
ww
.nepsi.com