1 Tag No. : Client: THANG LONG JOINT OPERATING COMPANY
2 Service: HST Microturbine House Plant Location: Offshore Vietnam (HST WHSP)
3 P & ID No. : Fabricator: TBA
4 Calculation Ref. : Purchase Order No. :
5 No. of Units: 02 Sets ( one set on the south side , one set on the east side)
6 Manufacturer Model Size & Type
7 SITE CONDITION
8 Ambient Temperature: 20.7~34.2oC, 40
oC (maximum)
9 Environment:
10 Wind:
11 Seismic:
12
13 Standard Certified as AMCA 500-L-12 Class B
14 5.68 (12480 CFM)
15 VTA
16 VTA
17 12.4 (0.05" Water collumn)
18 Louvre Size/duct connection size
19 Width: W = mm 914 (VTA) (36")
20 Height: H = mm 914 (VTA) (36")
21 Unit thickness: t = 100 (4")
22
23 Left: Yes/No No
24 Right: Yes/No No
25
26 VTA
27 Yes
28 VTA
29
30 Casing Material Steel (VTA)
31 Thickness Steel (VTA)
32 Blades Material Steel (VTA)
33 Thickness Steel (VTA)
34
35 Meshscreen Material VTA
36 Mesh Size VTA
37 Drain Material Steel (VTA)
38 Size Steel (VTA)
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55 * The draft drawing above is used for information only
56
57 NOTES:
58 1) VTA: Vendor to Advise; TBA: to be advised
59 2) The Louvers will be mounted on the walls of Microturbine Housing. Vendor to provide kits for installation
60 3) Vendor to resize and select correct louvers base on input data specified above and avaible area of Housing walls on drawings for
61 MTG Housing (HST-A-TS-M-DW-0010-01 to 06)
62 4) Design louvers, including comprehensive engineering analysis by a qualified engineer, using structural performance requirements and design criteria indicated.
63 5) Louvers shall withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated without permanent components,
64 noise or deformation of louver metal fatigue caused by louver blade rattle or flutter, or permanent damage to fasteners and anchors.
65 6) Wind Loads: Determine loads based on a uniform pressure no less than 12 kPa, acting inward or outward
66 7) Louvers shall be tested and certified to meet the requirement of standard AMCA 500-L-12 Class B under purchaser witness.
67
68
69
F01
A01
Rev.
mm
m3/s
m/s
Pa
Meshscreen
Lifting Lugs
Unit Weight
MATERIALS
kg
Flange
TECHANICAL DATA
Airflow / each side
Separation Efficiency
Face Velocity
Pressure Drop
Drain Outlet
Drain Outlet size
mm
mm
mm
mm
Yes/No
Yes/No
HST-A-TS-M-DS-0031
Datasheet for HST Microturbine Housing Louvers
Date Issue Description Originated
11-Dec-2013
17-Dec-2012 ISSUED FOR REVIEW
THANG LONG JOINT OPERATING COMPANY
HST FULL FIELD & HSD EARLY PRODUCTION SYSTEM DEVELOPMENT
Project No: 11010 SHEET
ISSUED FOR IDC
TLJOC APPVPTSC APPV
1 OF 1
NQ
NQ
Checked
DDM/ NDK
DDM/ NDK
Approved
Datasheet No:
mm
Salt Laden Tropical Marine Environment, Max. Relative Humidity 100%
44 m/s at 10m above MSL (3-sec gust with return period of 100 years)
Seismic Load shall not be considered.
THS
THS