High Current Measurements

  • Upload
    king

  • View
    225

  • Download
    0

Embed Size (px)

Citation preview

  • 7/26/2019 High Current Measurements

    1/39

    UNIVERSITI TUN HUSSEIN ONN

    MALAYSIA

    FACULTY OF ELECTRICAL AND ELECTRONIC

    ENGINEERING

    BEF 20903

    BEF 23903

    ELECTRICAL MEASUREMENTS

    High AC Cur rent Measurements

    Using Current Transformer

    Written By Dr. Zainal Alam Haron

    Dept of Electrical Power Engineering

    Universiti Tun Hussein Onn Malaysia

    Date

    Version First draft

  • 7/26/2019 High Current Measurements

    2/39

    2

    Contents

    1. Introduction

    2. Types of Current Transformers3. Equivalent Circuit of a current transformer

    4. Current Transformer Ratios

    5. Phasor Diagram of Current Transformer

    6. Errors in current transformer

    7. Phase angle error

    8. Methods to minimize errors

    9. Types of current transformer construction

    10.Clamp meter

  • 7/26/2019 High Current Measurements

    3/39

    3

    LEARNING OUTCOMES

    After completing this module you will be able to:

    1. Explain the principle of operation, construction and use of current transformers to

    measure AC currents,

    2. Interpret the different current transformers at suppliers catalog,

    3. Specify the different kinds of current transformers.

  • 7/26/2019 High Current Measurements

    4/39

    4

    1.0 INTRODUCTION

    High AC currents can be measured with shunts under special circumstances, but most

    often such direct connections to AC lines are extremely dangerous to humans. One

    way to get around the hazard is to use current transformers (CT) that isolate AC line

    voltages and reduce input current by a specified ratio. A current transformer produces

    a scaled down replica of the input quantity to the accuracy expected for the particular

    measurement. The common laws for transformers are valid for current transformers.

    Tasks of Current Transformers

    The main tasks of a current transformer are:

    1. To transform currents from a usually high value to a value easy to handle for

    measuring instruments.

    2. To insulate the metering circuit from the primary high voltage system.

    3. To provide possibilities of standardizing the measuring instruments to a few

    rated currents.

    Advantages of current transformers

    1. The measuring instruments can be placed for away from the high voltage side

    by connecting long wires to the current transformer. This ensures the safety of

    instruments as well as the operator.

    2. A current transformer can be used to extend the range of current measuring

    instruments like ammeters.

    3. The power loss in current transformers is very small as compared to power

    loss due to the resistance of shunts.

  • 7/26/2019 High Current Measurements

    5/39

    5

    Comparison Between Resistive Shunt And Current Transformer

    Table 1; Shunt versus current transformer trade-off

    Advantage Shunt Current

    transformer

    Meter cost X

    Meter can handle higher currents

    (greater than 100 A)

    X

    Meter power consumption X

    Fewer accuracy issues (saturation,

    phase response at high-power factors) X

    2.0 TYPES OF CURRENT TRANSFORMERS

    Based on the construction, two types of CTs can be identified.

    1) Clamp-on CT

    This is a C.T., in which the core can be opened with the help of a clamp and

    the conductor (whose current is to measured) can be inserted into the core.

    This conductor acts as a primary winding. The secondary winding is wound on

    the laminated core. A low range ammeter is connected across the secondary,

    which measures current of the conductor. It is a portable instrument, which

    can be used in laboratories.

    Figure 1. Clamp-on CT

  • 7/26/2019 High Current Measurements

    6/39

    6

    2) Bar type CT

    A bar type CT has a circular ring type core over which secondary winding is

    wound, across which a direct reading ampere meter is connected. When a bar

    conductor or a Bus bar whose current, is to be measured is inserted in to the

    ring, the ampere meter reads the current (Figure 2).

    Figure 2. Bar type CT

  • 7/26/2019 High Current Measurements

    7/39

    7

    3.0 EQUIVALENT CIRCUIT OF A CURRENT TRANSFORMER

    For quantitative analysis, a current transformer can be represented by the equivalent

    circuit of Figure 3.

    Figure 3. Equivalent circuit of a current transformer.

    where

    Vp : Primary voltage

    Ip : Primary currentRp : Primary winding resistance

    Xp : Primary winding reactance

    Io : Exciting current

    Ie : Core loss current

    Re : Equivalent core loss resistance

    Im : Magnetizing current

    Xm : Magnetizing reactance

    Ep : Primary winding induced voltage

    p, s : Primary and Secondary windings

    : Flux surrounding the windings

    Is : Secondary winding current

    Es : Secondary induced emf

    Rs : Secondary winding resistance

    Xs : Secondary winding reactance

    RL : Rsistance of external burden

    Np:Ns Is

    ZL= RL+ jX LEs

    Ip

    Im

    Io

    Ie

    Ep

    IsXp

    Re Xm

    XsRs

    Rp

    Vp Vs

    Ideal

    CT

  • 7/26/2019 High Current Measurements

    8/39

    8

    XL : Reactance of external burden

    KT : Turn ratio = Ns/Np

    It can be seen from the equivalent circuit diagram shown in Figure 3 that the primary

    current contains two components:

    An exciting current, which magnetizes the core and supplies the eddy current

    and hysteresis losses, etc.

    A remaining primary current component, which is available for transformation

    to secondary current in the inverse ratio of turns.

    Simplified equivalent circuit

    The equivalent diagram in Figure 3 comprises all quantities necessary for error

    calculations. The primary internal voltage drop does not affect the exciting current

    and the errors. Therefore the primary internal impedance is not indicated in the

    diagram.

    The secondary internal impedance, however, must be taken into account, but only the

    winding resistance Rs. The leakage reactance is negligible where continuous ring

    cores and uniformly distributed secondary windings are concerned. The exciting

    impedance is represented by an inductive reactance in parallel with a resistance. I m

    and Ie are the reactive and loss components of the exiting current. The resulting

    simplified equivalent circuit is shown in Figure 4.

    Figure 4. Simplified equivalent circuit of a current transformer.

    Np:Ns

    ZL= RL+ jX LEs

    Ip

    Ep

    Is

    Im

    Io

    Ie

    Re Xm

    Vp

    Is

    Vs

    Ideal

    CT

    Rs

  • 7/26/2019 High Current Measurements

    9/39

    9

    Equivalent Circuit Of CT Referred To The Secondary Side

    Figure 5 shows a simplified equivalent current transformer diagram converted to the

    secondary side.

    Figure 5. Simplified equivalent circuit of current transformer referred to the

    secondary side.

    Current Transformer Ratios

    The transformer ratios for a CT can be defined as follows:

    i. Turns ratio- This is the ratio of the turns of the transformer windings.

    p

    s

    tN

    N

    K

    where

    Ns= No. of turns in secondary winding

    Np= No. of turns in primary winding

    ii. Transformation (Actual) ratio--This is the ratio of primary winding

    current (Ip) to the secondary winding current (Is) of the transformer;

    ZL= RL+ jX L

    Ip

    Im

    Io

    Ie

    Re XeEs

    Is

    Vs

    Note: Rshas been assumed negligible here.

  • 7/26/2019 High Current Measurements

    10/39

    10

    s

    p

    actI

    IK

    iii. Nominal ratio- This is the ratio of the rated primary winding current(Ip(rated)) to the rated secondary winding current (Is(rated)) of the

    transformer.

    t

    p

    s

    s

    p

    nom KN

    N

    ratedI

    ratedIK

    )(

    )(

    iv. Ratio correction factor (R.C.F.) - This is equal to the transformation

    ratio divided by nominal ratio.

    nom

    act

    K

    KFCR ..

    Thus,

    nomact KFCRK .. and

    act

    nomK

    FCRK

    ..

    Note

    If the exciting current Io could be neglected the transformer should reproduce the

    primary current without errors and the following equation should apply to the primary

    and secondary currents:

    sts

    p

    s

    p IKIN

    NI

    In reality, however, it is not possible to neglect the exciting current.

    Worked Example 1

    A bar-type current transformer which has 1 turn on its primary and 160 turns on its

    secondary is to be used with a standard range of ammeters that have an internal

    resistance of 0.2 . The ammeter is required to give a full-scale deflection when the

  • 7/26/2019 High Current Measurements

    11/39

    11

    primary current is 800 A. Calculate the maximum secondary current and secondary

    voltage across the ammeter.

    Figure 6. Pictorial view of bar-type current transformer referred to in the Worked

    Example above.

    Solution

    Secondary current:

    AN

    NII

    s

    p

    ps 5160

    1800

    Voltage across ammeter:

    0.12.055 AAss

    RRIV volts

    Worked Example 2

    A current transformer has a rating of 50 VA, 400 A/5 A, 36 kV, 50 Hz. It is connected

    into an a.c. line having a line-to-neutral voltage of 14.4 kV. The ammeters, relays and

    connecting wires on the secondary side possess a total impedance (burden) of 1.2 .

    If the transmission line currentis 280 A, calculate:

    1. The secondary current

    2. The voltage across the secondary terminals

    3. The voltage drop across the primary.

  • 7/26/2019 High Current Measurements

    12/39

    12

    Figure 7.

    Solution

    (a) The secondary current

    80

    1

    400

    5

    p

    s

    s

    p

    I

    I

    N

    N

    5.380

    1280

    p

    s

    psN

    NII A

    (b) The voltage across the secondary terminals

    2.42.15.3 sss RIV V

    (c) The voltage across the primary terminals

    5.52400

    52.4

    s

    p

    spN

    NVV mV

    Exercise

    A toroidal transformer has a ratio of 1000 A/5 A. The line conductor carries a current

    of 600 A.

    (a)Calculate the voltage across the secondary winding if the ammeter has an

    impedance of 0.15 .

    (b)Calculate the voltage drop the transformer produces on the line conductor.

    (c) If the primary is looped four times through the toroidal opening, calculate the new

    current ratio.

  • 7/26/2019 High Current Measurements

    13/39

    13

    Figure 8.

    [Answer: 0.45 V; 2.24 mV; 250 A/5 A]

    Changing The Transformer Turns Ratio

    Relatively large changes in a current transformers turns ratio can be achieved by

    modifying the primary turns through the CTs window where one primary turn is

    equal to one pass and more than one pass through the window results in the electrical

    ratio being modified.

    So for example, a current transformer with a relationship of say, 300/5A can be

    converted to another of 150/5A or even 100/5A by passing the main primary

    conductor through its interior window two or three times as shown. This allows a

    higher value current transformer to provide the maximum output current for the

    ammeter when used on smaller primary current lines.

  • 7/26/2019 High Current Measurements

    14/39

    14

    PHASOR DIAGRAM OF CURRENT TRANSFORMER

    The vector diagram for the circuit shown in Figure 4 is shown in Figure 9 Here flux

    has been taken as reference. EMF Es and Ep lags behind the flux by 90o. The

    magnitude of the phasors Esand Epare proportional to secondary and primary turns.The excitation current Io is made up of two components, namely, Im and Ie. The

    secondary current Io lags behind the secondary induced emf Esby an angle s. The

    secondary current is now transferred to the primary side by reversing I sand multiplied

    by the turns ratio KT. The total current flows through the primary Ipis then vector sum

    of KTIsand Io.

    Is-Secondary Current

    Es- Secondary induced emf

    Ip- primary Current

    Ep- primary induced emf

    KT- turns ratio = numbers of

    secondary turns/number of primary

    turns

    Io- Excitation Current

    Im- magnetizing component of Io

    Iw- core loss component of Io

    m- main flux.

    Figure 9. Phasor diagram of a current transformer.

    Im

    Ip

    Ie Io

    KTIs

    -Ep

    Es

    Is

    O

  • 7/26/2019 High Current Measurements

    15/39

    15

    ERRORS IN CURRENT TRANSFORMER

    Current transformers suffer from two errors:

    1. Current ratio (or turns ratio) error

    2. Phase angle error

    1. The Current Ratio Error

    Figure 3 shows that not all the primary current passes through the secondary circuit.

    Part of it is consumed by the core, which means that the primary current is not

    reproduced exactly. The relation between the currents will in this case be:

    osTos

    p

    s

    s IIKIIN

    NI

    '

    Figure 10 shows a vector representation of the three currents in the equivalent

    diagram.

    Figure 10. Vector representation of the three currents in a CT.

    IpIs = KTIs

    Io

  • 7/26/2019 High Current Measurements

    16/39

    16

    Hence, the percentage current error in the primary current is

    %100

    )(

    )()(%

    actualI

    actualImeasuredI

    p

    pp

    %100

    p

    psT

    I

    IIK

    %100

    A

    AN

    K

    KK

    According to the definition above, the current error is positive if the secondary

    current is too high, and vice versa.

    Current error is an error that arises when the current value of the actual transformation

    ratio is not equal to rated transformation ratio.

    Current error %100%100'%

    p

    psN

    p

    ps

    I

    IIK

    I

    II

    KN= rated transformation ratio

    Ip= actual primary current

    Is= actual secondary current

    Worked Example 3

    In case of a 2000/5A class 1 5VA current transformer

    TN KK 400

    5

    2000

    Ip= 2000 A

  • 7/26/2019 High Current Measurements

    17/39

    17

    Is= 4.9 A

    Current error %22000

    20005400%100

    p

    psT

    I

    IIK

    Worked Example 4

    An application requires a 20:5 CT ratio, but only a 50:5 CT is available. Given that

    the number of primary turns (Np) is 3, determine the number of secondary turns that

    need to be added so that a 20:5 actual ratio will be obtained.

    Solution

    Given: Nameplate transformation ratio, 105

    50

    NK

    Number of primary turns, Np= 3

    We require 45

    20

    AK

    Therefore,3

    104

    saN

    giving Nsa= 2 turns

  • 7/26/2019 High Current Measurements

    18/39

    18

    2. Phase Angle Error

    For a ideal current transformer the angle between the primary and reversed

    secondary current vector is zero. But for an actual current transformer there is

    always a difference in phase between two due to the fact that primary current

    has to supply the component of the exiting current. The angle between the

    secondary current phasor reversed (Is) and the primary current (Ip) (see Figure

    8) is termed as Phase Angle Error; that is,

    ps II '

    The phase angle error is usually expressed in minutes, and if the reversed

    current phasor leads the primary current phasor then the phase angle error is

    defined as positive; otherwise it is taken as negative.

    It will be seen that with a moderately inductive burden, resulting in Is and Io

    approximately in phase, there will be little phase error and the exciting

    component will result almost entirely in ratio error. A reduction of the

    secondary winding by one or two turns is often used to compensate for this.

    Figure 11. Picture of current CTs in a switchyard.

  • 7/26/2019 High Current Measurements

    19/39

    19

    Worked Example 5

    The exciting current of a transformer (of ratio 1000A:5A) with a burden of 1 is 1 A

    at a p.f. = 0.4. Calculate actual transformation ratio and ratio error.

    Solution

    Given : Exciting current, Io= 1 A, p.f = 0.4

    Turns ratio, KT= NS/NP=1000/5 = 200

    Burden, ZL= 1 (resistive)

    Figure 12. Equivalent circuit of ideal current transformer connected to a 1 burden.

    Figure 13. Simplified equivalent circuit of non-ideal current transformer connected

    with a 1 burden.

    1000A:5A Is

    ZL= 1 Es

    Ip

    Im

    Io

    Ie

    Ep

    Is

    1000A:5A Is

    ZL= 1 ES

  • 7/26/2019 High Current Measurements

    20/39

    20

    Power factor of exciting current (Io),

    p.f. = 0.4 = cos

    Therefore,

    o42.664.0cos 1

    and

    oooo

    58.2342.669090

    Figure 14. Phasor diagram showing phase relationships between Io, Ie, and Im.

    Turns ratio

    2001000

    A5

    A

    NK

    Current flowing in secondary, Is= 5 A, p.f. = 1. Therefore, reflected secondary

    current is

    AA5

    A10005

    1000' AIKI

    sNs

    IeIo

    Im= 80 A

  • 7/26/2019 High Current Measurements

    21/39

    21

    Figure 15. Phasor diagram showing phase relationships between Ip, Io, and Is.

    From Figure 15, primary current

    22' cossin oosp IIII

    22 58.23cos158.23sin11000 oo

    A4.1000

    Therefore, actual turns ratio

    8.2005

    4.1000

    s

    p

    AI

    IK

    Ratio error,

    %04.08.200

    8.200200%

    actual

    actualmeasured

    K

    KKe Ans.

    Is

    Ip

    Io

  • 7/26/2019 High Current Measurements

    22/39

    22

    Worked Example 6

    A CT has a single turn primary and 400 secondary turns. The magnetizing curent is 90

    A while core loss current is 40 A. Secondary circuit phase angle is 28o. Calculate the

    actual primary current and ratio error when secondary current carries 5 A current.

    Solution

    The information given is only sufficient to be applied to the simplified equivalent

    circuit of a current transformer shown in Figure x.

    Figure 16. Simplified equivalent circuit of a current transformer.

    N

    p

    s

    T KN

    NK 400

    1

    400

    20005400'

    s

    p

    s

    s IN

    NI A

    Np:Ns

    ZLEs

    Ip

    Ep

    Is

    Im

    Io

    Ie

    Re Xm

    Vp

    Is

    Vs

    Ideal

    CT

  • 7/26/2019 High Current Measurements

    23/39

    23

    Figure 15. Phasor diagram showing phase relationships between Ip, Io, and Is.

    Y- component of primary-referred secondary current,

    176628cos2000cos'' oss IyI A

    X- component of primary-referred secondary current,

    9.93828sin2000sin'' oss IxI A

    X- component of excitation current, Im= 90 A

    Y- component of excitation current, Ie= 40 A

    Total x-component of primary current,

    1029909.938)()( ' msp IxIxI A

    Total y-component of primary current,

    1806401766)()( '

    esp IyIyI A

    Therefore, actual primary current

    Is

    Ip

    Io

    = 28

    o

  • 7/26/2019 High Current Measurements

    24/39

    24

    207918061029)()( 2222 yIxII ppp A Ans.

    Percentage current error

    )(

    )()(%

    actualI

    actualImeasuredI

    p

    pp

    p

    ps

    I

    II

    '

    %8.3%1002079

    20792000

    Therefore,

    %8.3% Ans.

    How to Reduce Errors in Current Transformer

    In current transformer design, the core characteristics must be carefully selected

    because excitation current Ioessentially subtracts from the metered current and affects

    the ratio and phase angle of the output current. The higher the exciting current or core

    loss the larger the error.

    It is desirable to reduce these errors, for better performance. For achieving minimum

    error in current transformer, one can follow the following,

    1. Using a core of high permeability, low hysteresis loss magnetic

    materials, and large cross section. The number of joints in the core

    should be minimum to minimize the air gaps and the reluctance.

    Three materials are preferred for making cores:

    i. Cold rolled grain oriented (CRGO) silicon steel

    ii. Hot rolled grain oriented (HRGO) silicon steel

    iii. Nickel Iron alloys.

  • 7/26/2019 High Current Measurements

    25/39

    25

    The grain-oriented materials are preferred as their grains are oriented

    in the direction so as to provide unidirection to the magnetic field,

    usually rectangular (Figure 160a) or a ring type (Figure 16b) shape is

    made. In ring shape, the joints may be eliminated and due to

    orientation of the grains, flux is always along the grains and so the

    reluctance as minimum.

    Figure 16. Current transformer cores. (a) rectangular core; (b) ring core.

    The various alloys used for making cores are

    (i) Silicon steel (4% silicon)

    (ii) Mumetal (76% nickel)

    (iii) Permendur (50% cobalt)

    (iv) Hypernik (50% nickel)

    2. Keeping the rated burden to the nearer value of the actual burden.

    3. Ensuring minimum length of flux path and increasing cross sectional

    area of the core, minimizing joint of the core.

    4. Lowering the secondary internal impedance.

    Secondary voltage of open-circuit CT

    Every precaution must be taken to never open the secondary circuit of a currenttransformer while current is flowing in the primary circuit. If the secondary is

  • 7/26/2019 High Current Measurements

    26/39

    26

    accidentally opened, the primary current Ipcontinues to flow unchanged because the

    impedance of the primary is negligible compared to that of the electrical load. The

    line current thus becomes the excitingcurrent of the transformer because there is no

    further bucking effect due to the secondary ampere-turns. Because the line current

    may be 100 to 200 times greater than the normal exciting current, the flux in the core

    reaches peaks much higher than normal. The flux is so large that the core is totally

    saturated for the greater part of every cycle. Referring to Figure 17, as the primary

    current rises and falls during the first half cycle, flux in the core also rises and falls,

    but remains at a fixed saturation level satfor most of the time.

    Figure 17. Primary current, flux, and secondary voltage when a CT is open-circuited.

    The same thing happens during the second half-cycle. During these saturation

    intervals, the induced voltage across the secondary winding is negligible because the

    flux changes very little. However, during the unsaturated intervals, the flux changes at

    an extremely hig rate, inducing voltage peaks of several thousand volts across the

    ip

    sat

    Ndtd

    e

    3000 V

    secondary

    voltage

  • 7/26/2019 High Current Measurements

    27/39

    27

    open-circuited secondary. This is a dangerous situation because an unsuspecting

    operator could easily receive a bad shock. The voltage is particularly high in current

    transformers having ratings above 50 VA.

    Thus, for reasons of safety, if a meter or relay in the secondary circuit of a CT has to

    be disconnected, we must first short-circuit the secondary winding and then remove

    the component. Short-circuiting a current transformer does no harm because the

    primary current remains unchanged and the secondary current can be greater than that

    determined by the turns ratio. The short-circuit across the secondary may be removed

    afterthe secondary circuit is again closed.

    To facilitate maintenance of ammeter instrumentation, short-circuiting switches are

    often installed in parallel with the CTs secondary winding, to be closed whenever the

    ammeter is removed for service (see Figure 18).

    Figure 18. Short-circuit switch allows ammeter to be removed from an active current

    transformer.

  • 7/26/2019 High Current Measurements

    28/39

    28

    Worked Example

    Current is to be measured in a single-phase line which supplies a 240-V, 20 kW load

    with a 0.8 power factor. Select an appropriate ammeter and current transformer.

    Direct reading ammeters are available with full-scale reading ranging from 2 to 20 A.

    Figure 19

    Step 2. Select Ammeter.

    Solution

    Measurement of larger currents requires the use of a

    current transformer. Standard practice is to use a 5-A full-

    scale ammeter with the appropriate current transformer.

    Ammeters so used are calibrated in accordance with the

    selected transformer.

    Step 1. Calculate Current

    pfV

    PI

    0.8240

    20,000

    A104I Therefore,

  • 7/26/2019 High Current Measurements

    29/39

    29

    TYPES OF CURRENT TRANSFORMER CONSTRUCTION

    Below are the types of current transformers in the manner of construction and

    applications.

    1. Bar-type Current Transformer

    A Bar-type current transformer is one that has a fixed and straight single

    primary winding turn passing through the magnetic circuit. The primary

    winding and secondary winding(s) are insulated from each other and from the

    core(s) and are assembled as an integral structure.

    2. Bushing-type Current Transformer

    A bushing-type current transformer is one that has an annular core and a

    secondary winding insulated from and permanently assembled on the core but

    has no primary winding and no insulation for a primary winding. This type of

    current transformer is for use with a fully insulated conductor as the primary

    winding. A bushing type current transformer usually is used in equipment

    where the primary conductor is a component pan of other apparatus.

    Step 3 Select Current Transformer

    Because the current is

    greater than 20 A, a current

    transformer is required. A

    transformer is chosen which

    can accommodate asomewhat higher current, a

    150:5 current transformer is

    therefore selected. The

    ammeter is a 5-A meter with

    its scale calibrated from 0 to150 A. Single-phase

    power line

    NL

    AC ammeter

    Current

    transformer

    Step 4: Draw the connection diagram.

    The ammeter is connected to the line, through the current

    transformer, as in the figure.

    Figure 20.

  • 7/26/2019 High Current Measurements

    30/39

    30

    3. Window-type Current Transformer

    A window-type current transformer is one that has a secondary winding

    insulated from- and permanently assembled on the core, but has no primary

    winding as an integral part of the structure. Primary insulation is provided in

    the window, through which one turn of the line conductor can be passed to

    provide the primary winding.

    4. Wound-type Current Transformer

    A wound-type current transformer is one that has a primary winding consisting

    of one or more turns mechanically encircling the core or cores. The primary

    winding(s) and secondary winding(s) are insulated from each other and from

    the core(s) and are assembled as an integral structure.

    Bar Type CT Bushing Type CT

    http://1.bp.blogspot.com/-KDqgan_Tqx4/Tb_Orvezo0I/AAAAAAAAAQE/5USXfVeN0qk/s1600/Bushing+Type+CT+%28BCT%29.JPGhttp://2.bp.blogspot.com/-SffsYcQlgUg/Tb_Om4HbV5I/AAAAAAAAAQA/pa2DEciE-gI/s1600/Bar+Type+CT.jpg
  • 7/26/2019 High Current Measurements

    31/39

    31

    Window Type CT Wound Type CT

    Figure 21: Type of current transformers

    Outdoor CTs

    Current Transformer could either be:

    1. Indoor current transformer: One that, because of its construction, must be

    protected from the weather.

    2. Outdoor current transformer: One of weather-resistant construction, suitable

    for service without additional protection from the weather.

    In a typical arrangement in outdoor HV CTs, the secondary is wound on bushing type

    insulated core. The prinary is mounted in insulator bushing insulation around the

    primary (see Figure 22)

    Figure 22

    http://4.bp.blogspot.com/-Ep63lXsmEK8/Tb_O3YxM3RI/AAAAAAAAAQM/-MU74OzeyK8/s1600/wound+type+CT.gif
  • 7/26/2019 High Current Measurements

    32/39

    32

    A CT for operation on a 110 kV grid

    Outdoor CTs

    Figure 23.Pictures of different outdoor current transformers of various constructions.

  • 7/26/2019 High Current Measurements

    33/39

    33

    CLAMP METER

    A clamp meter is an electrical tester that combines a basic digital multimeter with a

    current sensor. A common form of current sensor comprises a split ring made of

    ferrite or soft iron and hinged at one one to form a pair of jaws that can be opened to

    clamp around the conductor whose current is to be measured. A wire coil is wound

    round one or both halves, forming one winding of a current transformer. The

    conductor around which it is clamped forms the other winding. This allows properties

    of the electric current in the conductor to be measured, without having to make

    physical contact with it, or to disconnect it for insertion through the probe.

    Types Of Current ClampsThe output of the current clamp can be read by any AC ammeter whose input

    impedance is compatible with the specifications of the current clamp. Current clamps

    are also available that convert the current input signals into a voltage signal for

    measurement by a voltmeter.

    Some current clamps incorporate a rectifier circuit whose output is a DC voltage that

    is proportional to the average current being measured. Such clamps facilitate the use

    of strip chart recorders for obtaining real time trends of current loads. To obtain a

    TRUE RMS output, a DC-to-RMS converter is attached to output of the dc current

    clamp.

    1. Current Clamp with Current Output

    (a)

    http://en.wikipedia.org/wiki/Current_transformerhttp://en.wikipedia.org/wiki/Current_transformer
  • 7/26/2019 High Current Measurements

    34/39

    34

    (b)

    Figure 24. Schematic of an analogue AC current clamp meter.

    2. Current Clamp with Voltage Output

    (a)

  • 7/26/2019 High Current Measurements

    35/39

    35

    (b)

    Figure 25. Schematic of an analogue AC current clamp meter.

    The Output Voltage and Burden Resistor

    The output voltage (Vo) should be set as low as practically possible to minimize the

    insertion loss. Assuming 0.5 V is the optimum secondary output voltage in a circuit

    and the output current is 20 A, a 1:100 ratio transformer will yield a secondary current

    of 200 mA. Per Figure 26, the burden resistor should be:

    5.2200.0

    5.0

    s

    o

    o

    I

    V

    R

    Figure 26

    VResistiveshunt

  • 7/26/2019 High Current Measurements

    36/39

    36

    Current Clamp incorporating a rectifier and filter circuit

    Figure 27.Current clamp incorporating a rectifier and filter circuit to convert the ac

    current signal into a voltage signal.

    Figure 28. Picture of an analogue current clamp.

    Digital AC Current Clamp MeterThe most common application nowadays is the use of a current probe with a digital

    multimeter. The probe output is connected to a DMM set on the AC current range to

    handle the probe output.

  • 7/26/2019 High Current Measurements

    37/39

    37

    Figure 29. Block diagram of a digital AC current clamp meter.

  • 7/26/2019 High Current Measurements

    38/39

    38

  • 7/26/2019 High Current Measurements

    39/39