PVC INSULATED CABLES

1

CONTENTINTRODUCTION ________________________________________________2

PVC INSULATED CABLES 450/750 V, BS 6004 OR MS 136 ____________________________________3

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE 300/500 V, BS 6346 OR MS 274 ____________________________________4

PVC INSULATED, PVC SHEATHED ARMOURED CABLE 600/1000 V, BS 6346 OR MS 274 ___________________________________7

PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE 600/100 V, BS 6346 OR MS 274 ___________________________________10

PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE 600/1000 V, BS 6346 OR MS 274 __________________________________12

PVC INSULATED, PVC SHEATHED ARMOURED WITH REDUCED NEUTRAL CABLE 600/1000 V, BS 6346 OR MS 274 __________________________________13

CURRENT RATING

RATING FACTOR ______________________________________________14

CURRENT RATING _____________________________________________16

APPENDIX: TECHNICAL DATA

STRANDED ANNEALED COPPER AND ALUMINIUM CONDUCTORS FORMULA FOR ELECTRICAL CALCULATION ______________________21

WIRE GAUGES ________________________________________________23

COMMON CONVERSION FACTOR ________________________________24

PUBLICATIONS REFERRED TO __________________________________24

2

INTRODUCTIONLeader Cable Industry Berhad, incorporated in 1976, has grown steadily to become the country’s single largest cable manufacturer today since its 1990 merger with Universal Cable (M) Berhad under the flagship of its parents, Leader Universal Holdings Berhad (LEADER).

Through its far sighted planning and unceasing product and service innovation, LCIB has successfully cultivated a manufacturing profile of an extensive range of cable and wire products. From households, XLPE cables, telecommunication cables for both domestic and export markets. LCIB has achieved a distinguished reputation as a leading supplier of power and telecommunication cable to major corporations, both local and foreign.

Today, as a subsidiary of the LEADER group of companies, LCIB has one of the most advanced facilities for manufacturing PVC insulated cables in the Asia-Pacific region. The PVC insulated cables manufactured today by LCIB are internationally renowned for its world class quality standards.

PVC has been in use as an insulating and outersheathing material for a long time. Since PVC has some degree of flame retardance, and resistance to oils and chemicals, it has found many suitable applications including low power and control uses. Generally, there are two types of PVC, general purpose and heat resistant PVCs with maximum conductor temperatures of 70°C and 90°C respectively. PVC insulated cables are used in power distribution, building wire, appliance wiring, flexible cord and machine tool wiring. Communication applications use polyvinyl chloride coverings on a limited basis. Insulation and jackets made from polyvinyl chloride have a number of desirable properties that make them the insulation and jacketing material of choice for many common applications. These properties include flexibility, resistance to temperature, resistance to adverse environmental situations and low cost .

This catalogue serves as a guide to LCIB’s manufacturing processes and standards in the production of PVC insulated cables, both armoured and unarmoured, including one with reduced neutral conductor and a maximum phase-to-phase voltage of 1000 volt. The conductor used is mainly plain annealed copper. Other conductors, such as tinned copper and aluminium are also available and may be supplied upon request.

3

CU / PVC INSULATED CABLEConductor Plain annealed copper

Insulation PVC Compound

Colour of cores Red, Yellow, Blue, Black, White and Green or Green/Yellow

Conductor Thicknessof Insulation

Approx. overall diameter Approx net weight

Area Shapemm² mm mm Kg / Km

MS 136, BS 6004 & IEC 60227, 450/750 V1.51.52.5

2.546

101625

355070

95120150

185240300

400500630

s.c.r.m.s.c.

r.m.r.m.r.m.

r.m.r.m.c.c.

c.c.c.c.c.c.

c.c.c.c.c.c.

c.c.c.c.c.c.

c.c.c.c.c.c.

0.70.70.8

0.80.80.8

1.01.01.2

1.21.41.4

1.61.61.8

2.02.22.4

2.62.82.8

2.93.03.5

3.64.24.7

6.16.88.4

9.611.212.9

15.016.618.4

20.623.426.1

29.332.736.4

212333

355172

120175280

370500710

98012201490

187024503070

392049406280

Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded

4

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE ConductorsPlain annealed copper or aluminium

InsulationGeneral purpose PVC compound

Colour of coresSingle core - red and black 2 cores - red and black 3 cores - red, yellow and blue 4 cores - red, yellow, blue and black

Formation (i) Single core(ii) 2, 3, or 4 cores - stranded together and the interstices may be filled with the sheathing compound or textile. A non-

hygroscopic binder tape may be applied over the laid-up cores.

SheathBlack general purpose PVC compound

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (1-CORE)

ConductorThickness of

Insulation Thickness of sheath Approx. overall diameter Approx. net weightNominal

sectio nal area Shape

mm2 No./mm mm mm mm kg/km

BS 6004, 300/500V

1.52.54610162535

r.m.r.m.r.m.r.m.r.m.r.m.c.c.c.c.

0.70.80.80.81.01.01.21.2

0.80.80.90.90.91.01.11.1

4.75.36.36.88.29.411.312.6

37517699

150220340440

BS 6346 & MS 274, 600/1000V

5070951201501852403004005006308001000

c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.c.r.m.

1.41.41.61.61.82.02.22.42.62.82.82.83.0

1.41.41.51.51.61.71.81.92.02.12.22.32.5

14.916.919.220.823

25.528.831.835.439.143.347.853.1

6108301130138016902100274034104310538068208590

10760

Note : r.m. - circular stranded, c.c. - compacted circular stranded

5

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (2-CORE)

ConductorThickness of

InsulationThickness of

sheathApprox. overall

diameter Approx. net weightNominal sectional area Shape

mm2 No./mm mm mm mm kg/km

BS 6004, 300/500V

1.51.52.52.546

s.c.r.m.s.c.r.m.r.m.r.m.

0.70.70.80.80.80.8

1.21.21.21.21.21.2

8.58.99.7

10.111.212.3

100110140150200260

BS 6346 & MS 274, 600/ 1000V

10162535507095120150185240300400

r.m.r.m.c.c.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.

1.01.01.21.21.41.41.61.61.82.02.22.42.6

1.81.81.81.81.81.92.02.12.22.42.52.72.9

16.218.321.019.922.725.529.231.835.039.143.948.653.9

450620880920

122016702270280034104270556069308770

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (3-CORE)

ConductorThickness of

InsulationThickness of

sheathApprox. overall

diameter Approx. net weightNominal sectional area Shape

mm2 No./mm mm mm mm kg/km

BS 6004, 300/500V

1.51.52.52.546

s.c.r.m.s.c.r.m.r.m.r.m.

0.70.70.80.80.80.8

1.21.21.21.21.21.4

8.99.4

10.210.711.913.5

120130170180240320

BS 6346 & MS 274, 600/ 1000V

10162535507095120150185240300400

r.m.r.m.c.c.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.

1.01.01.21.21.41.41.61.61.82.02.22.42.6

1.81.81.81.81.81.92.12.22.32.52.62.83.1

17.219.422.322.826.129.534.137.140.945.751.457

63.6

530750

109013601810248033904180511064108360

1042013210

Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded

6

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (4-CORE)

ConductorThickness of

InsulationThickness of

sheathApprox. overall

diameter Approx. net weightNominal sectional area Shape

mm2 No./mm mm mm mm kg/km

BS 6004, 300/500V

1.51.52.52.546

s.c.r.m.s.c.r.m.r.m.r.m.

0.70.70.80.80.80.8

1.21.21.21.21.41.4

9.710.211.111.713.414.7

150160210220310410

BS 6346 & MS 274, 600/ 1000V

10162535507095120150185240300400

r.m.r.m.c.c

s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.s.m.

1.01.01.21.21.41.41.61.61.82.02.22.42.6

1.81.81.81.81.92.02.22.32.52.62.83.13.3

18.721.324.525.629.633.538.742.146.651.958.665.372.6

700960

14001820245033504580563069208640112901411017860

Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded

7

PVC INSULATED, PVC SHEATHED ARMOURED CABLEConductor Plain annealed copper or aluminium

Insulation General purpose PVC compound

Colour of cores Single core - red and black2 cores - red and black3 cores - red, yellow and blue4 cores - red, yellow, blue and black Formation(i) Single core(ii) 2,3, or 4 cores - stranded together and the interstices may be filled with the sheathing compound or textile. A non-

hygroscopic binder tape may be applied over the laid-up cores.

Bedding Black general purpose PVC compound

Armour Single core - Aluminium wire2,3, or 4 cores - Galvanised steel wire

Sheath Black general purpose PVC compound

PVC INSULATED, PVC SHEATHED UNARMOURED CABLE (1-CORE)

ConductorThickness of

InsulationThickness of

beddingDiameter of armour wire

Thickness of sheath

Approx. overall

diameter

Approx. net weightNominal

sectional area Shape

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000V

507095120

150185240300

4005006308001000

c.c.c.c.c.c.c.c.

c.c.c.c.c.c.c.c.

c.c.c.c.c.c.c.c.r.m.

1.41.41.61.6

1.82.02.22.4

2.62.82.82.83.0

0.80.80.81.0

1.01.01.01.0

1.21.21.21.41.4

1.251.251.251.6

1.61.61.61.6

2.02.02.02.52.5

1.51.61.61.7

1.71.81.91.9

2.12.12.22.42.5

19.421.423.726.6

28.631.134.437.2

42.245.749.955.961.1

840109014101790

2120258032703970

5110523077609890

12180

Note : r.m. - circular stranded, c.c. - compacted circular stranded

8

PVC INSULATED, PVC SHEATHED ARMOURED CABLE (2-CORE)

ConductorThickness of

InsulationThickness of

beddingDiameter of armour wire

Thickness of sheath

Approx. overall

diameter

Approx. net weight

Nominal sectional

areaShape

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000V

1.51.52.52.5

461016

25355070

95120150185

240300400

s.c.r.m.s.c.r.m.

r.m.r.m.r.m.r.m.

c.c.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

s.m.s.m.s.m.

0.60.60.70.7

0.80.81.01.0

1.21.21.41.4

1.61.61.82.0

2.22.42.6

0.80.80.80.8

0.80.80.80.8

1.01.01.01.0

1.21.21.21.4

1.41.61.6

0.90.90.90.9

0.91.9

1.251.25

1.61.61.61.6

2.02.02.02.5

2.52.52.5

1.31.41.41.4

1.41.51.61.6

1.71.81.91.9

2.12.22.32.4

2.52.72.9

11.912.513.313.7

15.216.520.122.2

26.225.328.330.9

36.038.641.847.1

51.957.062.3

290310360380

460550870

1090

1610169021002640

3680431050606570

8110979011940

PVC IINSULATED, PVC SHEATHED ARMOURED CABLE (3-CORE)

ConductorThickness of

InsulationThickness of

beddingDiameter of armour wire

Thickness of sheath

Approx. overall

diameter

Approx. net weight

Nominal sectional

areaShape

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000V

1.51.52.52.5

461016

25355070

95120150185

240300400

s.c.r.m.s.c.r.m.

r.m.r.m.r.m.r.m.

c.c.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

s.m.s.m.s.m.

0.60.60.70.7

0.80.81.01.0

1.21.21.41.4

1.61.61.82.0

2.22.42.6

0.80.80.80.8

0.80.80.80.8

1.01.01.01.2

1.21.21.41.4

1.61.61.6

0.90.90.90.9

0.91.251.251.25

1.61.61.62.0

2.02.02.52.5

2.52.52.5

1.41.41.41.4

1.41.51.61.6

1.71.81.92.0

2.12.22.42.5

2.62.83.0

12.312.913.814.3

15.918.021.123.3

27.528.231.736.3

40.743.749.153.7

59.865.471.8

320340390410

530750

10201300

1930223028203900

4990591075309060

114101378016860

Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded

9

PVC INSULATED , PVC SHEATHED ARMOURED CABLE (4-CORE)

ConductorThickness of

InsulationThickness of

beddingDiameter of armour wire

Thickness of sheath

Approx. overall

diameter

Approx. net weight

Nominal sectional

areaShape

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000V

1.51.52.52.5

461016

25355070

95120150185

240300400

s.c.r.m.s.c.r.m.

r.m.r.m.r.m.r.m.

c.c.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

s.m.s.m.s.m.

0.60.60.70.7

0.80.81.01.0

1.21.21.41.4

1.61.61.82.0

2.22.42.6

0.80.80.80.8

0.80.80.81.0

1.01.01.21.2

1.21.41.41.6

1.61.61.8

0.90.90.90.9

1.251.251.251.6

1.61.62.02.0

2.02.52.52.5

2.52.5

3.15

1.41.41.41.4

1.51.51.61.7

1.81.92.02.1

2.22.42.52.6

2.83.03.3

13.013.714.615.2

17.919.222.626.5

29.931.236.440.3

45.350.354.660.3

67.073.582.7

360380450470

730870

12001770

2340281038804960

64008110963011700

147501786023110

Note : s.c. - solid circular, r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded

10

PVC INSULATED, PVC SHEATHED ARMOURED CABLEConductor Plain annealed copper

Insulation General purpose PVC compound

Colour of cores White with black numbering

Formation Stranded together and the interstices may be filled with the sheathing compound. A non-hygroscopic binder tape may be applied over the laid-up cores

Bedding Black general purpose PVC compound

Armour Galvanised steel wire

Sheath Black general purpose PVC compound

PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (1.5 mm2)

Number of core

Nominal sectional

area

Construction, Number/ Wire

diameter

Thickness of

Insulation

Thickness of bedding

Diameter of armour

wire

Thickness of sheath

Approx. overall

diameter

Approx. net weight

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000 V

571012

19273748

1.51.51.51.5

1.51.51.51.5

7/0.537/0.537/0.537/0.53

7/0.537/0.537/0.537/0.53

0.60.60.60.6

0.60.60.60.6

0.80.80.80.8

0.81.01.01.0

0.90.9

1.251.25

1.251.61.61.6

1.41.41.51.5

1.61.71.81.9

14.515.419.219.6

22.326.929.533.1

430500780830

1090160019402360

11

PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (2.5mm2)

Number of core

Nominal sectional

area

Construction, Number/ Wire

diameter

Thickness of

Insulation

Thickness of bedding

Diameter of armour

wire

Thickness of sheath

Approx. overall

diameter

Approx. net weight

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000 V

571012

19273748

2.52.52.52.5

2.52.52.52.5

7/0.677/0.677/0.677/0.67

7/0.677/0.677/0.677/0.67

0.70.70.70.7

0.70.70.70.7

0.80.80.80.8

111

1.2

0.91.251.251.25

1.61.61.62.0

1.51.51.61.6

1.71.81.92.1

16.418.121.822.4

26.730.934.139.8

55075010001080

1640211026003520

PVC INSULATED, PVC SHEATHED ARMOURED AUXILIARY CABLE (4 mm2)

Number of core

Nominal sectional

area

Construction, Number/ Wire

diameter

Thickness of

Insulation

Thickness of bedding

Diameter of armour

wire

Thickness of sheath

Approx. overall

diameter

Approx. net weight

mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000 V

571012

19273748

4444

4444

7/0.857/0.857/0.857/0.85

7/0.857/0.857/0.857/0.85

0.80.80.80.8

0.80.80.80.8

0.80.81.01.0

1.01.21.21.2

1.251.251.61.6

1.62.02.02.0

1.51.61.71.7

1.82.02.12.2

19.120.626.126.8

30.637.241.046.1

82097015001630

2170317039104790

12

PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE (3C + E)ConductorPlain annealed copper

InsulationGeneral purpose PVC compound

Colour of coresRed, yellow, blue and black (neutral)

FormationStranded together and the interstices may be filled with the sheathing compound or textile. A non-hygroscopic binder tape may be applied over the laid-up cores

SheathBlack general purpose PVC compound

PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE

Phase Conductor Neutral ConductorThickness of sheath

Approx. overall

diameter

Approx. net weight

Nominal sectional

areaShape Thickness of

Insulation

Nominal sectional

areaShape

Thickness of

Insulation

mm2 No./mm mm mm2 No./mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000 V

25355070

95120150185

240300300400

c.c.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

1.21.21.41.4

1.61.61.82.0

2.22.42.42.6

16162535

50707095

120150185185

r.m.r.m.c.c.c.c.

c.c.c.c.c.c.c.c.

c.c.c.c.c.c.c.c.

1.01.01.21.2

1.41.41.41.6

1.61.82.02.0

1.81.81.92.0

2.12.22.42.5

2.72.92.93.2

24.525.629.633.5

38.541.946.451.7

58.464.864.872.4

1,2901,6502,2503,060

4,1505,1606,2307,850

10,19012,67012,94016,050

Note : r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded

13

PVC INSULATED, PVC SHEATHED ARMOURED WITH REDUCED NEUTRAL CABLE (3C + E)ConductorPlain annealed copper

InsulationGeneral purpose PVC compound

Colour of coresRed, yellow, blue and black (neutral)

FormationStranded together and the interstices may be filled with the sheathing compound or textile. A non-hygroscopic binder tape may be applied over the laid-up cores.

BeddingBlack general purpose PVC compound

ArmourGalvanised steel wire

SheathBlack general purpose PVC compound

PVC INSULATED, PVC SHEATHED UNARMOURED WITH REDUCED NEUTRAL CABLE

Phase Conductor Neutral Conductor Thickness of

bedding

Diameter of armour

wire

Thickness of sheath

Approx. overall

diameter

Approx. net

weightNominal sectional

areaShape

Thickness of

Insulation

Nominal sectional

areaShape

Thickness of

Insulation

mm2 No./mm mm mm2 No./mm mm mm mm mm mm kg/km

BS 6346 & MS 274, 600/ 1000 V

25355070

95120150185

240300300400

c.c.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

s.m.s.m.s.m.s.m.

1.21.21.41.4

1.61.61.82.0

2.22.42.42.6

16162535

50707095

120150185185

r.m.r.m.c.c.c.c.

c.c.c.c.c.c.c.c.

c.c.c.c.c.c.c.c.

1.01.01.21.2

1.41.41.41.6

1.61.82.02.0

1.01.01.01.2

1.21.41.41.4

1.61.61.61.8

1.61.61.62.0

2.02.52.52.5

2.52.52.5

3.15

1.81.81.92.0

2.22.32.42.5

2.72.92.93.1

29.931.035.040.1

45.350.154.459.7

66.873.273.282.3

2,2202,6303,3704,560

5,9807,6307,93010,840

16,64016,44016,71021,260

Note : r.m. - circular stranded, c.c. - compacted circular stranded, s.m. - shaped stranded

14

RATING FACTORS FOR GROUPS OF MORE THAN ONE CIRCUIT OF SINGLE - CORE CABLES, OR MORE THAN ONE MULTICORE CABLES

Methof of installation

Rating factor

Number of circuits or multicore cables

2 3 4 5 6 7 8 9 10 12 14 16 18 20

Enclosed, or bunched and clipped direct to a non-metallic surface 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38

Single layer clipped to a non-metallic surface

Touching 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 - - - - - -

Spaced* 0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 -

Single layer multicore on a perforated metal cable tray, vertical or horizontal

Touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 - - - -

Spaced* 0.91 0.89 0.88 0.87 0.87 - - - - - - - - -

Single layer single-core on a perforated metal cable tray, touching

Horizontal 0.90 0.85 - - - - - - - - - - - -

Vertical 0.85 - - - - - - - - - - - - -

Single layer multicore touching on ladder support 0.86 0.82 0.80 0.79 0.78 0.78 0.78 0.77 - - - - - -

* NOTE : Spaced by a clearance between adjacent surfaces of at least one cable diameter. Where the horizontal clearances between adjacent cables exceeds twice cable diameter no correction factor needs to be applied.

15

RATING FACTORS FOR CABLES INSTALLED IN ENCLOSED TRENCHES

Conductor cross

sectional area

Rating Factor

Trench size 450mm wide x 300 mm deep

Trench size 450mm wide x 600mm deep

Trench size 600mm wide x 760mm deep

2 single core

cables, or 1 three-or four core cables

3 single core

cables, or 2 two-core

cables

4 single core

cables, or 2 three-

or four-core cables

6 single core

cables, 4 two-core cables or 3 three-or four-core cables

6 single core

cables, 4 two-core cables or 3 three-or four-core cables

8 single core

cables, 4 three- or four-core

cable

12 single core

cables, 8 two- or 6 three-core or

four-core cables

12 single core

cables, 8 two- or 6 three-core or

four-core cables

18 single core

cables, 12 two-

core cables or 9 three- or four-core cables

24 single core

cables, 16 two-core cables or 12

three- or four-core cables

mm²

461016

2535507095

120150185240300

400500630

0.930.920.910.91

0.900.890.880.870.86

0.850.840.830.820.81

0.800.780.77

0.900.890.880.87

0.860.850.840.820.81

0.800.780.770.760.74

0.730.720.71

0.870.860.850.84

0.820.810.790.780.76

0.750.740.730.710.69

0.670.660.65

0.820.810.800.78

0.760.750.740.720.70

0.690.670.650.630.62

0.590.580.56

0.860.860.850.85

0.810.800.780.770.75

0.730.720.700.690.68

0.660.640.63

0.830.820.800.78

0.760.740.730.720.70

0.680.670.650.630.62

0.600.580.57

0.760.750.740.71

0.690.680.660.640.63

0.610.590.580.560.54

0.520.510.49

0.810.8

0.780.76

0.740.720.710.7

0.68

0.660.640.630.610.59

0.570.560.54

0.740.730.720.70

0.670.660.640.620.60

0.580.570.550.530.52

0.500.480.47

0.690.680.660.64

0.620.600.590.570.55

0.530.510.490.480.46

0.440.430.41

*NOTE: When cables having different conductor operating temperatures are grouped together the current rating shall be based on the lowest operating temperature of any cable in the group.

Type of protection

Rating Factor

Ambient temperature (oC)

25 30 35 40 45 50 55 60 65

Protective device is intended to provide short-circuit protection only*

1.03 1.0 0.94 0.87 0.79 0.71 0.61 0.50 0.35

Protective device is a semi-enclosed fuse to BS 3036 1.03 1.0 0.97 0.94 0.91 0.87 0.84 0.69 0.48

* NOTE: Except where the device is a semi-enclosed fuse to BS 3036, the factor also applies where the device is intended to provide overload protection.

16

CURRENT-CARRYING CAPACITY FOR SINGLE-CORE, NON-ARMOURED WITH OR WITHOUT SHEATH TO BS 6004 AND BS 6346

Conductor cross

sectional area

Current-carrying capacity

Method of installation

Enclosed in conduit in thermally insulated wall etc.

Enclosed in conduit on a wall or in trunking etc.

Clipped directOn a perforated

cable tray horizontal or vertical

In free air

Horizontal flat

spaced

Vertical flat

spacedTrefoil

2 cables, single-phase a.c. or

d.c.

3 or 4 cables three-phase a.c.

2 cables, single-phase a.c. or

d.c.

3 or 4 cables three-phase a.c.

2 cables, single-phase a.c. or d.c. flat

and touching

3 or 4 cables three-phase a.c. flat

and touching of trefoil

2 cables, single-phase a.c. or d.c. flat

and touching

3 or 4 cables three-phase a.c. flat

and touching of trefoil

2 cables, single-

phase a.c. or d.c. or 3 cables

three-phase a.c.

2 cables, single-phase a.c. or

d.c. or 3 cables three-phase

a.c.

3 cables, trefoil, three phase

a.c.

mm2 A A A A A A A A A A A

1.5

2.5461016

2535507095

120150185240300

4005006308001000

14.5

19.526344661

8099119151182

210240273320367

-----

13.5

1824314256

7389

108136164

188216245286328

-----

17.5

2432415776

101125151192232

269300341400458

546626720

--

15.5

2128365068

89110134171207

239262296346394

467533611

--

20

2737476587

114141182234284

330381436515594

694792904

10301151

18

2533435979

104129167214261

303349400472545

634723826943

1058

-

-----

126156191246300

349404463549635

732835953

10861216

-

-----

112141172223273

318369424504584

679778892

10201149

-

-----

146181219281341

396456521615709

852982113812651420

-

-----

130162197254311

362419480569659

795920

107011881337

-

-----

110137167216264

308356409485561

656749855971

1,079

17

VOLTAGE DROP FOR SINGLE-CORE, NON-ARMOURED WITH OR WITHOUT SHEATH TO BS 6004 AND BS 6346

Conductorcross

sectionalarea

2cabled.c.

2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.

Enclosed in conduit etc.

in or on a wall

Clipped direct

or on traystouching

In free air(spaced*)

Enclosed in conduit etc.

inor on a wall

Clipped direct,

on trays orin free air(in trefoil)

Clipped direct

or on trays (flat andtouching)

In free air(flat spaced*)

mm2 mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m1.52.54

61016

253550

7095120

150185240

300400500

6308001000

291811

7.34.42.8

1.751.250.93

0.630.460.36

0.290.230.180

0.1450.1050.086

0.0680.0530.042

291811

7.34.42.8

1.801.301.00

0.720.560.47

0.410.370.33

0.310.290.28

0.27--

291811

7.34.42.8

1.751.250.95

0.660.500.41

0.340.290.25

0.220.20

0.185

0.1750.1650.160

291811

7.34.42.8

1.801.300.97

0.690.540.45

0.390.350.31

0.290.270.26

0.250.250.24

25159.5

6.43.82.4

1.551.100.85

0.610.480.41

0.360.320.29

0.270.250.25

0.24--

25159.5

6.43.82.4

1.501.100.82

0.570.430.36

0.300.260.22

0.1900.1750.160

0.1500.1450.140

25159.5

6.43.82.4

1.551.100.84

0.600.470.40

0.340.310.27

0.250.240.23

0.220.220.21

25159.5

6.43.82.4

1.551.150.86

0.630.510.44

0.400.360.34

0.320.310.30

0.290.290.28

NOTE : * Spacings larger than those specified in free air will result in larger voltage drop.

18

CURRENT-CARRYING CAPACITY FOR MULTICORE, NON-ARMOURED TO BS 6004 AND BS 6346

Conductor cross

sectional area

Current-carrying capacity

Method of installation

Enclosed in conduit in thermally insulated wall etc.

Enclosed in conduit on a wall or in trunking etc. Clipped direct On a perforated cable tray

OR in free air

1 two-core cable, single-phase a.c. or

d.c.

1 three-core cable or 1 four-core

cable, three phase a.c.

1 two-core cable, single-

phase a.c. or d.c.

1 three-core cable or 1 four-core

cable, three phase a.c.

1 two-core cable, single

phase a.c. or d.c.

1 three-core cable or 1 four-

core, three phase a.c.

1 two-core cable, single-

phase a.c. or d.c.

1 three-core cable or 1 four-

core cable, three phase

a.c.

mm² A A A A A A A A

1.5

2.5461016

2535507095

120150185240300

400

14

18.525324357

7592110139167

192219248291334

-

13

17.523293952

688399

125150

172196223261298

-

16.5

2330385269

90111133168201

232258294344394

470

15

2027344662

8099118149179

206225255297339

402

19.5

2736466385

112138168213258

299344392461530

634

17.5

2432415776

96119144184223

259299341403464

557

22

3040517094

119148180232282

328378434514593

715

18.5

2534436080

101126153196238

276319364430497

597

VOLTAGE DROP FOR MULTICORE, NON-ARMOURED TO BS 6004 AND BS 6346

Conductor cross-section area Two-core cable, d.c. Two-core cable, single-phase a.c.

Three-or four-core cable, three-phase a.c.

mm2 mV / A/m mV / A/m mV / A/m1.52.54

61016

253550

7095120

150185240

300400

291811

7.34.42.8

1.751.250.93

0.630.460.36

0.290.23

0.180

0.1450.105

291811

7.34.42.8

1.751.250.94

0.650.500.41

0.340.290.24

0.210.185

25159.5

6.43.82.4

1.501.100.81

0.570.430.35

0.290.250.21

0.1850.160

19

CURRENT-CARRYING CAPACITY FOR SINGLE-CORE ARMOURED TO BS 6346

Ambient temperature : 30°C

Conductorcross

sectionalarea

Current-carrying capacityMethod of installation

Clipped direct On a perforatedcable tray

In free air2 cables,

single-phase a.c. 2 cables, d.c. 3 or 4 cables, three-phase a.c.

2 cables,single-phasea.c. or d.c.

flat andtouching

3 or 4 cablesthree-phasea.c. flat

and touching

2 cables,single-phasea.c. or

d.c.flat andtouching

3 or 4 cablesthree-phasea.c. flat

and touching

Horizontalflat

spaced

Verticalflat

spaced

Horizontalspaced

Verticalspaced

Horizontalflat

spaced

Verticalflat

spaced

3 cablestrefoil

mm2 A A A A A A A A A A A507095

120150185

240300400

5006308001000

193245296

342395447

525594687

763843919975

179225269

309354399

465515575

622669710737

205259313

360415469

550624723

805891976

1041

189238285

327375422

492547618

673728777808

229287349

401456511

593668737

810893943

1008

217272332

383436489

568640707

777856905967

229294357

415482548

648748885

1035121814411685

216279340

396460525

622719851

997117413901627

230286338

385436490

566616674

721771824872

212263313

357407456

528578632

676723772816

181231280

324373425

501567657

731809886945

VOLTAGE DROP FOR SINGLE-CORE ARMOURED TO BS 6346

Conductorcross sectional

area

2 cablesd.c.

2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.

Clipped direct or on trays(touching)

In free air(spaced*)

Clipped direct, ontrays or in free air

(in trefoil touching)

Clipped director on trays(flat and touching)

In free air(flat spaced*)

mm2 mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m mV / A/m507095

120150185

240300400

5006308001000

0.930.630.46

0.360.290.23

0.1800.1450.105

0.0860.0680.0530.042

0.950.680.52

0.430.370.32

0.270.240.22

0.210.1950.1850.180

0.970.720.58

0.500.440.39

0.350.320.30

0.290.270.250.24

0.820.580.45

0.370.320.27

0.230.21

0.195

0.1800.1700.1600.155

0.840.620.50

0.430.380.34

0.300.280.26

0.250.230.220.21

0.860.680.57

0.500.450.41

0.370.340.32

0.300.280.260.24

NOTE : * Spacings larger than those specified in free air will result in larger voltage drop.

20

CURRENT-CARRYING CAPACITY FOR MULTICORE, ARMOURED TO BS 6346

Conductorcross

sectionalarea

Current-carrying capacityMethod of installation

Clipped direct On a perforated cable tray horizontal or verticalOr in free air

1 two-core cable,single-phasea.c. or d.c.

1 three- or four-corecable,

three-phase a.c.

1 two-core cable,single-phasea.c. or d.c.

1 three- or four-corecable,

three-phase a.c.mm2 A A A A1.52.54

61016

253550

7095120

150185240

300400

212838

496789

118145175

222269310

356405476

547621

182533

425877

102125151

192231267

306348409

469540

223141

537297

128157190

241291336

386439516

592683

192635

456283

110135163

207251290

332378445

410590

VOLTAGE DROP FOR MULTICORE, ARMOURED TO BS 6346

Conductor cross-sectional area Two-core cable,d.c. Two-core cable, single-phase a.c.

Three-or four-core cablethree-phase a.c.

(mm2) (mV / A/m) (mV / A/m) (mV / A/m)1.52.54

61016

253550

7095120

150185240

300400

291811

7.34.42.8

1.751.250.93

0.630.460.36

0.290.23

0.180

0.1450.105

291811

7.34.42.8

1.751.250.94

0.650.500.41

0.340.290.24

0.210.185

25159.5

6.43.82.4

1.501.100.81

0.570.430.35

0.290.250.21

0.1850.160

21

APPENDIX - TECHNICAL DATA STRANDED ANNEALED COPPER AND ALUMINIUM CONDUCTORS

Nominal cross

sectional area

Minimum number of wired in the conductor Maximum resistance of conductor at 20°C

Circular conductor Circular compacted conductor Shaped conductor Annealed copper

conductor Plain aluminium conductorCu Al Cu Al Cu Al Plain Wires

Metal-coated wires

mm² ohm/ km ohm/ km ohm/ km

1.52.54610162535507095

1201501852403004005006308001000

77777777191919

37373761616161616161

--777777

191919

37373761616161616161

666666666

1215

18183034345353535353

-----6666

1215

15153030305353535353

------666

1215

1818303434535353--

------666

1215

1515303030535353--

12.17.414.613.081.831.15

0.7270.5240.3870.2680.193

0.1530.124

0.09910.07540.06010.04700.03660.02830.02210.0176

12.27.564.703.111.841.16

0.7340.5290.3910.2700.195

0.1540.1260.100

0.07620.06070.04750.03690.02860.02240.0177

--

7.414.613.081.911.200.8680.6410.4430.320

0.2530.2060.1640.1250.1000.07780.06050.04690.03670.0291

FORMULA FOR ELECTRIC CALCULATION

To calculate Given D.C. A.C. Single Phase A.C. 3 phase

Current (A) kW A = 1000 x kWV A = 1000 x kW

V x pf A = 1000 x kW1.73 x V x pf

Current (A) kVA - A = 1000 x kVAV A = 1000 x kVA

1.73 x V

Current (A) hp A = 746 x hpV x eff A = 746 x hp

V x eff x pf A = 1000 x kW1.73 x V x eff x pf

Power (kW) VA kW = A x V1000 kW = A x V x pf

1000 kW = 1.73 x A x V x pf1000

Apparent Power (kVA) VA - kVA = A x V1000 kW = 1.73 x A x V

1000

pf - Power factor of equipment or system under considerationeff - Efficiency of motor of machineryV - Line voltage

22

APPENDIX - TECHNICAL DATA WIRE GAUGES

Gauge system Diameter Cross sectional area Weight of copper

Weight of Aluminium

A.W.G. S.W.G. mm mil mm² sq. mil CM kg/ km kg/ km

6/05/0--

4/0

-3/0--

2/0

-0--1

-2--3

-4-5-

6-7-8

--9-

10

-1112--

-1314-

15

16-

1718 -

-19-

2021

--

7/06/0-

5/0-

4/03/0-

2/0-01-

2-34-

5-6-7

-8-9-

1011-

12-

13--

1415

--

16-

17

-18--

19

20-

21--

14.73213.11912.70011.78611.684

10.97310.40410.1609.4499.266

8.8398.2528.2307.6207.348

7.0116.5446.4015.8935.827

5.3855.1894.8774.6214.470

4.1154.0643.6653.6583.264

3.2512.9462.9062.6422.588

2.3372.3052.0532.0321.829

1.8281.6281.6261.4501.422

1.2911.2191.1501.0241.016

0.91440.91170.81280.81160.7230

580516.5500464460

432409.6400372

364.8

348324.9324300

289.3

276257.6252232

229.4

212204.3192

181.9176

162160

144.3144

128.5

128116

114.4104

101.9

9290.7480.81

8072

71.9664.08

6457.07

56

50.8248

45.2640.340

3635.89

3231.9528.46

170.5135.2126.7109.1107.2

94.5685.0181.0770.1267.43

61.3653.4953.1945.6042.41

38.6033.6332.1827.2726.66

22.7721.1518.6816.7715.69

13.3012.9710.5510.518.367

8.3026.8186.6335.4815.261

4.2894.1723.3093.2432.627

2.6242.0812.0751.6501.589

1.3091.167

1.03800.82270.8107

0.65670.65290.51890.51740.4105

264,200209,500196,400169,100166,200

146,600131,800125,700108,700104,500

95,10082,91082,45070,69065,730

59,83052,12049,88042,27041,330

35,30032,78028,95026,00024,320

20,62020,11016,35016,29012,970

12,87010,57010,2808,4958,155

6,6486,4675,1295,0274,072

4,0673,2253,2172,5582,463

2,0291,8101,6091,2751,257

1,0181,012804.2802.9636.3

336,400266,800250,000215,300211,600

186,600167,800160,000138,400133,100

121,100105,600105,00090,00083,690

76,18066,37063,50053,82052,620

44,94041,73036,86033,10030,970

26,25025,60020,82020,74016,510

16,38013,46013,09010,82010,380

8,4658,2346,5316,4005,185

5,1784,1074,0963,2573,136

2,5832,3042,0481,6241,600

1,2961,2881,0241,021810.1

151512021126969.9953.2

840.6755.8720.7623.4599.5

545.5475.5472.9405.4377.0

343.2299.0286.1242.4237.0

202.4188.0166.1149.1139.5

118.3115.393.7893.4174.39

73.8060.6158.9648.7246.77

38.1337.0929.4228.8323.35

23.3318.5018.4514.6714.13

11.6310.389.2267.3147.207

5.8385.8044.6134.6003.649

460.2365.0342.0294.6289.5

255.3229.5218.9189.3182.1

165.7144.4143.6123.1114.5

104.290.8086.8873.6371.99

61.4957.1050.4345.2842.37

35.9235.0228.4828.3722.59

22.4218.4117.9114.8014.21

11.5811.268.9358.7567.093

7.0855.6185.6044.4564.290

3.5343.5122.8022.2212.189

1.7731.7631.4011.3971.108

23

APPENDIX - TECHNICAL DATA WIRE GAUGES - continued

Gauge system Diameter Cross sectional area Weight of copper

Weight of Aluminium

A.W.G. S.W.G. mm mil mm² sq. mil CM kg/ km kg/ km

-22-

23-

24--

25-

26-

27-

28

--

29-

30

--

31-

32

-33-

34-

35-

36-

37

--

38-

39

-404142-

43-

4445-

464748-

49

-50

22-

23-

24

-2526-

27

-28-

29-

3031-

32-

3334-

35-

36-

37-

38

-39-

40-

4142-

43-

44-

45-

46

-47--

48

---

49-

50-

0.71120.64390.60960.57330.5588

0.51060.50800.45720.45460.4166

0.40490.37590.36060.34540.3211

0.31500.29470.28600.27430.2548

0.25400.23370.22680.21340.2019

0.19300.17980.17270.16020.1524

0.14260.13210.12700.12190.1131

0.11180.10160.10070.09140.0897

0.081280.079880.071130.063340.06096

0.056410.050800.050230.044740.04064

0.039840.035480.031590.030480.02813

0.025400.02505

2825.35

2422.57

22

20.12018

17.916.4

15.9414.814.213.6

12.64

12.411.6

11.2610.8

10.03

109.2

8.9288.4

7.95

7.67.086.8

6.3056

5.6155.25

4.84.453

4.44

3.9653.6

3.531

3.23.1452.8

2.4942.4

2.2212

1.9781.7611.6

1.5681.3971.2441.2

1.108

10.9863

0.39730.32560.29190.25810.2452

0.20470.20270.16420.16230.1363

0.12880.11100.1021

0.093720.08097

0.077910.068190.064220.059080.05097

0.050670.042890.040390.035750.03203

0.029270.025400.023430.020140.01824

0.015970.013700.012670.011670.01005

0.009810.0081070.0079680.0065670.006319

0.0051890.0050120.0039730.0031510.002919

0.0024990.0020270.0019820.0015720.001297

0.0012460.00098840.00078380.00072970.0006216

0.00050670.0004929

615.8504.7452.4400.1380.1

317.3314.2254.5251.6211.3

199.6172.0158.3145.3125.5

120.8105.799.5491.5879.01

78.5466.4862.6055.4249.64

45.3639.3736.3231.2228.27

24.7621.2419.6318.1015.57

15.2112.5712.3510.189.794

8.0427.7686.1594.8844.524

3.8733.1423.0722.4362.011

1.9321.5321.2151.131

0.9635

0.78540.7641

784.0642.6576.0509.4484.0

404.0400.0324.0320.4269.0

254.1219.0201.5185.0159.8

153.8134.6126.7116.6100.6

100.084.6479.7170.5663.20

57.7650.1346.2439.7536.00

31.5327.0125.0023.0419.83

19.3616.0015.7212.9612.47

10.249.8917.8426.2195.760

4.9324.0003.9113.1022.560

2.4601.9511.5471.4401.227

1.0000.9728

3.5322.8952.5952.2952.180

1.8201.8021.4601.4431.212

1.1450.98670.90770.83320.7198

0.69260.60620.57090.52520.4531

0.45050.38130.359

0.31780.2847

0.26020.22580.20830.17910.1622

0.1420.12180.11260.1038

0.08931

0.087210.072070.070840.058380.05616

0.046130.044560.035320.028010.02595

0.022220.018020.017620.013970.01153

0.011080.0087870.0069680.0064870.005526

0.0045050.004382

1.0730.87920.78800.69700.6622

0.55280.54720.44330.43830.368

0.34770.29970.27570.25300.2186

0.21040.18410.17340.15950.1376

0.13680.11580.1090

0.096530.08647

0.079020.068580.063260.054390.04925

0.043130.037000.034200.031520.02173

0.026490.021890.021510.017730.01706

0.014010.013530.01073

0.0085080.007880

0.0067470.0054720.0053510.0042440.003502

0.0033650.0026690.0021160.0019700.001678

0.0013680.001331

24

APPENDIX - TECHNICAL DATA COMMON CONVERSION FACTOR

Equivalent ReciprocalMass

1 cwt 1 oz 1 lb1 lb

1 ton (long)

=====

50.80228.3494536

0.004541.016

kggmkg

tonne ( metric)tonne ( metric)

0.01970.03522.2046220.26

0.09842Length

1 in1 ft1 yd

1 mile

====

25.40.30480.91441.6093

mmmmkm

0.039373.28081.09360.6214

Area1 in²1 ft²1 yd²

===

645.160.09290.8361

mm²m²m²

0.0015510.7642

1.196Volume

1 in³1 ft³1 ft³1 ft³1 yd³

1 fal (USA)

======

16.3870.02836.229

28.3280.76450.8327

cm3 (ml or cc)m3

gal (lmp)l

m3

gal (lmp)

0.06135.33350.16050.03531.30791.2009

Force1 lbf1 kgf

1 ton (long) f

===

0.45359.80659.964

kgfNkN

2.20460.1019

0.10036Pressure and Stress

1 atm1 atm

1 lbf/in² (psi)1 bar

====

0.10131.01336.894

1.0197

Mpabar

kN/mm2 (kPa)kgf/ cm2

9.8690.98690.145

0.09806Energy (Work and Heal)

1 HP.h1 Btu1 Btu1 Btu1 cal

=====

2544.50.000293

1.0551107.594.187

BtukW.h

kJkgf.m

J

0.003933413

0.94780.00929

0.239

1 mil = 0.001 in = 0.0254 mm

1 CM (circular mil) = 0.7854 x 10-6 in² = 0.5067 x 10-3 mm2

BS 6004 PVC - Insulated Cables (Non-Armoured) for Electrical Power and Lighting

BS 6346 PVC - Insulated Cables for Electric Supply

BS 6360 Conductors in Insulated Cables and Cords

BS 7671 Requirements for Electrical Installations

IEE Wiring Regulations, Sixteenth Edition

MS 136 PVC - Insulated Cables (Non-Armoured) for Electrical Power and Lighting