IEEE DG Anti-Islanding Paper

Embed Size (px)

Citation preview

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    1/17Driven by Energy

    IEEE DG Anti-islanding

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    2/17

    1758 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    A Power Line Signaling Based Techniquefor Anti-Islanding Protection of Distributed

    GeneratorsPart I: Scheme and AnalysisWilsun Xu , Fellow, IEEE , Guibin Zhang, Chun Li , Member, IEEE , Wencong Wang , Student Member, IEEE ,

    Guangzhu Wang , Member, IEEE , and Jacek Kliber , Student Member, IEEE

    Abstract Anti-islanding protection of distributed generators(DG) is a signicant technical barrier to the emerging DG in-dustry. This paper presents an innovative power line signalingbased anti-islanding scheme developed in response to the chal-lenge. The scheme broadcasts a signal from a substation to theDG sites using the distribution feeders as the signal paths. A DGis considered as islanded from the upstream system if the signalcannot be detected at the DG site. The proposed scheme has beenevaluated using analytical, simulation and eld tests. The resultsare very promising. This paper presents the main ideas of thescheme and its design considerations. Methods to create and detectthe signals are shown and their performances are analyzed.

    Index Terms Distributed generation, distributed generation(DG) interconnection, islanding detection.

    I. INTRODUCTION

    D ISTRIBUTED GENERATION (DG) has recently gaineda lot of momentum in the power industry due to marketderegulation and environmental concerns. An important re-quirement to interconnect a DG to power distribution systemsis the capability of the generator to detect island conditions.Islanding occurs when a portion of the distribution systembecomes electrically isolated from the remainder of the powersystem, yet continues to be energized by distributed genera-tors. Failure to trip islanded generators can lead to a numberof problems to the generators and the connected loads. Thecurrent industry practice is to disconnect all distributed gener-ators immediately after the occurrence of islands. Typically, adistributed generator should be disconnected within 100 to 300ms after loss of main supply [1], [2].

    To achieve such a goal, each distributed generator must beequipped with an islandingdetectiondevice, which is also called

    Manuscript received April 3, 2006; revised June 7, 2006. This work wassupported in part by the Alberta Energy Research Institute and four utilitycompanies in Alberta (ATCO, Epcor, Enmax, and FortisAlberta). Paper no.TPWRD-00174-2006.

    W. Xu, G. Zhang, W. Wang, and J. Kliber are with the Department of Elec-trical and Computer Engineering, University of Alberta, Edmonton AB T6G2V4, Canada (e-mail: [email protected]).

    C. Li is with Hydro One, Toronto, ON M5G 1P5, Canada (e-mail:[email protected]).

    G. Wang is with the School of Electrical Engineering, Shandong University,Jinan 250061, China (e-mail: [email protected]).

    Color versions of one or more of the gures in this paper are available onlineat http://ieeexplore.ieee.org.

    Digital Object Identier 10.1109/TPWRD.2007.899618

    anti-islanding device. The common devices used for this pur-pose are the modied versions of the under/over voltage andunder/over frequency relays such as the rate of change of fre-quency relay (ROCOF) and the vector surge relay (VSR) [3].These relays work on the principle that a power imbalance inthe islanded system will lead to frequency drift. However, theycannot function properly or fast enough if the generation andload mismatch is small [4].

    In order to overcome the above problem, a few schemes thatrequire a DG to inject small disturbances to the system havebeen proposed [5], [6]. Some of them have gained acceptancefor inverter-based DGs. However, no active schemes have beenfully developed for synchronous machine based DGs. Anothermain challenge facing the active schemes is the interactionamong the DGs that introduce similar disturbances to thesystem. At present, there is no answer to this question.

    In addition to the above local information based schemes,techniques that use telecommunication means to trip islandedDGs have been used in industry [7]. In addition to high cost,such a transfer trip scheme can be very complicated as well.For example, each openable device between the DG and thesupply system needs a transmitter. Some of the devices need tobe recongured and equipped with the capability of interfacingwith the signal transmitter. If telecommunication coverage isweak or non-existent, the cost of a transfer trip scheme alonecould kill a DG project.

    Over the past several years, anti-islanding protection for DGhasemerged as oneof themost challenging technicalbarriers forDG interconnection, especially for synchronous generators con-nected at medium voltages. Many research projects have beenconducted to solve the problem worldwide. Reference [8], [9]provides a good review on this issue.

    This paper presents a fundamentally different approach forDG anti-islanding protection. The scheme continuously broad-casts a signal from theutility substation to the downstream DGs.As a result, it transforms the detection of islanded DGs into thecheck of signal continuity between the substation and the DGsites. This scheme is quite unique as it combines the advantagesof the transfer trip and local detection schemes. Power line isused as a communication medium. The scheme is intended forsynchronous machine based DGsconnected to primary distribu-tion systems. It has been investigated for more than 3 years in-cluding extensive eld evaluations. The results have been quitepromising. The objective of this paper is to present key ideas of the scheme and their analysis. Field test results will be reported

    in a companion paper.0885-8977/$25.00 2007 IEEE

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    3/17

    XU et al. : POWER LINE SIGNALING PART I 1759

    Fig. 1. Illustration for the proposed anti-islanding scheme.

    II. DESCRIPTION OF THE PROPOSED SCHEMEThe proposed scheme shown in Fig. 1 includes two devices:

    a signal generator (SG) connected to the substation bus and asignal detector (SD) at the terminal of a given DG. The signalgenerator broadcasts a signal to all distribution feeders with apreset protocol continuously. If the detector of the DG does notsense the signal (caused by the opening of any devices betweenthe substation and the DG) for certain duration, it is consideredas an island condition and the DG can be tripped immediately. If the substation bus loses power, which is another islanding con-dition, the signal generator also loses power and stops broad-casting. So that downstream DGs will also trip. Furthermore,

    the signal generator has several auxiliary inputs. Any one of theinputs can stop the broadcast, resulting in tripping all DGs inthe system. This feature is particularly useful when transmis-sion system operators need to trip the DGs. It is also useful if atransmission system island is formed.

    This scheme works like a transfer trip scheme. However,since power line is used as signal carrier, the opening of anydevices can be detected automatically. It works independentof network topology changes (feeder recon guration). Thescheme is also economical since one SG installed at the substa-tion can satisfy the need of all the downstream DGs. Anotherimportant advantage is that the scheme can be tested withoutactually breaking up the distribution feeders. The main testscould be done by simply stopping the signal generator. Thesignal detectors should detect null signal in this case.

    A. Signal Generator (SG)

    Some mature techniques are available to send signals andeven information over power lines. Examples include ripplecontrol technique, waveform shift technique and waveformdistortion technique [10] [12]. For islanding detection purpose,the signaling technique should be reliable, low cost and have afast response. It is also desirable to have minimum interferencewith power communication schemes that already exist in adistribution system. After extensive evaluation on variousschemes, the waveform distortion technique is chosen as themeans to broadcast signals.

    Fig. 2. Signaling method and resulting waveforms.

    Principle of the waveform distortion technique is shown inFig. 2(a) [12]. A step down transformer (also called signal trans-former) reduces the secondary side voltage of the substation toa level for thyristor operation. It also limits short circuit cur-rent and voltage distortion when the thyristor is turned on. Thethyristor turns on several degrees before its voltage crosses zero,creating a momentary short circuit. The thyristor automaticallyturns off when its current reverses direction. Fig. 2(b) shows theresulting waveforms. It can be seen that there is a small distor-tion around the zero crossing point of primary feeder voltage.This distortion voltage is the signal. If the thyristor does not re,there is no waveform distortion and thus no signal.

    To facilitate detection, the anti-islanding signal can be as-signed certain patterns. For example, it can be broadcast forevery 2, 3 or 4 cycles and through a certain channel, say, phase

    A to Ground (denoted as A-G channel), B-G, or C-G. Phase-to-phase channels (A-B, B-C or C-A) are also available, in whicha thyristor is connected and red between two phases to createsignals over the phase-phase voltage. Two anti-parallel thyris-tors can be used to re at the voltage rising or falling edges somore signal patterns are available for use.

    B. Signal Detector (SD)

    The signal detector installed at the DG terminal examines thepresence of the anti-islanding signal and determines if an is-landing condition has occurred. A signi cant feature of the pro-posed scheme is that the signal is extracted by subtracting two

    consecutive voltage cycles (Fig. 3). The thyristor is red in away such that the voltage distortion exists in only one of twoconsecutive cycles. The difference between these two cycles isthe distortion voltage, i.e. the signal. This subtraction method isextremely powerful since it lters out the background distortionin the voltage waveforms. The scheme is therefore essentiallyimmune to background waveform distortions.

    After a voltage distortion signal is extracted, additional algo-rithms are needed to detect if a signal indeed exists. Details of the signal detection algorithms will be explained in Section V.

    III. D ESIGN PARAMETERS FOR SIGNAL GENERATOR

    There are two key design parameters for the signal generator.One is the size of the signal transformer and the other is the

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    4/17

    1760 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    Fig. 3. The subtraction method for signal extraction. (a) Voltage waveform(signal is at the 3rd cycle); (b) voltage distortion signal waveform.

    Fig. 4. Analysis of the signaling circuit.

    rating of the thyristor. The signal transformer is selected to en-sure there is suf cient signal strength. The thyristor is selectedto meet voltage and current stress requirements. The case whereSG res between phase A and ground as shown in Fig. 4(a) isused as an example to determine the design parameters. Thesteady state sinusoidal voltage at the secondary side of the signaltransformer when there is no signaling can be expressed as

    (1)

    where is the rated phase-to-phase voltage at the secondaryside of signal transformer. According to superposition principle,the signalingprocess is equivalent to injecting a negative voltagesource between phase A and the ground at point T. Thesignaling transient can be calculated with a circuit energized by

    as shown in Fig. 4(b), where is the self-inductanceof the supply system at point X,and is the signal transformer

    inductance. In this circuit, the other two phases are approxi-mated as open circuits, so are the loads connected to the feeders.

    If the thyristor is red ahead of s zero crossing point byan angle of , the thyristor conduction period will be , and thevoltage distortion signal at point X and the thyristor current canbe determined as

    (2)

    (3)

    where and . The correspondingwaveforms are shown in Fig. 5.

    Fig. 5. Waveforms of the anti-islanding signal and thyristor current.

    TABLE IEQUATIONS ABOUT SIGNAL STRENGTH AT POINT X

    The peak of represents the strength of the anti-is-landing signal, which is

    Dening the signal strength as the ratio of signal peak to thepeak of its carrier voltage, we can obtain

    (4)If the distribution system in Fig. 4 is grounded through an reac-tance , the signal strength will be

    (5)

    Both (4) and (5) can be converted to the form of Table I bysubstituting the impedances with the system fault level and thetransformer capacity. If the system neutral is grounded througha resistance , the above analytical method still works. How-

    ever, the signal strength cannot be calculated using (5) unlessis much smaller than .

    Table I summarizes the equations of signal strength P-G andP-P signaling channels. Note that for the P-P signaling, thesignal strength is not affected by system grounding condition.These equations can be used to select signaling transformer.

    Based on the above analysis, the average and RMS values of the thyristor current can be determined as

    (6)

    (7)

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    5/17

    XU et al. : POWER LINE SIGNALING PART I 1761

    TABLE IIEXAMPLE SG P ARAMETERS

    Fig. 6. Single line diagram of the simulation system.

    where

    Phase-Ground

    Phase-Phase signaling (8)

    stands for the interval between two ring events in the unitof number of cycles. A large such as 4, 5 or 6 can be used toreduce the heating stress on the thyristor. The side effect is thata larger may delay the response speed of the signal detector.

    As an example, a case where a SG is to be installed at a12 kV substation bus whose fault level isand is considered. If , ,

    , (ring at every 4th cycle), the min-imum size of signal transformer and thyristor current are listedin Table II.

    IV. S IGNAL CHARACTERISTICS

    This section investigates the characteristics of the anti-is-

    landing signal as seen at a DG site. A representative 25 kVdistribution system shown in Fig. 6 is used for this purpose.Parameters of the system are listed.

    Utility: 25 kV, impedance 6.25 j14.4 ohm, connected. Feeders: Line1 is10kmand Line2 is1 km; , , ,

    are 0.2138, 0.3928, 0.3875, 1.8801 ohm/km, respectively,and , are 4.2315 and 1.6058 Microsiemens/km,respectively.

    DG transformer: 25 k/480 V, connection, 6 MVA,impedance 6%.

    DG: 480 V, 5 MVA, impedance 25%; connected. Load: R-L load, 2 MVA; power factor of 0.9. Capacitor: 0.8 MVar. SG: 3-phase transformer 25/0.48 kV, 150 kVA, impedance

    3%; ring angle of 20 ; A-B signaling.

    Fig. 7. Equivalent circuit for signal propagation analysis.

    SD: located at the 480 V bus of DG transformer; detectionchannel is B-G (the P-G channel with the strongest signal).

    The equivalent circuit representing the system is shown inFig. 7. For simpli ed analysis, both the load and the resistivecomponents are ignored. According to the principle of superpo-sition, the anti-islanding signal at the DG site is the response of the system energized by a virtual voltage source , where

    is the steady state sinusoidal phase A-Bvoltage. This source is injected between phase A and B at the

    secondary side of the SG transformer during thyristor conduc-tion. Symbols , , , , and rep-resent the positive sequence inductances of the utility system,SG transformer, Line1, Line2, DG transformer and DG, respec-tively. represents the shunt capacitance.

    ,The Laplace transformation of anti-islanding signal is deter-

    mined to be

    (9)

    where

    (10)

    According to theaboveequations, the following conclusions canbe drawn.

    The signal at the DG site is initially driven by voltagesource during the thyristor conduction period.After that, the signal is oscillatory at the system natural fre-quency of the system .

    represents the signal level at theSG connection point X. The signal strength at DG terminalis reduced according to the ratio of . I t can be

    seen that a very large DG (meaning a small value)will lead to signal attenuation.Computer simulations have been carried out to study the anti-

    islanding signals. Representative signal waveformsare shown inFig. 8.

    To determine which system components have more impacton the characteristics of the signal, key system parameters arevaried. The variations of these parameters are shown as per-centages of the base case values. Key signal characteristics of interest are the signal peak value, signal attenuation, and its os-cillation frequencies.

    Fig. 9 shows the signal strength at the DG site. It can beseen that the impact of line length and load level is not verysigni cant. The utility impedance has a large impact since it isthe main factor in uencing the voltage distortion level at the SG

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    6/17

    1762 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    Fig. 8. Representative signal waveforms (all convertedto valuesat 25 kV side).

    Fig. 9. Signal strengths as affected by system parameters.

    site. The impact of the DG impedance can be signi cant if the

    impedance becomes quite small. The impact of shunt capaci-tance is not straightforward. There is a value where the capacitorproduces maximum signal level. Detailed analysis of the causereveals that the phenomenon is related to the natural frequencyof the system and the associated resonance situation. It is a co-incidence in this case that the peak signal level occurs at 100%capacitor value. The signal RMSvalue is also determined. It wasfound that it has similar characteristics to the signal peak value.

    Fig. 10 shows theattenuation characteristicsof thesignal. Theattenuation factor is de ned as . It characterizes thedegree of signal reduction when it travels from the substationto the DG site. The attenuation is useful to guide the selection

    of SG size. The gure shows that the DG impedance (or DGcapacity) is the main factor in uencing signal attenuation. Forthe given system, when DGs capacity is lower than 10MVA, thesignal attenuation is insigni cant. For larger DG installations, astronger signal generator may be needed. The result also showsthat heavy load together with large shunt compensation can alsocause notable signal attenuation. The system impedance has anegligible effect on signal attenuation.

    The characteristics of signal frequency are shown in Fig. 11.This frequency a critical parameter for the SD algorithm ex-plained later. The frequency is estimated using a duration of three cycles of signal oscillation so it represents the dominantnatural frequency of the system. The results show that the size of shunt capacitance affects the frequency most, which is followedby the utility impedance. The Line length and DG impedance

    Fig. 10. System attenuation as affected by system parameters.

    Fig. 11. Signal oscillation frequencies as affected by system parameters.

    have mild effects. The load has little effect. The results also re-veal that typical signal frequency is within 200 600 Hz.

    The case where SD is installed at the HV voltage side of theDG transformer (at 25 kV) has also been studied. It was foundthat the signal strength is increased from 3.6% to 4.4%. As aresult, connecting SD at the HV side is a very effective wayto enhance signal detectability or to reduce the size of signalgenerator. On the other hand, the SD installation becomes moreexpensive since primary voltage PTs are needed. The simula-tion results have been compared with the analytical results in(10). A good agreement between the simulation and analyticalresults has been found. For example, the calculated oscillation

    frequency at the base parameters is 461 Hz. It is very close to thesimulation results. Due to space limitation, detailed comparisonresults are not shown. Main conclusion drawn from the compar-ative studies is that (9) and (10) can be used to estimate the keycharacteristics of the signal.

    V. S IGNAL DETECTION ALGORITHMS

    As mentioned in Section II, after the voltage distortion be-tween two consecutive cycles (denoted as ) is extracted,an algorithm is needed to detect whether a signal is actuallypresent or not. Based on the characteristics of the signal at theDG site presented in the previous section, three signal detec-tion algorithms are proposed and investigated. The objective isto choose the best algorithm for eld implementation.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    7/17

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    8/17

    1764 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    Fig. 15. Waveform of a windowed sinusoidal template.

    where is the magnitude of the harmonic. Note thatdue to the width of the DFT window used, only even order har-monics exist. A signal is considered as existent if indexis above a threshold.

    The impact of signal frequency on the performance of theproposed algorithm has been investigated. A simulated signalwaveform with different oscillation frequencies is input to the

    spectrum-based algorithm. The resulting spectrums andare examined to verify whether is an adequate indicatorof signal presence. The results are shown in Fig. 14. Fig. 14(a)shows the magnitudes of spectrum components. It can be seenthat as varies from 200 to 600 Hz, the highest component ap-pears between the 2nd harmonic to 10th harmonic. Which har-monic exhibits peak value is dependent on the signal frequency.If we taken 4th, 6th, 8th and 10th harmonics into account inthe form of (9), most signal peaks will be included.Fig. 14(b) shows that value. It can be seen thatvaries with respect to the signal oscillation frequency . When

    is within 200 600 Hz range, has a high response. Itsuggests that the index is suitable for the intended application. Infact, the index lters out low and high frequency noisesand could exhibit a better performance than the rst algorithm.

    The 3rd detection method is to compare the distortion wave-form with a signal template using the following cor-relation equation:

    (13)

    A higher index suggests a higher degree of match betweenthe signal and template. A threshold for the index is ap-

    plied to determine if a signal exists. An important considera-tion for this template-based method is how to select an adequatesignal template. A system dependent template will generally im-prove the reliability of detection. But it makes thesignaldetectortoo complicated. After studying various options, a windowedsinusoidal waveform shown in Fig. 15 is selected as the tem-plate. The template is aligned to the thyristor ring instant onthe voltage waveform. Since the thyristor ring angle is usuallyxed (say, 30 ), the template position is xed. Under ideal con-dition, the frequency of the template sinusoid should be equal tothe signal oscillation frequency. This will give almost perfect match between the signal and the template. In reality, however,the signal frequency is unknown. To overcome this problem, aset of templates is proposed, each with a different frequency andaligned at the same position.Utilizing thenatural frequency data

    Fig. 16. Detection results of a template-based algorithm. (a) C R indicescomputed using different templates. (b) Template R M S response to differentsignal frequencies.

    of [13], ve templateswith frequencies equal to 5th, 6th, 7th, 8thand 9th harmonics are selected. The detection index is

    (14)

    where is the calculation result with the th template.The impact of signal frequency on the performance of the

    template-based algorithm has also been investigated as well.The same simulated signal is input to the algorithm. The re-sults are shown in Fig. 16. Fig. 16(a) shows the index cor-responding to different template orders. As expected, the best

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    9/17

    XU et al. : POWER LINE SIGNALING PART I 1765

    template that yields the highest value varies with signal fre-quency. For the signal frequency range of 200 Hz to 600 Hz, thepeak value is obtained for templates corresponding to the4th to the 10th harmonics. The indices for the 5th to 9thtemplates are combined to derive an aggregate value asshown in (11). Fig. 16(b) shows the index. It can be seen

    that the index has similar features to those of . Itcan also be used for detection.All three algorithms have been tested using eld data, which

    eventually decides which algorithm is the best choice. Thethresholds were selected based on eld test results as well. Thendings are reported in the companion paper.

    VI. C ONCLUSIONS

    This paper has presented a new and powerful anti-islandingprotection concept and associated scheme for DG applications.The scheme is similar to the telecomm-based transfer tripscheme. However, the signal is sent through power line, which

    makes the scheme applicable to any distribution systems re-gardless the availability of telecomm means. More importantly,since the signal passes through any switches, breakers andother openable components connected between the substationand DG sites; the scheme is able to detect automatically theopening of any components. This has resulted in a signi cantlysimpli ed transfer trip scheme. In addition, the scheme is alsoeconomically attractive to DG owners and utilities, especiallyfor systems with multiple DG installations.

    This paper investigated the design considerations for thesignal generator. A set of design formulas is established. Typ-ical signal generator parameters are illustrated using actualsystem data. The proposed scheme can be implemented usingother signalling techniques. Developing a signalling techniquethat can take advantage of the simple requirement of anti-is-landing signalling to reduce the cost of signal generator is stilla subject worth research.

    The paper further investigated the characteristics of theanti-islanding signal. Key factors that can affect the signalstrengthen, attenuation and frequency are identi ed. Based onthe ndings, three signal detection algorithms are proposed.The algorithms are tested using simulated waveforms.

    ACKNOWLEDGMENT

    The authors would like to thank the following companies andindividuals: ATCO Electric (B. Howell, T. Palladino, S. Mathur,T. Parsons, and D. Flasha), Epcor Power Corporation (A. Mak,J. Byron), FortisAlberta Ltd. (R. Bahry), Enmax Corporation(B. Dreyer) and Dr. S. T. Mak. They would also like to thank the following current and former researchers of the Universityof Alberta power quality research group for their help: Y. Cui,X. Wang, S. Abdulsalam, M. Zha, and A. Terheide.

    REFERENCES[1] IEEE Guide for Interfacing Dispersed Storage and Generation Fac-

    itlities With Electric Utility Systems, ANSI/IEEE, 1988, IEEE/ANSIStd. 1001-1988.

    [2] Recommendations for the Connection of Embedded Generating Plant to the Regional Electricity Companies Distribution Systems , Std.G59/1, Electricity Assoc., 1991, Electricity Assoc. Std..

    [3] N. Jenkins, R. Allan, P. Crossley, D. Kirschen, and G. Strbac , Em-bedded Generation , 1st ed. London, U.K.: Inst. Elect. Eng., 2000.

    [4] W.Freitas,Z. Huang,and W.Xu, A practical method for assessingtheeffectiveness of vector surge relays for distributed generation applica-tions, IEEE Trans. Power Del. , vol. 20, no. 1, pp. 57 63, Jan. 2005.

    [5] P. O. Kane and B. Fox, Loss of mains detection for embedded gen-eration by system impedance monitoring, in Development in Power System Protection, IEEE Conf. Publ. , Mar. 1997, vol. 434, pp. 95 98.

    [6] M. E. Ropp, M. Begovic, and A. Rohatgi, Prevention of islanding ingrid-connected photovoltaic systems, Progr. Photovoltaics: Researchand Applications , vol. 7, no. 1, pp. 39 59, 1999.

    [7] C. J. Mozina, Interconnection protection of IPP generators at com-mercial/industrial facilities, IEEE Trans. Ind. Appl. , vol. 37, no. 3, pp.681 689, May/Jun. 2001.

    [8] W. Bower and M. Ropp, Evaluation Of Islanding Detection MethodsFor Photovoltaic Utility Int. Energy Agency, Rep. IEA PVPS T5-09,2002 [Online]. Available: http://www.oja-services.nl/iea-pvps /prod-ucts/download/rep5_09.pdf.

    [9] W. Xu, K. Mauch, and S. Martel, August 2004, An assessmentof the islanding detection methods and distributed generationislanding issues for Canada. A report for CANMET Energy Tech-nology Centre Varennes, Nature Resources Canada, 65 pages.[Online]. Available: http://cetc-varennes.nrcan.gc.ca/ chier.php /39002/2004-074_e.pdf.

    [10] P. M. Foord, Bi-Directional muti-frequency ripple control system, U.S. Patent 4 868 539, Sep. 1989.

    [11] S. T. Mak and D. L. Reed, TWACS, A new viable two-way auto-matic communication system for distribution networks. Part I: Out-bound communication, IEEE Trans. Power App. Syst. , vol. 101, no.8, pp. 2941 2949, Aug. 1982.

    [12] S. T. Mak, A new method of generating TWACS type outbound sig-nals for communication on power distribution networks, IEEE Trans.Power App. Syst. , vol. PAS-103, no. 8, pp. 2134 2140, Aug. 1984.

    [13] S. T. Mak and R. L. Maginnis, Power frequency communication onlong feeders and high levels of harmonic distortion, IEEE Trans.Power Del. , vol. 10, no. 4, pp. 1731 1736, Oct. 1995.

    Wilsun Xu (F05) received the Ph.D. degree from the University of BritishColumbia, Vancouver, BC, Canada, in 1989.

    From 1989 to 1996, he wasan Electrical Engineer with BC Hydro, Vancouverand Surrey, respectively. Currently, he is with the Department of Electrical andComputer Engineering, University of Alberta, where he has been since 1996.His research interests are power quality and distributed generation.

    Guibin Zhang received the B.Sc. and M.Sc. degrees in electrical engineeringfrom Shandong University, Jinan, China, in 1995 and 1998, respectively, andthe Ph.D. degree from Zhejiang University, Hangzhou, China, in 2001.

    Currently he is with the AMC Technologies Corporation, Edmonton, AB,Canada. His main research interests are power quality, HVDC, and FACTS.

    Chun Li (S99M01) received the B.Eng. and Ph.D. degrees in electricalengineering from Tsinghua University, Beijing, China, in 1996 and 2000,respectively.

    Currently, he is with the Asset Management Department of Hydro One Inc.,Toronto, ON, Canada, working on power system transients, electromagneticinduction, insulation coordination, etc. Prior to joining Hydro One, he was aPostdoctoral Fellow in the Electrical and Computer Engineering Department,University of Alberta, Edmonton, AB, Canada.

    Wencong Wang (S05) received the B.E. and M.Sc. degrees in electrical en-gineering from Tsinghua University, Beijing, China, in 1999 and 2003, respec-tively, and is currently pursuing the Ph.D. degree in the Electrical and Computer

    Engineering Department, University of Alberta, Edmonton, AB, Canada.Her research interests are distributed generation-related subjects and groundfault detection in noneffectively grounded distribution systems.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    10/17

    1766 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    Guangzhu Wang (M 02) received the B.Sc. degree in electrical engineeringfrom Xi an University of Architecture and Technology, Xi an, China, in 1984,and the M.Sc. degree in control engineering from Harbin Institute of Tech-nology, Harbin, China, in 1987.

    He has been with the faculty with the School of Electrical Engineering, Shan-dong University, Jinan, China, since 1987. In 2003, he was a Visiting Professorwith the Electrical and Computer Engineering Research Facility, University of Alberta, Edmonton, AB, Canada. His research interests include analysis and

    control of power converters, active power lters, multilevel converters, powerquality, power cable fault location, and fault detection in distribution systems.

    Jacek Kliber (S06) received the B.Sc. degree in electrical engineering fromQueen s University, Kingston, ON, Canada, in 2004 and is currently pursuingthe M.Sc degree in the Electrical and Computer Engineering Department at theUniversity of Alberta, Edmonton, AB, Canada.

    His research interests are related to distributed generation and power quality.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    11/17

    IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007 1767

    A Power Line Signaling Based Schemefor Anti-Islanding Protection of Distributed

    GeneratorsPart II: Field Test ResultsWencong Wang , Student Member, IEEE , Jacek Kliber , Student Member, IEEE , Guibin Zhang,

    Wilsun Xu , Fellow, IEEE , Blair Howell, and Tony Palladino

    Abstract Anti-islanding protection of distributed generators(DG) is a signicant technical barrier to the emerging DG in-dustry. In response to this challenge, a power line signaling basedanti-islanding protection scheme has been proposed in a com-panion paper. The scheme broadcasts a signal from a substationto the DG sites using the distribution feeders as signal paths. A DGis considered as islanded from the upstream system if the signal isnot detected at the DG site. This paper presents extensive eld testresults and experiences obtained for the proposed scheme. The

    results conrm that the proposed scheme is a very promising andeconomical method to satisfy anti-islanding protection require-ments for synchronous DG interconnections.

    Index Terms Distributed generation (DG) interconnection, dis-tributed generation, islanding, protection.

    I. INTRODUCTION

    D ISTRIBUTED GENERATION (DG) has recently gaineda lot of momentum in the power industry due to marketderegulation and environmental concerns. An important re-quirement to interconnect a DG to power distribution systems

    is the capability of the generator to detect island conditions.Islanding occurs when a portion of the distribution systembecomes electrically isolated from the remainder of the powersystem, yet continues to be energized by distributed generators.Failure to trip islanded generators can lead to a number of problems to the generators and the connected loads. Currentindustry practice is to disconnect all distributed generatorsimmediately after the formation of islands [1], [2]. Typically,a distributed generator should be disconnected within 100 to300 ms after loss of main supply.

    Over the past several years, anti-islanding protection forDG has emerged as one of the most challenging technical

    Manuscript received April 3, 2006; revised June 7, 2006. This work was sup-ported in part by the Alberta Energy Research Institute and in part by fourutility companies in Alberta (ATCO, Epcor, Enmax, and FortisAlberta). Paperno. TPWRD-00175-2006.

    W. Wang, J. Kliber, G. Zhang, and W. Xu are with the Department of Elec-trical and Computer Engineering, University of Alberta, Edmonton, AB T6G2V4, Canada (e-mail: [email protected]; [email protected]; [email protected]).

    B. Howell is with ATCO Electric Ltd., Nisku, AB T9E 7S5, Canada (e-mail:[email protected]).

    T. Palladino is with ATCO Electric Ltd., Edmonton, AB T5J 2V6, Canada(e-mail: [email protected]).

    Color versions of one or more of the gures in this paper are available onlineat http://ieeexplore.ieee.org.

    Digital Object Identier 10.1109/TPWRD.2007.899620

    barriers for DG interconnection. Many research projects havebeen conducted to solve the problem worldwide [3], [4]. Untilrecently, there is still no reliable and economical solution toprevent distributed synchronous generators from sustainingunintended electrical islands.

    Through more than three years of research effort, the au-thors have developed an innovative anti-islanding scheme. Thescheme continuously broadcasts a signal from the utility substa-tion to the downstream DGs. As a result, it transforms the detec-tion of islanded DGs into the check of signal continuity betweensubstation and DG sites. The scheme is developed mainly forsynchronous generators but it is also applicable to other typesof DGs. Key features of the scheme and its performance anal-ysis have been presented in a companion paper [6].

    Theobjective of this paper is to present extensive eld test re-sults on the proposed anti-islanding scheme. A prototype signalgenerator and detector were constructed in 2003 at the Univer-sity of Alberta. They were installed in the distribution systemof ATCO Electric Ltd., an Alberta utility company, for eldtests and evaluation. The prototypes were tested for more than

    6 months in 2004 from January to March and from Septemberto October. A lot of valuable information was collected on thecharacteristics of signal propagation, performance of signal de-tection algorithms and even the interference of the proposedscheme with an AMR system.

    This paper is organized as follows. Section II explains theeld test arrangement including key information on the pro-totype device. Section III presents main ndings of the eldtests. Section IV analyzes the results and evaluates the pro-posed signal detection algorithms using the eld data. Section Vpresents observations on the tests that were designed to deter-mine the interference between the proposed scheme and theTWACS AMR scheme.

    II. FIELD TEST ARRANGEMENT

    Thegeneral arrangement of the eld test is shown in Fig. 1. Aprototype signal generator (SG) was connected to the 25 kV busof a 216 fault MVA substation through a three-phase 300 kVA,25 kV/480 V step down (signal) transformer. A prototype signaldetector (SD) implemented on a laptop-basedLabview platformwas installed at a 347 V bus of a pipeline pumping station about10 kM away.

    A picture of the signal generator installed at the substationis shown in Fig. 2. The signal generator is designed to re the

    thyristor at 5, 10, 15, and 20 at the negative-going voltage zero-0885-8977/$25.00 2007 IEEE

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    12/17

    1768 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    Fig. 1. Field test arrangement.

    Fig. 2. Signal generator installed at the substation.

    crossing point. The signals can be sent between phase to groundor phase to phase. Based on the system parameters, the signalstrengths are estimated as 2.5% for phase to ground signalingand 2.1% for phase to phase signaling respectively at

    and for phase to ground signal reception. For the test resultsreported in the subsequent sections, the SG sent signals usingthe phase to phase channel and . For this signalingarrangement, the thyristor peak current is estimated as 1382 A.It was a concern that such a high current could cause excessivetemperature rise if the thyristors are red too frequently. As aresult, a signaling pattern of ring once every four cycles wasused. The thyristor RMS current is about 168 A.

    The signal detector is designed to operate with the 4-cyclesignaling pattern. Four consecutive cycles is de ned to be onesignaling period. If a signal is absent for 3 continuous signalingperiods, i.e. 12 cycles, an islanding event is detected. This

    means that the delay time for islanding detection is 12 cycles or200 ms. If the signal is absent originally for three signaling pe-riods but is detected for next three consecutive signaling periods,the event is considered as the starting of DG and a startingevent is detected. With this design, an individual abnormalsignal (de nition see [6]) does not cause starting or islandingevent. But if the signals are abnormal for three continuous pe-riods or the signals are normal but their pattern does not followthe signal generation pattern, a warning event is recorded and 24cycles of data are saved for of ine analysis. The built-in signaldetection algorithm was the RMS algorithm. This algorithm wasthe rst one conceived for the project. It is therefore the onlyone implemented for the eld test. The other two algorithms(spectrum and template [6]) were developed after the eld testto overcome the problems encountered by the RMS algorithm.

    Fig. 3. Sample voltage waveform and anti-islanding signal waveform.

    TABLE ISUMMARY OF FIELD TEST RESULTS

    During the eld test, the signal peak value was also tested as adetection index. Field experience show that the peak value wasvery sensitive to noise and the peak index was abandoned.

    III. SUMMARY OF

    FIELD

    TEST

    RESULTS

    The eld tests were conducted in the spring and fall of 2004.The most useful results were obtained during the fall test.Sample voltage and signal waveforms recorded for this test areshown in Fig. 3. It can be seen that the signal is invisible fromthe voltage waveform, implying that the signal has little impacton power quality. The signal waveform was extractedby subtracting the 1st cycle by the 2nd cycle, the 3rd cycle by4th cycle and so on of the carrier (voltage) waveform. Since thevoltage waveform has eight cycles, the signal plot contains twosignaling periods. Each period has two segments. One of themcontains the signal and the other doesn t. For the plot shown

    in the gure, the signal is in the rst segment. The gure alsoplots which is used for signal strength determinationand for signal detection.

    Table I summarizes the main results using RMS based signaldetection algorithm. The signal generator was turned on for fourperiods. As expected, all SG turn-off events, which representgenuine islanding events, have been correctly detected. Themain concern here is if the signal detector could cause nuisancetrips of a DG due to the inability to detect the existence of theSG signals. It can be seen from Table I that a total of four nui-sance islanding events occurred. This implies that the signaldetector failed to detect the presence of the signal for some of thesignaling periods. The threshold used for detection is also listedin Table I. Note that the peak of the carrier voltage is 480 V. Sothe RMS threshold is about 0.3% of the rated voltage peak.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    13/17

    WANG et al. : POWER LINE SIGNALING PART II 1769

    Fig. 4. Signal level during the eld test period.

    Fig. 5. Dominant signal frequency during the eld test period.

    Fig. 6. Example of measured anti-islanding signal (Sep. 26, 00:01:22).

    Figs. 4 and 5 show the signal strength (the -index of [6])and dominant signal frequency during the test period respec-tively. The data points are determined as follows: 1) a 16 cyclesof waveform representing four signalling periods are selectedrandomly within every one-hour window; 2) signal strength foreach signalling period is then determined, which yields four

    values; and 3) these four values are averaged to arrive at onedata point. So each point of the gure represents one hour.An example of waveforms that result in nuisance islanding

    events is shown in Fig. 6. This gure shows that the signals arenot strong enough for the 1st, 2nd, and 3rd periods. Therefore,the cause for the above nuisance islanding events is identi edas a weak signal along with high noise. The signal peak is onlyabout 5 V or 1% in this case. The average signal strength inpeak is about 1.9% (Fig. 4). The 1% signal level is too low to bedetected by the RMS detection algorithm.

    It is not clear, however, why the signal level dropped to 1%from a typical value of 1.9%. Fig. 4 does con rm that the signalstrength varied during the test period. Such a phenomenonneeds to be investigated further. One solution to the nuisanceislanding detection problem is to increase the signal level to

    about 3% to 4%. Improvement of the signal detection algorithmand/or increasing signaling periods will also help. This subjectwill be discussed in the next section.

    The eld test also showed that disturbances or noises maypresent themselves as signals even if the SG is actually of ine.In this case, the SD will incorrectly record such events as the

    starting of the signal generator. This problem is mitigated byimproving the veri cation of the uniformity of the signal patternfor several signal periods. As a result of this improvement, mostnuisance starting events have been eliminated as well.

    The eld test task also evaluated various warning eventsrecorded. The ndings are omitted due to space limitation.Main conclusions drawn from this eld test are summarized asfollows.

    All SG shut off events which represent genuine islanding cases have been detected correctly.

    The SD failed to detect the presence of the anti-islandingsignal for 4 occasions. This means that the nuisance tripsof DG could occur. There is a need to address this issue.

    The average level of the signals is about 1.9%, which isconsistent with the estimated level of 2.1%. However, thesignal level uctuates. The cause is not clear at present.More eld measurement is needed.

    The signal frequency does not have signi cant variationsduring the test period. The frequency is around 430 Hz.This characteristic is important for the spectrum and tem-plate based signal detection algorithms.

    IV. E VALUATION OF ALTERNATIVE SD A LGORITHMS

    The spectrum and template based signal detection algorithmswere proposed in response to the poor performance of the RMS

    based algorithm. The algorithms have been described in thecompanion paper [6]. In this section, they are evaluated usingabout 18 400 signalling periods recorded during the eld tests.These periods were recorded because they have low signal levelsthat lead to warning events or false islanding detection. To testthe robustness of the template-based algorithm, the templatesare aligned at the instant corresponding to a ring angle of 30 ,which is slightly different from the actual ring angle of 20 .

    1) Typical Performance: A set of normal signalling periodsis used as an example to show how the algorithms performanceis assessed. Recall that each signalling period consists of twosegments of signal waveforms (Fig. 3). One of them contains the

    signal. and are calculated for both segments.Theresults corresponding to the signal-containing segment is la-belled as with signal and those corresponding to the no-signalsegment are labelled as without signal . The results are shownin Fig. 7. For reliable signal detection, the two sets of values should be far apart. The vertical separation of the twocurves shows the ability of an algorithm to distinguish signalsfrom noises. For the results shown in Fig. 7, there is a clearseparation between the segments with signal and those withoutsignal. A detection threshold of, say, 1.2 V (for the spectrummethod) and 15 p.u. (for the template method) can be used todetect the signal easily.

    2) Performance With Respect to Four Nuisance Islanding Events: Waveforms recorded for the 4 false islanding eventsthat could cause nuisance DG trips were analyzed in detail.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    14/17

    1770 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    Fig. 7.R M S

    andR M S

    of signaling/non-signaling cycles from 31 records.

    Fig. 8. Performance of the RMS algorithm.

    Figs. 8 10 show the signal characteristics when different de-tection algorithms are applied to the data. According to Fig. 8,it is very hard to separate the signal-containing data from thenon-signal data. This is especially true for event 4. The ndingsexplain why the RMS algorithm will lead to false islanding

    detection for the signalling periods. In comparison, indicesand show improved separation between the sig-nals and noises. There will be no nuisance islanding detectionaccording to the new algorithms. When these algorithms areused, the false islanding detection events are eliminated.

    3) Statistical Signal Strength Analysis: To understand thestatistical performance of three detection algorithms, all 18 400signalling periods are played back to the algorithms. The resultsare shown in Figs. 11 13. To avoid crowding caused by massiveamount of data points, the plots just show the points sampledfrom the original results at a rate of 1 sample per 12 data points.It can be seen that the signal strength is generally constant forthe test duration. However, there is a large uctuation of signalstrength for period IV. Some of the high signal cases were anal-ysed and the cause was found to be AMR interference (see next

    Fig. 9. Performance of the spectrum based algorithm.

    Fig. 10. Performance of the template based algorithm.

    Fig. 11. Statistical performance of the RMS based algorithm.

    Fig. 12. Statistical performance of the spectrum based algorithm.

    section). For theperiod III, the signal levelis lower than average.The causes have not been found.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    15/17

    WANG et al. : POWER LINE SIGNALING PART II 1771

    Fig. 13. Statistical performance of the template based algorithm.

    Fig. 14. Distribution of the signal noise ratio of R M S , R M S , and R M S .

    To quantify the signal detection capability of different algo-rithms, an index of signal to noise ratio is determined. The ratiois dened as

    (1)

    Fig. 14 shows the statistical distribution of the ratio index.According to the gure, the average signal to noise ratios of

    , and are about 3, 4.5 and 6 respectively.A higher ratio means that the corresponding algorithm can de-tect the signal more reliably. The results con rm the observa-tion that the RMS based algorithm has the poorest performance.Note that although the ratio of has the highest average,it distributes in a wider range than the other two ratios. In theworst case, the ratio of drops to 2.8 and is close to the

    worst case of .Based on the above results, we canconclude that the spectrum

    and template based algorithms have better performance than theRMS algorithm. There is no signi cant performance differencebetween the spectrum and template based algorithms. Either of them can be selected for implementation. However, the algo-rithms have different computational burden, which becomes adeciding factor.

    V. INTERFERENCE OF ANTI -ISLANDING AND AMR S CHEMES

    The proposed anti-islanding scheme adopts the waveformdistortion technique for signaling [6]. The same technique hasalso been applied for automatic meter reading (AMR) [5] andload control applications. The potential interference between

    Fig. 15. Parallel operation of anti-islanding and AMR schemes.

    the anti-islanding and the AMR schemes becomes a naturalconcern. Understanding the nature and degree of inference iscritical to the acceptance of the proposed anti-islanding schemeby industry. Fortunately, the ATCO Electric is the rst utilitycompany that deployed the waveform distortion based AMRscheme. As a result, the project had the opportunity to evaluatethe interference concern. The test set up for this study is shownin Fig. 15.

    The AMR system was running concurrently with the SGduring test periods II and IV. Note that the AMR system alsosends signals occasionally even if no meter reading takesplace. The purpose is to calibrate time for the revenue meters.Test periods I and III were run under such condition. For alltest periods, the channels used by the AMR were essentiallyrandom. Main ndings from these tests are as follows.

    When the SG is ON, the AMR signal caused SD to detectwarning events. A number of warning events were capturedduring the period IV. This is due to the following reason: if the AMR signal appears at the same waveform location asthe anti-islanding signal (say negative-going zero-crossing

    point) and it is in a cycle ahead of the anti-islanding signalcycle, the subtraction of the two adjacent cycles will showno signal or very weak signal. As a result, the anti-islandingsignal may not be detected. For the same reason, the AMRsignal may also strengthen the anti-islanding signal. Thehigh signal level recorded in period IV is due to this cause.

    When the SG is OFF , AMR signals resulted in warning andeven starting events. This is due to the fact that the signaldetector treats the AMR signal as the anti-islanding signalmistakenly.

    Theoretically, the AMR signals could cause nuisance DGtrips by erasing the anti-islanding signal. For such events

    to happen, the AMR signal must have a pattern comple-ment to that of the anti-islanding signal so that the subtrac-tion of two waveform cycles result in null signal. This isa low probability event and it was not encountered in theeld.

    In summary, the impact of the AMR signal on the proposedanti-islanding scheme is not signi cant. This is because theAMR has not caused nuisance islanding detection when theSG is ON. It only caused warning events. Furthermore, if a SGis put into operation to send anti-islanding signals, a lack of a SG signal means islanding has happened. The AMR signalwon t be able to reach the DG site either. As a result, AMRsignal cannot sustain an island. So we can conclude that theAMR is very unlikely to cause interference to the anti-islandingscheme.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    16/17

    1772 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

    It is likely that the anti-islanding signal will affect the oper-ation of the AMR system. The experience of the ATCO Me-tering Department during the test did not suggest that such in-terference has happened. The AMR system worked smoothlyduring the entire eld test. One of the explanations may be thatthe AMR signal at 4% is much stronger than the anti-islandingsignal that is at 1.9%. However, a lot more eld tests are neededto con rm if the anti-islanding signal is indeed troublesome toAMR. Should interference exist, one of the solutions is to letthe AMR signal transmitter broadcast both meter reading andanti-islanding signals but using different signaling channels.

    VI. C ONCLUSIONS

    This paper has presented eld results and their analysis fora novel DG islanding detection scheme. The eld test arrange-ment and device settings are explained. The main ndings fromthe eld test study are as follows.

    The proposed scheme performed successfully during the

    eld test. The four false islanding events encounteredduring the test can be eliminated using improved signaldetection algorithms.

    The improved algorithms, either spectrum-based or tem-plate based, are more reliable for signal detection. Theyare recommended for uses in the signal detector of the pro-posed scheme. The degree of implementation (program-ming) dif culties will decide which one of them will beselected eventually.

    Investigation on the interference between the AMR andanti-islanding schemes shows that the AMR system isunlikely to cause problems to the anti-islanding scheme.Although eld experience suggests that the anti-islandingscheme did not interfere with the AMR system, more eldtest is needed to clarify this issue.

    The eld test experience suggests that a signal level of 4%is probably the best compromise between reliable signaldetection and the cost of signal generator. Power quality isnot a concern at this signal level.

    ACKNOWLEDGMENT

    The authors would like to thank the organizations and indi-viduals who have supported this project technically and/or -nancially during the past four years: ATCO Electric (S. Mathur,

    T. Parsons, and D. Flasha), Epcor Power Corporation (A. Mak,J. Byron), FortisAlberta Ltd. (R. Bahry), Enmax Corporation(B. Dreyer) and Dr. S. T. Mak. The following current and formerresearchers of the University of Alberta power quality researchgroup are also fully acknowledged: C. Li, G. Zhang, Y. Cui,X. Wang, S. Abdulsalam, M. Zha, and A. Terheide.

    REFERENCES

    [1] IEEE Guide for Interfacing Dispersed Storage and Generation Facitl-ities With Electric Utility Systems , IEEE/ANSI Std. 1001-1988.

    [2] Electricity Assoc., G59/1 recommendations for the connection of em-bedded generating plant to the regional electricity companies distribu-tion systems Electricity Assoc. Std., 1991.

    [3] W. Bower and M. Ropp, Evaluation of islanding detection methodsfor photovoltaic utility Int. Energy Agency, Rep. IEA PVPS T5-09,2002. [Online]. Available: http://www.oja-services.nl/iea-pvps/prod-ucts/download/rep5_09.pdf.

    [4] W. Xu, K. Mauch, and S. Martel, August 2004, An assessment of the islanding detection methods and distributed generation islandingissues for Canada, A report for CANMET Energy TechnologyCentre Varennes, Nature Resources Canada, 65 pages. [Online].

    Available: http://www.cetc-varennes.nrcan.gc.ca/ chier.php/39002/ 2004-074_e.pdf.[5] S. T. Mak, A new method of generating TWACS type outbound sig-

    nals for communication on power distribution networks, IEEE Trans.Power App. Syst. , vol. PAS-103, no. 8, pp. 2134 2140, Aug. 1984.

    [6] W.Xu, G.Zhang,C. Li, W.Wang,G. Wang,and J.Kliber, A power linesignaling based technique for anti-islanding protection of distributedgenerators Part I: scheme and analysis a companion paper submittedfor review.

    Wencong Wang (S05) received the B.E. and M.Sc. degrees in electrical en-gineering from Tsinghua University, Beijing, China, in 1999 and 2003, respec-tively, and is currently pursuing the Ph.D. degree in the Electrical and ComputerEngineering Department, University of Alberta, Edmonton, AB, Canada.

    Her research interests are distributed generation-related subjects and groundfault detection in noneffectively grounded distribution systems.

    Jacek Kliber (S06) received the B.Sc. degree in electrical engineering fromQueen s University, Kingston, ON, Canada, in 2004 and is currently pursuingthe M.Sc degree in the Electrical and Computer Engineering Department at theUniversity of Alberta, Edmonton, AB, Canada.

    His research interests are related to distributed generation and power quality.

    Guibin Zhang received the B.Sc. and M.Sc. degrees in electrical engineeringfrom Shandong University, Jinan, China, in 1995 and 1998, respectively, andthe Ph.D. degree from Zhejiang University, Hangzhou, China, in 2001.

    Currently he is with the AMC Technologies Corporation, Edmonton, AB,Canada. His main research interests are power quality, HVDC, and FACTS.

    Wilsun Xu (F05) received the Ph.D. degree from the University of British Co-lumbia, Vancouver, in 1989.

    From 1989 to 1996, he was an Electrical Engineer with BC Hydro at Van-couver and Surrey, respectively. Currently, he is with the Department of Elec-tricaland Computer Engineering, University of Alberta, where he hasbeen since1996. His research interests are power quality and distributed generation.

    Blair Howell received the B.Sc. degree in electrical engineering from the Uni-versity of Saskatchewan, Saskatoon, SK, Canada, in 1982.

    Currently, he is Superintendent of Distribution Standards and Operations withATCO Electric Ltd. and has more than 20 years of experience with electricutility operations, distribution planning, and the design of power system facili-ties. He has extensive experience in the successful interconnection of generatorsto ATCO Electric s distribution system, and was involved throughout the entireprocess of developing Alberta s Distributed Generation Interconnection Guide.

    Tony Palladino received the B.Sc. degree in electrical engineering from theUniversity of Alberta, Edmonton, AB, Canada, in 1977.

    He has 29 years of experience in the electrical utility business, primarily indistribution engineering and marketing. Since joining ATCO Electric (formerlyAlberta Power Ltd.) in 1977, he has been responsible for planning, design, andproject management of the company s distribution systems, and has been in-volved in the regulatory changes as the industry transitions into wholesale andretail deregulation. During the project eld test period, he was a Senior Man-ager of Customer Services of ATCO, where he is currently Manager of HumanResources.

  • 8/6/2019 IEEE DG Anti-Islanding Paper

    17/17

    Unit #105, 117 Pembina RoadSherwood Park, AB, CanadaT8H 0J4

    Phone: 780-467-0303Toll Free: 866-796-0303Fax: 780-401-3519

    7 Cedar Street, Suite 203Sudbury, ON, CanadaP3B 4H5

    Phone: 705-693-4829Toll Free: 1-877-693-482

    627A Aljunied Road#04-01 BizTech CentreSingapore 389842

    Phone: (65) 64814106

    For more information on these o r other

    products & services email us at:

    [email protected]

    2009 Enertia Engineering Ltd All rights reserved no reproduction without permission