TECHNOLOGY
HSQ-3010Ethernet I/O ModuleUser Manual
v1.0
Limited Rights Legend
©2015 HSQ Technology Incorporated. All rights reserved.
Contractor: HSQ TECHNOLOGY, A Corporation.
The following data comprises software and/or hardware documentation relating to computer software and/or hardware furnished with restricted rights:
HSQ-3010 User Manual
Revision: 05/2015
Those portions of this technical data indicated as limited rights data shall not, without the written permission of the above Contractor, be either (a) used, released or disclosed in whole or in part outside the Government, (b) used in whole or in part by the Government for manufacture or, in the case of computer software documentation, for preparing the same or similar computer software, or (c) used by a party other than the Government, except for: (i) emergency repair or overhaul work only, by or for the Government, where the item or process concerned is not otherwise reasonably available to enable timely performance of the work, provided that the release or disclosure hereof outside the Government shall be made subject to a prohibition against further use, release or disclosure; or (ii) release to a foreign government, as the interest of the United States may require, only for emergency repair of overhaul work by or for such government under the conditions of (i) above. This legend, together with the indications of the portions of this data which are subject to such limitations shall be included on any reproduction hereof which includes any part of the portions subject to such limitations.
Copyright
The documentation and the software included with this product are copyrighted by HSQ Technology, Inc. No part of this manual may be reproduced, copied, translated, or transmitted in any form or by any means without prior written consent of HSQ Technology, A Corporation.
No responsibility is assumed for the use or reliability of software on equipment that is not supplied by HSQ Technology, A Corporation.
Intel® and Pentium® are trademarks of Intel™ Corporation. Microsoft® Windows™ and MS-DOS® are registered trademarks of Microsoft Corporation. All other brand or product names may be trademarks or registered trademarks of their respective companies or organizations.
i i
v1.0
Contents
About This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viConventions and Notations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viDocument Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .viMargin Icons. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viiGraphics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viiSafety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Static Electricity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viiiSafety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Section 1: Overview1.1—Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21.2—Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2.1—Hardware Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21.2.1.1—Analog Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-21.2.1.2—Digital Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31.2.1.3—Digital Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-31.2.1.4—General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1.2.2—Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-41.2.3—Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.3—Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Section 2: Configuration Tool2.1—Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22.2—Software Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.2.1—Standard Toolbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42.2.1.1—File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42.2.1.2—View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42.2.1.3—Customize . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-42.2.1.4—Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2.3—System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-52.3.1—IP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2.3.1.1—Changing the Host IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
i i iHSQ-3010 User Manual
Table of Contentsi v
2.3.1.2—Changing the Module IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-82.3.2—Device Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
2.3.2.1—System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-92.3.2.2—Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-102.3.2.3—Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-112.3.2.4—Stream. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2.4—Hardware Parameter Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-132.4.1—AI Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2.4.1.1—Input Type and Alarm Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-142.4.1.2—Frequency Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-182.4.1.3—Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
2.4.2—DI Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-192.4.2.1—Input Type Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
2.4.3—DO Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-222.4.3.1—Output Type Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Appendix A: I/O WiringA.1—I/O Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Appendix B: Modbus AddressesB.1—Modbus TCP Address (0x). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2B.2—Modbus TCP Address (4x). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4B.3—Range Code Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-9
Appendix C: Stream Data FormatC.1—Stream Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
HSQ Technology v1.0
PREFACE
The HSQ-3010 is an Ethernet I/O module that supports the Modbus TCP protocol and delivers various onboard I/Os including analog input, digital input, and digital output. It provides flexible options to satisfy versatile application requirements. It also features the powerful Domain Focused Configuration Tool.
vv1.0 HSQ-3010 User Manual
About This Manualv i
About This ManualThe HSQ-3010 User Manual is divided into sections that describe how to configure, address, and wire the HSQ-3010.
“Preface” — This section. It describes safety precautions, typographical conventions, and special symbols used throughout the text.
Section 1, “Overview” — describes the features and specifications of the HSQ-3010.
Section 2, “Configuration Tool” — details configuration steps.
Appendix A, “I/O Wiring” — provides a diagram for wiring the 3010.
Appendix B, “Modbus Addresses” — lists all the Modbus addresses.
Appendix C, “Stream Data Format” — contains a table of the stream data formatting.
Conventions and Notations
Throughout this manual, certain typographical conventions are used.
Document Feedback
To assist us in making improvements to this manual, we welcome any and all comments and constructive criticism. Please send all such correspondence to [email protected].
Convention Description
Italics Type This highlights the first use of terminology and unique information. It can also indicate checkboxes, tab names, or text that is important.
Bold Type This highlights the names of certain items or features. It can also indicate special note text.
Bold Italic Type This highlights the names of screens.
Fixed Width Type This highlights user entered text or computer code.
Fixed Width Italic Type
This highlights arguments or variables that are entered as part of a command.
Press Press a physical key on the keyboard.
Select Choose an item from a menu or selection list.
[Button] Indicates the name of an on-screen graphical button.
hyperlink This denotes a clickable link to another part of the document in the electronic version of the manual.
HSQ Technology v1.0
Preface v i i
Margin Icons
The following text boxes and icons are used throughout the manual to bring to your attention important information.
FYI: The FYI icon indicates additional information that is good to know when you are using the product.
Graphics
In some cases the screens shown in this manual may have been slightly altered after this manual was released.
All efforts have been made to ensure that the latest images are used. In all cases, the functionality described is current at the time of writing.
SupportTo request Technical Support, please email HSQ directly at [email protected].
Those interested in receiving information or literature from the HSQ Sales Department regarding software and hardware products that we produce and support, please email [email protected].
Those interested in budgetary or fixed price quotes for upgrades to existing VisualCL installations, new equipment, spare parts, system expansion, HSQ RTUs, or software modules, may also contact our sales department ([email protected]).
HSQ Technology26227 Research RoadHayward, CA 94545-3725
Voice: 510.259.1334Fax: 510.259.1391
www.hsq.com
v1.0 HSQ-3010 User Manual
Safety Precautionsv i i i
Safety Precautions
Static Electricity
Please follow these simple precautions to protect yourself from harm and the products from damage.
To avoid electrical shock, always disconnect the power from your HSQ-3010 chassis before you work on it. Do not touch any components on the CPU card or other cards while the 3010 is on.
Disconnect power before making any configuration changes. The sudden rush of power as you connect a jumper may damage sensitive electronic components.
Safety Instructions
1. Read these safety instructions carefully.
2. Keep this User Manual for later reference.
3. Disconnect equipment from any AC power source before cleaning. Use a damp cloth. Do not use liquid or spray detergents for cleaning.
4. For plug-in equipment, the power outlet socket must be located near the equipment and must be easily accessible.
5. Keep this equipment away from humidity.
6. Put this equipment on a reliable surface during installation. Dropping it or letting it fall may cause damage.
7. The openings on the enclosure are for air convection. Protect the equipment from overheating. DO NOT COVER THE OPENINGS.
8. Make sure the voltage of the power source is correct before connecting the equipment to the power outlet.
9. Position the power cord so that people cannot step on it. Do not place anything over the power cord.
10. All cautions and warnings on the equipment should be noted.
11. If the equipment is not used for a long time, disconnect it from the power source to avoid damage by transient overvoltage.
12. Never pour any liquid into an opening. This may cause fire or electrical shock.
13. Never open the equipment. For safety reasons, the equipment should be opened only by qualified service personnel.
HSQ Technology v1.0
Preface i x
14. If one of the following situations arises, get the equipment checked by service personnel:
The power cord or plug is damaged.
Liquid has penetrated into the equipment.
The equipment has been exposed to moisture.
The equipment does not work properly or you cannot get it to work according to the User Manual.
The equipment has been dropped and damaged.
The equipment has obvious signs of breakage.
15. DO NOT LEAVE THIS EQUIPMENT IN AN ENVIRONMENT WHERE THE STORAGE TEMPERATURE MAY GO BELOW -20° C (-4° F) OR ABOVE 70° C (158° F). THIS COULD DAMAGE THE EQUIPMENT. THE EQUIPMENT SHOULD BE IN A CONTROLLED ENVIRONMENT.
16. Ensure the sound pressure level at the operator's position according to IEC 704-1:1982 is no more than 70 dB.
DISCLAIMER: This set of instructions is given according to IEC 704-1. HSQ Technology disclaims all responsibility for the accuracy of any statements contained herein.
v1.0 HSQ-3010 User Manual
Safety Precautionsx
HSQ Technology v1.0
S E C T I O N 1
OVERVIEW
The HSQ-3010 is an Ethernet I/O module that supports the Modbus TCP protocol and delivers various onboard I/Os including analog input, digital input, and digital output, providing flexible options to satisfy versatile application requirements. It also features the powerful Domain Focused Configuration Tool. This section covers:
Features
Specifications
Dimensions
1 - 1v1.0 HSQ-3010 User Manual
Features1 - 2
1.1 | Features Modbus/TCP protocol
Mixed I/O in the module
Remote maintenance via Ethernet
Supports online device auto-scan or manual configure function
Auto push data to specification target function
Supports High/Low Alarm function
Supports cable burn-out check
Support pulse/accumulator input
1.2 | Specifications
1.2.1 | Hardware Specifications
1.2.1.1 | Analog Input
Channels — 8
Input Type — V, mA*1, RTD*2
Voltage Range — 0–10V
Current Range — 0–20 mA, 4–20 mA
RTD Type —
PT 100 (3-wire): -50–150º C, 0–100º C, 0–200º C, 0–400º C, -50–200º C
PT 1000 (3-wire): -40–160º C
IEC RTD 100Ω (=0.0385)
JIS RTD 100Ω (=0.0392)
Input Impedance — 2MΩ (voltage)
Accuracy — ±0.01 V (voltage), ±0.02 mA (current), ±0.5º C (RTD), or better
Span Drift — ±25 ppm / ºC
Zero Drift — ±6 µV / ºC
Resolution — 16-bit
Sampling Rate — 10 samples/second
Over Voltage Protection — ±35 VDC
Isolation Protection — 2500 VDC
HSQ Technology v1.0
Overview 1 - 3
CMR @ 50/60 Hz 90 dB
NMR @50/60 Hz 60 dB
Built-in TVS/ESD Protection
1.2.1.2 | Digital Input
Channels — 8
Dry Contact —
Logic level 0: Open
Logic level 1: Close to Ground
Supports 200 Hz pulse/accumulator input
Isolation Protection 2500 VDC
1.2.1.3 | Digital Output
Channels — 4
Power Dissipation — 300 mW for each channel
PWM Period — 20 ms – 3600 seconds
Open Collector to 30 V (30 mA maximum load)
PWM Minimum Duty On ≥2 ms
Isolation Protection 2500 VDC
1.2.1.4 | General
Dimensions — 120 x 120 x44 mm (4.72” x 4.72” x 1.73”)
LAN — 10/100 Base-T
Connectors —
1 x RJ-45 (LAN)
4 x Plug-in screw terminal block (I/O and power)
Watchdog — System (1.6 seconds)
Supported Protocols — Modbus/TCP
Power Input — 10–30 VDC
Power Consumption — 3 W @ 24 VDC
v1.0 HSQ-3010 User Manual
Dimensions1 - 4
1.2.2 | Indicators
There are system indicators on the front panel of the HSQ-3010 to show the running status:
Power Indicator — Lit when the module power is on.
DO Status Indicators — If the value of the digital output channel is logic high, its relative DO status indicator will be turned on.
1.2.3 | Environment
Humidity — 5–95% relative humidity (non-condensing)
Operation Temperature — -40–70º C (-40–158º F)
Storage Temperature — -40–70º C (-40–158º F)
FYI: Static electricity will be generated if the relative humidity is below 30%. Therefore, you must take measures against static electricity, such as grounding.
1.3 | Dimensions
Figure 1-1. Dimensional views
121.00
100.00
120.00
36.0
8.0
6.063.74
61.5
94.70
MM
HSQ Technology v1.0
S E C T I O N 2
CONFIGURATION TOOL
The Domain Focused Configuration Tool is a powerful utility that can be used to configure the HSQ-3010.
This section describes how to configure the 3010 with the Domain Focused Configuration Tool. It contains headings on:
Installation Procedure
Software Usage
System Configuration
Hardware Parameter Configuration
The requirements for the 3010 are:
Power Supply — 10–30 VDC
Operating System — Microsoft Windows
Network — Ethernet
2 - 1v1.0 HSQ-3010 User Manual
Installation Procedure2 - 2
2.1 | Installation ProcedureInsert the CD into your CD-ROM drive and run the Domain Focused Configuration Tool to start the InstallShield wizard. You will be guided through the installation.
1. Run Domain Focused Configuration Tool Setup.exe and the following screen will appear:
2. Click [Next] and the following dialog box displays:
The default installation path is C:\Program Files\Advantech\Advantech Domain Focused Configuraiton Tool Utility. You can click [Browse] to change the installation path.
HSQ Technology v1.0
Configuration Tool 2 - 3
3. Click [Next] and the following dialog box appears:
4. Click [Next] and the following dialog box will display:
5. Click [Next] and the software will automatically finish the installation.
After you have installed the software, it will appear in the Start menu.
v1.0 HSQ-3010 User Manual
Software Usage2 - 4
2.2 | Software UsageThe Domain Focused Configuration Tool consists of the following parts:
Standard Toolbar — Menu bar selection
Function List Block — Device and Object tree
Workspace Area — Configure the properties of the HSQ-3010
To start the Domain Focused Configuration Tool, double-click the icon on the desktop or launch it from the Start menu.
2.2.1 | Standard Toolbar
2.2.1.1 | File
To exit the program, click File > Exit.
2.2.1.2 | View
Status Bar — Shows or hides the Status Bar in the program window.
Function List — Shows or hides the function list zone in the program window.
2.2.1.3 | Customize
Advanced — On the HSQ-3010, Advance User and General User are the same.
Language — Sets the display language. Choose between English and Chinese.
Reset All — Restores all the settings to the default.
2.2.1.4 | Help
This displays the software edition.
HSQ Technology v1.0
Configuration Tool 2 - 5
2.3 | System ConfigurationThis section describes the configuration of the HSQ-3010.
2.3.1 | IP Configuration
Open the Domain Focused Configuration Tool.
The HSQ-3010 is located under the Modbus TCP list. Click Modbus TCP and the host username and IP information will be shown in the right-hand screen.
Click the host OP in the left function list, then the right workspace will show two buttons: [Search] and [Add Device…].
v1.0 HSQ-3010 User Manual
System Configuration2 - 6
The Domain Focused Configuration Tool provides scan functionality:
Manual Scan — Click [Add Device…] to manually input the IP address of the device to be scanned.
Auto Scan — Click [Search] and the system will automatically scan all online devices.
Use auto scan when starting the device for the first time. When scanning, HSQ-3010 (IP: 10.0.0.1) will appear in the left-hand function list and the right-hand workspace will show the default IP address.
HSQ Technology v1.0
Configuration Tool 2 - 7
FYI: If the default IP address of the HSQ-3010 is not in the same subnet as the host, you can only modify the device IP. Only when the subnet is the same can you enter the parameter configuration screen.
2.3.1.1 | Changing the Host IP Address
Change the IP address of the host (e.g., from 10.2.2.3 to 10.0.0.10). After resetting the host IP to 10.0.0.10, click Modbus TCP in the left column and return to the screen showing the host username and IP.
Click [Refresh] and the software will adjust the new address of the host to 10.0.0.10.
v1.0 HSQ-3010 User Manual
System Configuration2 - 8
Perform an auto scan. HSQ-3010 (IP: 10.0.0.1) will display under the host IP in the left-hand function list.
2.3.1.2 | Changing the Module IP Address
Change the IP address of the HSQ-3010 (e.g., from 10.0.0.1 to 10.2.2.1). After scanning, click HSQ-3010 (IP: 10.0.0.1) in the left-hand panel and the device IP information will display in the right-hand panel.
Input the new IP in the IP Address row (e.g., 10.2.2.1) and click [Apply]. You will be prompted to input the password, the initial password is 00000000. Click [OK].
HSQ Technology v1.0
Configuration Tool 2 - 9
After the IP address has been updated, HSQ-3010 (IP: 10.0.0.1) will appear under the host IP in the left-hand function list.
2.3.2 | Device Management
When the IP addresses of the host and HSQ-3010 are in the same subnet, click HSQ-3010 (IP: 10.x.x.x) and the following screen will appear. The left-hand column shows the AI Group / DI Group /DO Group list. The right-hand workspace is available for configuring relevant system information, password, network connection, and active uploading of: System Information, Password, Network, and Stream.
2.3.2.1 | System Information
This tab displays the current firmware version information and description of the module.
If you need to update the firmware, click [Update…].
v1.0 HSQ-3010 User Manual
System Configuration2 - 1 0
If you need to change the description of the module, enter the relevant content in the Description field and then click [Apply] to save it.
2.3.2.2 | Password
To protect the device, users need to input the password when entering the I/O channel configuration or changing the device IP.
The password can be reset (the default is 00000000). After setting a new password, click [Apply] to save it. If you need to restore the factory setting, click [Reset Password…].
HSQ Technology v1.0
Configuration Tool 2 - 1 1
2.3.2.3 | Network
This displays the device IP address and network connection information.
If you need to change the configuration, input the modifications and then click [Apply] to save them.
2.3.2.4 | Stream
The HSQ-3010 supports active data uploads.
This tab displays the host IP address that receives the data. It supports a maximum of eight hosts receiving data simultaneously. The data upload frequency can be configured.
If you need to monitor the upload state, click [Open Stream Monitor…].
v1.0 HSQ-3010 User Manual
System Configuration2 - 1 2
HSQ Technology v1.0
Configuration Tool 2 - 1 3
2.4 | Hardware Parameter ConfigurationAfter scanning the HSQ-3010, the I/O list will display in the Function List.
This section provides a detailed introduction on how to configure the HSQ-3010.
2.4.1 | AI Group
The HSQ-3010 has eight analog input channels. Click AI Group to see the input state of every AI channel.
v1.0 HSQ-3010 User Manual
Hardware Parameter Configuration2 - 1 4
CH — Channel numbers.
RangeCode — Input type of every channel.
Value (hex) — Input value is displayed as real-time data, hex = (float-analymin)/ (analymax-analymin)*65535.
Value (float) — Input value is displayed as float type.
BurnOut — Flag display during the burnout detection.
1 — The input will produce burnout.
0 — Normal input.
HighAlarm — High alarm flag display.
1 — The input value is greater than or equal to the set upper limit (abnormal).
0 — The input value is less than the set upper limit (normal).
LowAlarm — Low alarm flag display.
1 — The input value is less than or equal to the set lower limit (abnormal).
0 — The input value is greater than the set upper limit (normal).
2.4.1.1 | Input Type and Alarm Configuration
The AI Group has eight channels: AI0 through AI7. They all support 0–20 mA, 4–20 mA, and 0–10 V input. AI4 through AI7 also support the following RTD input signals:
PT100 (385): -50–150º C
PT100 (392): -50–150º C
HSQ Technology v1.0
Configuration Tool 2 - 1 5
PT100 (385): 0–100º C
PT100 (392): 0–100º C
PT100 (385): 0–200º C
PT100 (392): 0–200º C
PT100 (385): 0–400º C
PT100 (392): 0–400º C
PT100 (385): -50–200º C
PT100 (392): -50–200º C
PT1000: -40–160º C
Additionally, AIs 4-7 can be used as common DIs.
When selecting the input current of one AI channel, you need to configure the 120Ω resistor jumper. After that, you can configure the input type as a current input using the utility. Voltage input and RTD do not need the resistor jumper configuration. To configure the jumper:
1. Remove the top middle cover and then the screws that are accessible through the holes.
2. Remove the top case. The eight groups of jumpers (CN6 – CN13) will be visible on the board.
v1.0 HSQ-3010 User Manual
Hardware Parameter Configuration2 - 1 6
3. Connect the pins with the clip to close the jumper(s) of the selected channel(s).
You can configure the input types for the channels in two ways using the utility:
1. Configure all the channels in the AI Group.
AI Channel Jumper
AI0 CN6
AI1 CN7
AI2 CN8
AI3 CN9
AI4 CN10
AI5 CN11
AI6 CN12
AI7 CN13
HSQ Technology v1.0
Configuration Tool 2 - 1 7
For example:
Select CH1 and input 0–10 V and click [Apply]. Now CH1 will have an input configuration of 0–10 volts.
If AI0 – AI7 need to be configured as the same type of input, then set all channel columns to 0 and select the input type and click [Apply To All] to quickly configure multiple channels.
Select an input type of 0–20 mA and click [Apply To All]. Now all the channels are set to 0–20 mA.
Clicking [Reset All] sets all AI channels to the factory configurations.
For AI4 – AI7, when selecting RTD input, the system will provide a Temperature Compensation column. You can input the compensation value according to the actual requirements, click [Apply] to save.
When AI4 – AI7 are used as DIs, the input type should be set as RTD.
2. Click one channel in the function list to separately configure it. You can not only configure the input type here, but also complete the alarm configuration:
Burn Out
High Alarm
Low Alarm
v1.0 HSQ-3010 User Manual
Hardware Parameter Configuration2 - 1 8
Click [Apply] to save the configurations.
2.4.1.2 | Frequency Selection
According to the grid frequency, the selections are 50 Hz or 60 Hz.
Click [Apply] to save the configuration.
2.4.1.3 | Calibration
When executing zero calibration or span calibration operations, click [Zero Calibration…] or [Span Calibration…].
You can calibrate according to the instructions of the popup window. Click [Calibrate] when you are satisfied with the configuration.
HSQ Technology v1.0
Configuration Tool 2 - 1 9
2.4.2 | DI Group
The HSQ-3010 has eight digital input channels. Click DI Group to see the input state of every DI channel.
CH — Channel numbers.
RangeCode — Input type of every channel.
Start/Stop — When selecting a frequency of accumulator input, you can start or stop inputting manually.
v1.0 HSQ-3010 User Manual
Hardware Parameter Configuration2 - 2 0
Value —
When the input type is Normal DI : 1=with input, 0=without input or burnout.
When the input type is Frequency the input signal frequency is displayed.
When the input type is Accumulator the input signal pulses are displayed.
When AI4 – AI7 are used as common dry contact DIs, their input states can be displayed here, corresponding to DI8 – DI11. (Also refer to Appendix A, “I/O Wiring”.)
For example, use AI4 as a DI. Set CH4 of the AI Group as any RTD input type and short AI4 and AGND.
Now check the Value field of DI8 to view the input state of AI4. When AI4+ and AI4- are closed, the DI8 Value field will display 1. When AI4+ and AI4- are open, the DI8 Value field will display 0.
FYI: Value fields for DI8 – DI11 show 1 by default.
HSQ Technology v1.0
Configuration Tool 2 - 2 1
2.4.2.1 | Input Type Configuration
The DI Group has eight channels in total, supporting three input types:
Common DI
Frequency
Accumulator
You can set the input type in two ways:
1. Configure all the fields in the DI Group interface. Click [Apply] to save the configuration.
2. Configure fields separately by clicking a channel in the function list.
v1.0 HSQ-3010 User Manual
Hardware Parameter Configuration2 - 2 2
2.4.3 | DO Group
The HSQ-3010 has four digital output channels. Click DO Group to see the output state of every DO channel.
CH — Channel numbers.
RangeCode — Output type of every channel.
Start/Stop — When the output is PWM, double-click to start or stop the output manually.
Value — 1 = high level, 0 = low level. When is is Normal DO, double-click to start or stop the output manually.
HSQ Technology v1.0
Configuration Tool 2 - 2 3
2.4.3.1 | Output Type Configuration
The DO Group has four channels in total, supporting two output types:
Common DO
PWM
You can set the output type in two ways:
1. Configure all the fields in the DO Group interface. When selecting PWM output, you need to set the PWM period to 0.02–3600 and the duty cycle to 10–100%. Click [Apply] to save the configuration.
2. Configure fields separately by clicking a channel in the function list.
v1.0 HSQ-3010 User Manual
Hardware Parameter Configuration2 - 2 4
HSQ Technology v1.0
A P P E N D I X A
I/O WIRING
A - 1v1.0 HSQ-3010 User Manual
I/O Wiring DiagramA - 2
A.1 | I/O Wiring Diagram
Figure A-1. HSQ-3010 Connections
0 - 20mA4 - 20mA 0 - 10V
0 - 20mA4 - 20mA 0 - 10V RTD DI
RTD
GND
AI0
+
AI7
-
AI7
+
AGN
D
AI6
-
AI6
+
AGN
D
AI5
-
AI5
+
AGN
D
AI4
-
AI4
+
AI3
-
AI3
+
AI2
-
AI2
+
AI1
-
AI1
+
AI0
-
AGN
D
LAN
DI0
COM
DO
2
COM
DO
1
COM
DO
0
N/A
DI7
COM
DI6
DI5
COM
DI4
DI3
COM
DI2
DI1
COM
DO
3
N/A
N/A
COM
N/A
VS+
VS-
DODI
LOA
D
DCDC
DC
HSQ-3010
HSQ Technology v1.0
A P P E N D I X B
MODBUS ADDRESSES
B - 1v1.0 HSQ-3010 User Manual
Modbus TCP Address (0x)B - 2
B.1 | Modbus TCP Address (0x)Table B-1. Modbus TCP Addresses
Address Channel Description Attribute
00001 0 DI0 Value Read
00002 1 DI1 Value Read
00003 2 DI2 Value Read
00004 3 DI3 Value Read
00005 4 DI4 Value Read
00006 5 DI5 Value Read
00007 6 DI6 Value Read
00008 7 DI7 Value Read
00009 UDI0 UI4 as DI Value Read
00010 UDI1 UI5 as DI Value Read
00011 UDI2 UI6 as DI Value Read
00012 UDI3 UI7 as DI Value Read
00401 0 DO0 Value R/W
00402 1 DO1 Value R/W
00403 2 DO2 Value R/W
00404 3 DO3 Value R/W
00501 0 UI0 High Alarm Flag Read
00502 1 UI1 High Alarm Flag Read
00503 2 UI2 High Alarm Flag Read
00504 3 UI3 High Alarm Flag Read
00505 4 UI4 High Alarm Flag Read
00506 5 UI5 High Alarm Flag Read
00507 6 UI6 High Alarm Flag Read
00508 7 UI7 High Alarm Flag Read
HSQ Technology v1.0
B - 3
00601 0 UI0 Low Alarm Flag Read
00602 1 UI1 Low Alarm Flag Read
00603 2 UI2 Low Alarm Flag Read
00604 3 UI3 Low Alarm Flag Read
00605 4 UI4 Low Alarm Flag Read
00606 5 UI5 Low Alarm Flag Read
00607 6 UI6 Low Alarm Flag Read
00608 7 UI7 Low Alarm Flag Read
00701 0 UI0 Burn Out Read
00702 1 UI1 Burn Out Read
00703 2 UI2 Burn Out Read
00704 3 UI3 Burn Out Read
00705 4 UI4 Burn Out Read
00706 5 UI5 Burn Out Read
00707 6 UI6 Burn Out Read
00708 7 UI7 Burn Out Read
Table B-1. Modbus TCP Addresses (continued)
Address Channel Description Attribute
v1.0 HSQ-3010 User Manual
Modbus TCP Address (4x)B - 4
B.2 | Modbus TCP Address (4x)Table B-2. AI Float
Address Channel Description AttributeLength
(2 bytes)Remarks
40001 0 UI0 Float Value Read 2
40003 1 UI1 Float Value Read 2
40005 2 UI2 Float Value Read 2
40007 3 UI3 Float Value Read 2
40009 4 UI4 Float Value Read 2
40011 5 UI5 Float Value Read 2
40014 6 UI6 Float Value Read 2
40015 7 UI7 Float Value Read 2
Table B-3. AI Hex
Address Channel Description AttributeLength
(2 bytes)Remarks
40101 0 UI0 Hex Value Read 1
40102 1 UI1 Hex Value Read 1
40103 2 UI2 Hex Value Read 1
40104 3 UI3 Hex Value Read 1
40105 4 UI4 Hex Value Read 1
40106 5 UI5 Hex Value Read 1
40107 6 UI6 Hex Value Read 1
40108 7 UI7 Hex Value Read 1
HSQ Technology v1.0
B - 5
Table B-4. System Information
Address Channel Description AttributeLength
(2 bytes)Remarks
41201–41218
System Information Read 18
Module name: 10Version: 2AI Channel Number: 1DI Channel Number: 1Super User: 1AI Calibration: 1AO Calibration: 1Reserved: 1
41241Supports AI Range
CodeRead 16
bit0: UVbit1: UIbit3: PT100 bit4: PT1000
41273Supports DI Range
CodeRead 16
bit0: UVbit1: UIbit3: PT100bit4: PT1000
41289Supports DO Range
CodeRead 16
bit0: Nor DObit1: PWM
Table B-5. UI Function Code
Address Channel Description AttributeLength
(2 bytes)Remarks
40601 0 UI0 Range Code R/W 1
40602 1 UI1 Range Code R/W 1
40603 2 UI2 Range Code R/W 1
40604 3 UI3 Range Code R/W 1
40605 4 UI4 Range Code R/W 1
40606 5 UI5 Range Code R/W 1
40607 6 UI6 Range Code R/W 1
40608 7 UI7 Range Code R/W 1
v1.0 HSQ-3010 User Manual
Modbus TCP Address (4x)B - 6
Table B-6. UI Temperature Com
Address Channel Description AttributeLength
(2 bytes)Remarks
42001 0 UI0 Temperature R/W 2 Data Type Float
42003 1 UI1 Temperature R/W 2 Data Type Float
42005 2 UI2 Temperature R/W 2 Data Type Float
42007 3 UI3 Temperature R/W 2 Data Type Float
42009 4 UI4 Temperature R/W 2 Data Type Float
42011 5 UI5 Temperature R/W 2 Data Type Float
42013 6 UI6 Temperature R/W 2 Data Type Float
42015 7 UI7 Temperature R/W 2 Data Type Float
Table B-7. UI High Alarm
Address Channel Description AttributeLength
(2 bytes)Remarks
42101 0 High Alarm Value R/W 1 Set Value × 10
42102 1 High Alarm Value R/W 1 Set Value × 10
42103 2 High Alarm Value R/W 1 Set Value × 10
42104 3 High Alarm Value R/W 1 Set Value × 10
42105 4 High Alarm Value R/W 1 Set Value × 10
42106 5 High Alarm Value R/W 1 Set Value × 10
42107 6 High Alarm Value R/W 1 Set Value × 10
42108 7 High Alarm Value R/W 1 Set Value × 10
Table B-8. UI Low Alarm
Address Channel Description AttributeLength
(2 bytes)Remarks
42201 0 Low Alarm Value R/W 1 Set Value × 10
42202 1 Low Alarm Value R/W 1 Set Value × 10
42203 2 Low Alarm Value R/W 1 Set Value × 10
42204 3 Low Alarm Value R/W 1 Set Value × 10
HSQ Technology v1.0
B - 7
42205 4 Low Alarm Value R/W 1 Set Value × 10
42206 5 Low Alarm Value R/W 1 Set Value × 10
42207 6 Low Alarm Value R/W 1 Set Value × 10
42208 7 Low Alarm Value R/W 1 Set Value × 10
42301 0 Burn Out Value R/W 1 Set Value × 10
42302 1 Burn Out Value R/W 1 Set Value × 10
42303 2 Burn Out Value R/W 1 Set Value × 10
42304 3 Burn Out Value R/W 1 Set Value × 10
42305 4 Burn Out Value R/W 1 Set Value × 10
42306 5 Burn Out Value R/W 1 Set Value × 10
42307 6 Burn Out Value R/W 1 Set Value × 10
42308 7 Burn Out Value R/W 1 Set Value × 10
Table B-9. DI Function Code
Address Channel Description AttributeLength
(2 bytes)Remarks
43201 0 DI Range Code R/W 1
43202 1 DI Range Code R/W 1
43203 2 DI Range Code R/W 1
43204 3 DI Range Code R/W 1
43205 4 DI Range Code R/W 1
43206 5 DI Range Code R/W 1
43207 6 DI Range Code R/W 1
43208 7 DI Range Code R/W 1
Table B-8. UI Low Alarm (continued)
Address Channel Description AttributeLength
(2 bytes)Remarks
v1.0 HSQ-3010 User Manual
Modbus TCP Address (4x)B - 8
Table B-10. DO Function Code
Address Channel Description AttributeLength
(2 bytes)Remarks
44001 0 DO Range Code R/W 3
44004 1 DO Range Code R/W 3
44007 2 DO Range Code R/W 3
44010 3 DO Range Code R/W 3
Table B-11. DI Counter/Frequency
Address Channel Description AttributeLength
(2 bytes)Remarks
44801 0 DI Counter/Frequency R 2Data Type Float or
DWORD
44803 1 DI Counter/Frequency R 2Data Type Float or
DWORD
44805 2 DI Counter/Frequency R 2Data Type Float or
DWORD
44807 3 DI Counter/Frequency R 2Data Type Float or
DWORD
44809 4 DI Counter/Frequency R 2Data Type Float or
DWORD
44811 5 DI Counter/Frequency R 2Data Type Float or
DWORD
44813 6 DI Counter/Frequency R 2Data Type Float or
DWORD
44815 7 DI Counter/Frequency R 2Data Type Float or
DWORD
HSQ Technology v1.0
B - 9
B.3 | Range Code IndexTable B-12. AI Range Code
Address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
High Byte Low Byte
41601 Range Code 50 or 60 Hz
Table B-13. AI Type
Description Function Code
UI_B Input signal is 4–20 mA 7
PT100_F Input signal is PT100-392 Measuring range is -50–150º C 28
PT100_E Input signal is PT100-385 Measuring range is -50–200º C 29
PT100_D Input signal is PT100-385 Measuring range is 0–400º C 30
PT100_A Input signal is PT100-385 Measuring range is -50–150º C 31
PT100_B Input signal is PT100-385 Measuring range is 0–100º C 33
PT100_C Input signal is PT100-385 Measuring range is 0–200º C 34
PT100_G Input signal is PT100-392 Measuring range is 0–100º C 37
PT100_H Input signal is PT100-392 Measuring range is 0–200º C 38
PT100_I Input signal is PT100-392 Measuring range is 0–400º C 40
PT100_J Input signal is PT100-392 Measuring range is -50–200º C 41
PT1000_A Input signal is PT1000 Measuring range is -40–160º C 42
UI_A Input signal is 0–20 mA 70
UV10 Input signal is 0–10 V 72
Table B-14. DI Range Code
Address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
High Byte Low Byte
43201 Range Code If DI is a Counter, set on/off
v1.0 HSQ-3010 User Manual
Range Code IndexB - 1 0
Table B-15. DI Type
Description Function Code
Normal_DI 0
Counter 1
Frequency 2
Table B-16. DO Range Code
Address 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
High Byte Low Byte
44001 ON/OFF If DO is set as PWM to record the duty cycle.
44002 If DO is set as PWM to record the period.
44003
Table B-17. DO Type
Description Function Code
Normal_DO 0
PWM 1
HSQ Technology v1.0
A P P E N D I X C
STREAM DATA FORMAT
C - 1v1.0 HSQ-3010 User Manual
Stream Data FormatC - 2
C.1 | Stream Data FormatThe HSQ-3010 supports active data upload. The following table lists the packet formats that are sent.
Table C-1. Stream Data Format
Byte Order Byte Length Item Examples Remarks
0 1 Header 0x23 (‘#’)
1 1 Header 0x47 (‘G’)
2 1 Header 0x45 (‘E’)
3 1 Header 0x41 (‘B’)
4 1 Header 0x58 (‘A’)
5 1 Header 0x4d (‘M’)
6 1 Header 0x53 (‘S’)
7 1 Header 0x47 (‘G’)
8 1 Header 0x55
9 1 Header 0xaa
10 2 Sequence number 0x0001
12 1 Message code 0x10
15 2 Device type 0x0401
13 2 Data length
17 2 Firmware version major (wFWVMajor)
19 2 Firmware version minor (wFWVMinor)
21 2 Hardware version (wHWVersion)
23 4 Reserved1Reserved for future use
27 4 Reserved2Reserved for future use
31 160 Data
191
HSQ Technology v1.0