HI_800_357_E_Device_H7201 (1)

Embed Size (px)

Citation preview

  • 8/17/2019 HI_800_357_E_Device_H7201 (1)

    1/3

    H 7201 (1035)

     All rights and technical modifications reserved: 1/3 HIMA Paul Hildebrandt GmbH, P.O. Box 1261, D-68777 Brühl 

    H 7201

    H 7201: Feed Line and Distribution Fuse Board•  for SELV and PELV (24 V or 48 V power supply systems)

    •  L1/L2 rail current rating max. 92 A

    •  max. 63 A current rating for each individual feed terminal

    •  for safeguarding up to 6 individual circuits with circuit breakers

    •  the circuit breakers are not included within the scope of delivery.

    Loop for Circuit breakermonitoring

    Diagnostic Signalsfrom Circuit breakersSuitable for digital Inputs*) Contact 2 not used

    H 7201

    L1+L-

    L-

    L1+   L1+

    L2+

    L2+

    XG1

    1   2 3

    (1)   (2)

    L2+

    XG4

    F6F2 F4 F5F1SF6SF4SF2SF1 SF5

    3   4 65

    XG2

    F3SF3

    1   32132 1   3   1   3232

    XG7

    1 2

    XG12XG14

    1

    L-F6

    XG3

    1   2 3

    (3)

    1   2

    L-

    L- L-

    1   32

    L-

    1   32

    L-

    1   32

    L-

    1   32

    L-

    XG6 XG8   XG10   XG13 XG5XG9XG11

    42

    L-

    76543 82

    F1 F3 F5F4F2*)

    Figure 1: Circuit Diagram

    Explanations (1) Circuit breaker with monitoring contact.(2) Circuit breaker monitoring is operational (XG12) if the sliding switches

    (SF1 to SF6) are set to the used position on the circuit breaker slots in use:

    used position equipped with circuit breakerunused position not equipped with circuit breaker(3) By inserting the provided jumper into the XG2 terminal, the two separated power rails are con-

    nected with one another.

    Design:  For mounting on an NS 35 mounting rail in accordance with EN 60715.Printed circuit board with sockets for 2 circuit breakers of up to 60A and4 circuit breakers of up to 16A

    Width 208 mm (total width)Height 108 mm (total height)Installation depth 132 mm (equipped with circuit breakers) Protection class IP 20 Weight 0.80 kg (without circuit breakers)Temperature range 0 to 60 °C

  • 8/17/2019 HI_800_357_E_Device_H7201 (1)

    2/3

    H 7201 (1035)

    HI 800 357 Rev. 0.08 2/3 

    Preferred Type of Circuit Breaker (not included within the scope of delivery of the H 7201):

    Fuse Nominalcurrent

    Make Type HIMA no.

    F1, F2, F5, F6 4 A E-T-A® 2210-S211-P1T2-H111 4 A 57 0350040

    F1, F2, F5, F6 16 A E-T-A® 2210-S211-P1T2-H111 16 A 57 0350160

    F3, F4 30 A E-T-A®  8345-C01A-R0T1-DB1B2B 30A 57 0304031

    F3, F4 60 A E-T-A®  8345-C01A-R0T1-DB1B2B 60A 57 0304061

    Table 1: Preferred Type of Circuit Breakers

    Terminals and Wiring:

    Terminal Min./max. wire cross section (mm2)

    XG2: L+ feed line 0.2 / 16 flexible, 10 with wire end ferrule

    XG1:, XG3: L- feed line 0.2 / 16 flexible, 10 with wire end ferrule

    XG13: L+/L- outgoing line 0.5 / 25 flexible

    XG4 to XG7: L- outgoing line 0.2 / 2.5 flexible

    XG8 to XG11: L+ outgoing line 0.2 / 2.5 flexible

    XG12: circuit breaker monitoring 0.2 / 2.5 flexible

    Table 2: Terminals and Wiring

    Diagnostic Signal Connector XG14:The diagnostic signals can be used to detect the status of the outgoing lines XG8 throughXG11 and XG13.

    •  HIGH signal -> voltage present

    •  LOW signal -> voltage not present

    The diagnostic signals are suitable for digital inputs of type 3 (in accordance with IEC 61131-2) and can be evaluated by e.g. a PES.

    Front View:

    Figure 2: Front View w ith Circuit Breakers "F1...F6"

    MountingWe recommend mounting the H 7201 horizontally or vertically (with respect to the label lo-cated on the front) to ensure sufficient ventilation.

  • 8/17/2019 HI_800_357_E_Device_H7201 (1)

    3/3

    H 7201 (1035)

    HI 800 357 Rev. 0.08 3/3 

    Warning! Unnecessary shut down!

     At an ambient temperature ≥ 60°C and a nominal current rating of all circuit break-

    ers of the H 7201, the current rating must be reduced to ≤ 80 % of the nominal cur-rent rating.