HVAC BasicsThe Basics of Heating, Ventilation and Air Conditioning
Presented by: Mark Kartchner, PE, LEEDKartchner Engineering
Energy Use Office Buildings
Mechanical System CostsFirst Cost - Water cooled chillers beat Air cooled chillers at about 200 Tons (80,000 SF)SEL HQ VAV-$10.5/SF, FP-$1.9/SF, Plumb-$3.4/SF 90,000 SFCWC $12.5/SF WSHP & $3.5/SF Plumb 90,000 SF
Chart2
8
10.5
12
14
14.5
14.5
19
20
Mech Sys. Costs
Dollars ($)
Mechanical System Costs (Provide & Install)
Sheet1
RTU-Gas/Air Cooled8
RTU-Heat Pumps10.5
VAV-Elec Heat12
Multi Zone RTU14
VAV-Hot Wtr Heat14.5
WSHP-HP, Boiler, Chiller, Cooling Tower14.5
DOAS w/ 4-Pipe Fan Coil19
Variable Refrigerant Volume20
Sheet1
Mech Sys. Costs
Dollars ($)
Mechanical System Costs (Provide & Install)
Sheet2
Sheet3
HVAC Rules of ThumbAir - 1 CFM/SFCooling (office) 300/400 SF/TonCooling (office) 400 CFM/TonHeating 25-35 btuh/sf floor areaOutside Air 20 CFM/personToilet/Jan Closet 10 air changes/hour
HVAC Equipment/SFMechanical Room (Boilers/Chillers/Pumps/Misc) = GU College Hall = 2000 SF/186,000 = 1.1%
Mechanical Room (Boilers/Pumps/Misc) =RTF (tight) 300 SF/28,000 SF = 1.1%Colbert Elementary 312 SF/ 40,000 SF = 0.8%
RTU (Gas/Electric/VAV) =SEL Office (35x12 (2))/95,000 SF
Building Envelope
Load CalculationsHeating and CoolingAccuracy important!Design conditionsBuilding shell loadR, U valueInternal loadVentilation loadInfiltrationOccupancy schedules
Heat TransferConductionConvectionRadiationResistance (R-Value)U = 1 / RQ = U x A x T
U-Value is the rate of heat flow in Btu/h through a one ft2 area when one side is 1oF warmer
Actual R-Values
Window Types
The amount of solar heat energy allowed to pass through a windowExample: SHGC = 0.40Allows 40% through and turns 60% awaySolar Heat Gain Coefficient
Window PropertiesEnergy Calculations in the Spokane region show that reflective, and tinted windows increase energy usage on an annual basis.
Energy Saving Design Methods
Air Side Economizers Water Side Economizers Variable Frequency Drives Building Diversity Part Load Performance Thermal Storage Heat/Energy Recovery
HVAC SYSTEMSHeating, Ventilation and Air ConditioningProvides comfort for peopleAllows humans to exist under adverse conditions.
Basic Refrigeration Cycle
System Types Packaged Rooftop UnitSplit SystemAir to Air Heat PumpWater Source Heat PumpGeothermalVAV Variable Air VolumeUnder Floor Air Distribution (UFAD)Air to AirHydronic (water)PTAC / PTHP
Packaged Rooftop Units (RTU)
Split System
Heat Pump (Air to Air)Operate on simple refrigeration cycleReversing the cycle provides heatingTemperature limitationsAir to airWater sourceGeothermalLake coupled
Water Source Heat Pump
Geothermal Heat Pump Systems
(VAV) Variable Air Volume
VAV Terminal UnitsVariable volume: ParallelConstant volume: Series
Under Floor Air Distribution (UFAD)AdvantagesIndividual ControllabilityRe-Configurability2 Extra LEED PointsDisadvantagesMore Expensive ($8/SF for raised floor)Flexible for Change2 Extra LEED PointsInland Power & LightFirst UFAD in area
Hydronic systemsFour Pipe Fan CoilVAV w/ HW Reheat
Hydronic System Major EquipmentChillersBoilersCooling Towers
Chilled Water System
EconomizersAir SideWater Side
EconomizersFree cooling source: When available, use cool outdoor air instead of mechanically cooled air.55 oF80 oFMinimum supply of outside airNormal OperationOutside air dampers are positioned to provide the minimum outside airEconomizer OperationOutside air dampers are fully open. Maximum outside air is provided80 oF55 oF and up85%outside air85%exhaustHVAC-*
Enthalpy Wheels
Air DistributionGrilles, RegistersMany optionsGU Russell Theatre Return GrilleReturn PlenumExtra cost for plenum rated cable is less than cost of return ductworkNo Combustables
Outside Air Louvers
Outside Air Louvers provide an opening in a building wall to push air out, or pull air in.Provide clean outdoor air, avoid: loading docks exhaust vents plumbing stacks waste collection stagnant water
Metal DuctsSquare DuctworkMost commonLow heightRound DuctworkLess ExpensiveEasy to InstallLower static pressureTaller than RectangularHigher pressureLess SoundOval DuctworkSame advantages of roundHeight similar to rectangularMore expensive than rectangular
Fabric DuctsGreat for certain applicationsGymsPoolsManufacturingSpokane Science MuseumAdvantagesGreat DiffusionEasily CleanedFunSame cost as metal
Saved $300,000 in cost at high school. Lowered chilled water temp, & air temperatures
Additional EquipmentHeat ExchangersHumidifiersSilencers
Kitchen HoodsType 1: Hoods designed for grease exhaust applicationsType 2: Hoods designed for heat and steam removal and other non grease applications. (NFPA 96 does not cover)Where are Type 1 Commercial Hoods Required?NFPA 96 Cooking equipment used in processes producing smoke and grease-laden vapors shall be equipped withNPFA 96-A-1-1 intended to include residential cooking equipment where used for purposes other than residential family useType 1 Hood Clearances18 inches to combustible material3 inches to limited-combustible material 0 inches to noncombustible material
A restaurant with a commercial gas range is represented by the resteaurant owner to be used ony for the preparation of soups. What type hood is required?Type 1 hood is for collection and removal of grease laden vapors,and smoke. Type II hood is for removal of steam, odors, and vapors. It would be hard pressed to find a restaurant that only produces soups, with that commercial range. Hoods: where required, installed at or above all commercial-type deep fat fryers, broilers, fry grills, steam-jacketed kettles, hot-top ranges, ovens, barbeques, rotisseries, dishwashing machines, and similar equipment that produces comparable amounts of steam, smoke, grease, or heat in a food processing establishment. Food processing establishment shall include any building or portion used for the processing of food. Soup is a liquid food made up of simmering vegetables, seasonings, and often meat or fish. It is the potential of the equipment (Commercial gas range), rather than the utilization, that must be evaluated. So, what type of hood would be required for that commercial gas range in a restaurant would honestly be open for discussion. You will probably have some input from your local Fire Dept. through plan check as with the County Health dept. Requirements. I know of one City close to us that when a pizza parlor opens, no matter what, they require a type 1 hood. Depending on the type of pizza oven, we have allowed a type II.
Kitchen Hood TypesExhaust Hood w/ Supply Air Supplied by SpaceExhaust Hood w/Supply Air on Outside of HoodExhaust Hood w/Supply Air on Inside of HoodVapor HoodsSimple hoods designed to remove minimal heat, and high vapor.
ComfortComfort is primary intent of HVAC systems.ProductivityBuilding DurabilityHealthMold
ASHRAE Comfort Zone
PsychrometricsDry bulb temp.Wet bulb temp.HumidityDew pointMoisture contentHeatingCoolingHumidifyDe-Humidify
Historical Minimum Ventilation Rates (cfm/person)Tredgold 1836Nightengale 1865Billings 1895Flugge 1905Yaglou 1938ASHRAE 62-73ASHRAE 62-81Smoking 62-81ASH- RAE 62-89Smoking 62-89
Chart2
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
44
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
22.522.5
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
3030
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
1010
525
525
525
525
525
525
525
525
1560
1560
1560
1560
1560
1560
1560
1560
1560
1560
1560
Sheet1
183544Tredgold 1836
183644
183744
183844
183944
184044
184144
184244
184344
184444
184544
184644
184744
184844
184944
185044
185144
185244
185344
185444
185544
185644
185744
185844
185944
186044
186144
186244
186344
186444
186522.522.5Nightengale 1865
186622.522.5
186722.522.5
186822.522.5
186922.522.5
187022.522.5
187122.522.5
187222.522.5
187322.522.5
187422.522.5
187522.522.5
187622.522.5
187722.522.5
187822.522.5
187922.522.5
188022.522.5
188122.522.5
188222.522.5
188322.522.5
188422.522.5
188522.522.5
188622.522.5
188722.522.5
188822.522.5
188922.522.5
189022.522.5
189122.522.5
189222.522.5
189322.522.5
189422.522.5
18953030Billings 1895
18963030
18973030
18983030
18993030
19003030
19013030
19023030
19033030
19043030
19053030Flugge 1905
19063030
19073030
19083030
19093030
19103030
19113030
19123030
19133030
19143030
19153030
19163030
19173030
19183030
19193030
19203030
19213030
19223030
19233030
19243030
19253030
19263030
19273030
19283030
19293030
19303030
19313030
19323030
19333030
19343030
19351010Yaplou 1935
19361010
19371010
19381010
19391010
19401010
19411010
19421010
19431010
19441010
19451010
19461010
19471010
19481010
19491010
19501010
19511010
19521010
19531010
19541010
19551010
19561010
19571010
19581010
19591010
19601010
19611010
19621010
19631010
19641010
19651010
19661010
19671010
19681010
19691010
19701010
19711010
19721010
19731010
19741010
19751010ASHRAE 62-73
19761010
19771010
19781010
19791010
19801010
19811010
1982525ASHRAE 62-73Smoking 62-81
1983525
1984525
1985525
1986525
1987525
1988525
1989525
19901560ASHRAE 62-89Smoking 62-89
19911560
19921560
19931560
19941560
19951560
19961560
19971560
19981560
19991560
20001560
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
2026
2027
2028
2029
2030
2031
2032
2033
2034
2035
2036
2037
2038
2039
2040
2041
2042
2043
2044
2045
2046
2047
2048
2049
2050
2051
2052
2053
2054
2055
2056
2057
2058
2059
2060
2061
Sheet1
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
Sheet2
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
00
Sheet3
Improved Ventilation EffectivenessMechanically provide filtered and dehumidified outdoor air to the breathing spaceVary ventilation based on the number of occupants and process loads - changes in occupancy can be measured by CO2 sensors Consider designs that separate ventilation and space conditioningUtilize heat recovery systems to reduce system size and ventilation energy costs
Improved Ventilation EffectivenessEffective mixing of ventilation air within spaceNet positive pressure in the southeast; exhaust from appropriate spacesProvide clean outdoor air, avoid: loading docks exhaust vents plumbing stacks waste collection stagnant water
Acoustics
Octave Band
Directivity Factor
LEED Products
LEED-NC New Construction & Major Renovations LEED-EB Existing Buildings LEED-CI Commercial Interiors LEED-CS Core & Shell LEED-H Houses LEED-ND Neighborhood Developments LEED-Schools: K-12 Schools LEED-Retail: Retail facilities- In pilot stage LEED-Healthcare: Healthcare facilities- In pilot stage
LEED Checklisthttp://www.metrokc.gov/dnrp/summit/documents/LEED-Spataro.pdf
http://www.metrokc.gov/dnrp/summit/documents/LEED-Spataro.pdf
THANK YOU!
Additional Information / ResourcesASHRAE The American Society of Heating, Refrigerating and Air-Conditioning Engineerswww.ashrae.orgSouthface Energy Institute www.southface.orgGeothermal heat pump consortium www.geoexchange.orgwww.buildingscience.comwww.energycodes.govHVAC Acoustics for Green Buildings Mike Filler. Ashrae technical committee for Sound and VibrationMcQuay Application Guide AG 31-010 HVAC Acoustic FundamentalsEnergy Efficiency in Buildings Dr. Sam C M Hui Department of Mechanical Engineering
***********Solar Heat Gain Coefficient (SHGC)The glazings effectiveness in rejecting solar heat gain.Part of a system for rating window performance used by the National Fenestration Rating Council (NFRC)Gradually replacing shading coefficient (SC) in product literature and design standards convert SC to SHGC by multiplying the SC value by 0.87
*******An HVAC system consists of a heating and/or cooling source, a distribution system (e.g. ductwork or hot/chilled water piping) and temperature controls.
**********************************************