Honeywell Process Solutions
ControlEdge HC900 Controller
Communications User Guide
51-52-25-111
Revision: 14
April 2018
ii ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Copyright, Notices, and Trademarks
Printed in U.S.A. – © Copyright 2018 by Honeywell
Revision 14 – April 2018
Warranty/Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without
charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all
other warranties, expressed or implied, including those of merchantability and fitness for a
particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.
While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.
Honeywell Process Solutions
1250 W Sam Houston Pkwy S
Houston, TX 77042
Modbus is a registered trademark of MODICON, Inc.
Windows is an addressed trademark of Microsoft Inc.
The omission of a name from this list is not to be interpreted that the name is not a trademark.
Reference: Modicon Modbus Protocol Reference Guide - PI-MBUS-300 Rev. G
Revision 14 ControlEdge HC900 Controller Communications User Guide iii April 2018
About This Document
Abstract
This document provides information specific to the communications interface for Honeywell’s ControlEdge HC900
Controller. The protocol supported for connection to the controller’s Ethernet network port is Modbus/TCP
(Modbus RTU protocol in a TCP/IP wrapper). The document includes a summary of all ControlEdge HC900 data
available (primarily floating point) for Modbus RTU access read and write including methods for access.
Support & Contact Information
For Europe, Asia Pacific, North and South America contact details, refer to the back page of this manual or the appropriate Honeywell Solution Support web site:
Honeywell Organization WWW Address (URL)
Corporate http://www.honeywell.com
Honeywell Process Solutions http://www.hpsweb.honewell.com/ps
HPS Technical tips http://hpsweb.honeywell.com/Cultures/en-
US/Products/Instrumentation/hybrid/hc900/TechnicalTips
/documents.htm
Telephone and Email Contacts
Area Organization Phone Number
United States and Canada Honeywell Inc.
1-800-343-0228 Customer Service
1-800-423-9883 Global Technical Support
Global Email Support Honeywell Process Solutions
Email: (Sales)
or (TAC)
iv ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Contents
1. INTRODUCTION ................................................................................................... 1
1.1 Overview ........................................................................................................................................ 1
1.2 Modbus/TCP Interface ................................................................................................................... 2
1.3 Modbus RTU RS232/RS485 Communication Ports ...................................................................... 5
2. IEEE 32-BIT FLOATING POINT REGISTER INFORMATION .............................. 7
2.1 IEEE Floating Point Data Format .................................................................................................. 7
3. MODBUS DOUBLE REGISTER FORMAT ........................................................... 9
3.1 IEEE Floating Point Formats ....................................................................................................... 10
3.2 Unsigned/signed 32-bit Register Formats .................................................................................... 12
4. MODBUS/TCP & MODBUS RTU FUNCTION CODES ....................................... 15
4.1 Function code definitions ............................................................................................................. 15
4.2 Fixed Modbus Map ...................................................................................................................... 16
4.3 Function Code 01 – Read Digital Output Status .......................................................................... 18
4.4 Function Code 02 - Read Digital Input Status ............................................................................. 27
4.5 Function Code 03- Read Holding (Data) Registers...................................................................... 28
4.6 Function Code 04 - Read Input Registers .................................................................................... 30
4.7 Function Code 05 - Force Single Digital Output ......................................................................... 32
4.8 Function Code 06 - Preset Single Register ................................................................................... 33
4.9 Function Code 08 - Loopback Message ....................................................................................... 34
4.10 Function Codes 16 (10h) - Preset Multiple Registers .............................................................. 35
4.11 Function Code 17 (11h) - Report ControlEdge HC900 ID ....................................................... 36
5. MODBUS RTU EXCEPTION CODES ................................................................. 38
5.1 Introduction .................................................................................................................................. 38
6. PARAMETERS ACCESSIBLE WITH FUNCTION CODE 03, 06,10H ................ 40
6.1 Overview ...................................................................................................................................... 40
6.2 Fixed Map .................................................................................................................................... 42
6.3 Miscellaneous Parameters ............................................................................................................ 46
6.4 Loop Values ................................................................................................................................. 47
6.5 Analog Input - Function Code 03 ................................................................................................. 52
6.6 Variables....................................................................................................................................... 53
6.7 Time.............................................................................................................................................. 54
Revision 14 ControlEdge HC900 Controller Communications User Guide v April 2018
6.8 Set Point Programmer .................................................................................................................. 55
6.9 Signal Tags ................................................................................................................................... 62
6.10 Scheduler .................................................................................................................................. 64
6.11 Sequencer .................................................................................................................................. 72
6.12 Stage ......................................................................................................................................... 76
6.13 Ramp ......................................................................................................................................... 79
6.14 Hand/OFF/Auto Control ........................................................................................................... 81
6.15 Alternator .................................................................................................................................. 82
6.16 Device Control .......................................................................................................................... 88
6.17 User Defined Signals and Variables ......................................................................................... 89
6.18 Custom map parameters............................................................................................................ 89
INDEX ........................................................................................................................... 99
vi ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Tables Table 1-1 Modbus RTU Message Formats ________________________________________________ 5 Table 3-1 Modbus Double Register Format Selections _______________________________________ 9 Table 3-2 IEEE Floating Point Number Examples in FP B Format ____________________________ 11 Table 4-1 Modbus/TCP and Modbus RTU Function Codes Definitions ________________________ 15 Table 4-2 Maximum Number of Objects (fixed map only) ___________________________________ 16 Table 4-3 Maximum Number of Registers Allowable per Request ____________________________ 17 Table 4-4 DI/DO Address Map (v2.4 and higher, up to 32-channel) ___________________________ 19 Table 4-5 Rack #1 DI/DO Address map (version 2.4 and higher, up to 32-channel) ____________________ 20 Table 4-6 DI/DO Address Map (Firmware version 2.3 and earlier, 16 channels max) ______________ 24 Table 4-7 Rack #1 DI/DO address map (v2.3 and earlier, up to 16-channel) _____________________ 24 Table 4-8 ControlEdge HC900 AI Address Mapping supported by Function Code 03 ______________ 28 Table 4-9 ControlEdge HC900 AI Address Mapping supported by Function Code 04 (v2.3) ________ 30 Table 4-10 ControlEdge HC900 AI Address Mapping supported by Function Code 04 (v2.4 and higher)30 Table 5-1 Modbus RTU Data Layer Status Exception Codes _________________________________ 39 Table 6-1 Fixed Map (listed by increasing address) ________________________________________ 42 Table 6-2 Miscellaneous Parameters ____________________________________________________ 46 Table 6-3 Loop Values ______________________________________________________________ 47 Table 6-4 Analog Input Value Addresses - Function Code 03 ________________________________ 52 Table 6-5 Variables _________________________________________________________________ 53 Table 6-6 Time parameters ___________________________________________________________ 54 Table 6-7 Steps to Download a Setpoint Program using Modbus Function Codes 3, 6, 16 __________ 56 Table 6-8 Steps to Upload a Setpoint Program using Modbus Function Codes 3, 6, 16 ____________ 56 Table 6-9 Set Point Programmer parameters ______________________________________________ 57 Table 6-10 SP Programmer Segments ___________________________________________________ 60 Table 6-11 Signal Tags ______________________________________________________________ 62 Table 6-12 SP Scheduler Addresses _____________________________________________________ 65 Table 6-13 Steps to Download a Setpoint Schedule using Modbus Function Codes 3, 6, 16 _________ 65 Table 6-14 Steps to Upload a Setpoint Schedule using Modbus Function Codes 3, 6, 16 ___________ 66 Table 6-15 Scheduler Parameters ______________________________________________________ 66 Table 6-16 Scheduler #1 Segment Fixed Addresses ________________________________________ 68 Table 6-17 Schedule Segments 1-50 ____________________________________________________ 69 Table 6-18 Sequencers 1-4 Parameters Fixed Addresses _____________________________________ 72 Table 6-19 Sequencer 1-4 Step 1 Fixed Addresses _________________________________________ 72 Table 6-20 Sequencer 1-4 State Fixed Addresses __________________________________________ 73 Table 6-21 Sequencer Parameters ______________________________________________________ 73 Table 6-22 Stage Parameters __________________________________________________________ 76 Table 6-23 Ramp Parameters __________________________________________________________ 79 Table 6-24 HOA Control Parameters ___________________________________________________ 81 Table 6-25 Alternator Parameters ______________________________________________________ 82 Table 6-26 Device Control parameters __________________________________________________ 88 Table 6-27 User Defined Registers _____________________________________________________ 89 Table 6-28 Custom map Loop parameters ________________________________________________ 90 Table 6-29 Custom map Push Button and Four Selector Switch parameters ______________________ 90 Table 6-30 Custom map AGA Gross parameters ___________________________________________ 91 Table 6-31 Custom map AGA Detail parameters ___________________________________________ 91 Table 6-32 Custom map Calendar Event parameters ________________________________________ 92 Table 6-33 Custom map XYR5000 Base Station block parameters _____________________________ 96 Table 6-34 Custom map XYR5000 Transmitter block parameters _____________________________ 96
Revision 14 ControlEdge HC900 Controller Communications User Guide vii April 2018
Table 6-35 Custom map XYR6000 Transmitter block parameters _____________________________ 97 Table 6-36 Custom map UDC Loop block parameters_______________________________________ 97 Table 6-37 Custom map UDC Loop 2 block parameters _____________________________________ 98
viii ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Figures
Figure 1-1 Modbus RTU Protocol within a TCP/IP Frame ____________________________________ 2 Figure 1-2 Ethernet 10/100Base-T Network Connections ____________________________________ 4 Figure 2-1 IEEE Floating Point Data format _______________________________________________ 7 Figure 3-1 IEEE Floating Point Formats _________________________________________________ 11
Introduction
Overview
Revision 14 ControlEdge HC900 Controller Communications User Guide 1 April 2018
1. Introduction
1.1 Overview
Communication interfaces
The ControlEdge HC900 controller provides Modbus communication support on three communication
interfaces.
Network port: Modbus TCP on an Ethernet connection
Serial Port S1 RS232/RS485 selectable port. (Default RS232.): Modbus RTU
Serial Port S2 RS232/RS485 selectable port. (Default RS485.): Modbus RTU
View or print addresses
You can print out the Modbus addresses of various parameters of the configuration (signal tags, PID loops,
SP programmer, etc.) using the HC Designer report functions. With HC Designer Ver. 2.1 and later, these
reports may also be exported to .csv files for view/manipulation in a spreadsheet and possible import to
other HMI applications.
Fixed map or custom map
The type of addressing available: fixed or custom.
Fixed map Custom map
Contains limited types of parameters in limited quantities (e.g., 32 loops max)
More parameters to choose from. Quantities are limited only by available addresses. (e.g.,can have >32 loops.) Certain blocks can be assigned to the custom map that are not available in the fixed map. (See section 6.18.)
Objects of each type (e.g. loops 1-24, SP Programmers 1-4, etc.) are grouped and limited to certain address ranges.
Objects (e.g. loop) can be assigned any address or to multiple addresses and are not limited to certain ranges.
All parameters of a single object are addressed. For example, a PID loop has over 40 parameters and they all are mapped.
You can select which parameters of an object are mapped. For example, you can assign only 3 of a loop’s 40+ parameters to the map (such as PV, SP, output), thereby increasing efficiency.
Editing is limited to
-moving an object to another address within its allowed range.
-assigning up to 1000 signals and variables to addresses reserved for that purpose.
Edits are virtually unlimited. Uses fixed map settings but can be edited or rebuilt as needed without the fixed map’s limitations. Custom partitions can be created for organizing data however you prefer.
Available in all ControlEdge HC900 configuration versions
Available in ControlEdge HC900 configuration version 4.0 and higher
Introduction
Modbus/TCP Interface
2 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
1.2 Modbus/TCP Interface
Introduction
ControlEdge HC900 controllers support the Modbus/TCP (also called Modbus TCP/IP or Modbus
Ethernet) protocol for communications with third party HMI and SCADA software via a direct Ethernet
TCP/IP connection.
The controller’s Ethernet 10/100Base-T Host port is used for the Modbus/TCP connection. Ethernet TCP
allows multiple concurrent connections to hosts for data interchange. The ControlEdge HC900 (C30/C50)
supports 5 concurrent host connections using Modbus/TCP protocol messaging via this port; ControlEdge
HC900 (C70/C70R) supports 10.
Interface Preparation
ATTENTION
To access the controller you must have a current Process Control Designer configuration file available. Some data is referenced relative to number, such as Signal Tags and Variables.
Other principal blocks, such as PID blocks, have offsets for parameter access dependent on the order in which the blocks were placed on the Function Block Diagram.
It is strongly recommended that you upload the controller configuration using the Process Control
Designer configuration tool to assure that you have a current configuration.
The Process Control Designer tool provides a series of reports for use in Modbus Address identification.
The "Tag Information" report lists the variables and Signal Tags in numeric order along with their Modbus Addresses.
A "Block Modbus Address" report lists the starting addresses for all principal blocks configured, identifying the offset.
Modbus/TCP Protocol
Modbus/TCP protocol, developed by Groupe Schneider’s Modicon Division, is a popular, open standard for data
interchange over Ethernet TCP/IP networks using a Modbus RTU command structure.
It is simply an encapsulation of Modicon’s Modbus RTU protocol within a TCP/IP frame as shown below, which
includes header information and the Modbus frame.
Figure 1-1 Modbus RTU Protocol within a TCP/IP Frame
The Open Modbus/TCP Specification is followed with respect to the physical, data link, and network layers. The
message structure within the Modbus frame uses standard Modbus RTU function codes.
The Address part of the Modbus frame is not used (set to 00) since there is no sub-addressing intended or required.
The controller IP address is the identifying address, set independently at the controller.
Introduction
Modbus/TCP Interface
Revision 14 ControlEdge HC900 Controller Communications User Guide 3 April 2018
The error checking is supported by TCP/IP network protocols and not part of the Modbus frame.
The Transaction Identifiers and Protocol Identifiers in the header are normally all 0’s (4 bytes total) while the Length
field identifies the number of bytes in the Modbus frame. The controller will transmit the correct number of bytes for
the remainder of the frame. However, the controller does not check this field for messages received.
The standard IEEE 32-bit floating point and 16-bit integer formats are used.
Parameter Addressing
The definition in Table 6-1 is the fixed map overview listing starting and ending addresses.
Greater detail for parameter addressing relating to a particular function class (e.g, loops, setpoint programmer, signal
tags) is in referenced sub-sections. Function Codes 1, 2, 3, 4, 5, 6, 8, 16 (10h), and 17 (11h) are supported (see
Table 4-1 Modbus/TCP and Modbus RTU Function Codes Definitions).
Examples for read or write access to parameters supported by the various function codes are provided in Sections 4.3
through 4.11.
Reference
The Open Modbus/TCP Specification can be obtained at the Modicon website:
http://www.modicon.com/openmbus/standards/openmbus.htm
ControlEdge HC900 Ethernet Communications Setup
See the ControlEdge HC900 Control (HC) Designer Users Guide, Doc. # 51-52-25-110 or respective HC Designer
Help Files for setting up the following network parameters:
IP Address, Subnet Mask (optional), Default Gateway IP Address (optional)
1. Be sure the PC, HMI panel, or other Host device has a Network Interface Card (NIC) with an IP
address (fixed or DHCP served) that allows access to controllers on the same or other subnet. Consult
your IT department or network administrator for allocating IP addresses to the controllers as required.
2. You will need to set each controller’s IP address prior to network connection since every ControlEdge
HC900 controller is shipped with the default IP address of 192.168.1.254. Placing multiple controllers
on the same network before they have been given unique IP addresses will cause problems.
3. On the PC, use the Utilities Worksheet in the HC Designer software to set up the serial RS-232
connection to the controller at the desired baud rate. This will require a null modem cable.
4. Select the Set Controller’s Network Parameters button. Using the wizard (bottom radio button), select
the PC COM port to be used, then set the controller’s new network parameters including IP address,
Subnet Mask (if other than default, 255.255.255.0), and Default Gateway IP address (if required,
otherwise leave at default 0.0.0.0). See your IT network administrator for proper entries. (Refer to the
on-line help provided with the HC Designer software, Utilities Worksheet, Set Controller’s Network
Parameters, for further details on this step).
Note: This setup will require the controller to be placed temporarily in the Program mode. After the new
network parameters have been downloaded, the controller will conduct a Cold Start in its transition to RUN.
This will cause an initialization if there is a current configuration in the controller.
The fixed IP address of each controller shall be set independently prior to placing on the network. See your IT
systems administrator for allocating IP addresses, subnet masks, or default gateway IP address as necessary (network
address filtering and routing may be necessary if the controller network access will not to be confined locally within
the plant environment).
Introduction
Modbus/TCP Interface
4 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Ethernet 10/100Base-T Network Connections
Ethernet 10/100Base-T networks operating at 10/100MB/sec. are supported. A typical network arrangement is as
shown below.
PC HMI
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
Run/Pgm
Run/Pgm
RunPgm
RS232/RS485
Serial Ports S1 & S2
Ethernet Host Port E1
Ethernet Host Port E2
I/O Port
SwitchTo other subnets
IP Address
193.142.165.46
IP Address
193.142.165.45
10/100Base-T
10/100Base-T
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
C70
E1
E2
I/O
S2
S1
Run/Pgm
Run/Pgm
RunPgm
Run/Pgm
Run/Pgm
RunPgm
Figure 1-2 Ethernet 10/100Base-T Network Connections
Setting Up the Modbus/TCP Double Register Format
The ControlEdge HC900 predominantly uses an IEEE floating point format for communicating data to software
applications providing Modbus/TCP protocol communications drivers. A floating point value is sent as (2)
consecutive 16-bit registers, each register of which consists of two 8-bit bytes. Some software packages require the
registers and bytes to be sent in a certain order. The controller can be configured to deliver the data in four different
byte orders.
The Process Control Designer software tool allows this order to be selected as follows:
1. Using the Utilities Worksheet in the HC Designer software, access the Set Controller Network
Parameters button and make the selection to change the Modbus TCP Double Register Format (middle
radio button).
2. With the Port selected for downloading this order (using a COM port or Network port), select the
appropriate byte order format if the default (FP B) is not appropriate for the application. See Table
3-1, page 9.
3. Select Next and verify (by the response in the dialog box) that the change has been made in the
controller. This order can be changed in the RUN mode.
The Modbus TCP double register transmission format selection, FP LB “Little Endian Byte-Swapped”, would be
selected for interface to most third party software packages which use this format as standard. The default, FP B
“Big Endian” is used with SpecView32 or Honeywell’s PlantScape/Experion/EBI software and follows the
“Honeywell” default format of other control and recording products. It should be noted that most PC software
packages offer a register (word) swap selection in their driver package anyway, so there should never be an
incompatibility.
Introduction
Modbus RTU RS232/RS485 Communication Ports
Revision 14 ControlEdge HC900 Controller Communications User Guide 5 April 2018
1.3 Modbus RTU RS232/RS485 Communication Ports
This implementation is designed to provide a popular data exchange format connecting the ControlEdge HC900 to
both Honeywell and foreign master devices via the RS232 and RS485 communication ports. The Modbus RTU
allows the instrument to be a citizen on a data link shared with other devices, which subscribe to the Modicon
Modbus Protocol Reference Guide PI-MBUS-300 Rev. G specification.
These instruments DO NOT emulate any MODICON type device. The Modbus RTU specification is respected in the
physical and data link layers. The message structure of the Modbus RTU function codes is employed and standard
IEEE 32-bit floating point and integer formats are used. Data register mapping is unique to the ControlEdge HC900
and other Honeywell instruments. Section 6 describes the parameter mapping for the ControlEdge HC900.
Modbus RTU Message Format
Table 1-1 Modbus RTU Message Formats
Coding system 8 bit binary
Number of data bits per character
10, 11, or 12 Bits
start bits - 1
data bits - 8
parity bits – 0 or 1 selectable
stop bits – 1 or 2 selectable
Parity None, odd, even selectable
Bit transfer rate 1200, 2400, 4800, 9600, 19200, 38400, 57600 Selectable
Duplex Half duplex Transceiver or TX/RX
Error checking CRC (cyclic redundancy check)
Polynomial (CRC-16 10100000000001)
Bit transfer order LSB first
End of message Idle line for 3.5 or more characters (>1.82 msec for 19200).
Modbus RTU Link Layer
The link layer includes the following properties/behaviors:
Slave address recognition,
Start / End of Frame detection,
CRC-16 generation / checking,
Transmit / receive message time-out,
Buffer overflow detection,
Framing error detection,
Idle line detection.
Errors detected by the physical layer in messages received by the slave are ignored and the physical layer
automatically restarts by initiating a new receive on the next idle line detection.
Introduction
Modbus RTU RS232/RS485 Communication Ports
6 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
General Modbus RTU message format
Query message format
[Slave Address, Function Code, Function code dependent data, CRC 16]
Response message format
[Slave Address, Function Code*, Function code dependent data, CRC 16]
* If an error is detected in a valid message the response function code is modified by adding 80 (hex) and the
function code dependent data is replaced by an exception response code as described in 5. Modbus RTU
Exception Codes .
Between messages, the RS-485 link is in a high impedance state. During this time receiving devices are
more susceptible to noise generated false start of messages. Although noise-generated messages are rejected
due to address, framing, and CRC checking, they can cause the loss of a good message when they are
included in the message stream. In the slave the transmitting device enables its transmitter line diver and
forces an idle line state onto the link for three character time slots prior to transmitting. This forces
termination of any noise generated messages and improves message frame synchronization.
Modbus RTU Data Layer
The data layer includes:
Diagnostic loopback,
Function code recognition / rejection,
Busy / repoll,
Data error code generation
Errors detected by the data layer are rejected and the slave responds to the polling device with a Modbus-
type status exception error. A summary of the Modbus status exception codes is listed in Section 5. Modbus
RTU Exception Codes.
IEEE 32-bit Floating Point Register Information
IEEE Floating Point Data Format
Revision 14 ControlEdge HC900 Controller Communications User Guide 7 April 2018
2. IEEE 32-bit Floating Point Register Information
The Modbus interface supports IEEE 32-bit floating point information for several of the function codes.
2.1 IEEE Floating Point Data Format
The formula for calculating the floating point number is:
mantissa x 2
(exponent -127)
byte 4 byte 3 byte 2 byte 1
3 2 2 1 1
1 4 3 6 5 8 7 0
xxxxxxxx x.xxxxxxx xxxxxxxx xxxxxxx
mantissa (23 bits)
implied binary point for mantissa
exponent (8 bit unsigned value)
sign of the mantissa 0 = positive, 1 = negative
(23 bit signed binary with 8 bit biased binary exponent)
Figure 2-1 IEEE Floating Point Data format
Mantissa and Sign
The mantissa is defined by a sign bit (31) and a 23-bit binary fraction. This binary fraction is combined with
an “implied” value of 1 to create a mantissa value, which is greater than or equal to 1.0 and less than 2.0.
The mantissa is positive if the sign bit is zero (reset), and negative if the sign bit is one (set). For example:
DECIMAL HEXADECIMAL BINARY
100 42C80000 01000010 11001000 00000000 00000000
The sign bit (31) is zero, indicating a positive mantissa. Removing the sign bits and exponent bits, the
mantissa becomes:
HEXADECIMAL BINARY
480000 xxxxxxxx x1001000 00000000 00000000
Add an “implied” value of one to the left of the binary point:
BINARY
1.1001000 00000000 00000000
Using positioned notation, this binary number is equal to:
10 1 0 0 1 10 05 0 0 0 0 0 0625 15625. ( ) ( ) ( ) ( ) . . . . . . x2 x2 x2 x2-1 -2 -3 -4
IEEE 32-bit Floating Point Register Information
IEEE Floating Point Data Format
8 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Exponent
The exponent is defined by an unsigned 8-bit binary value (bits 23 through 30). The value of the exponent
is derived by performing a signed subtraction of 127 (decimal) from the 8-bit exponent value.
DECIMAL HEXADECIMAL BINARY
100 42C80000 01000010 11001000 00000000 00000000
Removing the sign and mantissa bits, the exponent becomes:
DECIMAL HEXADECIMAL BINARY
133 85 x1000010 1xxxxxxx xxxxxxxx xxxxxxxx
or:
1x2 x x2 x2 x2 x2 x2 x27 5 4 3 2 1 0 0 2 0 0 0 1 0 16
Subtract a bias of 127 (decimal) from the exponent to determine its value: 133 – 127 = 6.
Mantissa and Exponent Combination
Combining the mantissa and exponent from the two previous examples:
float number = mantissa x 2
float number = 1.5625 x 2 x 64 = 100.0
exponent
6 15625.
Below is a list of sample float values in IEEE format:
DECIMAL HEXADECIMAL
100.0 42C80000
-100.0 C2C80000
0.5 3F000000
-1.75 BFE00000
0.0625 3D800000
1 3F800000
0 00000000
Reserved Operands
Per the Standard certain exceptional forms of floating point operands are excluded from the numbering
system. These are as follows:
EXCEPTION EXPONENT MANTISSA
+/- Infinity All 1’s All 0’s
Not-a-Number (NAN) All 1’s Other than 0’s
Denormalized Number All 0’s Other than 0’s
Zero All 0’s All 0’s
Modbus Double Register Format
IEEE Floating Point Data Format
Revision 14 ControlEdge HC900 Controller Communications User Guide 9 April 2018
3. Modbus Double Register Format
Data that is 32 bits requires 2 sequential registers (4 bytes) to transfer its data. Data of this type includes IEEE 32-bit
floating point, 32-bit signed integer and 32-bit unsigned integer. The stuffing order of the bytes into the two registers
differs among Modbus/TCP hosts. To provide compatibility, the double register format for the ControlEdge HC900
controller is configurable.
To set the controller’s double register byte order, go to the “Set Controller Network Parameters ” wizard in the
"Controller Utilities Function" section of the Utilities Tab on the Process Control Designer and configure “Modbus
Double Register Format”. This can be done in the RUN mode.
The selections are:
Table 3-1 Modbus Double Register Format Selections
Selection Description Byte order
(See Figure 2-1)
Notes
FP B Floating Point Big Endian Format 4, 3, 2, 1 ControlEdge HC900 default
FP BB Floating Point Big Endian with byte-swapped
3, 4, 1, 2
FP L Floating Point Little Endian Format 1, 2, 3, 4
FP LB Floating Point Little Endian with byte-swapped
2, 1, 4, 3 Modicon and Wonderware standard
See IEEE Formats on page IEEE Floating Point Formats on page 10 and 32-bit integer formats on page 12.
NOTE: Byte Swapping only applies to Function Codes 3, 4, and 16.
Modbus Double Register Format
IEEE Floating Point Formats
10 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
3.1 IEEE Floating Point Formats
S E7 E6 E5 E4 E3 E2 E1
E0 M22 M21M20 M19 M18 M17 M16
REGISTER N
(High)
REGISTER N+1
(Low)
M15 M14 M13 M12 M11 M10 M9 M8
M7 M6 M5 M4 M3 M2 M1 M0
High Low High Low
Bit 0Bit 31
FP B - Floating Point Big Endian Format:
S=Sign E=Exponent M=Mantissa
S E7 E6 E5 E4 E3 E2 E1
E0 M22 M21M20 M19 M18 M17 M16
REGISTER N
(High)
REGISTER N+1
(Low)
M15 M14 M13 M12 M11 M10 M9 M8
M7 M6 M5 M4 M3 M2 M1 M0
High Low High Low
Bit 8
FP BB - Floating Point Big Endian with Byte Swapped Format:
S=Sign E=Exponent M=Mantissa
Bit 31 Bit 24
Bit 23 Bit 16 Bit 7 Bit 0
Bit 15
continued next page
Modbus Double Register Format
IEEE Floating Point Formats
Revision 14 ControlEdge HC900 Controller Communications User Guide 11 April 2018
REGISTER N
(High)
REGISTER N+1
(Low)
High Low High Low
FP L - Floating Point Little Endian Format:
S=Sign E=Exponent M=Mantissa
E0 M22 M21M20 M19 M18 M17 M16
Bit 23 Bit 16
S E7 E6 E5 E4 E3 E2 E1
Bit 31 Bit 24
M7 M6 M5 M4 M3 M2 M1 M0
Bit 7 Bit 0
M15 M14 M13 M12 M11 M10 M9 M8
Bit 8Bit 15
REGISTER N
(High)
REGISTER N+1
(Low)
High Low High Low
FP LB - Floating Point Little Endian with Byte Swapped Format:
S=Sign E=Exponent M=Mantissa
E0 M22 M21M20 M19 M18 M17 M16
Bit 23 Bit 16
S E7 E6 E5 E4 E3 E2 E1
Bit 31 Bit 24
M7 M6 M5 M4 M3 M2 M1 M0
Bit 7 Bit 0
M15 M14 M13 M12 M11 M10 M9 M8
Bit 8Bit 15
Figure 3-1 IEEE Floating Point Formats
Table 3-2 IEEE Floating Point Number Examples in FP B Format
Value
(decimal)
IEEE FP B
MSB LSB
Register N Register N+1
high low high low
100.0 42C80000h 42h C8h 00h 00h
55.32 425D47AEh 42h 5Dh 47h AEh
2.0 40000000h 40h 00h 00h 00h
1.0 3F800000h 3Fh 80h 00h 00h
-1.0 BF800000h BFh 80h 00h 00h
Modbus Double Register Format
Unsigned/signed 32-bit Register Formats
12 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
3.2 Unsigned/signed 32-bit Register Formats
The formats descriptions below use the value 12345678 Hex as an example. Where the binary representation is:
Byte 4 = 12 Hex Byte 3 = 34 Hex Byte 2 = 56 Hex Byte 1 = 78 Hex
Bits 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 1 0 1 0 1 1 0 0 1 1 1 1 0 0 0
FP B – Big Endian Format
The value 12345678 Hex will be represented as follows:
Bit 31 Bit 0
High
Low
High
Low
REGISTER N
(High)
REGISTER N+1
(Low)
Byte 4 12 Hex
Byte 3 34 Hex
Byte 2 56 Hex
Byte 1 78 Hex
Modbus Double Register Format
Unsigned/signed 32-bit Register Formats
Revision 14 ControlEdge HC900 Controller Communications User Guide 13 April 2018
FP BB – Big Endian Byte Swapped Format
The value 12345678 Hex will be represented as follows:
Bit 23 Bit 0
High
Low
High
Low
REGISTER N
(High)
REGISTER N+1
(Low)
Byte 4 12 Hex
Byte 3 34 Hex
Byte 2 56 Hex
Byte 1 78 Hex
Bit 16 Bit 15 Bit 8 Bit 7 Bit 24 Bit 31
Modbus Double Register Format
Unsigned/signed 32-bit Register Formats
14 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
FP L – Little Endian Format
The value 12345678 Hex will be represented as follows:
Bit 7 Bit 16
High
Low
High
Low
REGISTER N
(High)
REGISTER N+1
(Low)
Byte 2 56 Hex
Byte 1 78 Hex
Byte 4 12 Hex
Byte 3 34 Hex
Bit 0 Bit 31 Bit 24 Bit 23 Bit 8 Bit 15
FP LB – Little Endian Byte Swap Format
The value 12345678 Hex will be represented as follows:
Bit 15 Bit 24
High
Low
High
Low
REGISTER N
(High)
REGISTER N+1
(Low)
Byte 2 56 Hex
Byte 1 78 Hex
Byte 4 12 Hex
Byte 3 34 Hex
Bit 8 Bit 23 Bit 16 Bit 31 Bit 0 Bit 7
Modbus/TCP & Modbus RTU Function Codes
Function code definitions
Revision 14 ControlEdge HC900 Controller Communications User Guide 15 April 2018
4. Modbus/TCP & Modbus RTU Function Codes
4.1 Function code definitions
The ControlEdge HC900 Modbus protocol uses a subset of the standard Modbus function codes to provide access to
process-related information. These standard function codes provide basic support for IEEE 32-bit floating point
numbers, 32-bit unsigned/signed integer and 16-bit integer register representation of instrument’s process data.
Repolling of data is not supported by this instrument.
Table 4-1 Modbus/TCP and Modbus RTU Function Codes Definitions
Function Code Name Usage
01 Read Coil Status Read the state of a digital output
02 Read Input Status Read the state of a digital input
03
Read Holding Registers
Read data in 16-bit Register Format (high/low). Used to read integer or floating point process data. Registers are consecutive and are imaged from the instrument to the host.
04 Read Input Registers Provides Read access to any Analog Input Channel positioned in any Rack or Slot.
05 Force Single Coil Write data to force a digital output ON/OFF Values of FF 00 forces digital output ON Values of 00 00 forces digital output OFF Values of FF FF releases the force of the digital output All other values are illegal and will not effect the digital output.
06 Preset Single Register Write Data in 16-bit Integer Format (high/low) ONLY.
08 Loopback Test Used for diagnostic testing of the communications port.
16 (10h) Preset Multiple Registers Write Data in 16-bit Format (high/low). Used to write integer and floating point override data. Registers are consecutive and are imaged from the host to the instrument.
17 (11h) Report Device ID Read instrument ID and connection information, ROM version, etc.
Modbus/TCP & Modbus RTU Function Codes
Fixed Modbus Map
16 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.2 Fixed Modbus Map
Table 4-2 and Table 4-3 list the the maximum number of Object Addresses and maximum number of registers
allowed per request. Also shown are differences between firmware versions 2.3 and 2.4.
Note 1: In versions 4.0 and higher these maximums apply to fixed map but not to the custom map.
Note 2: In versions 4.0 and higher function code 03 is not available for analog inputs.
Table 4-2 Maximum Number of Objects (fixed map only)
Note: objects marked with * have multiple parameters and therefore occupy multiple registers. For example, a PID loop has over 40 parameters that can be accessed.
Object Name Max. No. of Objects
Function Code C30 C50/C70/C70R
Analog Inputs 96/12 slots v2.3 192/12 slots v2.4
640 v2.3 1280 v2.4
3: can only access first 8 slots of rack 1. Not available in version 4.0 or higher.
4: can access all slots and racks
Discrete Input 192/12 slots v2.3 384/12 slots v2.4
1280 v2.3 2560 v2.4
2
Discrete Output/Coil 192/12 slots v2.3 384/12 slots v2.4
1280 v2.3 2560 v2.4
1: read 5: force
Loop* 8 32 3
Variable Value 600 600 3
Set Point Programmer Value* 8 8 3
Segments per Set Point Programmer*
50 50 3
Signal tags 2000 2000 (C50) 5000 (C70/C70R)
3
Scheduler Value* 2 2 3
Segments per Schedule* 50 50 3
Sequencer* 4 4 3
Stage* 8 8 3
Ramp* 8 8 3
Hand-Off-Auto* 16 16 3
Alternator* 6 6 3
Device Control* 16 16 3
User Defined Registers 1024 1024 3
Modbus/TCP & Modbus RTU Function Codes
Fixed Modbus Map
Revision 14 ControlEdge HC900 Controller Communications User Guide 17 April 2018
Table 4-3 Maximum Number of Registers Allowable per Request
Function
Code
Max. No. of
Registers
1, 2 2040 bits
3, 4 127 Registers 63 Floats
5 1 Coil
6 1 Register
10h 127 Registers 63 Floats
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
18 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.3 Function Code 01 – Read Digital Output Status
Description
Function code 01 (0X references) is used to read a digital output’s ON/OFF status of the ControlEdge
HC900 using 16 bit addressing for DO access and data is returned in a binary format mapped into bytes.
The Modbus Comm Digital I/O Channel-to-address mapping is shown starting on page 24.
Broadcast is not supported.
Query
The query message specifies the starting Digital Output (DO) and the quantity of DOs to read. The DO
address in the message is based on the rack slot and channel number of the digital output being read.
Example Query: Read DO channels 1 to 16, located in Rack #1, Slot #1; from the controller with slave
address 1.
Query message format for function code 01
Slave Address
(00 for TCP)
Function Code
Starting Address
High
Starting Address
Low
Number DO
High
Number DO Low
CRC (RTU)
CRC (RTU)
TCP Example 00 01 00 00 00 10
RTU Example 01 01 00 00 00 10 CRC CRC
Response
The DO status in the response message is packed as one DO per bit of the data field. Status is indicated as:
1 = ON; 0 = OFF. The LSB of the first data byte contains the DO addressed in the query. The other DOs
follow toward the high order end of this byte, and from low order to high order in subsequent bytes.
If the returned DO quantity is not a multiple of eight, the remaining bits in the final data byte will be padded
with zeros (toward the high order end of the byte). The byte count field specifies the quantity of data bytes
returned.
Example Response: DO channels 2 and 6 located in Rack #1, Slot #1 are on; all others are off.
Response message format for function code 01
Slave Address
(00 for TCP)
Function Code
Byte Count
Data Data CRC (RTU)
CRC (RTU)
TCP Example 00 01 02 22 00
RTU Example 01 01 02 22 00 CRC CRC
In the response the status of DOs 1 - 8 is shown as the byte value 22 hex, or 0010 0010 binary. DO 8 is the
MSB of this byte, and DO 1 is the LSB. Left to right, the status of DO 8 through 1 is: OFF-OFF-ON-OFF-
OFF-OFF-ON-OFF. The status of DOs 9 - 16 are shown a 00hex, or 0000 0000 with the same bit ordering.
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
Revision 14 ControlEdge HC900 Controller Communications User Guide 19 April 2018
Digital I/O Channel to Address Mapping
If you have any 32-channel DI/DO modules or if you have firmware version 2.4 or higher you must use the
newer maps in Table 4-4 and Table 4-5. However, use the older maps in Table 4-6 and Table 4-7 if:
Your controller is firmware version 2.3 or earlier or
You have already mapped out 16-channel DI/DO, have no 32-channel DI/DO modules, and don’t
want to change to the newer map.
Note: Up to 16 slots are accommodated in the protocol even though the largest rack available supports 12
slots.
Each DI/DO consumes 1 Modbus bit address.
Decimal addressing is typically non-zero based for DI/DO access (1-based), applicable to coil or register
address.
Table 4-4 DI/DO Address Map (v2.4 and higher, up to 32-channel)
Rack Channels Coil number/register number Modbus Hex
Address Range
1* 1 - 512 2001 – 2512 7D0 – 9CF
2 513 – 1024 2513 – 3024 9D0 – BCF
3 1025 – 1536 3025 – 3536 BD0 – DCF
4 1537 - 2048 3537 – 4048 DD0 – FCF
5 2049 - 2560 4049 - 4560 FD0 – 11CF
6 2561 – 3072 4561 - 5072 11D0 – 13CF
7 3073 - 3584 5073 - 5584 13D0 – 15CF
8 3583 - 4096 5585 - 6096 15D0 – 17CF
9 4097 - 4608 6097 – 6608 17D0 – 19CF
10 4609 - 5120 6609 – 7120 19D0 – 1BCF
11 5121 – 5632 7121 - 7632 1BD0 – 1DCF
12 5633 - 6144 7633 - 8144 1DD0 – 1FCF
*See Table 4-5 for detailed map of Rack #1
The coil (register) number for a DI/DO is based on the DI/DO’s position in the card cage. It is determined
from the formula:
Coil (register) Number = [(Rack-1)*512] + [(Slot-1)*32] + channel in module + 2000
Example: To monitor a coil (register) located in the 2nd channel of slot 10 of rack 3, the Modbus coil
(register) number is:
[(3-1)*512] + [(10-1)*32] + 2 + 2000 = 3314
Some third party software packages will require the 1-based coil/register number to be used for the address
while others will require the 0-based hex address.
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
20 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Table 4-5 Rack #1 DI/DO Address map (version 2.4 and higher, up to 32-channel)
Slot 1 Slot 2 Slot 3 Slot 4
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
32 2032 7EF 32 2064 80F 32 2096 82F 32 2128 84F
31 2031 7EE 31 2063 80E 31 2095 82E 31 2127 84E
30 2030 7ED 30 2062 80D 30 2094 82D 30 2126 84D
29 2029 7EC 29 2061 80C 29 2093 82C 29 2125 84C
28 2028 7EB 28 2060 80B 28 2092 82B 28 2124 84B
27 2027 7EA 27 2059 80A 27 2091 82A 27 2123 84A
26 2026 7E9 26 2058 809 26 2090 829 26 2122 849
25 2025 7E8 25 2057 808 25 2089 828 25 2121 848
24 2024 7E7 24 2056 807 24 2088 827 24 2120 847
23 2023 7E6 23 2055 806 23 2087 826 23 2119 846
22 2022 7E5 22 2054 805 22 2086 825 22 2118 845
21 2021 7E4 21 2053 804 21 2085 824 21 2117 844
20 2020 7E3 20 2052 803 20 2084 823 20 2116 843
19 2019 7E2 19 2051 802 19 2083 822 19 2115 842
18 2018 7E1 18 2050 801 18 2082 821 18 2114 841
17 2017 7E0 17 2049 800 17 2081 820 17 2113 840
16 2016 7DF 16 2048 7FF 16 2080 81F 16 2112 83F
15 2015 7DE 15 2047 7FE 15 2079 81E 15 2111 83E
14 2014 7DD 14 2046 7FD 14 2078 81D 14 2110 83D
13 2013 7DC 13 2045 7FC 13 2077 81C 13 2109 83C
12 2012 7DB 12 2044 7FB 12 2076 81B 12 2108 83B
11 2011 7DA 11 2043 7FA 11 2075 81A 11 2107 83A
10 2010 7D9 10 2042 7F9 10 2074 819 10 2106 839
9 2009 7D8 9 2041 7F8 9 2073 818 9 2105 838
8 2008 7D7 8 2040 7F7 8 2072 817 8 2104 837
7 2007 7D6 7 2039 7F6 7 2071 816 7 2103 836
6 2006 7D5 6 2038 7F5 6 2070 815 6 2102 835
5 2005 7D4 5 2037 7F4 5 2069 814 5 2101 834
4 2004 7D3 4 2036 7F3 4 2068 813 4 2100 833
3 2003 7D2 3 2035 7F2 3 2067 812 3 2099 832
2 2002 7D1 2 2034 7F1 2 2066 811 2 2098 831
1 2001 7D0 1 2033 7F0 1 2065 810 1 2097 830
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
Revision 14 ControlEdge HC900 Controller Communications User Guide 21 April 2018
Slot 5 Slot 6 Slot 7 Slot 8
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
32 2160 86F 32 2192 88F 32 2224 8AF 32 2256 8DF
31 2159 86E 31 2191 88E 31 2223 8AE 31 2255 8CE
30 2158 86D 30 2190 88D 30 2222 8AD 30 2254 8CD
29 2157 86C 29 2189 88C 29 2221 8AC 29 2253 8CC
28 2156 86B 28 2188 88B 28 2220 8AB 28 2252 8CB
27 2155 86A 27 2187 88A 27 2219 8AA 27 2251 8CA
26 2154 869 26 2186 889 26 2218 8A9 26 2250 8C9
25 2153 868 25 2185 888 25 2217 8A8 25 2249 8C8
24 2152 867 24 2184 887 24 2216 8A7 24 2248 8C7
23 2151 866 23 2183 886 23 2215 8A6 23 2247 8C6
22 2150 865 22 2182 885 22 2214 8A5 22 2246 8C5
21 2149 864 21 2181 884 21 2213 8A4 21 2245 8C4
20 2148 863 20 2180 883 20 2212 8A3 20 2244 8C3
19 2147 862 19 2179 882 19 2211 8A2 19 2243 8C2
18 2146 861 18 2178 881 18 2210 8A1 18 2242 8C1
17 2145 860 17 2177 880 17 2209 8A0 17 2241 8C0
16 2144 85F 16 2176 87F 16 2208 89F 16 2240 8BF
15 2143 85E 15 2175 87E 15 2207 89E 15 2239 8BE
14 2142 85D 14 2174 87D 14 2206 89D 14 2238 8BD
13 2141 85C 13 2173 87C 13 2205 89C 13 2237 8BC
12 2140 85B 12 2172 87B 12 2204 89B 12 2236 8BB
11 2139 85A 11 2171 87A 11 2203 89A 11 2235 8BA
10 2138 859 10 2170 879 10 2202 899 10 2234 8B9
9 2137 858 9 2169 878 9 2201 898 9 2233 8B8
8 2136 857 8 2168 877 8 2200 897 8 2232 8B7
7 2135 856 7 2167 876 7 2199 896 7 2231 8B6
6 2134 855 6 2166 875 6 2198 895 6 2230 8B5
5 2133 854 5 2165 874 5 2197 894 5 2229 8B4
4 2132 853 4 2164 873 4 2196 893 4 2228 8B3
3 2131 852 3 2163 872 3 2195 892 3 2227 8B2
2 2130 851 2 2162 871 2 2194 891 2 2226 8B1
1 2129 850 1 2161 870 1 2193 890 1 2225 8B0
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
22 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Slot 9 Slot 10 Slot 11 Slot 12
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
32 2288 8EF 32 2320 90F 32 2352 92F 32 2384 94F
31 2287 8EE 31 2319 90E 31 2351 92E 31 2383 94E
30 2286 8ED 30 2318 90D 30 2350 92D 30 2382 94D
29 2285 8EC 29 2317 90C 29 2349 92C 29 2381 94C
28 2284 8EB 28 2316 90B 28 2348 92B 28 2380 94B
27 2283 8EA 27 2315 90A 27 2347 92A 27 2379 94A
26 2282 8E9 26 2314 909 26 2346 929 26 2378 949
25 2281 8E8 25 2313 908 25 2345 928 25 2377 948
24 2280 8E7 24 2312 907 24 2344 927 24 2376 947
23 2279 8E6 23 2311 906 23 2343 926 23 2375 946
22 2278 8E5 22 2310 905 22 2342 925 22 2374 945
21 2277 8E4 21 2309 904 21 2341 924 21 2373 944
20 2276 8E3 20 2308 903 20 2340 923 20 2372 943
19 2275 8E2 19 2307 902 19 2339 922 19 2371 942
18 2274 8E1 18 2306 901 18 2338 921 18 2370 941
17 2273 8E0 17 2305 900 17 2337 920 17 2369 940
16 2272 8DF 16 2304 8FF 16 2336 91F 16 2368 93F
15 2271 8DE 15 2303 8FE 15 2335 91E 15 2367 93E
14 2270 8DD 14 2302 8FD 14 2334 91D 14 2366 93D
13 2269 8DC 13 2301 8FC 13 2333 91C 13 2365 93C
12 2268 8DB 12 2300 8FB 12 2332 91B 12 2364 93B
11 2267 8DA 11 2299 8FA 11 2331 91A 11 2363 93A
10 2266 8D9 10 2298 8F9 10 2330 919 10 2362 939
9 2265 8D8 9 2297 8F8 9 2329 918 9 2361 938
8 2264 8D7 8 2296 8F7 8 2328 917 8 2360 937
7 2263 8D6 7 2295 8F6 7 2327 916 7 2359 936
6 2262 8D5 6 2294 8F5 6 2326 915 6 2358 935
5 2261 8D4 5 2293 8F4 5 2325 914 5 2357 934
4 2260 8D3 4 2292 8F3 4 2324 913 4 2356 933
3 2259 8D2 3 2291 8F2 3 2323 912 3 2355 932
2 2258 8D1 2 2290 8F1 2 2322 911 2 2354 931
1 2257 8D0 1 2289 8F0 1 2321 910 1 2353 930
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
Revision 14 ControlEdge HC900 Controller Communications User Guide 23 April 2018
Slot 13 Slot 14 Slot 15 Slot 16
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
32 2416 96F 32 2448 98F 32 2480 9AF 32 2512 9CF
31 2415 96E 31 2447 98E 31 2479 9AE 31 2511 9CE
30 2414 96D 30 2446 98D 30 2478 9AD 30 2510 9CD
29 2413 96C 29 2445 98C 29 2477 9AC 29 2509 9CC
28 2412 96B 28 2444 98B 28 2476 9AB 28 2508 9CB
27 2411 96A 27 2443 98A 27 2475 9AA 27 2507 9CA
26 2410 969 26 2442 989 26 2474 9A9 26 2506 9C9
25 2409 968 25 2441 988 25 2473 9A8 25 2505 9C8
24 2408 967 24 2440 987 24 2472 9A7 24 2504 9C7
23 2407 966 23 2439 986 23 2471 9A6 23 2503 9C6
22 2406 965 22 2438 985 22 2470 9A5 22 2502 9C5
21 2405 964 21 2437 984 21 2469 9A4 21 2501 9C4
20 2404 963 20 2436 983 20 2468 9A3 20 2500 9C3
19 2403 962 19 2435 982 19 2467 9A2 19 2499 9C2
18 2402 961 18 2434 981 18 2466 9A1 18 2498 9C1
17 2401 960 17 2433 980 17 2465 9A0 17 2497 9C0
16 2400 95F 16 2432 97F 16 2464 99F 16 2496 9BF
15 2399 95E 15 2431 97E 15 2463 99E 15 2495 9BE
14 2398 95D 14 2430 97D 14 2462 99D 14 2494 9BD
13 2397 95C 13 2429 97C 13 2461 99C 13 2493 9BC
12 2396 95B 12 2428 97B 12 2460 99B 12 2492 9BB
11 2395 95A 11 2427 97A 11 2459 99A 11 2491 9BA
10 2394 959 10 2426 979 10 2458 999 10 2490 9B9
9 2393 958 9 2425 978 9 2457 998 9 2489 9B8
8 2392 957 8 2424 977 8 2456 997 8 2488 9B7
7 2391 956 7 2423 976 7 2455 996 7 2487 9B6
6 2390 955 6 2422 975 6 2454 995 6 2486 9B5
5 2389 954 5 2421 974 5 2453 994 5 2485 9B4
4 2388 953 4 2420 973 4 2452 993 4 2484 9B3
3 2387 952 3 2419 972 3 2451 992 3 2483 9B2
2 2386 951 2 2418 971 2 2450 991 2 2482 9B1
1 2385 950 1 2417 970 1 2449 990 1 2481 9B0
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
24 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Table 4-6 DI/DO Address Map (Firmware version 2.3 and earlier, 16 channels max)
Rack Channels Coil number/
Register number
Modbus Hex
Address Range
1* 1 - 256 1 – 256 0 - FF
2 257 - 512 257 - 512 100 - 1FF
3 513 - 768 513 – 768 200 - 2FF
4 769 - 1024 769 – 1024 300 - 3FF
5 1025 - 1280 1025 - 1280 400 - 4FF
*See Table 4-7 for detailed addresses of Rack #1
The coil (register) number for a digital I/O is based on the DI/DO’s position in the card cage. It is
determined from the formula:
Coil (register) Number = [(Rack-1)*256] + [(Slot-1)*16] + channel in module
Example: To monitor a coil (register) located in the 2nd channel of slot 10 of rack 3, the Modbus coil
(register) number is:
[(3-1)*256] + [(10-1)*16] + 2 = 658
Some third party software packages will require the 1-based coil/register number to be used for the address
while others will require the 0-based hex address.
Table 4-7 Rack #1 DI/DO address map (v2.3 and earlier, up to 16-channel)
Slot 1 Slot 2 Slot 3 Slot 4
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
16 16 0F 16 32 1F 16 48 2F 16 64 3F
15 15 0E 15 31 1E 15 47 2E 15 63 3E
14 14 0D 14 30 1D 14 46 2D 14 62 3D
13 13 0C 13 29 1C 13 45 2C 13 61 3C
12 12 0B 12 28 1B 12 44 2B 12 60 3B
11 11 0A 11 27 1A 11 43 2A 11 59 3A
10 10 9 10 26 19 10 42 29 10 58 39
9 9 8 9 25 18 9 41 28 9 57 38
8 8 7 8 24 17 8 40 27 8 56 37
7 7 6 7 23 16 7 39 26 7 55 36
6 6 5 6 22 15 6 38 25 6 54 35
5 5 4 5 21 14 5 37 24 5 53 34
4 4 3 4 20 13 4 36 23 4 52 33
3 3 2 3 19 12 3 35 22 3 51 32
2 2 1 2 18 11 2 34 21 2 50 31
1 1 0 1 17 10 1 33 20 1 49 30
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
Revision 14 ControlEdge HC900 Controller Communications User Guide 25 April 2018
Slot 5 Slot 6 Slot 7 Slot 8
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
16 80 4F 16 96 5F 16 112 6F 16 128 7F
15 79 4E 15 95 5E 15 111 6E 15 127 7E
14 78 4D 14 94 5D 14 110 6D 14 126 7D
13 77 4C 13 93 5C 13 109 6C 13 125 7C
12 76 4B 12 92 5B 12 108 6B 12 124 7B
11 75 4A 11 91 5A 11 107 6A 11 123 7A
10 74 49 10 90 59 10 106 69 10 122 79
9 73 48 9 89 58 9 105 68 9 121 78
8 72 47 8 88 57 8 104 67 8 120 77
7 71 46 7 87 56 7 103 66 7 119 76
6 70 45 6 86 55 6 102 65 6 118 75
5 69 44 5 85 54 5 101 64 5 117 74
4 68 43 4 84 53 4 100 63 4 116 73
3 67 42 3 83 52 3 99 62 3 115 72
2 66 41 2 82 51 2 98 61 2 114 71
1 65 40 1 81 50 1 97 60 1 113 70
Slot 9 Slot 10 Slot 11 Slot 12
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
CH# Coil/
register
Addr.
Hex
16 144 8F 16 160 9F 16 176 AF 16 192 BF
15 143 8E 15 159 9E 15 175 AE 15 191 BE
14 142 8D 14 158 9D 14 174 AD 14 190 BD
13 141 8C 13 157 9C 13 173 AC 13 189 BC
12 140 8B 12 156 9B 12 172 AB 12 188 BB
11 139 8A 11 155 9A 11 171 AA 11 187 BA
10 138 89 10 154 99 10 170 A9 10 186 B9
9 137 88 9 153 98 9 169 A8 9 185 B8
8 136 87 8 152 97 8 168 A7 8 184 B7
7 135 86 7 151 96 7 167 A6 7 183 B6
6 134 85 6 150 95 6 166 A5 6 182 B5
5 133 84 5 149 94 5 165 A4 5 181 B4
4 132 83 4 148 93 4 164 A3 4 180 B3
3 131 82 3 147 92 3 163 A2 3 179 B2
2 130 81 2 146 91 2 162 A1 2 178 B1
1 129 80 1 145 90 1 161 A0 1 177 B0
Modbus/TCP & Modbus RTU Function Codes
Function Code 01 – Read Digital Output Status
26 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Slot 13 Slot 14 Slot 15 Slot 16
CH# Coil/
register
Addr.
Hex CH# Coil/
register
Addr.
Hex CH# Coil/
register
Addr.
Hex CH# Coil/
register
Addr.
Hex
16 208 CF 16 224 DF 16 240 EF 16 256 FF
15 207 CE 15 223 DE 15 239 EE 15 255 FE
14 206 CD 14 222 DD 14 238 ED 14 254 FD
13 205 CC 13 221 DC 13 237 EC 13 253 FC
12 204 CB 12 220 DB 12 236 EB 12 252 FB
11 203 CA 11 219 DA 11 235 EA 11 251 FA
10 202 C9 10 218 D9 10 234 E9 10 250 F9
9 201 C8 9 217 D8 9 233 E8 9 249 F8
8 200 C7 8 216 D7 8 232 E7 8 248 F7
7 199 C6 7 215 D6 7 231 E6 7 247 F6
6 198 C5 6 214 D5 6 230 E5 6 246 F5
5 197 C4 5 213 D4 5 229 E4 5 245 F4
4 196 C3 4 212 D3 4 228 E3 4 244 F3
3 195 C2 3 211 D2 3 227 E2 3 243 F2
2 194 C1 2 210 D1 2 226 E1 2 242 F1
1 193 C0 1 209 D0 1 225 E0 1 241 F0
Modbus/TCP & Modbus RTU Function Codes
Function Code 02 - Read Digital Input Status
Revision 14 ControlEdge HC900 Controller Communications User Guide 27 April 2018
4.4 Function Code 02 - Read Digital Input Status
Description
Function code 02 (1X references) is used to read a digital input’s ON/OFF status using 16 bit addressing for
DI access and data is returned in a binary format mapped into bytes.
The Modbus Comm Digital I/O Channel to address mapping is shown starting on page 24.
Broadcast is not supported.
Query
The query message specifies the starting input and the quantity of inputs to read. The DI address in the
message is based on the slot and channel number of the digital input being read.
Example: Read inputs for channels 1 to 16 in Rack #1, Slot 1, from the controller with slave address 1.
Query message format for function code 02
Slave Address
(00 for TCP)
Function Code
Starting Address
High
Starting Address
Low
Number Inputs High
Number Inputs Low
CRC (RTU)
CRC (RTU)
TCP Example 00 02 00 00 00 10
RTU Example 01 02 00 00 00 10 CRC CRC
Response
The input status in the response message is packed as one input per bit of the data field. Status is indicated
as: 1 = ON; 0 = OFF. The LSB of the first data byte contains the input addressed in the query. The other
inputs follow toward the high order end of this byte, and from low order to high order in subsequent bytes.
If the returned input quantity is not a multiple of eight, the remaining bits in the final data byte will be
padded with zeros (toward the high order end of the byte). The byte count field specifies the quantity of
data bytes returned.
Example: Inputs for channels 2 and 6 in Rack #1, Slot 1 are on, all others are off.
Response message format for function code 02
Slave Address
(00 for TCP)
Function Code
Byte Count Data Data CRC (RTU)
CRC (RTU)
TCP Example 00 02 02 22 00
RTU Example 01 02 02 22 00 CRC CRC
In the response the status of inputs 1 - 8 is shown as the byte value 22 hex, or 0010 0010 binary. Input 8 is
the MSB of this byte, and input 1 is the LSB. Left to right, the status of input 6 through 1 is: OFF-OFF-ON-
OFF-OFF-OFF-ON-OFF. The status of inputs 9-16 are shown as 00 hex, or 0000 0000 with the same bit
ordering.
Modbus/TCP & Modbus RTU Function Codes
Function Code 03- Read Holding (Data) Registers
28 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.5 Function Code 03- Read Holding (Data) Registers
Description
Function code 03 (also referred to as 4X decimal references) is used to read 32-bit floating point, 32-bit
unsigned/signed integer and 16 bit integer data in the controller as described in Section 6. Registers are
consecutive.
In pre-4.0 configurations only it is also used to Read certain analog input modules for commonality of
UMC800 controller addresses. This applies to analog input modules positioned ONLY in the first 8 Slots of
Rack #1, providing support ONLY for the first 64 channels. Use Function Code 04 to address all analog
inputs in the ControlEdge HC900 controller.
Table 4-8 ControlEdge HC900 AI Address Mapping supported by Function Code 03
Rack Channel Register Range Hex
Address Range
1 1 - 64
65 - 128
1 - 127
65 - 255
0 -7F (uses register
addressing 1800 - 187Fh)
Not Supported
If a request is made to an address that does not exist in the map in Section 6 , the controller will honor that
request and return zeros for that address. This behavior will greatly enhance the bandwidth on the link vs.
making several different requests for non-contiguous data elements. (i.e. Consider a controller that is
configured for AI #1 and AI #3 and for some reason AI #2 is an invalid request.) The contiguous method
would allow the read of AI #1 through AI #3 and the data location for AI #2 would be zeros.
Broadcast is not supported.
Query
The query message specifies the starting register and quantity of registers to be read. Registers are
addressed starting at zero: registers 1-16 are addressed as 0-15.
Example: Read PV, Remote SP, Working SP, and Output as floating point values for Loop #1 in the
controller at slave address 1.
Query message format for function code 03
Slave Address
(00 for TCP)
Function Code
Starting Address
High
Starting Address
Low
Number Addresses
High
Number Addresses
Low
CRC (RTU)
CRC (RTU)
TCP Example 00 03 00 40 00 08
RTU Example 01 03 00 40 00 08 CRC CRC
Modbus/TCP & Modbus RTU Function Codes
Function Code 03- Read Holding (Data) Registers
Revision 14 ControlEdge HC900 Controller Communications User Guide 29 April 2018
Response
The register data in the response message is packed as two bytes per register. For each register, the first byte
contains the high order bits and the second contains the low order bits.
The floating point values require two consecutive registers. The byte order of the floating point number is
determined by the setting of the byte swap configuration value. In this example, and the examples that
follow, the byte swap order is FP B. Refer to page 9. The first 16 bits of the response contain the IEEE
MSB of the float value. The second 16 bits of the response contain the IEEE LSB of the float value. If the
master station requests only one register at an address of a floating point value then half of a float will be
returned.
The Modbus RTU protocol has a single byte count for function code 03, therefore the Modbus RTU
protocol can only process up to 63 floating point and 127 16-bit integer values in a single request.
Example: PV, Remote SP, Working SP, and Output where PV=100.0, RSP=100.0, WSP=100.0, and
Out=55.32 as floating point values where AI #1 = 100.0 and AI #2 = 55.32
Response message format for function codes 03
Slave Address
(00 for TCP)
Function Code
Byte Count
Data Data Data Data CRC (RTU)
CRC (RTU)
TCP Example 00 03 10 42 C8 00 00
(100)
42 C8 00 00
(100)
42 C8 00 00
(100)
42 5D 47 AE
(55.32)
RTU Example 01 03 10 42 C8 00 00
(100)
42 C8 00 00
(100)
42 C8 00 00
(100)
42 5D 47 AE
(55.32)
CRC CRC
Modbus/TCP & Modbus RTU Function Codes
Function Code 04 - Read Input Registers
30 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.6 Function Code 04 - Read Input Registers
Description
Function code 04(3X references) provides read access to Analog Input modules positioned in any Rack or
Slot. All values are in IEEE 32-bit floating point format.
For ControlEdge HC900 CPUs and Scanners with firmware version 2.3 and earlier, each Rack is allocated
space for a maximum of 16 Slots and each Slot assumes Modules with a maximum of 8 Channels, which
consumes 16 Modbus Register addresses. See Table 4-9.
For ControlEdge HC900 CPUs and Scanners with firmware version 2.4 and higher, each Rack is allocated
space for a maximum of 16 Slots and each Slot assumes Modules with a maximum of 16 Channels, which
consumes 32 Modbus Register addresses. See Table 4-10.
In Table 4-9 and Table 4-10 the register addressing is 1-based while the hex addressing is 0-based.
Table 4-9 ControlEdge HC900 AI Address Mapping supported by Function Code 04 (v2.3)
Rack Channels Register Range
(decimal)
Hex
Address Range
1 1 - 128 1 - 255 0 –FE
2 129 - 256 257 - 511 100 - 1FE
3 257 - 384 513 - 767 200 - 2FE
4 385 - 512 769 - 1023 300 - 3FE
5 513 - 640 1025 - 1279 400 - 4FE
Table 4-10 ControlEdge HC900 AI Address Mapping supported by Function Code 04 (v2.4
and higher)
Rack Channels Register Range
(decimal)
Hex
Address Range
1 1 – 256 2001 – 2511 0 -9CE
2 257 - 512 2513 – 3023 9D0 – BCE
3 513 - 768 3025 – 3535 BD0 – DCE
4 769 - 1024 3537 – 4047 DD0 – FCE
5 1025 - 1280 4049 - 4559 FD0 – 11CE
6 1281 - 1536 4561 – 5071 11D0 – 13CE
7 1537 - 1792 5073 – 5583 13D0 – 15CE
8 1793 - 2048 5585 – 6095 15D0 – 17CE
9 2049 - 2304 6097 – 6607 17D0 – 19CE
10 2305 - 2560 6609 – 7120 19D0 – 1BCE
11 2561 - 2816 7122 – 7632 1BD0 – 1DCE
12 2817 - 3072 7634 - 8144 1DD0 – 1FCE
Modbus/TCP & Modbus RTU Function Codes
Function Code 04 - Read Input Registers
Revision 14 ControlEdge HC900 Controller Communications User Guide 31 April 2018
If a request is made to an address that does not exist in the map in Section 1, the controller will honor that
request and return zeros for that address. This behavior will greatly enhance the bandwidth on the link vs.
making several different requests for non-contiguous data elements. (i.e. Consider a controller that is
configured for AI #1 and AI #3 and for some reason AI #2 is an invalid request.) The contiguous method
would allow the read of AI #1 through AI #3 and the data location for AI #2 would be zeros.
Broadcast is not supported.
Query
The query message specifies the starting register and quantity of registers to be read. Registers are
addressed starting at zero: registers 1-16 are addressed as 0-15.
Example: Read analog inputs #1 and #2 (Rack #1, Module #1) addresses 0-3, as floating point values from
the controller at slave address 1.
Query message format for function code 04
Slave Address
(00 for TCP)
Function Code
Starting Address
High
Starting Address
Low
Number Addresses
High
Number Addresses
Low
CRC (RTU)
CRC (RTU)
TCP Example 00 04 00 00 00 04
RTU Example 01 04 00 00 00 04 CRC CRC
Response
The register data in the response message is packed as two bytes per register. For each register, the first byte
contains the high order bits and the second contains the low order bits.
The floating point values require two consecutive registers. The byte order of the floating point number is
determined by the setting of the byte swap configuration value. In this example, and the examples that
follow, the byte swap order is FP B. Refer to subsection 1.3. The first 16 bits of the response contain the
IEEE MSB of the float value. The second 16 bits of the response contain the IEEE LSB of the float value.
If the master station requests only one register at an address of a floating point value, then half of a float
will be returned.
The Modbus RTU protocol has a single byte count for function code 04, therefore the Modbus RTU
protocol can only process up to 63 floating point values in a single request.
Example: Analog inputs #1 and #2 as floating point values where AI #1 = 100.0 and AI #2 =55.32
Response message format for function codes 04
Slave Address
(00 for TCP)
Function Code
Byte Count
Data Data CRC (RTU)
CRC (RTU)
TCP Example 00 04 08 42 C8 00 00
(100)
42 5D 47 AE
(55.32)
RTU Example 01 04 08 42 C8 00 00
(100)
42 5D 47 AE
(55.32)
CRC CRC
Modbus/TCP & Modbus RTU Function Codes
Function Code 05 - Force Single Digital Output
32 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.7 Function Code 05 - Force Single Digital Output
Description
Force a single digital output (0X reference) to either ON or OFF. These are the same digital outputs (DO)
used in Function Code 01.
The Modbus Comm Digital I/O Channel to address mapping is shown in Table 4-5.
(Table 4-7 for V 2.3 and older CPUs).
The ControlEdge HC900 does not support broadcast, and forcing can only be done in the Run or Run/Prog
mode.
Write Coil instructions are not supported for outputs configured in the 8 DO FB in controllers of version
4.4xx or earlier. Use single DO FB when executing write coils to ControlEdge HC900 outputs.
Query
The query message specifies the DO to be forced. In CPU firmware revisions 2.4 or greater, DO coils are
addressed starting at 2001d (7D0h). DO 1 is bit address 2001d.
The requested ON/OFF state is specified by a constant in the query data field.
A value of FF 00 hex forces the output to be ON.
A value of 00 00 hex forces the output to be OFF.
A value of FF FF releases the force.
ATTENTION: Any query (ON or OFF) causes a force mode of this point in the ControlEdge HC900
controller. The DO module’s diagnostic LED flashes Amber when a force condition is present. While in this
mode, internal control of function blocks cannot communicate to this point. DON’T FORGET to send a
query to release this force.
Example: Force DO Card Rack #1, Slot 1, Channel 6 ON in the controller at slave address 1.
Query message format for function code 05
Slave Address
(00 for TCP)
Function Code
DO Address
High
DO Address
Low
Force Data High
Force Data Low
CRC (RTU)
CRC (RTU)
TCP Example 00 05 07 D5 FF 00
RTU Example 01 05 07 D5 FF 00 CRC CRC
Response
The normal response is an echo of the query, returned after the DO state has been forced.
Example: Force DO Card Rack #1, Slot 1, Channel 6 ON in the controller at slave address 1.
Response message format for function code 05
Slave Address
(00 for TCP)
Function Code
DO Address
High
DO Address
Low
Force Data High
Force Data Low
CRC (RTU)
CRC (RTU)
TCP Example 00 05 07 D5 FF 00
RTU Example 01 05 07 D5 FF 00 CRC CRC
The Modbus Comm Digital I/O Channel to address mapping is shown starting on page 24.
Modbus/TCP & Modbus RTU Function Codes
Function Code 06 - Preset Single Register
Revision 14 ControlEdge HC900 Controller Communications User Guide 33 April 2018
4.8 Function Code 06 - Preset Single Register
Description
Presets integer value into a single register (also refered to as 4X references).
The ControlEdge HC900 does not support Broadcast.
The registers that are specified in Section 6 with an access type “W” and integer and bit packed (16-bit
register) data types, can be written to via Function Code 06. Also, digital variables in 32-bit floating point
format can be written using this function code. Writing a non-zero value to either register of the digital
variable will result in a floating point 1 to be written to the variable. Writing a zero value to either register
will result in the variable being set to 0.
Query
The query message specifies the register references to be preset. Registers are addressed starting at zero:
Register 1 is addressed as 0.
Example: Set Rack #1, Loop #1 to Auto (address 00FAh) in the controller at slave address 1
Query message format for function code 06
Slave Address
(00 for TCP)
Function Code
Address High
Address Low
Preset Data High
Preset Data Low
CRC (RTU)
CRC (RTU)
TCP Example 00 06 00 FA 00 01
RTU Example 01 06 00 FA 00 01 CRC CRC
Response
The normal response is an echo of the query returned after the register contents have been preset.
Example: Set Rack #1, Loop #1 to Auto (address 00FAh) in the controller at slave address 1.
Response message format for function code 06
Slave Address
(00 for TCP)
Function Code
Address High
Address Low
Preset Data High
Preset Data Low
CRC (RTU)
CRC (RTU)
TCP Example 00 06 00 FA 00 01
RTU Example 01 06 00 FA 00 01 CRC CRC
Modbus/TCP & Modbus RTU Function Codes
Function Code 08 - Loopback Message
34 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.9 Function Code 08 - Loopback Message
Description
Echoes received query message.
Query
Message can be any length up to half the length of the data buffer minus 8 bytes.
Example: 00 08 01 02 03 04
Query message format for function code 08
Slave Address
(00 for TCP)
Function Code
Any data, length limited to approximately half the length of the data buffer
CRC (RTU)
CRC (RTU)
TCP Example 00 08 01 02 03 04
RTU Example 01 08 01 02 03 04 CRC CRC
Response
Example: 00 08 01 02 03 04
Response message format for function code 08
Slave Address
(00 for TCP)
Function Code
Data bytes received CRC (RTU)
CRC (RTU)
TCP Example 00 08 01 02 03 04
RTU Example 01 08 01 02 03 04 CRC CRC
Modbus/TCP & Modbus RTU Function Codes
Function Codes 16 (10h) - Preset Multiple Registers
Revision 14 ControlEdge HC900 Controller Communications User Guide 35 April 2018
4.10 Function Codes 16 (10h) - Preset Multiple Registers
Description
Presets values into a sequence of holding registers (also refered to as 4X references). The ControlEdge
HC900 does not support Broadcast. The register assignments specified in Section 6 with an access type
“W”, can be written to via Function Code 16 (10h).
Writing to half of a digital variable will be accepted. A non-zero write to either register will result in a
floating point 1 to be written to the variable. Writing a zero to either register will result in the variable being
set to 0.
Query
The query message specifies the register references to be preset. Registers are addressed starting at zero:
Register 1 is addressed as 0.
Example: Preset Rack #1, Variable #1 (address 18C0h) to 100.0 in the controller at slave address 1.
Query message format for function code 16 (10h)
Slave Address (00
for TCP)
Function Code
Start Address
High
Start Address
Low
Number Addresses
High
Number Addresses
Low
Byte Count
Data CRC (RTU)
CRC (RTU)
TCP Example
00 10 18 C0 00 02 04 42 C8 00 00
RTU Example
01 10 18 C0 00 02 04 42 C8 00 00 CRC CRC
Response
The normal response returns the slave address, function code, starting address and the quantity of registers
preset.
The floating point values require two consecutive addresses. A request to preset a single floating point value
must be for two addresses. The byte order of the floating point number is determined by the setting of the
byte swap configuration value. In this example the byte swap order is FP B. Refer to subsection 1.3. The
first 16 bits of the response contain the IEEE MSB of the float value. The second 16 bits of the response
contain the IEEE LSB of the float value. The Byte order is configurable See Subsection 1.3. If the master
station requests only one address at an address of a floating point value the slave will respond with an
illegal data address exception code (See Section 5).
Example: Response from presetting Rack #1, Variable #1 (address 18C0h) to 100.0 from the controller.
Response message format for function code 16 (10h)
Slave Address (00
for TCP)
Function Code
Start Address
High
Start Address
Low
Number Addresses
High
Number Addresses
Low
CRC (RTU)
CRC (RTU)
TCP Example 00 10 18 C0 00 02
RTU Example 01 10 18 C0 00 02 CRC CRC
Modbus/TCP & Modbus RTU Function Codes
Function Code 17 (11h) - Report ControlEdge HC900 ID
36 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
4.11 Function Code 17 (11h) - Report ControlEdge HC900 ID
Description
Function code 17 (11h) is used to report the device information such as Slave ID, device description and
firmware version.
Query
The query message specifies the function code only.
Example: Read Device ID from a slave at address 2.
Query message format for function code 17 (11h)
Slave Address (00 for TCP)
Function Code
CRC (RTU) CRC (RTU)
TCP Example 00 11
RTU Example 02 11 CRC CRC
Response
The response is a record format describing the instrument.
Response message format for function code 17 (11h)
Slave Address
Function Code
Byte Count
Slave ID
Run Indicator Status
Device Description
Model ID
Device Class
ID
Device Mapping
CRC (RTU)
CRC (RTU)
Slave Address – 00 for TCP. RTU is slave address. Example: 02
Slave ID - The Slave ID number for the HC930 is 93 (hex). For the HC950 it is 95 (hex) (one byte) (byte
3). For HC970 it is 70 (hex). For HC970R it is 7A (hex).
Run Indicator Status - (one byte) (byte 4). 00=OFF; FF=ON
Device Description - (bytes 5-20)- 16 Character ASCII Message with the following format:
‘H’ ‘C’ ‘9’ ‘5’ or ‘3’ or ‘7’
‘0’ or ‘A’
‘’ ‘‘ up to 9 character version number in floating point notation.
zeros are appended for the remaining bytes
For example, an HC950 with version number 2.000 would have the following device description:
‘H’ ‘C’ ‘9’ ‘5’ ‘0’ ‘’ ‘‘ ‘2’ ‘.’ ‘0’ ‘0’ ‘0’ 0 0 0 0
Model ID - 00 (one byte) (byte 21)
Device Class ID - The Device Classification. (one byte) (byte 22)
Class ID Class
00 Generic Class (Fixed Address Mappable)
01-FF Future
Continued
Modbus/TCP & Modbus RTU Function Codes
Function Code 17 (11h) - Report ControlEdge HC900 ID
Revision 14 ControlEdge HC900 Controller Communications User Guide 37 April 2018
Generic Class (00) Device Mapping - Describes the I/O and feature mapping.
Number of Records
Record #1
Record #2
Record ...
Record #n
Number of Records - 1 Byte unsigned value 00-FFh (byte 23)
Record Description:
Byte Description
00 Type of Data Element (See Data Element Values Table Below)
01 Starting Address of Data Element Record (High)
02 Starting Address of Data Element Record (Low)
03 Number of Data Elements (High)
04 Number of Data Elements (Low)
Data Element Values Table:
Value Description
00 Analog Inputs
01 Not Applicable. Number of elements equals 0.
02 Discrete Inputs
03 Discrete Outputs
04 Control Loops
05 Set Point Programmers
06 Variables
07 Not applicable. Number of elements equals 0.
08 Not applicable. Number of elements equals 0.
09 Not applicable. Number of elements equals 0.
10 Schedulers
11 Signal tags
12 Signal tags List 2
13 Analog Inputs Accessed Using 3x Registers
14 Sequencers
15 Stage
16 Ramp
17 Hand Off Auto
18 Alternators
19 Device Controls
20 Control Loops Extended
21 Setpoint Programmers Extended
22 Schedulers Extended
23 Sequencers Extended
Modbus RTU Exception Codes
Introduction
38 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
5. Modbus RTU Exception Codes
5.1 Introduction
When a master device sends a query to a slave device it expects a normal response. One of four possible
events can occur from the master’s query:
Slave device receives the query without a communication error and can handle the query normally.
It returns a normal response.
Slave does not receive the query due to a communication error.
No response is returned. The master program will eventually process a time-out condition for the query.
Slave receives the query but detects a communication error (parity, LRC or CRC).
No response is returned. The master program will eventually process a time-out condition for the query.
Slave receives the query without a communication error but cannot handle it (i.e., request is to a non-
existent coil or register).
The slave will return with an exception response informing the master of the nature of the error (Illegal
Data Address.)
The exception response message has two fields that differentiate it from a normal response:
Function Code Field:
In a normal response, the slave echoes the function code of the original query in the function code field of
the response. All function codes have a most-significant bit (MSB) of 0 (their values are below 80 hex). In
an exception response, the slave sets the MSB of the function code to 1. This makes the function code value
in an exception response exactly 80 hex higher than the value would be for a normal response.
With the function code’s MSB set, the master’s application program can recognize the exception response
and can examine the data field for the exception code.
Data Field:
In a normal response, the slave may return data or statistics in the data field. In an exception response, the
slave returns an exception code in the data field. This defines the slave condition that caused the exception.
Query
Example: Internal slave error reading 2 registers starting at address 1820h from the controller at slave
address 01.
TCP: 00 03 18 20 00 02
RTU: 01 03 18 20 00 02 CRC CRC
Response
Example: Return MSB in Function Code byte set with Slave Device Failure (04) in the data field.
TCP: 00 83 04
RTU: 01 83 04 CRC CRC
Modbus RTU Exception Codes
Introduction
Revision 14 ControlEdge HC900 Controller Communications User Guide 39 April 2018
Table 5-1 Modbus RTU Data Layer Status Exception Codes
Exception
Code
Definition Description
01 Illegal Function The message received is not an allowable action for the addressed device.
02 Illegal Data Address The address referenced in the function-dependent data section of the message is not valid in the addressed device.
03 Illegal Data Value The value referenced at the addressed device location is not within range.
04 Slave Device Failure The addressed device has not been able to process a valid message due to a bad device state.
06 Slave Device Busy The addressed device has rejected a message due to a busy state. Retry later.
07 NAK, Negative Acknowledge
The addressed device cannot process the current message. Issue a PROGRAM POLL to obtain device-dependent error data.
Parameters accessible with Function Code 03, 06,10h
Overview
40 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6. Parameters accessible with Function Code 03, 06,10h
6.1 Overview
What’s in this section?
Section 6 describes all parameters accessible by Function Code 03, 06 and 10h. Your particular controller
may not contain all parameters shown. If you see a function that is not on your controller, either it is not
available for that controller model or it is not in your configuration.
Considerations for SIL-compliant Controllers
For SIL-compliant controllers such as C30S, C50S, etc, it must be noted that if a function block or variable
is on a Safety worksheet, then all the parameters or values for that block or variable is READ-ONLY. This
overrides all description of blocks/variables in the sections below. If the function block is on a Process
worksheet, then the description of blocks/variables in the below sections apply as described.
How parameters are mapped to addresses
There are two methods available for accessing Modbus parameters:
Use a fixed map to access pre-defined parameters at fixed addresses. These parameters and their fixed
addresses are described in Sections 6.2 through 6.17.
Build a custom map to assign parameters to any addresses. These parameters are described in Sections
6.2 through 6.17. Also, the custom map can contain additional parameters not available to the fixed
map, see Section 6.18. The custom map uses the fixed map’s address assignments as the default but,
unlike the fixed map, you can change these addresses and assign any parameter to any address.
Therefore, the addresses shown for the fixed map don’t necessarily apply to your custom map. You
can see the custom map addresses in HCDesigner, as well as view or print the custom map.
Your version of ControlEdge HC900 configuration (pre-4.0 or 4.0 and up) determines the type of address
mapping available, see table below.
Fixed map Custom map
Available in all ControlEdge HC900 configuration versions
Available in ControlEdge HC900 configuration version 4.0 and higher. Certain blocks can be assigned to the custom map that are not available in the fixed map. (See section 6.18.)
Contains limited types of parameters in limited quantities (e.g., 32 loops max)
More parameters to choose from and unlimited quantities (e.g., >32 loops)
Function block type (e.g. loop) can be assigned to any address partitioned for that block type.
Can create from scratch or can import fixed map for customization. Function block type (e.g. loop) can be assigned to any address or to multiple addresses.
Parameters are partitioned using fixed partitions according to type (e.g. loops 1-24, SP Programmers 1-4, etc.)
Parameters need not be partitioned or can use custom partitions
Must use fixed addresses Can use fixed addresses, or can assign parameters to desired addresses
Can access only the parameters shown in the fixed map
Can access the same parameters as the fixed map but can use any addresses. Can access additional parameters not available in fixed map.
Contains gaps in addresses especially between partitions
Address gaps can be eliminated by assigning parameters to contiguous addresses.
Parameters accessible with Function Code 03, 06,10h
Overview
Revision 14 ControlEdge HC900 Controller Communications User Guide 41 April 2018
Which parameters can be mapped?
Function Block Category/Filter Selection
Available in Fixed
Map
Available in
Custom Map
AGA8-Detail Block AGAs No Yes
AGA8-Gross Block AGAs No Yes
Alternator Block Alternators Yes Yes
XYR5000 Base Station Block Communications No Yes
XYR5000 Transmitter Block Communications No Yes
XYR6000 Transmitter Block Communications No Yes
UDC Loop Block Communications No Yes
UDC Loop2 Block Communications No Yes
Calendar Event Block Counters/Timers No Yes
Device Control Block Device Controls Yes Yes
Hand Off Auto Block Hand Off Autos Yes Yes
Four Selector Switch Block Logic No Yes
Push Button Block Logic No Yes
PID Loop Block Loops Yes Yes
On Off Loop Block Loops Yes Yes
Carbon Loop Block Loops Yes Yes
Three Pos. Step Cont. Block Loops Yes Yes
Auto Manual Bias Block Loops Yes Yes
Set Point Programmer Block Programmers Yes Yes
Ramp Block Ramps Yes Yes
Set Point Scheduler Block Schedulers Yes Yes
Sequencer Block Sequencers Yes Yes
Stage Block Stages Yes Yes
Position Proportional Output Block NA No No
Peer-Peer Block NA No No
Modbus Slave Block NA No No
Modbus/TCP Slave Block NA No No
XYR6000 Gateway NA No No
For parameters available only in a custom map, see section 6.18.
Parameters accessible with Function Code 03, 06,10h
Fixed Map
42 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.2 Fixed Map
Table 6-1 describes the fixed register map for Function Code 03, 06 and 10h.
Except for User-Defined Signals and Variables, all items shown are assigned automatically to the
addresses shown.
Details on each item type are in sections 6.3 through 6.17.
There are several gaps of unused addresses in the fixed map; Table 6-1 does not explicitly show
these gaps, it shows only the range of addresses used by items. For example, there is a gap of
unused addresses between Loop 1’s end address 00FF and Loop 2’s start address 0140. There are
also gaps of unused addresses within Loop 1’s range.
Parameters for blocks such as Setpoint Programmers and Sequencers are divided into two or three
sections of the map.
Custom maps can contain additional quantities and parameters beyond what is included in the
fixed map.
Conversion between Address (Hex) Number and Register (Decimal) Number
To convert the address number to the register number, convert the address from hexidecimal to decimal and
add 1. Registers are addressed starting at zero: registers 1-16 are addressed as 0-15.
To convert the register number to the address number, subtract 1 from the register and convert to hex.
Table 6-1 Fixed Map (listed by increasing address)
Fixed
Start
Address
(hex)
Fixed
End
Address
(hex)
Item Description See
section
0000 < 0040 Miscellaneous Parameters 6.3
0040 00FF Loop #1 (floating point & bit packed) 6.4
0140 01FF Loop #2 (floating point & bit packed)
0240 02FF Loop #3 (floating point & bit packed)
0340 03FF Loop #4 (floating point & bit packed)
0440 04FF Loop #5 (floating point & bit packed)
0540 05FF Loop #6 (floating point & bit packed)
0640 06FF Loop #7 (floating point & bit packed)
0740 07FF Loop #8 (floating point & bit packed)
0840 08FF Loop #9 (floating point & bit packed)
0940 09FF Loop #10 (floating point & bit packed)
0A40 0AFF Loop #11 (floating point & bit packed)
0B40 0BFF Loop #12 (floating point & bit packed)
0C40 0CFF Loop #13 (floating point & bit packed)
0D40 0DFF Loop #14 (floating point & bit packed)
0E40 0EFF Loop #15 (floating point & bit packed)
0F40 0FFF Loop #16 (floating point & bit packed)
1040 10FF Loop #17 (floating point & bit packed)
1140 11FF Loop #18 (floating point & bit packed)
1240 12FF Loop #19 (floating point & bit packed)
1340 13FF Loop #20 (floating point & bit packed)
1440 14FF Loop #21 (floating point & bit packed)
1540 15FF Loop #22 (floating point & bit packed)
Parameters accessible with Function Code 03, 06,10h
Fixed Map
Revision 14 ControlEdge HC900 Controller Communications User Guide 43 April 2018
Fixed
Start
Address
(hex)
Fixed
End
Address
(hex)
Item Description See
section
1640 16FF Loop #23 (floating point & bit packed)
1740 17FF Loop #24 (floating point & bit packed)
1800 187F Analog Input Value (#1-#64) First 8 slots of Rack #1 only - Function Code 03 6.5
18C0 1D6F Variable Value (#1 - #600) 6.6
1DF0 1DF6 Time 6.7
1E00 1E0F Set Point Programmer #1 6.8
1E10 1E1F Set Point Programmer #2
1E20 1E2F Set Point Programmer #3
1E30 1E3F Set Point Programmer #4
1F00 1F3F Set Point Programmer #1 (Additional Values)
1F40 1F7F Set Point Programmer #2 (Additional Values)
1F80 1FBF Set Point Programmer #3 (Additional Values)
1FC0 1FFF Set Point Programmer #4 (Additional Values)
2000 27CF Signal Tags (#1 - #1000) (legacy) 6.9
2800 29FF Set Point Programmer #1 Segments 6.8
2A00 2BFF Set Point Programmer #2 Segments
2C00 2DFF Set Point Programmer #3 Segments
2E00 2FFF Set Point Programmer #4 Segments
3000 304F Scheduler #1 Value 6.10
3050 309F Scheduler #2 Value
3200 3B5F Scheduler #1 Segments
3B60 5A9F Signal Tags (#1 - #4000) (ControlEdge HC900) 6.9
5AA0 5ABF Sequencer #1 Parameters 6.11
5AC0 5CBF Sequencer #1 Step 1 Table (64 steps in sequence) 6.11
5CC0 5CFF Sequencer #1 State Table 6.11
5D00 5D1F Sequencer #2 Parameters 6.11
5D20 5F1F Sequencer #2 Step 1 Table (64 steps in sequence) 6.11
5F20 5F5F Sequencer #2 State Table 6.11
5F60 5F7F Sequencer #3 Parameters 6.11
5F80 617F Sequencer #3 Step 1 Table (64 steps in sequence) 6.11
6180 61BF Sequencer #3 State Table 6.11
6200 6227 Stage #1 6.12
6230 6257 Stage #2
6260 6287 Stage #3
6290 62B7 Stage #4
62C0 62E7 Stage #5
62F0 6317 Stage #6
6320 6347 Stage #7
6350 6377 Stage #8
6400 642D Ramp #1 6.13
6430 645D Ramp #2
6460 648D Ramp #3
Parameters accessible with Function Code 03, 06,10h
Fixed Map
44 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Start
Address
(hex)
Fixed
End
Address
(hex)
Item Description See
section
6490 64BD Ramp #4
64C0 64ED Ramp #5
64F0 651D Ramp #6
6520 654D Ramp #7
6550 657D Ramp #8
6600 6606 Hand Off Auto #1 6.14
6610 6616 Hand Off Auto #2
6620 6626 Hand Off Auto #3
6630 6636 Hand Off Auto #4
6640 6646 Hand Off Auto #5
6650 6656 Hand Off Auto #6
6660 6666 Hand Off Auto #7
6670 6676 Hand Off Auto #8
6680 6686 Hand Off Auto #9
6690 6696 Hand Off Auto #10
66A0 66A6 Hand Off Auto #11
66B0 66B6 Hand Off Auto #12
66C0 66C6 Hand Off Auto #13
66D0 66D6 Hand Off Auto #14
66E0 66E6 Hand Off Auto #15
66F0 66F6 Hand Off Auto #16
6700 6725 Alternator #1 6.15
6730 6755 Alternator #2
6760 6785 Alternator #3
6790 67B5 Alternator #4
67C0 67E5 Alternator #5
67F0 6815 Alternator #6
6820 6845 Alternator #7
6850 6875 Alternator #8
6880 68A5 Alternator #9
68B0 68D5 Alternator #10
68E0 6905 Alternator #11
6910 6935 Alternator #12
6940 6965 Alternator #13
6970 6995 Alternator #14
69A0 69C5 Alternator #15
69D0 69F5 Alternator #16
6B00 6B09 Device Control #1 6.16
6B10 6B19 Device Control #2
6B20 6B29 Device Control #3
6B30 6B39 Device Control #4
6B40 6B49 Device Control #5
Parameters accessible with Function Code 03, 06,10h
Fixed Map
Revision 14 ControlEdge HC900 Controller Communications User Guide 45 April 2018
Fixed
Start
Address
(hex)
Fixed
End
Address
(hex)
Item Description See
section
6B50 6B59 Device Control #6
6B60 6B69 Device Control #7
6B70 6B79 Device Control #8
6B80 6B89 Device Control #9
6B90 6B99 Device Control #10
6BA0 6BA9 Device Control #11
6BB0 6BB9 Device Control #12
6BC0 6BC9 Device Control #13
6BD0 6BD9 Device Control #14
6BE0 6BE9 Device Control #15
6BF0 6BF9 Device Control #16
6C00 755F Scheduler #2 Segments 6.10
7840 78FF Loop #25 (floating point & bit packed) 6.4
7940 79FF Loop #26 (floating point & bit packed)
7A40 7AFF Loop #27 (floating point & bit packed)
7B40 7BFF Loop #28 (floating point & bit packed)
7C40 7CFF Loop #29 (floating point & bit packed)
7D40 7DFF Loop #30 (floating point & bit packed)
7E40 7EFF Loop #31 (floating point & bit packed)
7F40 7FFF Loop #32 (floating point & bit packed)
8000 800F Set Point Programmer #5 6.8
8010 801F Set Point Programmer #6
8020 802F Set Point Programmer #7
8030 803F Set Point Programmer #8
8070 80AF Set Point Programmer #5 (Additional Values)
80B0 80EF Set Point Programmer #6 (Additional Values)
80F0 812F Set Point Programmer #7 (Additional Values)
8130 816F Set Point Programmer #8 (Additional Values)
8200 83FF Set Point Programmer #5 Segments
8400 85FF Set Point Programmer #6 Segments
8600 87FF Set Point Programmer #7 Segments
8800 89FF Set Point Programmer #8 Segments
A000 A01F Sequencer #4 Parameters 6.11
A020 A21F Sequencer #4 Step 1 Table (64 steps in sequence)
A220 A25F Sequencer #4 State Table
B000 B3E7 User defined signal or variable. Read-only if a signal tag. Read/write if a variable. 6.17
Note: Additional parameters are available for custom maps only. See Section 6.18.
Parameters accessible with Function Code 03, 06,10h
Miscellaneous Parameters
46 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.3 Miscellaneous Parameters
In HC Designer’s custom map these parameters are grouped under the Item Filter “System Parameters.”
Table 6-2 Miscellaneous Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
0000 0001 Instrument Mode R/W Bit Packed
Indicators:
Bit 0: 1:Diagnostic Bit 1: 1:Calibration (unused by UMC800/HC9xx) Bit 2: 1:Maintenance/Offline mode Bit 3: 1:Program mode Bit 4: 1:Reset Unit/Force Cold Start (Write Only) Bit 5: 1:On-Line/Run mode Bit 6: 1:Fail-over (Write Only; C70R Only) Bit 7: Lead slot position: 0: A; 1: B (C70R Only) Bit 8: 1:On-demand write database to FLASH Bit 9: Database write status: 0: Done; 1: Busy Bit 10-15: Unused
0002 0003 Load Recipe R/W Floating Point
Read: Returns zero Write: Loads the recipe, identified in the request, from the recipe pool.
0004 0005 Reserve Status R Bit Packed Bit 0: Available for failover Bit 1: Available for failover with no RSM Bit 2: Available for failover with switch bad Bit 3: Available for failover with scanner communication failure Bit 4: Unsynchronized database Bit 5: Invalid database Bit 6: Software version mismatch Bit 7-15: Reserved
C70R Only
Parameters accessible with Function Code 03, 06,10h
Loop Values
Revision 14 ControlEdge HC900 Controller Communications User Guide 47 April 2018
6.4 Loop Values
About loop addresses
This table contains fixed addresses of Loop #1. See Table 6-1 for starting and ending fixed addresses
(hex) for Loop #2 through Loop #32. Each successive control loop is offset by 256 with the exception that
loop 25 has a new starting address and loop 26 – 32 are offset by 256. The loop number corresponds to the
PID block entry sequence during Process Control Designer configuration. The Modbus loop number
address for a loop can also be obtained from the Process Control Designer printout of Block Modbus
Addresses.
The addresses given in Table 6-3 do not necessarily apply to loops in the custom map. For custom
addresses view or print a report in HC Designer.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )
Writes – Function Code 6 for presetting an integer value
Table 6-3 Loop Values
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Loop type Access Notes
PID On/
Off
Carb 3Pos AMB
0040 0065 PV R Floating Point in Engineering Units.
0042 0067 Remote Set Point; SP2
R/W Floating Point in Engineering Units.
When the remote setpoint source is configured as LSP2, the value can be written.
0044 0069 Working Set Point R/W Floating Point in Engineering Units.
On a write to this register the instrument will update the proper set point according to the loop’s currently selected set point.
0046 0071 Output R/W Floating Point in Engineering Units.
0048 0073 PV R Floating Point in Engineering Units.
004A 0075 Carbon Potential block temperature
R Floating Point in Engineering Units
004C 0077 Gain #1 (Prop Band #1 if active)
R/W Floating Point . (in units per what was configured in the ControlEdge HC900: Gain or Proportional Band)
004E 0079 Direction R Floating Point 0.0=Direct; 1.0=Reverse
0050 0081 Reset #1 R/W Floating Point in Repeats/Minute or Minutes/Repeat.
0052 0083 Rate #1 R/W Floating Point in Minutes
0054 0085 Cycle Time for Analog Scan
R Floating Point in Seconds
0056 0087 PV Low Range R Floating Point in Engineering Units.
0058 0089 PV High Range R Floating Point in Engineering Units.
005A 0091 Alarm #1 SP #1 R/W Floating Point in Engineering Units.
005C 0093 Alarm #1 SP #2 R/W Floating Point in Engineering Units.
0060 0097 Gain #2 (Prop Band #2 if active)
R/W Floating Point
0062 0099 Three Position Step Motor Deadband
R/W Floating Point in percent
Parameters accessible with Function Code 03, 06,10h
Loop Values
48 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Loop type Access Notes
PID On/
Off
Carb 3Pos AMB
0064 0101 Reset #2 R/W Floating Point in Repeats/Minute or Minutes/Repeat as configured in the ControlEdge HC900.
0066 0103 Rate #2 R/W Floating Point in Minutes
0068 0105 Cycle Time for Analog Scan
R Floating Point in Seconds
006A 0107 LSP #1 R/W Floating Point in Engineering Units
006C 0109 LSP #2 R/W Floating Point in Engineering Units.
006E 0111 Alarm #2 SP #1 R/W Floating Point in Engineering Units.
0070 0113 Alarm #2 SP #2 R/W Floating Point in Engineering Units.
0074 0117 SP Low Limit R/W Floating Point in Engineering Units. Operator Limit
0076 0119 SP High Limit R/W Floating Point in Engineering Units. Operator Limit
0078 0121 Working Set Point R/W Floating Point in Engineering Units.
On a write to this register the instrument will update the proper set point according to the loop’s currently selected set point.
007A 0123 Output Low Limit R/W Floating Point in Engineering Units.
007C 0125 Output High Limit R/W Floating Point in Engineering Units.
007E 0127 Output Working Value R/W Floating Point in Engineering Units.
0086 0135 Ratio R/W Floating Point in Engineering Units.
0088 0137 Bias R/W Floating Point in Engineering Units. Auto/Man bias block, value is Read-Only
008A 0139 Deviation R Floating Point in Engineering Units. (SP-PV)
008E 0143 Manual Reset R/W Floating Point in Engineering Units.
0090 0145 Feed-forward Gain R/W Floating Point in Engineering Units.
0092 0147 Local Percent Carbon Monoxide
R/W Floating Point in Engineering Units.
0094 0149 Furnace Factor R/W Floating Point in Engineering Units.
0096 0151 Percent Hydrogen R/W Floating Point in Engineering Units.
0098 0153 On/Off Output Hysterisis
R/W Floating Point in percent of input span
009A 0155 Carbon Potential Dewpoint
R/W Floating Point in Engineering Units
009C 0157 Three Position Step Motor Time
R/W Floating Point in seconds
00F7 0248 Enable/Disable Fuzzy R/W Bit Packed Bit 0: 0:Disable; 1:Enable
00F8 0249 Demand Tune Request
R/W Bit Packed (one shot action, activates autotuning until autotuning completed) Bit 0: 0:Off; 1:On Bit 1-15: Unused
00F9 0250 Anti-soot set point limit enable
R/W Bit Packed Bit 0: 0:Off; 1:On Bit 1-15: Unused
00FA 0251 Auto/Manual State R/W Bit Packed Bit 0: 0:Manual; 1:Auto Bit 1-15: Unused
Parameters accessible with Function Code 03, 06,10h
Loop Values
Revision 14 ControlEdge HC900 Controller Communications User Guide 49 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Loop type Access Notes
PID On/
Off
Carb 3Pos AMB
00FB 0252 Set Point State R/W Bit Packed (selects either SP1 or SP2 as a local SP if the ControlEdge HC900 is configured as such in PID setup) Bit 0: 0:SP1; 1:SP2 Bit 1-15: Unused
00FC 0253 Remote/Local Set Point State
R/W Bit Packed Bit 0: 0:LSP; 1:RSP Bit 1-15: Unused
00FD 0254 Tune Set State R/W Bit Packed (selects tuning constant set) Bit 0: 0:Tune Set #1; 1:Tune Set #2 Bit 1-15: Unused
00FE 0255 Loop Status R Bit Packed Bit 0: Mode: 0:Manual; 1:Auto Bit 1: Set Point: 0:SP1; 1:SP2 Bit 2: Remote/Local: 0:LSP; 1:RSP Bit 3: Tune Set: 0:Set #1; 1:Set #2 Bit 4: IMAN: 0:Inactive; 1:Active Bit 5: LO: 0: Inactive; 1:Active Bit 6-15: Reserved
See Table 6-28 on page 90for additional loop parameters for custom maps only.
Parameters accessible with Function Code 03, 06,10h
Loop Values
50 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Examples for loop queries using Function Codes 3, 6, 16
Example 1
Query: Read PV, Remote SP, Working SP, Output for Loop 1 from ControlEdge HC900 at slave address 01 using
Function Code 3 (hex codes). This will be accomplished by accessing contiguous registers.
TCP:
00 03 00 40 00 08
RTU:
01 03 00 40 00 08 CRC CRC
Response: where PV=1000.0, Remote SP=1000.0, Working SP=1000.0, Output=50.0
TCP:
00 03 10 44 7A 00 00 44 7A 00 00 44 7A 00 00 42 48 00 00
RTU:
01 03 10 44 7A 00 00 44 7A 00 00 44 7A 00 00 42 48 00 00 CRC CRC
Example 2:
Query: Write a Local Setpoint , (address 006A) to 100.0 for loop 1 at ControlEdge HC900 at slave address 01
using Function Code 16 (10 hex). Function code 16 is used for presetting multiple registers. Registers
are addressed starting at zero: Register 1 is addressed as 0.
TCP:
00 10 00 6A 00 02 04 42 C8 00 00
RTU:
01 10 00 6A 00 02 04 42 C8 00 00 CRC CRC
Response: from preset of LSP#1, address 006A to 100.0.
TCP:
00 10 00 6A 00 02
RTU:
01 10 00 6A 00 02 CRC CRC
Example 3:
Query: Using Function code 6, set Loop #1 to Auto (register 00FA hex) at controller at slave address 01. This is
a bit-packed single register data type. Registers are addressed starting at 0: Register 1 is addressed as 0.
TCP:
00 06 00 FA 00 01
RTU:
01 06 00 FA 00 01 CRC CRC
Parameters accessible with Function Code 03, 06,10h
Loop Values
Revision 14 ControlEdge HC900 Controller Communications User Guide 51 April 2018
Response: from preset of LSP#1, address 006A to 100.0 at address 1.
TCP:
00 06 00 FA 00 01
RTU:
01 06 00 FA 00 01 CRC CRC
Parameters accessible with Function Code 03, 06,10h
Analog Input - Function Code 03
52 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.5 Analog Input - Function Code 03
Summary
Not available for versions 4.0 and later. Used to access analog input parameters for the first 8 channels of
the first 8 modules of Rack #1. (Address compatible with UMC800.)
To access any analog input channels use Function Code 04. See page 30.
Analog Input Example: AI1 through AI64. The mapping is with respect to card position starting with the
first card module position and continuing to the 8th module position. The first module position would be
AI1 thru AI8. The next AI card in slot 2 would be AI9 thru AI16 and so on.
Function Code Support:
Reads – Function Codes 03 (limited to the first 8 slots of Rack #1)
Table 6-4 Analog Input Value Addresses - Function Code 03
Fixed
Address
(hex)
Fixed
Register
(decimal)
Channel Number Access Notes
1800 6145 Analog Input #1 R
Floating Point in Engineering Units.
1802 6147 Analog Input #2 R
1804 6149 Analog Input #3 R
1806 6151 Analog Input #4 R
1808 6153 Analog Input #5 R
180A 6155 Analog Input #6 R
180C 6157 Analog Input #7 R
180E 6159 Analog Input #8 R
1810 6161 Analog Input #9 R
1812 6163 Analog Input #10 R
1814 6165 Analog Input #11 R
1816 6167 Analog Input #12 R
: : :
187E 6271 Analog Input #64 R
Example
Read Analog Inputs 1 and 2 from ControlEdge HC900 at slave address 01 using Function Code 03.
TCP:
00 03 18 00 00 04
RTU:
01 06 00 FA 00 01 CRC CRC
Response from ControlEdge HC900 where AI1 = 100.0 and AI 2 = 55.32
TCP:
00 03 08 42 C8 00 00 42 5D 47 AE
RTU:
01 03 08 42 C8 00 00 42 5D 47 AE CRC CRC
Parameters accessible with Function Code 03, 06,10h
Variables
Revision 14 ControlEdge HC900 Controller Communications User Guide 53 April 2018
6.6 Variables
Summary
Variables (analog or digital) are writeable parameters in ControlEdge HC900 attached to input pins of
function blocks. Digital Variable status is also represented in floating point: 0.0 for OFF or logic 0 and 1.0
for ON or logic 1. The Variable number in the table corresponds to the Variable number in the ControlEdge
HC900 configuration.
You will need to access the ControlEdge HC900 Control Designer configuration or corresponding
configuration printout of Tag Information Report to identify the Variable numbers desired.
Single byte writes are permitted to digital variables. A non-zero will automatically set the digital variable to
a floating point 1 and a zero write to a single register will set the digital variable to 0.
Function Code Support:
Read – Function Code 3
Write – Function Codes 6 (digital variables only), 16 (10 Hex)
The addresses given in Table 6-5 do not necessarily apply to variables in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-5 Variables
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
18C0 6337 Variable Value #1 R/W Floating Point in Engineering Units.
18C2 6339 Variable Value #2 R/W
18C4 6341 Variable Value #3 R/W
18C6 6343 Variable Value #4 R/W :
18C8 6345 Variable Value #5 R/W :
18CA 6347 Variable Value #6 R/W :
18CC 6349 Variable Value #7 R/W :
18CE 6351 Variable Value #8 R/W :
18D0 6353 Variable Value #9 R/W :
18D2 6355 Variable Value #10 R/W :
18D4 6357 Variable Value #11 R/W :
18D6 6359 Variable Value #12 R/W :
18D8 6361 Variable Value #13 R/W :
18DA 6363 Variable Value #14 R/W :
18DC 6365 Variable Value #15 R/W :
18DE 6367 Variable Value #16 R/W :
18E0 6369 Variable Value #17 R/W :
18E2 6371 Variable Value #18 R/W :
18E4 6373 Variable Value #19 R/W :
18E6 6375 Variable Value #20 R/W :
: : : :
1D6E 7535 Variable Value #600 R/W :
Parameters accessible with Function Code 03, 06,10h
Time
54 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Example
Query: Read Variables 1 and 2 from ControlEdge HC900 at address 1 using Function Code 3 (hex codes).
TCP:
00 03 18 C0 00 04
RTU:
01 03 18 C0 00 04 CRC CRC
Response: from ControlEdge HC900 where Variable 1 = 100.0 and Variable 2 = 55.32
TCP:
00 03 08 42 C8 00 00 42 5D 47 AE
RTU:
01 03 08 42 C8 00 00 42 5D 47 AE CRC CRC
6.7 Time
The addresses given in Table 6-6 do not necessarily apply to time parameters in the custom map. For
custom addresses view or print a report in HC Designer.
In HC Designer’s custom map these parameters are grouped under the Item Filter “System Parameters.”
You must add them all to the custom map in order to write to them. See Attention below.
Table 6-6 Time parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
1DF0 7665 Hours R/W 0 to 23
1DF1 7666 Minutes R/W 0 to 60
1DF2 7667 Seconds R/W 0 to 60
1DF3 7668 Month R/W 1 to 12
1DF4 7669 Day R/W 1 to 31
1DF5 7670 Year R/W 1970 to 2037
The values read are always in the range of 1970 to 2037 for a write. 0 – 37 represents 2000 – 2037, 70 – 99 represents 1970 – 1999
1DF6 7671 Week Day R 0 to 6 (0 = Sunday)
ATTENTION
Time registers must all be written in a single transaction. Writing to Week Day is optional.
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
Revision 14 ControlEdge HC900 Controller Communications User Guide 55 April 2018
6.8 Set Point Programmer
Summary
The SP Programmer parameters are listed according to category related to program status and interaction, other
programmer parameters and program segment mapping.
In the fixed map each SP Programmer is assigned to three non-contiguous sections of the map:
SP Programmer parameters (Table 6-9)
SP Programmer Additional parameters (Table 6-9, page 58)
SPP Programmer segments (Table 6-10).
In a custom map the above parameters may be contiguous.
Function Code Support:
Read – Function Code 3
Write – Function Code 16 (10 Hex)
Considerations and Methods for Downloading. Operating, and Reading Status of SP Programs
A SP programmer interface can be developed (and recipes containing a SP profile can be created) in third
party software using the parameters listed in the following table.
In creating a SP Programmer interface showing a number of segments, a graphic display might include a
table referencing the maximum number of ramp/soak segments that you will be using for your process. The
parameters to be referenced for each segment are listed in Table 6-10.
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
56 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Procedure for Downloading Setpoint Profile
These steps are for programmer 1. For programmers 2, 3, 4, 5, 6, 7, and 8 adjust the register addresses
accordingly by adding offset for starting addresses.
Table 6-7 is for downloading using Function Codes 3, 4, 6, 16.
If using a custom map, you need to know the addresses of the parameters referred to in this procedure. Use
HC Designer to print a report showing the Modbus registers of the SP Programmers.
Table 6-7 Steps to Download a Setpoint Program using Modbus Function Codes 3, 6, 16
Step Action
1 Set the programmer to RESET by writing any number to Reset parameter (p. 58). This can be done either with function code 6 or 16.
2 Clear the program by writing a 0 to Current Program Number (p. 58). This is a floating point register and requires a multiple register write (function code 16). This is the safest way to insure that all registers are cleared for the next program download.
3 Write the header information for parameters relevant to the profile (leave all others at 0). See Table 6-9 items marked with **. Do not write yet to Program Save Request (p. 58). Floating point registers must be written using function code 16. Bit-packed registers can be written with either function code 6 or 16.
Note: Display High Range Limit and Display Low Range Limit (p. 58) are not presently used in the ControlEdge HC900 but can be used on external operator interfaces.
4 Write the information for each segment required in the profile. Each segment uses 8 registers and all 400 registers of the 50 segments are contiguous. See Table 6-10. The first 2 registers of each segment are bit-packed and can be written with either function code 6 or 10; the last 6 registers are float and must be written using function code 16.
5 Save the program to a program (profile) number archive by writing a floating point number to Program Save Request (p. 58). This will store the downloaded data utilized by the programmer block to the program (profile) number used. Profile numbers may range from 1-99.
The program is now ready to run. Note that the Current Program Number (p. 58) is automatically set to the saved program number.
Procedure for Uploading Setpoint Programs
If using a custom map, you need to know the addresses of the parameters referred to in this procedure. Use
HC Designer to create a report showing the Modbus registers of the SP Programmers.
Table 6-8 Steps to Upload a Setpoint Program using Modbus Function Codes 3, 6, 16
Step Action
1 Set the programmer to RESET by writing any number to the address (p. 58). This can be done either with function code 6 or 16.
2 Load the program into the setpoint programmer block by writing the program number to Current Program Number (p. 58). This is a floating point register and requires a multiple register write (function code 16).
3 Using function code 3, read the header information desired. See Table 6-9 items marked with **.
4 Read the information for each segment desired using function code 3. See Table 6-10.
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
Revision 14 ControlEdge HC900 Controller Communications User Guide 57 April 2018
Set Point Programmer parameters
This table contains Values of SP Programmers. Fixed addresses are for SP Programmer #1; see Table 6-1
for fixed addresses of other SP Programmers.
Parameters commonly used for controlling a program are marked with a single asterisk*.
Parameters commonly used to define a setpoint profile are marked with two asterisks **.
The addresses given in Table 6-9 do not necessarily apply to programmers in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-9 Set Point Programmer parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
1E00 7681 Set Point Programmer Output*
R Floating Point in Engineering Units.
1E02 7683 Current Segment Number* R/W Floating Point; 1...Max Segment # 50
A write changes the segment number.
1E04 7685 Program Elapsed Time* R Floating Point in Minutes Continues to run when in Hold
1E08 7689 Segment Time Remaining* R Floating Point in Minutes
1E0A 7691 Current Segment Events* R Bit Packed Indicates status of events 1-16 in one register
Bit 0: Event #1 : Bit 15: Event #16 0: Event OFF 1: Event ON
1E0B 7692 Status* R Bit Packed
Bit 0: 1=Ready Bit 1: 1=Run Bit 2: 1=Hold Bit 3: 1=End Bit 4: 1=Reserved Bit 5: 1=Time Units in Minutes Bit 6: 1=Time Units in Hours Bit 7: Ramp Units 0: Time 1: Rate Bit 8: Reserved Bit 9: If bit 2 Set 0: Operator hold 1: Guaranteed soak hold Bit 10: 0: Current segment is a soak 1: Current segment is a ramp
Bit 11-15: Reserved
1E0C 7693 Run* W Signed 16 bit integer
Write to location Starts Profile; Data ignored
1E0D 7694 Hold* W Signed 16 bit integer
Write to location Holds Profile; Data ignored
1E0E 7695 Advance* W Signed 16 bit integer
Write to location Advances Profile one segment while in Hold mode; Data ignored
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
58 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
1E0F 7696 Reset* W Signed 16 bit integer
Write to location Resets Profile after program is first in Hold mode; Data ignored
Setpoint Programmer Additional Parameters:
1F00 7937 Current Program Number* R/W Floating Point Indicates the present profile number in use. This also allows entry of a profile number from the ControlEdge HC900 stored profile memory (if profiles have been stored in the controller) and will retrieve the profile data for a display showing a SP profile segment table. Typically, when recipes are downloaded from third party software, this will be the number generated by the Program Save Request parameter
A write to this register loads the program into the set point programmer function block; if 0 is written, the function block’s program is cleared.
1F02 7939 Program Save Request** R/W Floating Point
Assigns profile parameters downloaded to a profile number such as 1. This is required by the ControlEdge HC900 to be the last parameter downloaded. This overwrites what is in this ControlEdge HC900 SP Profile memory location on each download of a new SP profile.
Saves the program into the archive. Writing to this register is prohibited in the run mode.
1F04 7941 Auxiliary Output* R Floating Point
1F06 7943 Guaranteed Soak Low** R/W Floating Point Presets High Deviation setting in engineering units. Writing to this register is only permissible in the reset or ready mode
1F08 7945 Guaranteed Soak High** R/W Floating Point Presets Low Deviation setting in engineering units. Writing to this register is only permissible in the reset or ready mode
1F0A 7947 Restart Ramp Rate R/W Floating Point Writing to this register is only permissible in the reset or ready mode
1F0C 7949 Display High Range Limit R/W Floating Point Writing to this register is only permissible in the reset or ready mode. Not presently used in the ControlEdge HC900 but can be used on external operator interfaces.
1F0E 7951 Display Low Range Limit R/W Floating Point Writing to this register is only permissible in the reset or ready mode. Not presently used in the ControlEdge HC900 but can be used on external operator interfaces
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
Revision 14 ControlEdge HC900 Controller Communications User Guide 59 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
1F10 7953 Jog Segment R/W Floating Point Writing to this register is only permissible in the reset or ready mode
1F12 7955 Loop Start R/W Floating Point 0 indicates no loop. Writing to this register is only permissible in the reset or ready mode
1F14 7957 Loop End R/W Floating Point 0 indicates no loop. Writing to this register is only permissible in the reset or ready mode
1F16 7959 Repeats R/W Floating Point 0 indicates loop forever. Writing to this register is only permissible in the reset or ready mode
1F3A 7995 Time Units** R/W Bit Packed Bit 0: Reserved 1: minutes 2: hours 3-15: Unused
1F3B 7996 Ramp Units** R/W Bit Packed Bit 0: 0:Time; 1:Rate Bit 1-15: Unused Writing to this register is only permissible in the reset or ready mode
1F3C 7997 Guaranteed Soak Type ** R/W Bit Packed For selection of Soak (or Hold) guarantee – Per Segment (requiring selection per segment in a table)
Bit 0: per segment 1: all soaks 2: all segments 3-15: Unused None if none of the bits is set Writing to this register is only permissible in the reset or ready mode
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
60 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Set Point Profile Segments
The table below describes the registers that are part of a setpoint profile segment. A profile contains up to
50 segments and each segment consumes 8 registers, therefore each profile uses 400 contiguous registers.
To determine the actual register address for a parameter within a segment, add the register offset to the start
address of the segment. This table contains fixed addresses of SP Programmer #1 Segments; see Table 6-1
for starting addresses of other SP Programmer Segments.
The addresses given in Table 6-10 do not necessarily apply to segments in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-10 SP Programmer Segments
Fixed
Address
(Hex)
Fixed
Register
(Decimal)
Register
Offset
Parameter Access Notes
2800 10241 0 Segment #1 Ramp/Soak Segment
Guaranteed Soak Enable
R/W Bit Packed
Bit 0: 1 = ramp segment; 0=soak segment
Bit 1: 1 = guaranteed soak enabled 0 = guaranteed soak disabled
Bit 0 is ignored in the hold mode.
Writing to this register is not permissible in the run mode.
2801 10242 1 Segment #1 Events R/W Bit Packed
Bit 0: Event #1 : : Bit 15: Event #16
0: Event OFF 1: Event ON
Writing to this register is only permissible in reset or ready mode.
2802 10243 2 Segment #1 Time or Rate R/W Floating Point in time units configured for the set point programmer
Writing to this register is not permissible in the run mode.
2804 10245 4 Segment #1 Ramp or Soak value
R/W Floating Point
Writing to this register is not permissible in the run mode.
2806 10247 6 Segment #1 Soak value for auxiliary output (use “Time or Rate” for duration)
R/W Floating Point
Writing to this register is not permissible in the run mode.
2808 10249 8 Segment #2 Ramp/Soak Segment
Guaranteed Soak Enable
R/W Bit Packed
Bit 0: 1 = ramp segment; 0=soak segment
Bit 1: 1 = guaranteed soak enabled 0 = guaranteed soak disabled
Bit 0 is ignored in the hold mode.
Writing to this register is not permissible in the run mode.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
298E 10639 398 Segment #50 Soak value for auxiliary output (use “Time or Rate” for duration)
R/W Floating Point
Writing to this register is not permissible in the run mode.
Parameters accessible with Function Code 03, 06,10h
Set Point Programmer
Revision 14 ControlEdge HC900 Controller Communications User Guide 61 April 2018
Example For Determining a Segment Register’s fixed address
Note: Custom map users should ignore this procedure. Obtain segment addresses by printing a Modbus
Register Report in HC Designer.
To change the ramp value in segment #8 of setpoint programmer #2, the register address is determined as
follows.
Step 1: Use Table 6-1 to determine the start address for setpoint programmer #2 segments. The value is
2A00 Hex.
Step 2: Calculate the offset address for segment 8 in a profile. This is calculated as:
Segment #8 offset address = (segment number – 1) * 8
= (8-1) * 8
= 56 or 38 Hex
Step 3: Use the table above to determine the register offset for the ramp value. The value is 4.
Step 4: Calculate the address by adding the results of steps 1, 2, and 3 to determine the register address.
Register address = Setpoint program #2 segment start address
+ Segment 8 offset address
+ Ramp value register offset
= 2A00 + 38 + 4
= 2A3C
Parameters accessible with Function Code 03, 06,10h
Signal Tags
62 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.9 Signal Tags
Summary
Signal tags are connected to output pins of function blocks, representing analog or digital parameters, and
are read-only parameters. Digital Signal tags are also represented in floating point, 0.0 for OFF or logic 0,
1.0 for ON or logic 1. The signal tag number in Table 6-11 corresponds to the signal tag number in the
ControlEdge HC900 Control Designer configuration. You will need to access the Process Control Designer
configuration "Tag Information" report to identify the Signal Tag numbers desired.
Note: to convert floating point values (analog or digital) to integer 16, (for use with third party touch panels
and associated HMI software, for example), use the user-defined signals and variables for assigning new
Modbus addresses and associated data type, configurable in HC Designer, Ver. 2.0 or later.
Function Code Support:
Read – Function Code 3
NOTES:
Floating Point in Engineering Units
Digital Signal Tags are represented as 0.0 for OFF, 1.0 for ON.
Access is Read Only
Signal tags 1-1000 have two addresses each; one for legacy use and one for ControlEdge
HC900. For example, signal tag #1 is at hex addresses 2000 and 3B60.
The addresses given in Table 6-11 do not necessarily apply to signal tags in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-11 Signal Tags
Legacy ControlEdge HC900 Range
Fixed
Address
(hex)
Fixed Register
(decimal)
Parameter Fixed
Address
(hex)
Fixed Register
(decimal)
Channel Number
2000 8193 Signal tag #1 3B60 15201 Signal tag #1
2002 8195 Signal tag #2 3B62 15203 Signal tag #2
2004 8197 Signal tag #3 3B64 15205 Signal tag #3
2006 8199 Signal tag #4 3B66 15207 Signal tag #4
2008 8201 Signal tag #5 3B68 15209 Signal tag #5
200A 8203 Signal tag #6 3B6A 15211 Signal tag #6
200C 8205 Signal tag #7 3B6C 15213 Signal tag #7
200E 8207 Signal tag #8 3B6E 15215 Signal tag #8
2010 8209 Signal tag #9 3B70 15217 Signal tag #9
2012 8211 Signal tag #10 3B72 15219 Signal tag #10
.
.
. 27CE
.
.
. 10191
.
.
. Signal tag #1000
.
.
. 432E
.
.
. 17199
.
.
. Signal tag #1000
4330 . . . 5A9E
17201 . . . 23199
Signal tag #1001 . . . Signal tag #4000
Parameters accessible with Function Code 03, 06,10h
Signal Tags
Revision 14 ControlEdge HC900 Controller Communications User Guide 63 April 2018
Example
Query: Read Signal Tags 3 and 4 from ControlEdge HC900 at address 1 using Function Code 3 (hex
codes).
TCP:
00 03 20 04 00 04
RTU:
01 03 20 04 00 04 CRC CRC
Response: from ControlEdge HC900 where Signal Tag 3 = 100.0 and Signal Tag 4 = 55.32
TCP:
00 03 08 42 C8 00 00 42 5D 47 AE
RTU:
01 03 08 42 C8 00 00 42 5D 47 AE CRC CRC
Parameters accessible with Function Code 03, 06,10h
Scheduler
64 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.10 Scheduler
Summary
The SP Scheduler parameters are listed according to category related to SP Scheduler status plus interaction
and scheduler segment mapping. A section is also provided to aid in configuring a Scheduler and recipe
interface for third party software.
In the fixed map each Scheduler is assigned to two non-contiguous sections of the map:
Scheduler parameters (Table 6-15)
Schedule segments (Table 6-16).
In a custom map the above parameters may be contiguous.
Function Code Support
Read – Function Code 3
Write – Function Code 16 (10 hex)
Scheduler Value Register Map
You will need to define the parameters for the Schedule as required by the application. Application notes
for these parameters are provided and further defined in the Scheduler Value Register Map.
Table 6-15 contains Value Register addresses of SP Scheduler #1. See Table 6-1 for starting and ending
addresses (hex) for SP Scheduler #2.
Scheduler Segment Register Map
Table 6-16 indicates the range of addresses applicable to a scheduler segment. Each segment uses 48
registers (30 hex).
Segment Register Map Addresses
Table 6-17 describes the registers that are part of a schedule segment. To determine the actual register
address for a parameter within a segment, add the register offset to the start address of the segment.
Considerations and Methods for Downloading, Operating, and Reading Status of SP Schedules
A SP Scheduler interface can be developed (and recipes containing a schedule can be created) in third party
software using the parameters listed in Table 6-17.
In creating a Scheduler interface showing a number of segments and outputs for each segment on a graphic
display might include a table referencing the maximum number of segments that you will be using for your
process. Refer to the Scheduler Segment Register Map - Table 6-16 for the range of addresses applied to
each scheduler segment. Each segment uses 48 registers (30 hex). Use the Segment Register Map - Table
6-17 for the parameters to be referenced for read/write within each segment. Application notes for these
segment parameters is provided.
Parameters accessible with Function Code 03, 06,10h
Scheduler
Revision 14 ControlEdge HC900 Controller Communications User Guide 65 April 2018
Scheduler Addresses
The parameters that follow refer to SP Scheduler #1. Table 6-12 lists the Starting and Ending addresses for
all of the SP Schedulers. For custom addresses view or print a report in HC Designer.
Table 6-12 SP Scheduler Addresses
Scheduler Number Starting
Address
(Hex)
Starting
Register
(Decimal)
Ending
Address
(Hex)
Ending
Register
(decimal)
SP Scheduler 1 3000 12289 304F 12368
SP Scheduler 2 3050 12369 309F 12448
Procedures for Downloading Setpoint Schedules
Table 6-13 is for downloading using Function Codes 3, 6, 16.
Table 6-13 Steps to Download a Setpoint Schedule using Modbus Function Codes 3, 6, 16
Step Action
1 Set the scheduler to RESET by writing any number to Reset (p. 68). This can be done either with function code 6 or 16.
2 Clear the schedule by writing a 0 to Current Program Number (p. 67). This is a floating point register and requires a multiple register write (function code 16). This is the safest way to insure that all registers are cleared for the next schedule download.
3 Write the header information for parameters relevant to the schedule, that is, Guaranteed Soak Limits 1-8 (p. 67), Jog Segment (p. 67), Time Units (p. 68). Guaranteed Soak Limits 1-8 and Jog Segment are floats and must be written using function code 16. Time Units is bit-packed and can be written with either function code 6 or 16. Leave all others at 0.
4 Write the information for each segment required in the schedule (p. 69). The first 9 registers are bit-packed and can be written with either function code 6 or 10. The rest of the registers are float and must be written using function code 16.
5 Save the schedule to a schedule number archive by writing a floating point number to Schedule Save Request (p. 67). This will store the downloaded data utilized by the scheduler block to the schedule number used. Schedule numbers may range from 1-50.
The schedule is now ready to run. Note that the current program (schedule) number (p. 67) is automatically set to the saved schedule number.
Parameters accessible with Function Code 03, 06,10h
Scheduler
66 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Procedure for Uploading Setpoint Schedules
Table 6-14 Steps to Upload a Setpoint Schedule using Modbus Function Codes 3, 6, 16
Step Action
1 Set the scheduler to RESET by writing any number to Reset (p. 68). This can be done either with function code 6 or 16.
2 Load the schedule into the setpoint scheduler block by writing the schedule number to Current Program Number (p. 67). This is a floating point register and requires a multiple register write (function code 16)
3 Read the header information desired. Guaranteed Soak Limits 1-8 (p. 67), Jog Segment (p. 67), Time Units (p. 68). Use function code 3.
4 Read the information for each segment in the schedule (p. 69) using function code 3.
Scheduler parameters
This table contains Values of Schedulers. Fixed addresses are for Scheduler #1; see Table 6-1 for fixed
addresses of other Schedulers.
Parameters commonly used for controlling a scheduler are marked with a single asterisk*.
Parameters commonly used to define a schedule are marked with two asterisks **.
The addresses given in Table 6-15 do not necessarily apply to schedulers in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-15 Scheduler Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
3000 12289 Scheduler Output 1** R Floating Point in Engineering Units.
3002 12291 Scheduler Output 2** R Floating Point in Engineering Units.
3004 12293 Scheduler Output 3** R Floating Point in Engineering Units.
3006 12295 Scheduler Output 4** R Floating Point in Engineering Units.
3008 12297 Scheduler Output 5** R Floating Point in Engineering Units.
300A 12299 Scheduler Output 6** R Floating Point in Engineering Units.
300C 12301 Scheduler Output 7** R Floating Point in Engineering Units.
300E 12303 Scheduler Output 8** R Floating Point in Engineering Units.
3010 12305 Scheduler Auxiliary Output 1** R Floating Point in Engineering Units.
3012 12307 Scheduler Auxiliary Output 2** R Floating Point in Engineering Units.
3014 12309 Scheduler Auxiliary Output 3** R Floating Point in Engineering Units.
3016 12311 Scheduler Auxiliary Output 4** R Floating Point in Engineering Units.
3018 12313 Scheduler Auxiliary Output 5** R Floating Point in Engineering Units.
301A 12315 Scheduler Auxiliary Output 6** R Floating Point in Engineering Units.
301C 12317 Scheduler Auxiliary Output 7** R Floating Point in Engineering Units.
301E 12319 Scheduler Auxiliary Output 8** R Floating Point in Engineering Units.
Parameters accessible with Function Code 03, 06,10h
Scheduler
Revision 14 ControlEdge HC900 Controller Communications User Guide 67 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
3020 12321 Current Program Number* R/W Floating Point Indicates the present schedule number in use. This also allows entry of a schedule number from the ControlEdge HC900 stored schedule memory (if schedules have been stored in the controller) and will retrieve the schedule data for a display showing a SP schedule segment table. Typically, when recipes are downloaded from third party software, this will be the number generated by the Schedule Save Request parameter
A write to this register loads the program into the scheduler function block; if 0 is written, the scheduler’s schedule is cleared. Writing to this register is only permissible in reset or ready mode.
3022 12323 Current Segment Number* R/W Floating Point; 1 thru Max Segment #
A write changes the segment number.
3024 12325 Program Elapsed Time* R Floating Point in Time Units Includes or runs when in Hold
3026 12327 Segment Time Remaining* R Floating Point in Time Units
3028 12329 Schedule Save Request* R/W Floating point.
Assigns profile parameters downloaded to a schedule number such as 1. This is required by the ControlEdge HC900 to be the last parameter downloaded. This overwrites what is in this ControlEdge HC900 SP Schedule memory location on each download of a new SP Schedule.
Saves the schedule into the archive. Writing to this register is prohibited in the run mode.
302A 12331 Guaranteed Soak Limit 1** R/W Floating Point
302C 12333 Guaranteed Soak Limit 2** R/W Floating Point
302E 12335 Guaranteed Soak Limit 3** R/W Floating Point
3030 12337 Guaranteed Soak Limit 4** R/W Floating Point
3032 12339 Guaranteed Soak Limit 5** R/W Floating Point
3034 12341 Guaranteed Soak Limit 6** R/W Floating Point
3036 12343 Guaranteed Soak Limit 7** R/W Floating Point
3038 12345 Guaranteed Soak Limit 8** R/W Floating Point
303A 12347 Jog Segment* R/W Floating Point Defines segment for schedule to jog based on an enable to an input pin
3049 12362 Current Segment Events* (Bit Packed)
R Bit Packed
Indicates status of events
Bit 0: Event #1 : : Bit 15: Event #15
0: Event OFF
1: Event ON
Parameters accessible with Function Code 03, 06,10h
Scheduler
68 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
304A 12363 Status* (Bit Packed)
R Bit Packed
Bit 0: 1=Ready 1: 1=Run 2: 1=Hold 3: 1=End 4: 1=Time Units in Seconds 5: 1=Time Units in Minutes 6: 1=Time Units in Hours 7: If bit 2 Set 0: Operator hold 1: Guaranteed soak hold 8-15: Reserved
304B 12364 Start* W Signed 16 bit integer
Write to location Starts Schedule; Data ignored
304C 12365 Hold* W Signed 16 bit integer
Write to location Holds Schedule; Data ignored
304D 12366 Advance* W Signed 16 bit integer
Write to location Advances Schedule; Data ignored
304E 12367 Reset* W Signed 16 bit integer
Write to location Resets Schedule; Data ignored
304F 12368 Time Units* R/W Bit Packed
Bit 0: Reserved 1: minutes 2: hours 3-15: Unused
Scheduler Segment Fixed Register Map
A schedule can contain up to 50 segments. Each segment is made up of 48 (30 hex) registers, for a total of
2400 contiguous registers. This table contains Segment Map fixed addresses of SP Scheduler #1. See Table
6-1 for starting and ending addresses (hex) for SP Scheduler #2 Addresses.
The addresses given in Table 6-16 do not necessarily apply to scheduler segments in the custom map. For
custom addresses view or print a report in HC Designer.
Table 6-16 Scheduler #1 Segment Fixed Addresses
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Fixed End
Address
(Hex)
Fixed End
Register
(Decimal)
Description
3200 12801 322F 12847 Scheduler #1 Segment 1
3230 12849 325F 12896 Scheduler #1 Segment 2
3260 12897 328F 12944 Scheduler #1 Segment 3
: : : :
3B30 15153 3B5F 15200 Scheduler #1 Segment 50
Parameters accessible with Function Code 03, 06,10h
Scheduler
Revision 14 ControlEdge HC900 Controller Communications User Guide 69 April 2018
Segment registers
The table below describes the registers that are part of a setpoint schedule. A schedule contains 50
segments. Each segment is made up of 28 parameters (Segment n Guaranteed Soak Type 1 through
Segment n Recycle Segment) which consumes 48 (30 hex) registers, for a total of 2400 contiguous
registers. This table contains fixed addresses of Schedule #1 Segments; see Table 6-1 for fixed addresses of
Schedule Segments. In a custom map the segment registers contiguously follow the other Schedule registers
listed in Table 6-15.
All 50 segments are used to define a schedule. You can’t specify which segments get assigned.
The addresses given in Table 6-17 do not necessarily apply to segments in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-17 Schedule Segments 1-50
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Offset
(Hex)
Offset
(Decimal)
Parameter Name Access Notes
3200 12801 0000 0000 Segment #1 Guaranteed Soak Type 1 (Bit Packed)
R/W Bit Packed
Bit 0: Off Bit 1: Low Bit 2: High Bit 3: Low & High Bit 4…15: Unused
Note 1
3201 12802 0001 0001 Segment #1 Guaranteed Soak Type 2
R/W See Guaranteed Soak Type 1
3202 12803 0002 0002 Segment #1 Guaranteed Soak Type 3
R/W See Guaranteed Soak Type 1
3203 12804 0003 0003 Segment #1 Guaranteed Soak Type 4
R/W See Guaranteed Soak Type 1
3204 12805 0004 0004 Segment #1 Guaranteed Soak Type 5
R/W See Guaranteed Soak Type 1
3205 12806 0005 0005 Segment #1 Guaranteed Soak Type 6
R/W See Guaranteed Soak Type 1
3206 12807 0006 0006 Segment #1 Guaranteed Soak Type 7
R/W See Guaranteed Soak Type 1
3207 12808 0007 0007 Segment #1 Guaranteed Soak Type 8
R/W See Guaranteed Soak Type 1
3208 12809 0008 0008 Segment #1 Events R/W Bit Packed
Bit 0: Event #1 : : Bit 15: Event #15
0: Event OFF
1: Event ON Note 2
320A 12811 000A 0010 Segment #1 Time R/W Floating Point in seconds Note 1
320C 12813 000C 0012 Segment #1 Output #1 Ramp or Soak value
R/W Floating Point Note 1
320E 12815 000E 0014 Segment #1 Output #2 Ramp or Soak value
R/W Floating Point Note 1
3210 12817 0010 0016 Segment #1 Output #3 Ramp or Soak value
R/W Floating Point Note 1
3212 12819 0012 0018 Segment #1 Output #4 Ramp or Soak value
R/W Floating Point Note 1
Parameters accessible with Function Code 03, 06,10h
Scheduler
70 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Start
Address
(Hex)
Fixed
Start
Register
(Decimal)
Offset
(Hex)
Offset
(Decimal)
Parameter Name Access Notes
3214 12821 0014 0020 Segment #1 Output #5 Ramp or Soak value
R/W Floating Point Note 1
3216 12823 0016 0022 Segment #1 Output #6 Ramp or Soak value
R/W Floating Point Note 1
3218 12825 0018 0024 Segment #1 Output #7 Ramp or Soak value
R/W Floating Point Note 1
321A 12827 001A 0026 Segment #1 Output #8 Ramp or Soak value
R/W Floating Point Note 1
321C 12829 001C 0028 Segment #1 Soak value for Auxiliary Output #1
R/W Floating Point Note 1
321E 12831 001E 0030 Segment #1 Soak value for Auxiliary Output #2
R/W Floating Point Note 1
3220 12833 0020 0032 Segment #1 Soak value for Auxiliary Output #3
R/W Floating Point Note 1
3222 12835 0022 0034 Segment #1 Soak value for Auxiliary Output #4
R/W Floating Point Note 1
3224 12837 0024 0036 Segment #1 Soak value for Auxiliary Output #5
R/W Floating Point Note 1
3226 12839 0026 0038 Segment #1 Soak value for Auxiliary Output #6
R/W Floating Point Note 1
3228 12841 0028 0040 Segment #1 Soak value for Auxiliary Output #7
R/W Floating Point Note 1
322A 12843 002A 0042 Segment #1 Soak value for Auxiliary Output #8
R/W Floating Point Note 1
322C 12845 002C 0044 Segment #1 Recycle R/W Number of times to recycle Floating Point Note 2
322E 12847 002E 0046 Segment #1 Recycle Segment R/W Floating Point Note 2
The above parameters are repeated for segments 2 through 50.
3230 12848 0030 0048 Segment #2 Guaranteed Soak Type 1 (Bit Packed)
R/W Bit Packed
Bit 0: Off Bit 1: Low Bit 2: High Bit 3: Low & High Bit 4…15: Unused
Note 1
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
3B5E 15199 095E 2398 Segment #50 Recycle Segment R/W Floating Point Note 2
Note 1: Writing to this register is not permissible in the run mode.
Note 2: Writing to this register is only permissible in reset or ready mode
Parameters accessible with Function Code 03, 06,10h
Scheduler
Revision 14 ControlEdge HC900 Controller Communications User Guide 71 April 2018
Example for Determining a Segment Fixed Register
Note: Custom map users must get segment addresses by printing a Modbus Register Report in HC Designer.
Note: To change the ramp value for Output #6 in segment #5 of setpoint scheduler #2, the register address
is determined as follows.
Step 1: Use Table 6-1 to determine the start address for scheduler #2’s segments. The value is 6C00 Hex.
Step 2: Calculate the offset address for segment 5 in a schedule. This is calculated as:
Segment offset address = (segment number – 1) * 48
= (5-1) * 48
= 192 or C0 Hex
Step 3: Use the table above to determine the register offset for Output #6 ramp value. The value is 16 Hex.
Step 4: Calculate the address by adding the results of steps 1, 2, and 3 to determine the register address.
Register address = Schedule #2 segment start address
+ Segment 5 offset address
+ Output #6 ramp value register offset
= 6C00+ C0 + 16
= 6CD6
Parameters accessible with Function Code 03, 06,10h
Sequencer
72 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.11 Sequencer
Summary
In the fixed map each Sequencer uses three non-contiguous sections of the map:
Sequencer parameters (Table 6-21)
Sequencer steps (Table 6-21)
Sequencer states (Table 6-21).
In a custom map the above parameters are contiguous.
Function Code Support
Read – Function Code 3
Write – Function Code 16 (10 hex)
Sequencers 1-4 Parameter Addresses
The addresses given in Table 6-18 do not necessarily apply to sequencers in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-18 Sequencers 1-4 Parameters Fixed Addresses
Starting
Address
(Hex)
Starting
Register
(Decimal)
Ending
Address
(Hex)
Ending
Address
(Decimal)
Sequencer #1 Parameters 5AA0 23201 5AB5 23222
Sequencer #2 Parameters 5D00 23809 5D1F 23840
Sequencer #3 Parameters 5F60 24417 5F7F 24448
Sequencer #4 Parameters A000 40961 A01F 40992
Sequencers 1-4 Step 1 Addresses
The addresses given in Table 6-19 do not necessarily apply to sequencer steps in the custom map. For
custom addresses view or print a report in HC Designer.
Table 6-19 Sequencer 1-4 Step 1 Fixed Addresses
Starting
Address
(Hex)
Starting
Register
(Decimal)
Ending
Address
(Hex)
Ending
Address
(Decimal)
Sequencer #1 Step 1 Table 5AC0 23233 5CBF 23744
Sequencer #2 Step 1 Table 5D20 23841 5F1F 24532
Sequencer #3 Step 1 Table 5F80 24449 617f 24960
Sequencer #4 Step 1 Table A020 40993 A21F 41504
Sequencers 1-4 State Addresses
The addresses given in Table 6-20 do not necessarily apply to sequencer states in the custom map. For
custom addresses view or print a report in HC Designer.
Parameters accessible with Function Code 03, 06,10h
Sequencer
Revision 14 ControlEdge HC900 Controller Communications User Guide 73 April 2018
Table 6-20 Sequencer 1-4 State Fixed Addresses
Starting
Address
(Hex)
Starting
Register
(Decimal)
Ending
Address
(Hex)
Ending
Address
(Decimal)
Sequencer #1 State Table 5CC0 23745 5CFF 23808
Sequencer #2 State Table 5F20 24353 5F5F 24416
Sequencer #3 State Table 6180 24961 61BF 25024
Sequencer #4 State Table A220 41505 A25F 41568
Sequencer Parameters
Fixed addresses are for Sequencer #1. For fixed addresses of other Sequencers see Table 6-1, or Table
6-18, Table 6-19, and Table 6-20.
Parameters commonly used for controlling a sequencer are marked with a single asterisk*.
Parameters commonly used to define a sequence are marked with two asterisks **.
Note: in the custom map either all or none of the segment step data is addressed, you can’t specify which
steps get addressed.
The addresses given in Table 6-21 do not necessarily apply to sequencers in the custom map. For custom
addresses view or print a report in HC Designer.
Table 6-21 Sequencer Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
5AA0 23201 Not used N/A Not used
5AA1 23202 Save current sequence request**
R/W Integer, Saves current sequence to archive and assigns it to the number written (1-20).
5AA2 23203 Reset* W Integer, Write to this location results in reset action and data is ignored.
5AA3 23204 Run* W Integer, Write to this location starts run action and data is ignored.
5AA4 23205 Hold* W Integer, Write to this location results in reset action and data is ignored.
5AA5 23206 Advance* W Integer, Write to this location results in an advance to next step and data is ignored.
Writing to this register is only permissible in the hold mode.
5AA6 23207 Not used N/A Not used
5AA7 23208 Step jumped to on Jog* R/W Integer Step number for jog.
5AA8 23209 Current Sequence number * R Integer Sequence number loaded.
5AA9 23210 Step Number* R Integer value for current step number.
5AAA 23211 Load Sequence number * R/W Integer, sequence number loaded to sequencer. Writing to this register is only permissible in the Ready mode.
Parameters accessible with Function Code 03, 06,10h
Sequencer
74 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
5AAB 23212 Step number change request* R/W Integer, go to a step number in any mode.
5AAC 23213 Outputs* R Integer, Bit packed for 16 output values 0:OFF 1:ON
5AAD 23214 Time units** R/W Integer, 0=hrs, 1=minutes.
5AAE 23215 Elapsed Sequence Time* R Floating point value for elapsed sequence time in minutes.
5AB0 23217 Time Remaining in current step* R Floating point value for time remaining in current step in minutes.
5AB2 23219 Sequence status* R Integer value for bit packed current sequence state :
Bit 0 = Ready Bit 1 = Run Bit 2 =Hold Bit 3 = Stop Bit 4 = Disable Bit 5 = time units (minutes) Bit 6 = time units (hours)
5AB4 23221 State* R Integer value for current state number
5AB6 23223 Auxiliary Output* R Floating point value auxiliary output
The following parameters are partitioned as Sequencer Steps and are not contiguous with the previous partition. All 64 steps are used to define a sequence.
5AC0 23233 Sequencer #1 Step #1 Time Next step
R/W Integer value of the next step executed when time expires.
5AC1 23234 Sequencer #1 Step #1 Event1 Next step
R/W Integer value of the next step executed when configured event 1 transitions from OFF to ON.
5AC2 23235 Sequencer #1 Step #1 Event2 Next step
R/W Integer value of the next step executed when configured event 2 transitions from OFF to ON.
5AC3 23236 Sequencer #1 Step #1 Advance Next step
R/W Integer value of the next step executed when Advance transitions from OFF to ON.
5AC4 23237 Sequencer #1 Step #1 Step Time
R/W Floating value for time of present step.
5AC6 23239 Sequencer #1 Step #1 Auxiliary Output
R/W Floating Auxiliary analog value associated with the step.
5AC8 23241 Sequencer #1 Step #2 Time Next step
R/W Integer value of the next step executed when time expires.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
5CBE 23743 Sequencer #1 Step #64 Auxiliary Output
R/W Floating Auxiliary analog value associated with the step.
The following parameters are partitioned as Sequencer States and are contiguous with the previous partition. All 64 state numbers are used to define a sequence.
Parameters accessible with Function Code 03, 06,10h
Sequencer
Revision 14 ControlEdge HC900 Controller Communications User Guide 75 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Access Notes
5CC0 23745 Sequencer #1 State Number Step #1
R/W Integer state number of the output definitions as configured between 1 and 50.
5CC1 23746 Sequencer #1 State Number Step #2
R/W Integer state number of the output definitions as configured between 1 and 50.
5CC2 23747 Sequencer #1 State Number Step #3
R/W Integer state number of the output definitions as configured between 1 and 50.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
5CFF 23808 Sequencer #1 State Number Step #64
R/W Integer state number of the output definitions as configured between 1 and 50.
Parameters accessible with Function Code 03, 06,10h
Stage
76 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.12 Stage
Summary
This section contains addresses for the Stage function blocks.
See the Stage Register Maps in Table 6-1 for starting and ending addresses (hex) for Stage #1 through
Stage #8 Map Addresses.
The Modbus Stage number address for a Stage block can also be obtained from the Process Control Designer
report.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point)
Writes – Function Code 6 for presetting an integer value
For custom addresses view or print a report in HC Designer.
Table 6-22 Stage Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6200 25089 PV1 R Floating Point in Engineering Units
6202 25091 PV2 R Floating Point in Engineering Units
6204 25093 Stage #1-4 Override Status
R Bit Packed:
Bit 0: Stage #1 Override Active: 0=NO, 1=YES
Bit 1: Stage #1 Override ON: 0=OFF, 1=ON
Bit 2: Stage #2 Override Active: 0=NO, 1=YES
Bit 3: Stage #2 Override ON: 0=OFF, 1=ON
Bit 4: Stage #3 Override Active: 0=NO, 1=YES
Bit 5: Stage #3 Override ON: 0=OFF, 1=ON
Bit 6: Stage #4 Override Active: 0=NO, 1=YES
Bit 7: Stage #4 Override ON: 0=OFF, 1=ON
Bits 8-15: Unused
6205 25094 Stage #1-4 PV On/Off Comparison
R Bit Packed:
Bit 0: Stage #1 On Comparitor: 0=PV1, 1=PV2
Bit 1: Stage #1 Off Comparitor: 0=PV1, 1=PV2
Bit 2: Stage #2 On Comparitor: 0=PV1, 1=PV2
Bit 3: Stage #2 Off Comparitor: 0=PV1, 1=PV2
Bit 4: Stage #3 On Comparitor: 0=PV1, 1=PV2
Bit 5: Stage #3 Off Comparitor: 0=PV1, 1=PV2
Bit 6: Stage #4 On Comparitor: 0=PV1, 1=PV2
Bit 7: Stage #4 Off Comparitor: 0=PV1, 1=PV2
Bit 8-15: Unused
Parameters accessible with Function Code 03, 06,10h
Stage
Revision 14 ControlEdge HC900 Controller Communications User Guide 77 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6206 25095 Stage #1-4 Previous/Next Interlock
R Bit Packed:
Bit 0: Stage #1 Interlock with Previous Stage
0=NO, 1=YES
Bit 1: Stage #1 Interlock with Next Stage
0=NO, 1=YES
Bit 2: Stage #1 Error with Interlocks 0=NO, 1=YES
Bit 3: Stage #2 Interlock with Previous Stage
0=NO, 1=YES
Bit 4: Stage #2 Interlock with Next Stage
0=NO, 1=YES
Bit 5: Stage #2 Error with Interlocks 0=NO, 1=YES
Bit 6: Stage #3 Interlock with Previous Stage
0=NO, 1=YES
Bit 7: Stage #3 Interlock with Next Stage
0=NO, 1=YES
Bit 8: Stage #3 Error with Interlocks 0=NO, 1=YES
Bit 9: Stage #4 Interlock with Previous Stage
0=NO, 1=YES
Bit 10: Stage #4 Interlock with Next Stage
0=NO, 1=YES
Bit 11: Stage #4 Error with Interlocks 0=NO, 1=YES
Bit 12 - 15: Unused
6207 25096 Stage #1-4 Output Status (Request)
R Bit Packed:
Bit 0: Stage #1 Output Enable: 0=NO, 1=YES
Bit 1: Stage #1 Output ON: 0=OFF, 1=ON
Bit 2: Stage #2 Output Enable: 0=NO, 1=YES
Bit 3: Stage #2 Output ON: 0=OFF, 1=ON
Bit 4: Stage #3 Output Enable: 0=NO, 1=YES
Bit 5: Stage #3 Output ON: 0=OFF, 1=ON
Bit 6: Stage #4 Output Enable: 0=NO, 1=YES
Bit 7: Stage #4 Output ON: 0=OFF, 1=ON
Bit 8-15: Unused
6208 25097 Stage #1 ON Setpoint
R/W Floating Point in Engineering Units
620A 25099 Stage #2 ON Setpoint
R/W Floating Point in Engineering Units
620C 25101 Stage #3 ON Setpoint
R/W Floating Point in Engineering Units
Parameters accessible with Function Code 03, 06,10h
Stage
78 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
620E 25103 Stage #4 ON Setpoint
R/W Floating Point in Engineering Units
6210 25105 Stage #1 OFF Setpoint
R/W Floating Point in Engineering Units
6212 25107 Stage #2 OFF Setpoint
R/W Floating Point in Engineering Units
6214 25109 Stage #3 OFF Setpoint
R/W Floating Point in Engineering Units
6216 25111 Stage #4 OFF Setpoint
R/W Floating Point in Engineering Units
6218 25113 Stage #1 Latch Delay
R/W Floating Point in Seconds
621A 25115 Stage #2 Latch Delay
R/W Floating Point in Seconds
621C 25117 Stage #3 Latch Delay
R/W Floating Point in Seconds
621E 25119 Stage #4 Latch Delay
R/W Floating Point in Seconds
6220 25121 Stage #1 Unlatch Delay
R/W Floating Point in Seconds
6222 25123 Stage #2 Unlatch Delay
R/W Floating Point in Seconds
6224 25125 Stage #3 Unlatch Delay
R/W Floating Point in Seconds
6226 25127 Stage #4 Unlatch Delay
R/W Floating Point in Seconds
Parameters accessible with Function Code 03, 06,10h
Ramp
Revision 14 ControlEdge HC900 Controller Communications User Guide 79 April 2018
6.13 Ramp
Summary
This section contains parameters and addresses for the Ramp.
See the Ramp Register Maps in Table 6-1 for starting and ending addresses (hex) for Ramp #2 through
Ramp #8 Map Addresses.
The Modbus Ramp number address for a Ramp can also be obtained from the Process Control Designer printout
of "Block Modbus Addresses".
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point)
Writes – Function Code 6 for presetting an integer value
For custom addresses view or print a report in HC Designer.
Table 6-23 Ramp Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6400 25601 PV R Floating Point in Engineering Units
6402 25603 Ramp Output R Floating Point in Engineering Units
6404 25605 Ramp Default R Floating Point in Engineering Units
6406 25607 Ramp Lag Time R/W Floating Point in Seconds
6408 25609 Ramp Transfer Up R/W Floating Point in Engineering Unit/Second
640A 25611 Ramp Transfer Dn R/W Floating Point in Engineering Unit/Second
640C 25613 Ramp #1-4 Enable R Bit Packed:
Bit 0: Ramp #1 Enable: 0=NO, 1=YES
Bit 1: Ramp #2 Enable: 0=NO, 1=YES
Bit 2: Ramp #3 Enable: 0=NO, 1=YES
Bit 3: Ramp #4 Enable: 0=NO, 1=YES
Bit 4-15: Unused
640D 25614 Ramp #1-4 Override Status
R Bit Packed
Bit 0: Ramp #1 Override Active: 0= NO, 1=YES
Bit 1: Ramp #1 Override to High Limit:
0=Low Limit, 1= High Limit Bit 2: Ramp #2 Override Active: 0= NO, 1=YES
Bit 3: Ramp #2 Override to High Limit:
0=Low Limit, 1= High Limit
Bit 4: Ramp #3 Override Active: 0= NO, 1=YES
Bit 5: Ramp #3 Override to High Limit:
0=Low Limit, 1= High Limit
Bit 6: Ramp #4 Override Active: 0= NO, 1=YES
Bit 7: Ramp #4 Override to High Limit:
0=Low Limit, 1= High Limit
Bit 8-15: Unused
640E 25615 Ramp #1 Output Scale High
R/W Floating Point in Engineering Units
Parameters accessible with Function Code 03, 06,10h
Ramp
80 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6410 25617 Ramp #2 Output Scale High
R/W Floating Point in Engineering Units
6412 25619 Ramp #3 Output Scale High
R/W Floating Point in Engineering Units
6414 25621 Ramp #4 Output Scale High
R/W Floating Point in Engineering Units
6416 25623 Ramp #1 Output Scale Low
R/W Floating Point in Engineering Units
6418 25625 Ramp #2 Output Scale Low
R/W Floating Point in Engineering Units
641A 25627 Ramp #3 Output Scale Low
R/W Floating Point in Engineering Units
641C 25629 Ramp #4 Output Scale Low
R/W Floating Point in Engineering Units
641E 25631 Ramp #1 Input Limit High
R/W Floating Point in Engineering Units
6420 25633 Ramp #2 Input Limit High
R/W Floating Point in Engineering Units
6422 25635 Ramp #3 Input Limit High
R/W Floating Point in Engineering Units
6424 25637 Ramp #4 Input Limit High
R/W Floating Point in Engineering Units
6426 25639 Ramp #1 Input Limit Low
R/W Floating Point in Engineering Units
6428 25641 Ramp #2Input Limit Low
R/W Floating Point in Engineering Units
642A 25643 Ramp #3Input Limit Low
R/W Floating Point in Engineering Units
642C 25645 Ramp #4Input Limit Low
R/W Floating Point in Engineering Units
Parameters accessible with Function Code 03, 06,10h
Hand/OFF/Auto Control
Revision 14 ControlEdge HC900 Controller Communications User Guide 81 April 2018
6.14 Hand/OFF/Auto Control
Summary
This table contains Hand/Off/Auto Map addresses of HOA #1.
See the HOA Register Maps Table 6-1 for starting and ending addresses (hex) for Hand/Off/Auto #2
through Hand/Off/Auto #16 Map Addresses.
The Modbus HOA number address for a HOA can also be obtained from the Process Control Designer
printout of "Block Modbus Addresses".
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point)
Writes – Function Code 6 for presetting an integer value
For custom addresses view or print a report in HC Designer.
Table 6-24 HOA Control Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6600 26113 Status R Bit Packed
Bits 0 – 3: Hand-Off-Auto State Bit 0: Off : 0=NO, 1=YES Bit 1: Hand: 0=NO, 1=YES Bit 2: Auto: 0=NO, 1=YES Bit 3: Bypass: 0=NO, 1=YES
Bit 4: Request Output 0 = OFF, 1 = ON
Bit 5: Local Source ON: 0=NO, 1=YES
Bit 6: Remote Source ON: 0=NO, 1=YES
Bit 7: Local and Remote ON: 0=NO, 1=YES
Bit 7-15: Unused
6601 26114 Remote Off-state Change Request
W Unsigned 16 Integer
Data Ignored
6602 26115 Remote Hand-state Change Request
W Unsigned 16 Integer
Data Ignored
6603 26116 Remote Auto-state Change Request
W Unsigned 16 Integer
Data Ignored
6604 26117 Local Source W Unsigned 16 Integer
Data Ignored
6605 26118 Remote Source W Unsigned 16 Integer
Data Ignored
6606 26119 Local and Remote Source W Unsigned 16 Integer
Data Ignored
Parameters accessible with Function Code 03, 06,10h
Alternator
82 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.15 Alternator
Summary
This section contains addresses for the Alternator #1group.
See the Alternator Register Maps in Table 6-1 for starting and ending addresses (hex) for Alternator #2
through Alternator #16 Map Addresses.
The Modbus Alternator number address for an Alternator can also be obtained from the Process Control
Designer report.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )
Writes – Function Code 6 for presetting an integer value
ATTENTION
Output Order Sequence registers must be written in a single transaction. Duplicate sequence values (1-16)
are not permitted.
For custom addresses view or print a report in HC Designer.
Table 6-25 Alternator Parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6700 26369 Alternator Status R Bit Packed
Bit 0: Enable: 0=NO, 1=YES
Bit 1: Low Capacity
0=Meeting Capacity, 1=Low Capacity
Bit 2-15: Unused
6701 26370 Device Ready (#1-16) R Bit Packed:
Bit 0: Device #1 Ready: 0=NO, 1=YES
Bit 1: Device #2 Ready: 0=NO, 1=YES
Bit 2: Device #3 Ready: 0=NO, 1=YES
Bit 3: Device #4 Ready: 0=NO, 1=YES
Bit 4: Device #5 Ready: 0=NO, 1=YES
Bit 5: Device #6 Ready: 0=NO, 1=YES
Bit 6: Device #7 Ready: 0=NO, 1=YES
Bit 7: Device #8 Ready: 0=NO, 1=YES
Bit 8: Device #9 Ready: 0=NO, 1=YES
Bit 9: Device #10 Ready: 0=NO, 1=YES
Bit 10: Device #11 Ready: 0=NO, 1=YES
Bit 11: Device #12 Ready: 0=NO, 1=YES
Bit 12: Device #13 Ready: 0=NO, 1=YES
Bit 13: Device #14 Ready: 0=NO, 1=YES
Bit 14: Device #15 Ready: 0=NO, 1=YES
Bit 15: device #16 Ready: 0=NO, 1=YES
Parameters accessible with Function Code 03, 06,10h
Alternator
Revision 14 ControlEdge HC900 Controller Communications User Guide 83 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6702 26371 Input Status #1-8 R Bit Packed:
Bit 0: Input #1 Enable: 0=NO, 1=YES
Bit 1: Input #1 ON: 0=OFF, 1=ON
Bit 2: Input #2 Enable: 0=NO, 1=YES
Bit 3: Input #2 ON: 0=OFF, 1=ON
Bit 4: Input #3 Enable: 0=NO, 1=YES
Bit 5: Input #3 ON: 0=OFF, 1=ON
Bit 6: Input #4 Enable: 0=NO, 1=YES
Bit 7: Input #4 ON: 0=OFF, 1=ON
Bit 8: Input #5 Enable: 0=NO, 1=YES
Bit 9: Input #5 ON: 0=OFF, 1=ON
Bit 10: Input #6 Enable: 0=NO, 1=YES
Bit 11: Input #6 ON: 0=OFF, 1=ON
Bit 12: Input #7 Enable: 0=NO, 1=YES
Bit 13: Input #7 ON: 0=OFF, 1=ON
Bit 14: Input #8 Enable: 0=NO, 1=YES
Bit 15: Input #8 ON: 0=OFF, 1=ON
6703 26372 Input Status #9-16 R Bit Packed:
Bit 0: Input #9 Enable: 0=NO, 1=YES
Bit 1: Input #9 ON: 0=OFF, 1=ON
Bit 2: Input #10 Enable: 0=NO, 1=YES
Bit 3: Input #10 ON: 0=OFF, 1=ON
Bit 4: Input #11 Enable: 0=NO, 1=YES
Bit 5: Input #11 ON: 0=OFF, 1=ON
Bit 6: Input #12 Enable: 0=NO, 1=YES
Bit 7: Input #12 ON: 0=OFF, 1=ON
Bit 8: Input #13 Enable: 0=NO, 1=YES
Bit 9: Input #13 ON: 0=OFF, 1=ON
Bit 10: Input #14 Enable: 0=NO, 1=YES
Bit 11: Input #14 ON: 0=OFF, 1=ON
Bit 12: Input #15 Enable: 0=NO, 1=YES
Bit 13: Input #15 ON: 0=OFF, 1=ON
Bit 14: Input #16 Enable: 0=NO, 1=YES
Bit 15: Input #16 ON: 0=OFF, 1=ON
Parameters accessible with Function Code 03, 06,10h
Alternator
84 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6704 26373 Output Status #1-4 R Bit Packed:
Bit 0: Output #1 Enable: 0=NO, 1=YES
Bit 1: Output #1 Used: 0=NO, 1=YES
Bit 2: Output #1 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #2 Enable: 0=NO, 1=YES
Bit 5: Output #2 Used: 0=NO, 1=YES
Bit 6: Output #2 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #3 Enable: 0=NO, 1=YES
Bit 9: Output #3 Used: 0=NO, 1=YES
Bit 10: Output #3 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #4 Enable: 0=NO, 1=YES
Bit 13: Output #4 Used: 0=NO, 1=YES
Bit 14: Output #4 ON: 0=OFF, 1=ON
Bit 15: Unused
6705 26374 Output Status #5-8 R Bit Packed:
Bit 0: Output #5 Enable: 0=NO, 1=YES
Bit 1: Output #5 Used: 0=NO, 1=YES
Bit 2: Output #5 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #6 Enable: 0=NO, 1=YES
Bit 5: Output #6 Used: 0=NO, 1=YES
Bit 6: Output #6 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #7 Enable: 0=NO, 1=YES
Bit 9: Output #7 Used: 0=NO, 1=YES
Bit 10: Output # ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #8 Enable: 0=NO, 1=YES
Bit 13: Output #8 Used: 0=NO, 1=YES
Bit 14: Output # ON: 0=OFF, 1=ON
Bit 15: Unused
Parameters accessible with Function Code 03, 06,10h
Alternator
Revision 14 ControlEdge HC900 Controller Communications User Guide 85 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6706 26375 Output Status #9-12 R Bit Packed:
Bit 0: Output #9 Enable: 0=NO, 1=YES
Bit 1: Output #9 Used: 0=NO, 1=YES
Bit 2: Output #9 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output #10 Enable: 0=NO, 1=YES
Bit 5: Output #10 Used: 0=NO, 1=YES
Bit 6: Output #10 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #11 Enable: 0=NO, 1=YES
Bit 9: Output # Used: 0=NO, 1=YES
Bit 10: Output #11 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #12 Enable: 0=NO, 1=YES
Bit 13: Output #12 Used: 0=NO, 1=YES
Bit 14: Output #12 ON: 0=OFF, 1=ON
Bit 15: Unused
6707 26376 Output Status #13-16 R Bit Packed:
Bit 0: Output #13 Enable: 0=NO, 1=YES
Bit 1: Output #13 Used: 0=NO, 1=YES
Bit 2: Output #13 ON: 0=OFF, 1=ON
Bit 3: Unused
Bit 4: Output # Enable: 0=NO, 1=YES
Bit 5: Output #14 Used: 0=NO, 1=YES
Bit 6: Output #14 ON: 0=OFF, 1=ON
Bit 7: Unused
Bit 8: Output #15 Enable: 0=NO, 1=YES
Bit 9: Output #15 Used: 0=NO, 1=YES
Bit 10: Output #15 ON: 0=OFF, 1=ON
Bit 11: Unused
Bit 12: Output #16 Enable: 0=NO, 1=YES
Bit 13: Output #16 Used: 0=NO, 1=YES
Bit 14: Output #16 ON: 0=OFF, 1=ON
Bit 15: Unused
6708 26377 Request Style R Bit Packed:
Bit 0: Direct: 0=NO, 1=YES
Bit 1: Rotary: 0=NO, 1=YES
Bit 2: FOFO: 0=NO, 1=YES
Bit 3: Fixed: 0=NO, 1=YES
Bit 4-15: Unused
6709 26378 Direct Request W Unsigned 16 Integer
Data Ignored
670A 26379 Rotary Request W Unsigned 16 Integer
Data Ignored
670B 26380 First on/First off Request
W Unsigned 16 Integer
Data Ignored
670C 26381 Fixed Request W Unsigned 16 Integer
Data Ignored
Parameters accessible with Function Code 03, 06,10h
Alternator
86 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
670D 26382 Advance Request W This does not apply if current style is Direct or if Advance Active configuration parameter is set to OFF
Unsigned 16 Integer
Data Ignored
670E 26383 Input Count R Floating Point in Counts
6710 26385 Output On-Delay R/W Floating Point in Seconds
6712 26387 Output Off-Delay R/W Floating Point in Seconds
6714 26389 Input Enable (1-16) R/W Bit Packed:
Bit 0: Device #1 Enable: 0=NO, 1=YES
Bit 1: Device #2 Enable: 0=NO, 1=YES
Bit 2: Device #3 Enable: 0=NO, 1=YES
Bit 3: Device #4 Enable: 0=NO, 1=YES
Bit 4: Device #5 Enable: 0=NO, 1=YES
Bit 5: Device #6 Enable: 0=NO, 1=YES
Bit 6: Device #7 Enable: 0=NO, 1=YES
Bit 7: Device #8 Enable: 0=NO, 1=YES
Bit 8: Device #9 Enable: 0=NO, 1=YES
Bit 9: Device #10 Enable: 0=NO, 1=YES
Bit 10: Device #11 Enable: 0=NO, 1=YES
Bit 11: Device #12 Enable: 0=NO, 1=YES
Bit 12: Device #13 Enable: 0=NO, 1=YES
Bit 13: Device #14 Enable: 0=NO, 1=YES
Bit 14: Device #15 Enable: 0=NO, 1=YES
Bit 15: Device #16 Enable: 0=NO, 1=YES
6715 26390 Output Enable (1-16) R/W Bit Packed:
Bit 0: Device #1 Enable: 0=NO, 1=YES
Bit 1: Device #2 Enable: 0=NO, 1=YES
Bit 2: Device #3 Enable: 0=NO, 1=YES
Bit 3: Device #4 Enable: 0=NO, 1=YES
Bit 4: Device #5 Enable: 0=NO, 1=YES
Bit 5: Device #6 Enable: 0=NO, 1=YES
Bit 6: Device #7 Enable: 0=NO, 1=YES
Bit 7: Device #8 Enable: 0=NO, 1=YES
Bit 8: Device #9 Enable: 0=NO, 1=YES
Bit 9: Device #10 Enable: 0=NO, 1=YES
Bit 10: Device #11 Enable: 0=NO, 1=YES
Bit 11: Device #12 Enable: 0=NO, 1=YES
Bit 12: Device #13 Enable: 0=NO, 1=YES
Bit 13: Device #14 Enable: 0=NO, 1=YES
Bit 14: Device #15 Enable: 0=NO, 1=YES
Bit 15: Device #16 Enable: 0=NO, 1=YES
6716 26391 Output Order Sequence #1
R Unsigned 16 integer
6717 26392 Output Order Sequence #2
R Unsigned 16 integer
6718 26393 Output Order Sequence #3
R Unsigned 16 integer
6719 26394 Output Order Sequence #4
R Unsigned 16 integer
Parameters accessible with Function Code 03, 06,10h
Alternator
Revision 14 ControlEdge HC900 Controller Communications User Guide 87 April 2018
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
671A 26395 Output Order Sequence #5
R Unsigned 16 integer
671B 26396 Output Order Sequence #6
R Unsigned 16 integer
671C 26397 Output Order Sequence #7
R Unsigned 16 integer
671D 26398 Output Order Sequence #8
R Unsigned 16 integer
671E 26399 Output Order Sequence #9
R Unsigned 16 integer
671F 26400 Output Order Sequence #10
R Unsigned 16 integer
6720 26401 Output Order Sequence #11
R Unsigned 16 integer
6721 26402 Output Order Sequence #12
R Unsigned 16 integer
6722 26403 Output Order Sequence #13
R Unsigned 16 integer
6723 26404 Output Order Sequence #14
R Unsigned 16 integer
6724 26405 Output Order Sequence #15
R Unsigned 16 integer
6725
26406 Output Order Sequence #16
R Unsigned 16 integer
Parameters accessible with Function Code 03, 06,10h
Device Control
88 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
6.16 Device Control
Summary
This table contains addresses for the Device Control group #1.
See the Device Control Register Maps in Table 6-1 for starting and ending addresses (hex) for Device
Control #2 through Device Control #16 Map Addresses.
The Modbus Device Control number address for a Device Control can also be obtained from the Process
Control Designer report.
Function Code Support:
Reads – Function Code 3
Writes – Function Code 16 (10 hex) for preset of multiple registers (e.g., for floating point )
Writes – Function Code 6 for presetting an integer value
For custom addresses view or print a report in HC Designer.
Table 6-26 Device Control parameters
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
6B00 27393 Reset Request W Unsigned 16 Integer
Data Ignored
6B01 27394 Status Indicator R Bit Packed
Bits 0 – 6: Device Control State
Bit 0: Ready: 0=NO, 1=YES
Bit 1: Prestart: 0=NO, 1=YES
Bit 2: Starting: 0=NO, 1=YES
Bit 3: Running: 0=NO, 1=YES
Bit 4: Stopping: 0=NO, 1=YES
Bit 5: Disabled: 0=NO, 1=YES
Bit 6: Failed: 0=NO, 1=YES
Bit 7: Run Request Input State; 0=OFF, 1=ON
Bit 8: Device Feedback Started; 0=NO, 1=YES
Bit 9: Device Failed; 0=NO, 1=YES
Bit 10: Automatic Reset; 0=Manual, 1=Auto
Bit 11-15: Unused
6B02 27395 Remaining Delay Time
R Floating Point in Seconds
6B04 27397 Start Delay R/W Floating Point in Seconds
6B06 27399 Stop Delay R/W Floating Point in Seconds
6B08 27401 Feedback Fail Delay R/W Floating Point in Seconds
Parameters accessible with Function Code 03, 06,10h
User Defined Signals and Variables
Revision 14 ControlEdge HC900 Controller Communications User Guide 89 April 2018
6.17 User Defined Signals and Variables
Each register can be assigned to a signal tag or variable defined in a function block diagram. The data type is
configurable to be floating-point, signed-16, unsigned-16, signed-32, or unsigned-32. Floating point, signed-32, and
unsigned-32 must start on an even hex address. 32-bit data uses the same byte-order format as defined for the port’s
double-register format. Writing a non-zero to a digital variable will set the variable to ON regardless of the data type.
Single register writes to 32-bit digital variables are permitted. Integer data is scaled based on the number of decimal
places defined for the variable/signal.
For custom addresses view or print a report in HC Designer.
Table 6-27 User Defined Registers
Fixed
Address
(hex)
Fixed
Register
(decimal)
Parameter Name Access Notes
B000 to B3E7
45057 to 46056
User defined signal or variable
Signal: R
Variable: R/W
Read only if a signal tag
Read/write if a variable
6.18 Custom map parameters
These parameters are available only if you are building a custom map, that is, for configuration versions 4.0 and
later. Note that parameters elsewhere in section 6 are also available for the custom map.
For custom addresses view or print a report in HC Designer.
Table Page
Table 6-28 Custom map Loop parameters 90
Table 6-29 Custom map Push Button and Four Selector Switch parameters 90
Table 6-30 Custom map AGA Gross parameters 91
Table 6-31 Custom map AGA Detail parameters 91
Table 6-32 Custom map Calendar Event parameters 92
Table 6-33 Custom map XYR5000 Base Station block parameters 96
Table 6-34 Custom map XYR5000 Transmitter block parameters 96
Table 6-35 Custom map XYR6000 Transmitter block parameters 97
Table 6-36 Custom map UDC Loop block parameters 97
Table 6-37 Custom map UDC Loop 2 block parameters 98
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
90 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Table 6-28 Custom map Loop parameters
Parameter Name Loop type Access Notes
PID On/
Off
Carb 3Pos AMB
Accutune III Selection R/W Integer:
0 – disable
1 – limit cycle
2 – SP tuning
SP Change Steps R/W Float in the range of 5% to 15%
SP Step Direction Integer:
0 = UP
1 = DOWN
PV Adabtive Enable/Disable
R/W Integer:
0 = Disable
1 = Enable
Autotune Error R/W 0=Tune Not Ready or in Wait State
1=Tune Ready
2=Tune Running
3=Failed Process Identification – SP Tune
4=SP Error – SP Tune
5=Bad Kpg – SP Tune
6=Failed Output Limit – SP Tune
7=Failed Minimum PV – SP Tune
8=PV Adaptive Running
9=Tuning Aborted
AutoManual LocalRemote Mode
R/W
R/W
R/W
R
R
R/W
Unsigned 16
0.0 = LSP MAN
1.0 = LSP AUTO
2.0 = RSP AUTO
4.0 = LSP IMAN or RSP IMAN
5.0 = LSP LO or RSP LO
6.0 = RSP_MAN
Table 6-29 Custom map Push Button and Four Selector Switch parameters
Parameter Name Access Notes
Button F1 W Integer: Write 1 to “push” the button
Button F2 W Integer: Write 1 to “push” the button
Button F3 W Integer: Write 1 to “push” the button
Button F4 W Integer: Write 1 to “push” the button
Bank A State R/W Integer in the range of 1 to 4
Bank B State R/W Integer in the range of 1 to 4
Bank C State R/W Integer in the range of 1 to 4
Bank D State R/W Integer in the range of 1 to 4
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
Revision 14 ControlEdge HC900 Controller Communications User Guide 91 April 2018
Table 6-30 Custom map AGA Gross parameters
Parameter Name Access Notes
Copy Entered Gas Vals Local R/W FLOAT 32 BIT
CO2 Entered R/W FLOAT 32 BIT
Hydrogen Entered R/W FLOAT 32 BIT
CO Entered R/W FLOAT 32 BIT
Method2 Nitrogen Entered R/W FLOAT 32 BIT
TB R/W FLOAT 32 BIT
PB R/W FLOAT 32 BIT
Use online Gas Analyzer Vals R/W FLOAT 32 BIT
Override Range Error R/W FLOAT 32 BIT
Method Used R/W FLOAT 32 BIT
Gas Rel Density R/W FLOAT 32 BIT
Rel Density Ref Temp R/W FLOAT 32 BIT
Rel Density Ref Press R/W FLOAT 32 BIT
Method1 Heat Val R/W FLOAT 32 BIT
Method1 Cal Ref Temp R/W FLOAT 32 BIT
Method1 Cal Ref Press R/W FLOAT 32 BIT
Method1 Comb Ref Temp R/W FLOAT 32 BIT
CO2 LCL R FLOAT 32 BIT
Hydrogen LCL R FLOAT 32 BIT
CO LCL R FLOAT 32 BIT
Method2 Nitrogen LCL R FLOAT 32 BIT
Table 6-31 Custom map AGA Detail parameters
Parameter Name Access Notes
Copy Entered Gas Vals Local R/W FLOAT 32 BIT
Methane Entered R/W FLOAT 32 BIT
Nitrogen Entered R/W FLOAT 32 BIT
CO2 Entered R/W FLOAT 32 BIT
Ethane Entered R/W FLOAT 32 BIT
Propane Entered R/W FLOAT 32 BIT
H2O Entered R/W FLOAT 32 BIT
H2S Entered R/W FLOAT 32 BIT
Hydrogen Entered R/W FLOAT 32 BIT
CO Entered R/W FLOAT 32 BIT
Oxygen Entered R/W FLOAT 32 BIT
I-Butane Entered R/W FLOAT 32 BIT
N-Butane Entered R/W FLOAT 32 BIT
I-Pentane Entered R/W FLOAT 32 BIT
N-Pentane Entered R/W FLOAT 32 BIT
Hexane Entered R/W FLOAT 32 BIT
Heptane Entered R/W FLOAT 32 BIT
Octane Entered R/W FLOAT 32 BIT
Nonane Entered R/W FLOAT 32 BIT
Decane Entered R/W FLOAT 32 BIT
Helium Entered R/W FLOAT 32 BIT
Argon Entered R/W FLOAT 32 BIT
TB R/W FLOAT 32 BIT
PB R/W FLOAT 32 BIT
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
92 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Parameter Name Access Notes
Use online Gas Analyzer Vals R/W FLOAT 32 BIT
Override Range Error R/W FLOAT 32 BIT
Methane LCL R FLOAT 32 BIT
Nitrogen LCL R FLOAT 32 BIT
CO2 LCL R FLOAT 32 BIT
Ethane LCL R FLOAT 32 BIT
Propane LCL R FLOAT 32 BIT
H2O LCL R FLOAT 32 BIT
H2S LCL R FLOAT 32 BIT
Hydrogen LCL R FLOAT 32 BIT
CO LCL R FLOAT 32 BIT
Oxygen LCL R FLOAT 32 BIT
I-Butane LCL R FLOAT 32 BIT
N-Butane LCL R FLOAT 32 BIT
I-Pentane LCL R FLOAT 32 BIT
N-Pentane LCL R FLOAT 32 BIT
Hexane LCL R FLOAT 32 BIT
Heptane LCL R FLOAT 32 BIT
Octane LCL R FLOAT 32 BIT
Nonane LCL R FLOAT 32 BIT
Decane LCL R FLOAT 32 BIT
Helium LCL R FLOAT 32 BIT
Argon LCL R FLOAT 32 BIT
Table 6-32 Custom map Calendar Event parameters
Parameter Name Access Notes
SetPoint Request R UNSIGNED 16 BIT 1 - 5
Display Event Type 1
Thru
Display Event Type 8
R UNSIGNED 16 BIT 0 = disable 1 = 5 day week 2 = 7 day week 3 = day of week 4 = monthly 5 = yearly
Display Hour 1
Thru
Display Hour 8
R UNSIGNED 16 BIT 0 - 23
Display Minute 1
Thru
Display Minute 8
R UNSIGNED 16 BIT
0 - 59
Display Month 1
Thru
Display Month 8
R UNSIGNED 16 BIT
1 - 12
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
Revision 14 ControlEdge HC900 Controller Communications User Guide 93 April 2018
Parameter Name Access Notes
Display Day 1
Thru
Display Day 8
R UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Event Type Grp-1 Evt-1
Thru
Event Type Grp-1 Evt-8
R/W UNSIGNED 16 BIT 0 = disable 1 = 5 day week 2 = 7 day week 3 = day of week 4 = monthly 5 = yearly
Event Type Grp-2 Evt-1
Thru
Event Type Grp-2 Evt-8
R/W UNSIGNED 16 BIT 0 = disable 1 = 5 day week 2 = 7 day week 3 = day of week 4 = monthly 5 = yearly
Event Type Grp-3 Evt-1
Thru
Event Type Grp-3 Evt-8
R/W UNSIGNED 16 BIT 0 = disable 1 = 5 day week 2 = 7 day week 3 = day of week 4 = monthly 5 = yearly
Event Type Grp-4 Evt-1
Thru
Event Type Grp-4 Evt-8
R/W UNSIGNED 16 BIT 0 = disable 1 = 5 day week 2 = 7 day week 3 = day of week 4 = monthly 5 = yearly
Event Type Grp-5 Evt-1
Thru
Event Type Grp-5 Evt-8
R/W UNSIGNED 16 BIT 0 = disable 1 = 5 day week 2 = 7 day week 3 = day of week 4 = monthly 5 = yearly
Event Hour Grp-1 Evt-1
Thru
Event Hour Grp-1 Evt-8
R/W UNSIGNED 16 BIT 0 - 23
Event Hour Grp-2 Evt-1
Thru
Event Hour Grp-2 Evt-8
R/W UNSIGNED 16 BIT 0 - 23
Event Hour Grp-3 Evt-1
Thru
Event Hour Grp-3 Evt-8
R/W UNSIGNED 16 BIT 0 - 23
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
94 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Parameter Name Access Notes
Event Hour Grp-4 Evt-1
Thru
Event Hour Grp-4 Evt-8
R/W UNSIGNED 16 BIT 0 - 23
Event Hour Grp-5 Evt-1
Thru
Event Hour Grp-5 Evt-8
R/W UNSIGNED 16 BIT 0 - 23
Event Min Grp-1 Evt-1
Thru
Event Min Grp-1 Evt-8
R/W UNSIGNED 16 BIT
0 - 59
Event Min Grp-2 Evt-1
Thru
Event Min Grp-2 Evt-8
R/W UNSIGNED 16 BIT
0 - 59
Event Min Grp-3 Evt-1
Thru
Event Min Grp-3 Evt-8
R/W UNSIGNED 16 BIT
0 - 59
Event Min Grp-4 Evt-1
Thru
Event Min Grp-4 Evt-8
R/W UNSIGNED 16 BIT
0 - 59
Event Min Grp-5 Evt-1
Thru
Event Min Grp-5 Evt-8
R/W UNSIGNED 16 BIT
0 - 59
Event Month Grp-1 Evt-1
Thru
Event Month Grp-1 Evt-8
R/W UNSIGNED 16 BIT
1 - 12
Event Month Grp-2 Evt-1
Thru
Event Month Grp-2 Evt-8
R/W UNSIGNED 16 BIT
1 - 12
Event Month Grp-3 Evt-1
Thru
Event Month Grp-3 Evt-8
R/W UNSIGNED 16 BIT
1 - 12
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
Revision 14 ControlEdge HC900 Controller Communications User Guide 95 April 2018
Parameter Name Access Notes
Event Month Grp-4 Evt-1
Thru
Event Month Grp-4 Evt-8
R/W UNSIGNED 16 BIT
1 - 12
Event Month Grp-5 Evt-1
Thru
Event Month Grp-5 Evt-8
R/W UNSIGNED 16 BIT
1 - 12
Event Day Grp-1 Evt-1
Thru
Event Day Grp-1 Evt-8
R/W UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-2 Evt-1
Thru
Event Day Grp-2 Evt-8
R/W UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-3 Evt-1
Thru
Event Day Grp-3 Evt-8
R/W UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-4 Evt-1
Thru
Event Day Grp-4 Evt-8
R/W UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Event Day Grp-5 Evt-1
Thru
Event Day Grp-5 Evt-8
R/W UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Special Day Mode R/W UNSIGNED 16 BIT 0 = disable outputs 1 = use alternate time
Special Day Out 1
Thru
Special Day Out 8
R/W FLOAT 32 BIT 0 = normal behavior 1 = do what Special Day mode specifies
Special Day Day-1
Thru
Special Day Day-16
R/W UNSIGNED 16 BIT Day of month: 1 – 31 Day of week: 1 – 7 where 1 = Sunday
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
96 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Parameter Name Access Notes
Special Day Month-1
Thru
Special Day Month-16
R/W UNSIGNED 16 BIT
1 - 12
Special Day Alt Hour-1
Thru
Special Day Alt Hour-8
R/W UNSIGNED 16 BIT 0 - 23
Special Day Alt Min-1
Thru
Special Day Alt Min-8
R/W UNSIGNED 16 BIT
0 - 59
Table 6-33 Custom map XYR5000 Base Station block parameters
Parameter Name Access Notes
Base Radio Status R unsigned 16
Expected Transmitter Count R unsigned 16
Transmitter Count R unsigned 16
Transmitter Status 1-16 R unsigned 16
Transmitter Status 17-32 R unsigned 16
Transmitter Status 33-48 R unsigned 16
Transmitter Status 49-64 R unsigned 16
Transmitter Status 65-80 R unsigned 16
Transmitter Status 81-96 R unsigned 16
Transmitter Status 97-100 R unsigned 16
Table 6-34 Custom map XYR5000 Transmitter block parameters
Parameter Name Access Notes
Primary Sensor R float 32
Secondary Sensor R float 32
Tertiary Sensor R float 32
Transmitter Online R unsigned 16
Low Battery R unsigned 16
Alarm Condition R unsigned 16
Sensor Error R unsigned 16
Sensor Overload R unsigned 16
System Error R unsigned 16
Switch Input 1 Closed R unsigned 16
Switch Input 2 Closed R unsigned 16
Square Root Function R unsigned 16
Device Type R float 32
Device Status R float 32
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
Revision 14 ControlEdge HC900 Controller Communications User Guide 97 April 2018
Table 6-35 Custom map XYR6000 Transmitter block parameters
Parameter Name Access Notes
PV1 R float 32
PV2 R float 32
PV3 R float 32
PV4 R float 32
Elec Failure R unsigned 16
Mech Failure R unsigned 16
Input Failure R unsigned 16
Output Failure R unsigned 16
Low Battery R unsigned 16
External Power R unsigned 16
Config Error R unsigned 16
Calibration Error R unsigned 16
Radio Error R unsigned 16
Memory Error R unsigned 16
Firmware Error R unsigned 16
Watchdog Error R unsigned 16
Diagnostic R unsigned 16
Device Status R unsigned 32
Table 6-36 Custom map UDC Loop block parameters
Parameter Name Access Notes
Loop1 PV R float 32
Loop1 WSP R float 32
Loop1 Output R/W float 32
Loop1 LSP1 R/W float 32
Loop1 LSP2 R/W float 32
Loop1 LSP3 R/W float 32
Loop1 LSP4 R/W float 32
Loop1 Mode Auto/Manual W unsigned 16
Loop1 Mode Local/Remote W unsigned 16
Loop1 Mode A/M/L/R R unsigned 16
Loop1 Ramp SP R/W float 32
Loop1 LSP Select R/W unsigned 16
Parameters accessible with Function Code 03, 06,10h
Custom map parameters
98 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
Table 6-37 Custom map UDC Loop 2 block parameters
Parameter Name Access Notes
Loop2 PV R float 32
Loop2 WSP R float 32
Loop2 OUT R/W float 32
Loop2 Mode A/M/L/R R unsigned 16
Loop2 LSP1 R/W float 32
Loop2 LSP2 R/W float 32
Loop2 LSP3 R/W float 32
Loop2 LSP4 R/W float 32
Loop2 Auto/Manual W unsigned 16
Loop2 Local/Remote W unsigned 16
Loop2 Ramp SP R/W float 32
Loop2 LSP Select R/W unsigned 16
Index
Revision 14 ControlEdge HC900 Controller Communications User Guide 99 April 2018
Index
A
Advance, 59, 70, 75
Advance Next step, 76
Advance Request, 88
Alarm #1 SP #1, 49
Alarm #1 SP #2, 49
Alarm #2 SP #1, 50
Alarm #2 SP #2, 50
Alternator #1 Register Map, 84
Alternator Status, 84
Analog Input Value Register Map Addresses -
Function Code 03, 54
Analog input, access any channel with Function code
04, 32
Analog input, access channels 1-64 on only Rack 1
with Function code 03, 54
Anti-soot set point limit enable, 50
Auto/Manual State, 50
Auxiliary Output, 60, 76
B
Bias, 50
Block Modbus Address" report, 2
C
Carbon Potential block temperature, 49
Carbon Potential Dewpoint, 50
Current Program Number, 60, 69
Current Segment Events, 59, 69
Current Segment Number, 59, 69
Cycle Time for Analog Scan, 49, 50
D
Demand Tune Request, 50
Deviation, 50
Device Control #1 Register Map, 90
Device Ready, 84
Direct Request, 87
Direction, 49
Display High Range Limit, 60
Display Low Range Limit, 60
Downloading Setpoint Programs, 58
Downloading Setpoint Schedules, 67
E
Elapsed Sequence Time, 76
Enable/Disable Fuzzy, 50
Ethernet 10Base-T, 2
Ethernet 10Base-T Network Connections, 4
Ethernet Communications Setup, 3
Event1 Next step, 76
Event2 Next step, 76
Events, 62
Exception Codes, 40, 41
F
Feedback Fail Delay, 90
Feed-forward Gain, 50
First on/First off Request, 87
Fixed Map overview, 44
Fixed Request, 87
Floating Point Big Endian, 10
Floating Point Big Endian with byte-swapped, 10
Floating Point Little Endian, 10
Floating Point Little Endian with byte-swapped, 10
floating point value, 4
Force Single Coil, 17, 34
Function code 01, 20
Function code 02, 29
Function code 03, 30
Function code 04, 32
Function Code 05, 34
Function Code 06, 35
Function Code 08, 36
Function Code 16 (10h), 37
Function code 17 (11h), 38
Function Code Field, 40
Function Codes, 17
Furnace Factor, 50
G
Gain #1 (Prop Band #1 if active, 49
Gain #2 (Prop Band #2 if active), 49
Guaranteed Soak High, 60
Guaranteed Soak Limit, 69
Guaranteed Soak Low, 60
Guaranteed Soak Type, 61
Index
100 ControlEdge HC900 Controller Communications User Guide Revision 14 April 2018
H
HC900 AI Address Mapping supported by Function
Code 03, 30
HC900 AI Address Mapping supported by Function
Code 04, 32
HOA Control #1 Register Map, 83
Hold, 59, 70, 75
I
IEEE 32-bit Floating Point Register, 7
Illegal Data Address, 41
Illegal Data Value, 41
Illegal Function, 41
Input Count, 88
Input Limit High, 82
Input Limit Low, 82
Input Status, 85
Interface Preparation, 2
J
Jog Segment, 61, 69
Jog to step number, 75
L
Latch Delay, 80
Load both Sequence and Step numbers (Set), 75
Local and Remote Source, 83
Local Percent Carbon Monoxide, 50
Local Source, 83
Loop End, 61
Loop Start, 61
Loop Status, 51
Loop Values, 49
Loopback Message, 36
Loopback Test, 17
LSP #1, 50
LSP #2, 50
M
Mantissa and Exponent Combination, 8
Mantissa and Sign, 7
Manual Reset, 50
Miscellaneous Parameters, 48
Modbus Comm Digital I/O Channel to Address
Mapping - Rack #1, 22, 26
Modbus Double Register Format, 10
Modbus RTU Protocol within a TCP/IP Frame, 2
Modbus/TCP Double Register Format, 4
Modbus/TCP Interface, 2
Modbus/TCP Protocol, 2
N
Negative Acknowledge, 41
Number of Registers Allowable, 19
O
Object Addresses, 18
OFF Setpoint, 80
ON Setpoint, 79
On/Off Output Hysterisis, 50
Open Modbus/TCP Specification, 3
Output, 49
Output High Limit, 50
Output Low Limit, 50
Output Off-Delay, 88
Output On-Delay, 88
Output Order Sequence, 88
Output Scale High, 81
Output Scale Low, 82
Output Working Value, 50
Outputs, 76
Override Status, 81
P
Parameter Addressing, 3
Parameters accessible with function code 03, 06, 10h,
42
Percent Hydrogen, 50
Preset Multiple Registers, 17, 37
Preset Single Register, 17, 35
Previous/Next Interlock, 79
Program Elapsed Time, 59, 69
Program Save Request, 60
PV, 49, 81, 91, 92
PV High Range, 49
PV Low Range, 49
PV On/Off Comparison, 78
PV1, 78
PV2, 78
R
Ramp Default, 81
Ramp Lag Time, 81
Ramp or Soak value, 62
Ramp Output, 81
Ramp parameters, 81
Ramp Transfer Dn, 81
Ramp Transfer Up, 81
Ramp Units, 61
Ramp/Soak Segment, 62
Rate #1, 49
Rate #2, 50
Read Coil Status, 17, 20
Read Holding Registers, 17
Index
Revision 14 ControlEdge HC900 Controller Communications User Guide 101 April 2018
Read Input Registers, 17, 30
Read Input Status, 17, 29
Remaining Delay Time, 90
Remote Auto-state Change Request, 83
Remote Hand-state Change Request, 83
Remote Off-state Change Request, 83
Remote Set Point; SP2, 49
Remote Source, 83
Remote/Local Set Point State, 51
Repeats, 61
Report Device ID, 17, 38
Reserved Operands, 9
Reset, 60, 70, 75
Reset #1, 49
Reset #2, 50
Reset Request, 90
Restart Ramp Rate, 60
Rotary Request, 87
Run, 59, 75
S
Save current sequence request, 75
Schedule Save Request, 69
Scheduler Segment Addresses, 70
Scheduler Segment Register Map, 66
Scheduler Value Register Map, 66
Scheduler Value Register Map Addresses, 68
Segment Register Map Addresses, 66
Segment Time Remaining, 59, 69
Sequence number, 75
Sequence State addresses, 75
Sequence status, 76
Sequence Step addresses, 74
Sequencer Parameter addresses, 74
Sequencer Parameters, 75
Set Point Programmer, 57
Set Point Programmer Output, 59
Set Point Programmer parameters table, 59
Set Point State, 51
Setpoint programmer, how to determine address, 63
Signal Tag Addresses, 64
Signal Tags, 64
signals and variables, user defined, 91
Slave Device Busy, 41
Slave Device Failure, 41
Soak value for auxiliary output, 62
SP High Limit, 50
SP Low Limit, 50
SP Programmer Segment parameters, 62
SP Scheduler Addresses, 67
Stage #1-4 Override Status, 78
Stage parameters, 78
Start, 70
Start Delay, 90
Starting step number, 76
State, 76
State Number Step, 77
Status, 70, 83
Status Indicator, 90
Step jumped to on Jog, 75
Step Number, 75
Step Time, 76
Stop Delay, 90
T
Tag Information" report, 2
Telephone and Email Contacts, iii
third party software, 57, 66
Three Position Step Motor Deadband, 49
Three Position Step Motor Time, 50
Time Map Addresses, 56
Time Next step, 76
Time or Rate, 62
Time Remaining in current step, 76
Time units, 76
Time Units, 61, 70
Tune Set State, 51
U
Unlatch Delay, 80
Uploading Setpoint Programs, 58
Uploading Setpoint Schedules, 68
User Defined signals and variables, 91
V
Variable Addresses, 55
Variables (analog or digital), 55
W
Working Set Point, 49, 50
For more information To learn more about ControlEdge HC900,
visit www.honeywellprocess.com Or contact your Honeywell Account Manager
Process Solutions Honeywell
1250 W Sam Houston Pkwy S Houston, USA, TX 77042
Honeywell Control Systems Ltd Honeywell House, Skimped Hill Lane Bracknell, England, RG12 1EB
51-52-25-111, Rev.14 April 2018
2018 Honeywell International Inc.
Shanghai City Centre, 100 Jungi Road Shanghai, China 20061
www.honeywellprocess.com
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below.
ASIA PACIFIC
Honeywell Process Solutions,
(TAC) hfs-tac-
Australia Honeywell Limited Phone: +(61) 7-3846 1255 FAX: +(61) 7-3840 6481 Toll Free 1300-36-39-36 Toll Free Fax: 1300-36-04-70
China – PRC - Shanghai Honeywell China Inc. Phone: (86-21) 5257-4568 Fax: (86-21) 6237-2826
Singapore Honeywell Pte Ltd. Phone: +(65) 6580 3278 Fax: +(65) 6445-3033
South Korea Honeywell Korea Co Ltd Phone: +(822) 799 6114 Fax: +(822) 792 9015
EMEA
Honeywell Process Solutions,
Phone: + 80012026455 or +44 (0)1344 656000
Email: (Sales)
or
(TAC)
AMERICA’S
Honeywell Process Solutions,
Phone: (TAC) 1-800-423-9883 or 215/641-3610
(Sales) 1-800-343-0228
Email: (Sales)
or
(TAC)