39
Copyright 2012 HVAC Systems at Y2E2 CEE 243 CEE 243 Week 2 HVAC systems at Y2E2

HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

  • Upload
    others

  • View
    19

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

CEE 243

Week 2

HVAC systems at Y2E2

Page 2: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Today’s lecture will focus on HVAC systems and the

type of systems contained in Y2E2

Basic info about Y2E2

2

Introduce Product Hierarchies

to begin data analysis

Introduce the data collection system

and how to access that data

Contains a diverse range of HVAC

Systems and zone equipment

Page 3: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243 3

This class focuses on the analytical process to

understand actual building performance

Page 4: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Y2E2 design intent: maintain thermal comfort in

spaces by using the minimal amount of energy

4

Page 5: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

HVAC systems must account for a variety of inter-

related factors and ensure building function

• Building geometry

• Constructions and Materials

• Internal loads – People

– Lights

– Equipment

– Solar gains

• Air infiltration

• HVAC system – System type

– Equipment parameters

– Operating schedules

– Controls

• Weather

5

Room

Page 6: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Y2E2 is a new, large multi-purpose building

4 stories with approx 160,000 sf

6

A diverse range of space types ensures

a worthy challenge for analysis

Page 7: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Low energy features to mitigate peak load & reduce

overall energy consumption

Atria provide daylighting, support natural ventilation

7

Manually and automatically operable

windows support natural ventilation

Page 8: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Exposed concrete floors increase building

thermal mass

8

Page 9: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Active beams provide efficient conditioned fresh

air to spaces: mostly passive

9

Page 10: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Small PV units on roof contribute 1-2% of total

building electricity

10

PV Arrays

Page 11: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

District heating and cooling supplies most of the hot and

chilled water required on campus

11

http://news.stanford.edu/news/2009/october19/stanford-carbon-footprint-101909.html

Cardinal cogeneration plant

Page 12: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

HVAC Systems

Page 13: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

supplies chilled water directly, steam to tempered

water heat exchanger for heating

13

AHU Coils Active beams

(cooling)

Fan coil:

coils

CAV/VAV

box: coils

Secondary loop

AHU Coils

Active beams

Radiant slab

VAVs

(heating)

Baseboard

radiators

Heat

Exchanger

CAV

box: coils

Secondary loop

Cold water loop

Hot water loop

Stanford

CoGen Plant

Page 14: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Main chilled water loop serves cooling coils and

server rack and tempered water loop

14

Serves:

• Tempered water loop

• Cooling coils

(AHU, FC, CVs, VAVs)

• Server Rack

Page 15: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Main chilled water loop

15

Serves:

• Tempered water loop

• Cooling coils

(AHU, FC, CVs, VAVs)

• Server Rack

Page 16: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

The tempered chilled water loop serves active

beams

16

Serves:

• Active beams

Page 17: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tempered chilled water

loop

17

Serves:

• Active beams

Page 18: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

The main hot water loop serves heating coils,

radiators and tempered water loop

18

Serves:

• Tempered water loop

• Heating coils

(AHU, CVs)

• Radiators

Page 19: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Main hot water loop

19

Serves:

• Tempered water loop

• Heating coils

(AHU, CVs)

• Radiators

Page 20: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tempered hot water loop serves active beams

radiant slab, heating coils (VAVs)

20

Serves:

• Active beams

• Radiant slab

• Heating coils (VAVs)

Page 21: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tempered hot water loop

21

Serves:

• Active beams

• Radiant slab

• Heating coils (VAVs)

Page 22: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Zoning Example: 2nd Floor

Page 23: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Integrated HVAC air systems serve offices and exhaust

through an atrium

23

CAV or VAV

box

Active beam

(cooling/

heating)

Diffuser

Zone 1

Active beam

(cooling/

heating)

Active beam

and/or

diffuser

Zone 2 Zone 3 Zone …

CAV or VAV

box

AHU

Atrium

Outside Air

Page 24: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

North facing space contain radiators to balance

out fabric losses

24

Fabric heat loss through materials w/ temperature

difference, e.g., walls, windows, floor, roof.

Page 25: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

A typical air handling unit contains fans, coils and HR

25 HR = heat recovery subsystem

Page 26: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Air handling unit

26

Page 27: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Fan coil units condition mechanical, electrical and

data rooms

27

Page 28: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Active beams provide supplementary heating or

cooling

28

Page 29: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Two representative offices on the north side contain

measurement points for radiant heating and ceiling

29

Page 30: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Two representative offices on the south/west side

contain measurement points for active beams

30

Active beams for heating and cooling

Page 31: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243 31

The overall mechanical ventilation strategy uses

atria for to exhaust air

Page 32: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243 32

Naturally ventilated perimeter zones exhaust to the

atria, air flow rates are controlled by dampers

Page 33: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Tobias

data logger

The control system enables building and campus wide access

to data

33

Saved at one minute interval

into MySQL database

LONWORKS based

control system

iLON servers as interface

between LON and Ethernet

Data access via MySQL client

IP: 171.67.81.12

Username: CEE243

Password: Iwantmoredata

More info in tutorial

Page 34: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Product Hierarchies (original) enable a view of

buildings for the purpose of performance analysis

Site

Portfolio

Building

Building Story

Tennant

Zone/Micro Zone

Zone/Micro Zone

HVAC Systems

System Components

34

Legend:

Physical asset

System or component

Has Part

HVAC Systems

Page 35: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Product Hierarchies (Maile 2010) link geometric

and HVAC representations of building objects

35

Page 36: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Product Hierarchies have multiple uses including

displaying efficacy of measurement points

36

Page 37: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Product Hierarchies: Y2E2

37

Page 38: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243

Concluding

38

Page 39: HVAC systems at Y2E2 - Stanford University · HVAC Systems at Y2E2 CEE 243 HVAC systems must account for a variety of inter-related factors and ensure building function • Building

Copyright 2012

HVAC Systems at Y2E2

CEE 243 39