A cross-coils ohmmeter is used to show the insulation resistance readings directly in Megohms. The meter's deflecting circuit is assisted by a CURRENT AMPLIFIER on its upper range, so that a high reading on a wide scale can be achieved.
Citation preview
HGTINSULATION TESTERHand Operated Generator
Highly stable test voltage combinedwith high sensitivity
High Charging Current
Type Tested as per BIS2992 : 87
CE
5000
4000
3000
2000
1000
2 510 20 50 100 200 500 1000 2000 50000 100000
v
(MW)
Terminal outputs plottedon log scale
Free Accessories
Main lead 2m long.
One 3m Earth test lead with shrouded clips.
Operating manual.
One Screened 3m Line test lead with shrouded clips.
GENERALThe HGT series Insulation Testers are suitable for high voltage, heavy duty
work. The A.C. generator supplying the test voltage may be turned by a hand
crank. The output from the multi-pole generator is fed to a voltage multiplier
and stabilizing circuit and becomes the insulation test voltage. Stability of this
voltage is better than 0.1% under hand-cranking voltage stability is assisted
by a mechanical clutch.
A cross-coils ohmmeter is used to show the insulation resistance readings
directly in Megohms. The meter's deflecting circuit is assisted by a CURRENT
AMPLIFIER on its upper range, so that a high reading on a wide scale can be
achieved.
The three terminals marked 'L', 'GUARD' and 'E' are mounted on a small
panel recessed in to the side of the case, if required the 'GUARD' terminal
may be connected to divert any leakage currents to the voltage source rather
than allowing them to pass through the ohmmeter, thus eliminating their effects.
Each instrument is assembled in a Teak-wood case with a laminated
top panel.
*Specifications are subject to change without prior notice
APPLICATIONSThe instrument covers a wide variety of insulation testing requirements and
is especially suited to work on energy network systems. The insulation
tester is ideal for high voltage, heavy duty work, for example, such
applications as are found in the maintenance or servicing of large industrial
electrical installations, generators, distribution networks, switchgear etc.
The instrument can also be employed to make measurements designed to
show the gradual decline that takes place in insulation when this is attacked
by corrosion, dirt, grease, moisture etc. during the operational life of a
particular installation. Such monitoring enables the Maintenance Engineer to
anticipate future performance and to plan ahead.
The instrument can be used to show the improvement in insulation within
motor, generator and transformer windings etc. that results from drying out
procedures, where these have become necessary because of excessive
humidity or because of operation in a moisture laden atmosphere. The high
sensitivity of the instrument enables sensible reading to be obtained.
The terminal voltage characteristics show how this instrument produce
about 90% of its rated maximum voltage at loads as heavy as 50 megohms.
Maintaining near rated test voltage at heavy load is essential in true insulation
testing and is a characteristic of this instrument.
RIL/MK/C-08
SPECIFICATION
RANGES
2500 V 0-10,000 SR 2500
5000 V 0-10,000SR 5000
Voltage Outputd.c.
Insulation Range(Megohms)
OrderingCode
9kg (approx.)Weight
Short CircuitTerminal Current (max.)
2 mA d.c.SR50002.5 mA d.c. SR2500
_+3% of rated voltageTerminal Voltage (Setting at infinity)
+_0.76 mm (0.03 in) oras per BIS2992 : 87
Accuracy
160rpm (approx.)of generator
Clutch Slipping
320x230x170mm (approx.)Dimensions
Handle speedSpeed