151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
May 11, 2018 To All Contractors Bidding On the:
Harloe Elementary School Classrooms
Addendum No. Two is hereby made a part of the Contract Documents pertaining to the above project and shall be binding upon each entity submitting bids. It shall be the responsibility of each Contractor to notify the sub contractors, materialmen and suppliers concerning the contents of this Addendum as they specifically apply them. ITEM NO. 1: As a matter of clarification, the General Contractor shall prepare and file and obtain all local AHJ required permits and authorizations, including but not limited too: APCD, City of AG, PG&E and RWQCB for the work on this project. All fees to these entities will be paid by the District. Contractor shall coordinate permits, applications and other items with the District and Architect as support. ITEM NO. 2: The new electrical service to the site shall be installed under Halcyon Road by pit-boring. General Contractor shall coordinate all required encroachment permits and ROW access as well as furnishing and installing the new conduits described on the construction documents. ITEM NO. 3: Sheets SP-3 & C-2.0 ; the asphalt paving shown underneath the relocatable classrooms shall be omitted. Install Class II base to the noted elevations. All other utilities, grading etc. shall remain including the asphalt access in front of the relos and the ramps to the relos. The Class II base section shall be 6” min. over 12” compacted subgrade. Asphalt walkway remains 2” AC Paving over 4” Class II base. ITEM NO. 4: Sheets SP-1, general, and SP-3, note 03; The Contractor shall remove the chain link dugout fencing on the north side, paralleling the sidewalk and the return section. The existing backstop and west side dugout shall remain in place and be protected during construction. ITEM NO. 5: Sheet SP-3, the location of the relo classrooms are critical and must be set to allow 72” clear at the bottom of the access ramp. GC and Owner shall coordinate their efforts to ensure the proper location and clearances are maintained. ITEM NO. 6: Sheet SP-5; See attached exhibit for revisions to the accessible path of travel from the existing HC parking stalls to the building. ITEM NO. 7: Detail 4/AA-4, Install #4 smooth slip dowel at 12” oc across expansion joint. See attached detail. ITEM NO. 8: Specifications section 02740, Asphalt Paving; The exist spec shall be discarded. See attached revised specification for Asphalt Paving. ITEM NO. 9: Install new 8’-0” chain link fencing enclosures around new electrical transformers as shown on attached exhibits. See sheet E-101 for location of new transformers. ITEM NO.10: The District will furnish the 2 new transformers, the 2 disconnecting breakers and the distribution panelboard to the relocatable classrooms. The contractor shall transport the equipment from the District Facilities Maintenance yard to the site, and install per the construction documents. The contractor shall furnish and install all other electrical equipment as indicated on the plans and specs.
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
7/17
ITEM NO.11: See the attached Electrical addendum from Thoma Engineering revising sheets E-002, E-003, E-100, E-101, E-102 and E-103. The existing sheets shall be removed from the bid set and replaced accordingly with the sheets listed above.
End of Addendum No. 2
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
1 2" E
XP
AN
SIO
N J
OIN
T A
SO
CC
UR
S O
N S
ITE
PLA
N
4" T
HIC
K C
ON
CR
ETE
SLA
BW
/ #3
@ 2
4" O
.C. E
AC
H W
AY
18" M
IN. C
OM
PA
CTE
D E
NG
INE
ER
ED
FILL
. S
EE
SO
ILS
RE
PO
RT
4" M
IN. P
LAC
E A
ND
CO
MP
AC
TS
AN
D T
O M
IN. 9
5% O
F M
AX
DE
NS
ITY
#4 1
2" S
MO
OTH
DO
WE
LS @
24"
O.C
.
HA
RLO
E E
LEM
EN
TAR
Y A
DD
EN
DU
M #
1
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
9'-0"
Min.
3'-0"
3'-0"
8'-0"
3'-0
"
9'-0"
18'-0
"
Min.
18'-0
"
Min.
4'-0"
MIN.
3'-0
" O.C
.M
IN.
HA
RLO
E E
LEM
EN
TAR
Y A
DD
EN
DU
M #
1
INS
TALL
NE
W T
RU
NC
ATE
DD
OM
ES
ON
EX
ISTI
NG
CU
RB
RA
MP
.R
EFE
R T
O D
ETA
IL 2
ON
AA
-3.
EX
ISTI
NG
CO
NC
RE
TES
LAB
TO
RE
MA
IN
RE
MO
VE
EX
ISTI
NG
STR
UC
TUR
E
INS
TALL
NE
W C
ON
CR
ETE
CU
RB
RA
MP
& N
EW
TR
UN
CA
TED
DO
ME
SR
EFE
R T
O D
ETA
ILS
1 &
2 O
N A
A-3
.
EX
ISTI
NG
CO
NC
RE
TEC
UR
B T
O R
EM
AIN
RE
MO
VE
EX
ISTI
NG
PA
INTE
D C
RO
SS
WA
LKLI
NE
S
INS
TALL
NE
W T
RU
NC
ATE
DD
OM
ES
ON
EX
ISTI
NG
CU
RB
RA
MP
.R
EFE
R T
O D
ETA
IL 2
ON
AA
-3.
RE
-PA
INT
NE
W A
CC
ES
SIB
LEP
AR
KIN
G L
INE
S
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
3'-0"3'
-0"
HA
RLO
E E
LEM
EN
TAR
Y A
DD
EN
DU
M #
1
NE
W T
RA
NS
FOR
ME
RLO
CA
TIO
N O
N N
EW
HO
US
EK
EE
PIN
G P
AD
(RE
FER
TO
ELE
CTR
ICA
L S
HE
ETS
)
NE
W 8
'-0" T
ALL
CH
AIN
LIN
KFE
NC
E A
RO
UN
D N
EW
TR
AN
SFO
RM
ER
.R
EFE
R T
O D
ETA
IL 0
4 O
N A
A-5
.
NE
W D
OU
BLE
HIN
GE
D 8
'-0" T
ALL
CH
AIN
LIN
K G
ATE
WIT
H A
CC
ES
SFR
OM
SID
EW
ALK
. FI
NA
L G
ATE
WID
TH T
O B
E D
ETE
RM
INE
D.
RE
FER
TO
DE
TAIL
03
ON
AA
-5.
Harloe Elementary Addendum No. 2
151 West Branch Street; Suite E, Arroyo Grande CA 93420 P: 805.574.1550 F: 805.574.1553
6"
1'-0
"
1'-0"
1'-0
"
HA
RLO
E E
LEM
EN
TA
RY
AD
DE
ND
UM
#1
NE
W T
RA
NS
FO
RM
ER
LOC
AT
ION
ON
NE
WH
OU
SE
KE
EP
ING
PA
D (
RE
FE
R T
OE
LEC
TR
ICA
L S
HE
ET
S)
NE
W 8
'-0"
TA
LL C
HA
IN L
INK
FE
NC
E A
RO
UN
D N
EW
TR
AN
SF
OR
ME
R.
RE
FE
R T
O D
ET
AIL
04
ON
AA
-5.
NE
W 3
'-0"
WID
E X
8'-0
" T
ALL
CH
AIN
LIN
K G
AT
E W
ITH
AC
CE
SS
FR
OM
SID
EW
ALK
. F
INA
L G
AT
EW
IDT
H T
O B
E D
ET
ER
MIN
ED
.R
EF
ER
TO
DE
TA
IL 0
3 O
N A
A-5
.
CHECKED: PM
DRAWN BY: JM
PROJECT NO.:
May 11, 2018
PR
OJE
CT
T
IT
LE
RE
VIS
IO
NS
15
1 W
est B
ra
nch
S
tre
et; S
uite
E
Arro
yo
G
ra
nd
e, C
A 9
34
20
(8
05
) 5
74
-1
55
0
1 2 3 4
EXPIRES: 06/30/19
THOMA #17-8124
San Luis O
bispo, C
A 93406
3562 E
mpleo S
t.
TH
OM
A E
LE
CT
RIC
, IN
C.
Phone: (805) 543-3850
Fax: (805) 543-3829
SHEET TITLE:
A
R
E
T
M
A
.
E
C
F
NO. 10757
E
L
T
S
O
E
A
T
E
SI
GE
R
I
W
L
T
L
I
E
A
R
O
L
I
C
RT
I
L
F
CA
A
I
N
H
O
M
N
A
RE
E
G
I
N
O
R
P
D
N
A
OI
EF
SS
L
Lucia M
ar U
nified S
chool D
istrict
HA
RLO
E E
LE
ME
NT
AR
Y S
CH
OO
L
90
1 F
AIR
O
AK
S A
VE
NU
E, A
RR
OY
O G
RA
ND
E, C
A 9
34
20
AP
N #
0
77
-2
83
-0
02
20
18
.0
5.1
1
E-002
ELECTRICAL
SINGLE LINE
DIAGRAM
M
(E) "R"
120/208V, 250AMP, 3Ø, 4W
(E) "MSB"
120/208V, 600 AMP, 3Ø, 4W
REFERENCE NOTES
1. (N) ELECTRICAL DISTRIBUTION PANEL "MS", 1600A, 120/208V, 3PH, 4W,
65KAIC, PAD-MOUNTED, NEMA 3R SWITCHBOARD AS NEW SERVICE TO
CAMPUS. SEE SITE PLAN FOR LOCATION AND MOUNTING REQUIREMENTS.
PROVIDE NEW METER-MAIN AND BACK-FEED OLD MAIN SWITCHBOARD AS
SHOWN. (N) SWITCHBOARD SHALL BE SQUARE-D "I-LINE" TYPE.
2. (E) MAIN SWITCHBOARD 'MSB'. EC SHALL REMOVE COPPER JUMPER
BETWEEN NEUTRAL BUS AND EQUIPMENT GROUND BUS AT THIS LOCATION.
AFTER NEW ELECTRICAL DISTRIBUTION SYSTEM IS IN PLACE, REMOVE
EXISTING SECONDARY FEEDER AND SALVAGE METER TO PG&E AND
PROVIDE BLANK COVER.
3. NEW PRIMARY PG&E FEEDER. TRENCH AND BACKFILL PER PG&E
GREENBOOK.
4. EXISTING PANELS FOR RELOCATABLE CLASSROOM, AND FEEDER TO BE
REMOVED BACK TO SOURCE.
5. EXISTING PANEL "R", 120/208V, 3Ø, 4W, TO BE REMOVED AND SALVAGED
BACK TO DISTRICT.
6. (N) 400A, 120/208V, 3PH, 4W, 10KAIC, NEMA 1, WALL-MOUNTED DISTRIBUTION
PANEL INSIDE NEW MODULAR CLASSROOM WING. EC SHALL USE SQUARE-D
"I-LINE" TYPE DISTRIBUTION PANELBOARD. SEE ENLARGED FLOORPLANS
FOR LOCATION DETAILS AND MOUNTING INSTRUCTIONS.
7. (N) 400A, 120/208V, 3PH, 4W, 10KAIC, NEMA 3R, WALL-MOUNTED
DISTRIBUTION PANEL IN EQUIPMENT YARD OUTSIDE NEW MODULAR
CLASSROOM WING. EC SHALL USE SQUARE-D "I-LINE" TYPE DISTRIBUTION
PANELBOARD. SEE ENLARGED FLOORPLANS FOR LOCATION DETAILS AND
MOUNTING INSTRUCTIONS.
8. (N) SPLIT-BUS ELECTRICAL PANELS (CAPABLE OF LOAD DESEGREGATION)
PROVIDED BY MODULAR BUILDING SUPPLIER. SHOWN FOR REFERENCE
ONLY. EC SHALL PROVIDE CONDUIT AND CONDUCTORS FROM
DISTRIBUTION PANEL, AND CONNECT #6 AWG THWN FROM EQUIPMENT
GROUND BUS TO BUILDING STEEL AT EACH PANEL. REFER TO MODULAR
BUILDING SUPPLIER ELECTRICAL SHEETS FOR CONNECTIVITY DETAILS. EC
SHALL PROVIDE ARC-FLASH SIGNAGE AT EACH PANEL PER DETAIL 5/E-003.
9. (N) 100A, 120/208V, 3PH, 4W, NEMA 1 PANEL TO SERVE
TELECOMMUNICATIONS SPACE IN NEW MODULAR BUILDING.
10. (N) 400A, 120/208V, 3PH, 4W, NEMA 3R, 10KAIC RATED DISTRIBUTION PANEL
(SQUARED-D 'I-LINE') SURFACE MOUNTED TO BACKBOARD AT TEMPORARY
HOUSING RELOCATABLES. SEE SITE PLAN FOR DETAILS.
11. (N) ELECTRICAL PANELS PROVIDED WITH RELOCATABLE BUILDING. EC
SHALL PROVIDE CONDUIT AND CONDUCTORS PER SINGLE LINE DIAGRAM,
AND ROUTE PER SITE PLAN FOR NEW RELOCATABLE CLASSROOMS. FIELD
COORDINATE STUB-UP LOCATIONS BASED ON ACTUAL ELECTRICAL PANEL
PLACEMENT.
12. PROVIDE MEANS FOR REDUCING INCIDENT ARC-FAULT ENERGY PER CEC
240.87.
13. PROVIDE CONCRETE PAD FOR PG&E TRANSFORMER PER UTILITY
REQUIREMENTS.
14. PROVIDE REINFORCED CONCRETE PAD TO MOUNT SWITCH BOARD. REFER
TO DETAIL 5/E-303 AND 1/E-303 FOR PAD CONSTRUCTION REQUIREMENTS.
15. PROVIDE TELEPHONE OUTLET (OSP RATED CAT6 TERMINATED IN 1-PORT
BISCUIT) IN VESTIBULE OF SWITCH BOARD WITH 1" CONDUIT TO IDF ROOM
IN BUILDING "B".
16. (E) PULL-BOX WITH NAME AS NOTED, SEE E-100 AND E-101 FOR LOCATION
AND SIZE.
17. LOCATE EXISTING POWER SERVICE TO EQUIPMENT, DEMO CONDUCTORS
AND RE-CONNECT TO NEW MAIN SERVICE 'MS' AS SHOWN.
18. PANEL/FEEDER TO BE REMOVED.
19. (N) MODULAR SURGE PROTECTION DEVICE, RATINGS AS INDICATED,
INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS TO
MINIMIZED LEAD LENGTH.
20. (N) 60A/3P CIRCUIT BREAKER WITH (3) #6 AWG THWN, & (1) #6 GND SERVING
NEW SURGE PROTECTION DEVICE. VERIFY CIRCUIT BREAKER SIZE AND
WIRE SIZE WITH SERVING EQUIPMENT APPROVED SUBMITTALS PRIOR TO
PURCHASING EQUIPMENT.
21. (N) SPECIAL CONFIGURATION, 112.5KVA, NEMA 3R STEP-UP TRANSFORMER.
DRY-TYPE, 120/208V DELTA TO 480V DELTA. PAD-MOUNT ACCORDING TO
DETAIL 3/E-304. EC SHALL PROVIDE (1) SET OF SPARE FUSES.
22. (N) 112.5KVA, NEMA 3R, STEP-DOWN TRANSFORMER WITH LOCKABLE,
3-POLE, 200A-FRAME, 175A-TRIP, NEMA 3R 3-POLE ENCLOSED CIRCUIT
BREAKER MOUNTED ON TRANSFORMER SIDE. DRY-TYPE, 480V DELTA TO
120/208V WYE. PAD MOUNT ACCORDING TO DETAIL 3/E-304.
23. (N) 400A, 120/208V, 3-POLE ENCLOSED CIRCUIT BREAKER, WALL-MOUNTED
IN SAME LOCATION AS DEMO'D (E) 250A/3P DISCONNECT. EC SHALL
PROVIDE DEVICE WITH LOCKABLE HANDLE.
24. (N) PG&E #5 FLUSH IN-GRADE ELECTRICAL PULL-BOX WITH NAME AS NOTED,
SEE E-101 AND E-102 FOR LOCATIONS AND SIZES.
25. FAULT CURRENT INDICATED IN BRACKETS, BASED UPON 42KAIC PRESENT
AT (N) SERVICE 'MS'.
26. (N) ELECTRICAL PULL-BOX WITH NAME AS NOTED, SEE E-101 AND E-102 FOR
LOCATION AND SIZE.
27. (E) SEWER PUMP AND ASSOCIATED CIRCUIT BREAKER AND FEEDER. EC
SHALL COORDINATE WITH DISTRICT FOR REMOVAL OF CIRCUIT AND
EQUIPMENT DURING DEMO PHASE.
250A
3P
PANEL PANEL
PANEL PANEL PANEL PANEL PANEL
PANEL PANEL
1 1/2" C
(4) #3
2" C
(4) #4 T
W
(4) #2
2P
60A
2P
60A
2P
60A
3P
60A
PANEL
2P
60A
PANEL
2P
60A
PANEL
2P
60A
3P
225A
PULLBOXES
230
EXISTING
225 AMP DISTRIBUTION
PANEL @ SWITCHGEAR
ROOM IN 040
EXISTING PULLBOX AT
REAR OF RELOCATABLE
2" C; (4) #3/0
200 220
125AF
200AS
PANEL
210 '07 180 190
4" C
; (4) 250 M
CM
140 150 160
090
LOCATED OUTSIDE 210
080010B
070010A060050040030020
LOCATED IN 040
ELECTRICAL SINGLE LINE DIAGRAM
(E)
DISCONNECT
SWITCH IN
ELECTRICAL
ROOM
NOTE: EQUIPMENT SHOWN AS (E) IS EXISTING, (D) AS DEMO, (N) AS NEW.
EQUIPMENT NOT SHOWN AS (E) SHALL BE NEW.
(E) DISCONNECT
SWITCH IN
ELECTRICAL ROOM
TO BE REMOVED AND
REPLACED WITH (N)
'TDISC'
PANEL
RS
PANEL
RS
PANEL
RS
PANEL
RS
PANEL
RS
PANEL
RS
PANEL
RS
J
GF
IEBCA
HD
(N) PG&E
PADMOUNTED
TRANSFORMER
M
3P
1600A
(N) "MS"
120/208V, 1600 AMP, 3Ø, 4W, 65KAIC
3804
(N) "THP"
120/208V, 400 AMP, 3Ø, 4W, NEMA 3R
(N) PANEL
RM 1 RM 2 RM 3 RM 4 RM 5 RM 6 RM 7
RS
29
RS
30
RS
31
1
2
3
4
3P
(E) (E) (E) (E) (E) (E) (E)
(E) (E)
(E)
(D) (D) (D) (D) (D) (D) (D)
(E) (E) (E)
(E) (E)
(E)
SINGLE LINE DIAGRAM NOTES
A. ALL CONDUCTORS SHALL BE COPPER WITH TYPE [THHN/THWN]
INSULATION UNLESS OTHERWISE NOTED.
B. ALL SWITCHES, CIRCUIT BREAKERS AND OTHER EQUIPMENT, AS
SPECIFIED, SHALL HAVE TERMINATION PROVISIONS LISTED AND
IDENTIFIED FOR USE WITH 75 DEG. CONDUCTORS, AND ALL
FEEDER CONDUCTORS, AND CONDUITS, ARE SIZE BASED ON USE
OF 75 DEG. C COPPER WIRES TYPE THWN/THHN.
C. ALL EQUIPMENT SHALL HAVE AN APPROVED TESTING
LABORATORY LABEL ATTACHED [UL, CSA, ETC.] (CEC 110-2).
D. FEEDER DISTANCE IS SHOWN FOR REFERENCE ONLY AS THE
BASIS OF VOLTAGE DROP CALCULATIONS. CONDUCTOR
DISTANCE AS INDICATED SHALL NOT BE USED FOR
BIDDING/CONSTRUCTION PURPOSES. SHOULD THE FEEDER
DISTANCE EXCEED THE LENGTH NOTED PER INSTALLATION
CONDITIONS, NOTIFY THE ENGINEER OF RECORD. TYPICAL.
E. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CONTACT
AND COORDINATE WITH THE SERVING UTILITY TO ENSURE ALL
SERVING UTILITY REQUIREMENTS ARE MET.
5
1153V3 1153V2 1153V1 1153 1153 1153V1 1153V2
4
E-302
10
3P
400A
(N) 'DPA'
120/208V, 400 AMP, 3Ø, 4W, NEMA 3R, 10KAIC
CR1 CR2 CR3
1153 1153 1153 1153
7
3P
400A
(N) 'DPB'
120/208V, 400 AMP, 3Ø, 4W, NEMA 1, 10KAIC
CR5 CR6 CR7
1153 1153 1153
6
8
8
3804
11
12
CONDUIT ONLY WITH PULL-ROPE.
(2) 4"CCO24
CONDUIT ONLY WITH PULL-ROPE
(1) 4"CCO14
CONDUIT ONLY WITH PULL-ROPE. REFER TO PG&E
HANDOUT PACKAGE AND COMPLY WITH PG&E GREENBOOK
(5) 5"CCO55
1154(4) #2 THWN & (1) #6 GND.(1) 2"C
(3) #2 THWN & (1) #6 GND.1153
(1) 1-1/2"C
CO14 CO55
(N)
(N)
18
17
13
14
15
1504(4) #1/0 THWN & (1) #6 GND.(1) 2"C
3804(4) #500 KCMIL THWN & (1) #2 GND.(1) 4"C
BUILDING "B"
B
1153
9
BUILDING "B"
BUILDING "A"
BUILDING "A"
1
E-001
(3) #4/0 THWN & (1) #4 GND.2003V
(1) 3"C
(N)
1
E-001
1
E-001
(N)
400A
3P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(E)
600A
3P
(E)
200A
3P
(E)
225A
3P
(E)
100A
3P
(E)
100A
3P
(E)
100A
3P
(E)
100A
2P
(E)
100A
2P
(E)
125A
3P
(E)
100A
3P
SPD
(N)
60A
3P
20
240KA (L-L)
120KA (L-N)
19
CONDUIT WITH (N) OSP RATED CAT6 TO IDF (SEE SITE PLAN)
AND (N) PULL-ROPE. REFER TO PG&E HANDOUT PACKAGE
(1) 1"CCO11
SPD
(N)
60A
3P
20
120KA (L-L)
60KA (L-N)
19
1
E-001
SPD
(N)
60A
3P
20
120KA (L-L)
60KA (L-N)
19
TYPICAL
CR4
(N)
400A
3P
(N)
400A
3P
(N)
80A
3P
TO (E) PG&E
TRANSFORMER
CO11
100A
2P
70A
2P
70A
2P
70A
2P
70A
2P
70A
2P
70A
2P
70A
2P
250A
3P
(E) "MSB" LOAD-CALC:
12-MONTH HISTORY (MAX DEMAND) = 148.3 KVA
SUBTOTAL x 1.25 = 185.4 KVA
= 516A @ 120/208V,3PH
(E) LOAD TO REMOVE (PNL 'R' = 7 RELOCATABLES) = - 250A
(E) LOAD TO REMOVE (PNL 'J' = 125A) = - 125A
(N) LOAD TO ADD (PNL 'THP' = 7 RELOCATABLES) = + 322A
(N) "MSB" CONNECTED LOAD: = 468A @ 120/208V, 3PH
130120
(E)
PANEL
(E)
PANEL
110
(E)
PANEL
100
(E)
PANEL
(E)
(E)(E)(E)(E)
400A
3P
(N) WALL-MOUNTED
ENCLOSED CIRCUIT
BREAKER, WITH
LOCKABLE HANDLE IN
ELECTRICAL ROOM
4203
(N) 112.5KVA STEP-UP
TRANSFORMER,
PAD-MOUNTED,
DRY-TYPE, DELTA-DELTA,
208V TO 480V.
"XTH-U"
21
#1/0
#1/0
2003V
(N) 112.5KVA STEP-DOWN
TRANSFORMER, PADMOUNTED,
DRY-TYPE, DELTA-WYE,
120/208V TO 480V, WITH
ENCLOSED CIRCUIT BREAKER
"XTH-D"
22
4204G
"TDISC"
23
EC SHALL RE-TAP BUS IF NEW
LUGS/CONDUCTORS ARE
INCOMPATIBLE WITH (E) TAP
4204G(4) #600 KCMIL THWN & (1) #1/0 GND.(1) 4"C
(E)
853
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
(N)
100A
2P
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
(N) PANEL
100A
2P
"RDISC"
(E)
80A
2P
(E)
3P
(E)
WELL
PUMP
(E) CONDUCTORS
TO REMAIN
DEMO (E) FEEDER AND
PRESERVE (E) CONDUIT
PATHWAY FOR (N)
FEEDER TO 'XTH-U'. SEE
E-100 & E-101
TH1 TH2 TH3 TH4 TH5 TH6 TH7
(N)
125A
3P
(N)
600A
3P
1504 6204V
24
'PBE-00'
1
E-303
5
E-303
24
'PBE-02'
25
[8.31KAIC]
25
[7.14KAIC]
25
[11.58KAIC]
(4) #500 KCMIL THWN & (1) #1/0 GND. EACH6204V
(2) 4"C
16
'PBE-01'
16'PBE-02'
(SHALL BE RE-PURPOSED AS
LOW-VOLTAGE PATHWAY
AND CALLED 'PBC-04')
[42KAIC]
26
'PBE-TH1'
24
'PBE-TH2'
24
'PBE-04'
CO24CO14
CO24
853
17
25
[4.17KAIC]
25
[7.44KAIC]
(3) #1/0 THWN & (1) #3 GND.1153V1
(1) 2"C
(3) #3/0 THWN & (1) #2 GND.1153V2
(1) 2"C
(3) #4/0 THWN & (1) #1 GND.1153V3 (1) 3"C
18
4203(3) #600 KCMIL THWN & (1) #2 GND.(1) 4"C
1
1
1
1
1
1
1
(3) #4 THWN & (1) #8 GND.(1) 1-1/2"C
5
E-003
1
5
E-003
1
5
E-003
1
5
E-003
1
5
E-003
20A
1P
(E)
SEWER
PUMP
27
1
1
CHECKED: PM
DRAWN BY: JM
PROJECT NO.:
May 11, 2018
PR
OJE
CT
T
IT
LE
RE
VIS
IO
NS
15
1 W
est B
ra
nch
S
tre
et; S
uite
E
Arro
yo
G
ra
nd
e, C
A 9
34
20
(8
05
) 5
74
-1
55
0
1 2 3 4
EXPIRES: 06/30/19
THOMA #17-8124
San Luis O
bispo, C
A 93406
3562 E
mpleo S
t.
TH
OM
A E
LE
CT
RIC
, IN
C.
Phone: (805) 543-3850
Fax: (805) 543-3829
SHEET TITLE:
A
R
E
T
M
A
.
E
C
F
NO. 10757
E
L
T
S
O
E
A
T
E
SI
GE
R
I
W
L
T
L
I
E
A
R
O
L
I
C
RT
I
L
F
CA
A
I
N
H
O
M
N
A
RE
E
G
I
N
O
R
P
D
N
A
OI
EF
SS
L
Lucia M
ar U
nified S
chool D
istrict
HA
RLO
E E
LE
ME
NT
AR
Y S
CH
OO
L
90
1 F
AIR
O
AK
S A
VE
NU
E, A
RR
OY
O G
RA
ND
E, C
A 9
34
20
AP
N #
0
77
-2
83
-0
02
20
18
.0
5.1
1
E-003
ELECTRICAL PANEL
SCHEDULES
1
PANEL SCHEDULE 'MS'
SCALE: NTS
2
PANEL SCHEDULE 'DPB'
SCALE: NTS
3
PANEL SCHEDULE 'DPA'
SCALE: NTS
4
PANEL SCHEDULE 'THP'
SCALE: NTS
5
ARC FLASH SIGNAGE
SCALE: NTS
NOTE:
IN ACCORDANCE WITH CEC 110.16. PROVIDE ARC FLASH PROTECTION WARNING LABELS ON EACH
SWITCHBOARD, PANELBOARD, AND TRANSFORMER. LABELS SHALL BE PER ANSI Z535.4 GUIDELINES.
1
FAIR OAKS AVENUE
SO
UT
H H
ALC
YO
N R
D.
AL
DE
R S
TR
EE
T
PLAYGROUND
HARLOE ELEMENTARY
SCHOOL
901 FAIR OAKS AVENUE
ARROYO GRANDE, CA 93420
8.83 ACRES
APN# 077-283-002
DSA FILE # 40-39
EXISTING
CLASS
110
A-52009
EXISTING
COMPUTER
LAB/CLASSROOM/SDC
090
A-47121
EXISTING
CLASS
120
A-52009
EXISTING
CLASS
130
A-52009
EXISTING
LAB
100
A-52009
EXISTING
CLASSROOM
070
A-17358
EXISTING
CLASSROOM
080
A-17358
EXISTING
CLASSROOM
060
A-12204
A-49853
EXISTING
CLASSROOM/SDC
050
A-12204
A-49853
EXISTING
CLASSROOM
040
A-12204
A-49853
BOYS
RR
A-49853
GIRLS
RR
A-49853
MULTI-USE
010A
A-12204
A-49853
ADMIN
010
A-12204
A-49853
M/W
STAFF
RR
A-49853
CLASSROOM
020
A-12204
CLASSROOM
030
A-17358
PLAYGROUND
(E)
ELEC.
WOMEN
RR
MEN
RR
ELEC.
EXISTING
CLASS
07
EXISTING
CLASS
230
EXISTING
CLASS
220
EXISTING
CLASS
210
EXISTING
CLASS
200
EXISTING
CLASS
190
EXISTING
CLASS
180
EXISTING
CLASSROOM
160
EXISTING
CLASSROOM
150
EXISTING
CLASSROOM
140
EXISTING
RESTROOM
(E) PNL 'A'
WP
WP
(D)
WP(D)
WP
(D)WP
WP
2
1(E) 'MSB'
"R"
3
(E) PNL 'D'
3
(E) PNL 'H'
3
(E) PNL 'F'
3
(E) PNL 'E'
3
(E) PNL 'C'
3
(E) PNL 'B'
3
(E) PNL 'I'
3
(E) PNL 'G'
3
(E) PNL 'J'
3
7
9
8
5
4
6
(D)
CO
MM
.
PW
R.
CO
MM
.
PW
R.
CO
MM
.
PW
R.
CO
MM
.
PW
R.
CO
MM
.
PW
R.
CO
MM
.
PW
R.
CO
MM
.
PW
R.
"TCR1"
PWR.
PW
R.
11
10
10
10
15
13
TYPICAL ALONG
COVERED WALKWAY
MDF
(E)
14
'FACP-1'
IDF
(E)
22
23
PW
R.
PW
R.
5
CO
MM
.
12'PBC-03'
19'PBE-02'
18
20
(E) 'RDISC'
16
17
(E) 'PBC-02'
11
TO PNL. 'J'
13
10
'PBE-01'
11
(E) 'PBC-01'
(E) 'PBC-00'
11
(E) 'PBC-07'
(E) (E)
21
IDF
(D)
IDF
(D)
1
1
CHECKED: PM
DRAWN BY: JM
PROJECT NO.:
May 11, 2018
PR
OJE
CT
T
IT
LE
RE
VIS
IO
NS
15
1 W
est B
ra
nch
S
tre
et; S
uite
E
Arro
yo
G
ra
nd
e, C
A 9
34
20
(8
05
) 5
74
-1
55
0
1 2 3 4
EXPIRES: 06/30/19
THOMA #17-8124
San Luis O
bispo, C
A 93406
3562 E
mpleo S
t.
TH
OM
A E
LE
CT
RIC
, IN
C.
Phone: (805) 543-3850
Fax: (805) 543-3829
SHEET TITLE:
A
R
E
T
M
A
.
E
C
F
NO. 10757
E
L
T
S
O
E
A
T
E
SI
GE
R
I
W
L
T
L
I
E
A
R
O
L
I
C
RT
I
L
F
CA
A
I
N
H
O
M
N
A
RE
E
G
I
N
O
R
P
D
N
A
OI
EF
SS
L
Lucia M
ar U
nified S
chool D
istrict
HA
RLO
E E
LE
ME
NT
AR
Y S
CH
OO
L
90
1 F
AIR
O
AK
S A
VE
NU
E, A
RR
OY
O G
RA
ND
E, C
A 9
34
20
AP
N #
0
77
-2
83
-0
02
20
18
.0
5.1
1
E-100
ELECTRICAL
PLAN - DEMO
REFERENCE NOTES
1. EXISTING MAIN SWITCHBOARD 'MSB', TO REMAIN. REMOVE METERING EQUIPMENT AND PROVIDE
NEW FEEDER FROM NEW MAIN SWITCHBOARD 'DPA'. SEE SINGLE LINE DIAGRAM FOR CONDUIT
AND CONDUCTOR SIZING.
2. EXISTING DISTRIBUTION PANEL "R" TO BE REMOVED. SEE SINGLE LINE DIAGRAM AND SHEET
E-101 FOR (E) FEEDER CONDUIT TO BE RE-USED.
3. (E) ELECTRICAL PANEL TO REMAIN, SHOWN ON THIS PLAN FOR REFERENCE.
4. EXISTING COMMUNICATIONS/FIRE ALARM CABINET TO BE REMOVED. SEE SHEET E-300 FOR (E)
RELOCATABLE REFEED.
5. EXISTING RELOCATABLE BUILDING TO BE REMOVED. DISCONNECT AND REMOVE POWER,
COMMUNICATIONS AND FIRE ALARM CONNECTIONS BACK TO SOURCE. ALL
TELECOMMUNICATIONS EQUIPMENT, INCLUDING RACKS, NETWORK SWITCHES, WIRELESS
ACCESS POINTS, FIRE ALARM DEVICES, ETC. SHALL BE REMOVED AND SALVAGED TO DISTRICT.
COORDINATE OUTAGES AND SYSTEM DOWNTIME WITH DISTRICT'S REPRESENTATIVE FOR FIRE
ALARM AND COMMUNICATIONS SYSTEMS, MINIMUM (5) BUSINESS DAYS ADVANCED NOTICE IS
REQUIRED PRIOR TO DISCONNECTION/REMOVAL.
6. (E) (4) RELOCATABLE BUILDINGS TO REMAIN. BUILDING POWER IS FED FROM 'MSB' AND
COMMUNICATIONS FROM CABINET "TCR1". DISCONNECT LOW-VOLTAGE SYSTEMS CABLING
(PHONE, INTERCOM, BELLS, PA, ETC.) PULL-BACK TO NEAREST COMMON PULL-BOX AND RE-FEED
VIA NEW UNDERGROUND INFRASTRUCTURE SHOWN ON E-101 AND TELECOMMUNICATIONS
RISER DIAGRAM E-300. (E) FIRE ALARM DEVICES SHALL BE RECONNECTED IN-KIND.
7. EXISTING WELL/IRRIGATION EQUIPMENT TO REMAIN, CURRENTLY SERVED FROM (E) PANEL 'J'.
RE-FEED FROM PROPOSED (N) SERVICE, SEE SINGLE LINE DIAGRAM AND SITE PLAN.
8. EXISTING CAMPUS ELECTRICAL SERVICE PG&E UNDERGROUND SECONDARY CONDUIT. UTILITY
TO REMOVE CONDUCTORS. CONDUIT TO BE ABANDONED IN PLACE.
9. UTILITY POLE WITH TRANSFORMER SERVING CAMPUS. COORDINATE WITH PG&E.
10. EXISTING 4" CONDUIT FOR LOW-VOLTAGE SIGNALING UNDERNEATH EXISTING COVERED CANOPY.
TO REMAIN.
11. EXISTING LOW-VOLTAGE PULL-BOX MOUNTED TO UNDERSIDE OF EXISTING COVERED CANOPY.
TO REMAIN.
12. (E) WALL-MOUNTED PULL-BOX FOR LOW-VOLTAGE SYSTEMS TO REMAIN.
13. LOCATE EXISTING BUILDING 90 POWER FEEDER AND REMOVE, INCLUDING BUS-TAP AND
DISCONNECT SWITCH IN (E) ELECTRICAL ROOM. RECONNECT PANEL TO NEW SERVICE PER
SINGLE LINE DIAGRAM.
14. APPROXIMATE LOCATION OF (E) CAMPUS FIRE ALARM CONTROL PANEL 'FACP-1' IN
ADMINISTRATION OFFICE. FIELD LOCATE.
15. (E) UNDERGROUND CONDUITS FOR LOW VOLTAGE SYSTEMS SERVING 'TCR1' FROM PULL-BOX ON
BUILDING 090. SEE NEW SITE PLAN FOR EXTENSION/RELOCATION OF LOW-VOLTAGE CABLES.
16. (E) DASHED SECTION OF 4" CONDUIT FOR FEEDER TO PANEL 'R' TO BE REMOVED FROM CANOPY.
17. (E) SECTION OF 4" CONDUIT FORMERLY FEEDING TO PANEL 'R' (SHOWN AS SOLID LINE) TO BE
REMAIN AND BE RE-PURPOSED FOR (N) TEMP-HOUSING FEEDER. REFER TO E-101 FOR DETAILS.
18. EC SHALL FIELD VERIFY FUNCTION OF PULL-BOX. (E) POWER FEEDER FOR RELOCATABLE
CLASSROOMS TO REMAIN, THROUGH PULL-BOX AT EXTERIOR OF BUILDING 'J'. EC SHALL
PROTECT IN PLACE.
19. (E) ELECTRICAL PULL-BOX LOW ON WALL AT EXTERIOR OF BUILDING 'J' TO REMAIN. REMOVE (E)
FEEDER TO PANEL 'R' FROM SOURCE (LEAVE (E) CONDUIT IN PLACE UNLESS OTHERWISE NOTED),
AND RE-USE AS COMMUNICATIONS PULL-BOX FOR LOW-VOLTAGE PATHWAY AS SHOWN ON NEW
SITE PLAN E-101.
20. EC SHALL REMOVE AND REPLACE (E) DISCONNECT SWITCH ON WALL 'RDISC' FOR PANEL 'R'
FEEDER UNDER CANOPY WITH (N) DISCONNECT PER SINGLE LINE DIAGRAM. PRESERVE (E)
CONDUIT SO AS TO REPLACE WITH FEEDER PER SINGLE LINE DIAGRAM.
21. (E) COMMUNICATIONS SERVICE TO (E) ROOM 100, SHALL BE REMOVED AND RE-FED PER E-101
AND TELECOMMUNICATIONS RISER DIAGRAM E-300. (E) FIRE ALARM DEVICES SHALL BE RE-FED IN
KIND THROUGH (N) UNDERGROUND UTILITY INFRASTRUCTURE AS SHOWN ON E-101.
22. (E) MAIN DISTRIBUTION FRAME ('MDF') TO REMAIN. SEE TELECOMMUNICATIONS RISER DIAGRAM
E-300 FOR CONNECTIVITY REQUIREMENTS OF BOTH (N) AND (E) SERVICES AS NECESSARY
UNDER THE SCOPE OF THIS PROJECT.
23. (E) COMMUNICATIONS PULL-BOX AND CONNECTION TO (E) PORTABLES SHALL REMAIN TO BE
RE-FED WITH (E) LOW-VOLTAGE SYSTEMS. INTERMEDIATE DISTRIBUTION FRAME ('IDF') SHALL BE
RE-CONNECTED AS SHOWN ON TELECOMMUNICATIONS RISER DIAGRAM E-300.
NORTH
SCALE:
ELECTRICAL PLAN - DEMO
1"=30'-0"
GENERAL DEMOLITION PLAN NOTES
A. REFER TO ARCHITECTURAL DEMOLITION SHEETS FOR ADDITIONAL INFORMATION.
B. EQUIPMENT SHOWN TO BE REMOVED IS SHOWN FOR REFERENCE ONLY. INFORMATION WAS
OBTAINED FROM ORIGINAL BUILDING DRAWINGS AND LIMITED FIELD INVESTIGATION AND MAY NOT
REPRESENT ALL ELECTRICAL DEMOLITION. FIELD VERIFY CONDITIONS AND DISCONNECT/REMOVE
ALL EQUIPMENT AS REQUIRED TO MEET THE INTENT OF THAT SHOWN ON THE LIGHTING AND
POWER/SIGNAL DRAWINGS.
C. ALL ELECTRICAL EQUIPMENT SHOWN ON DRAWING (OR REQUIRED) TO BE DEMOLISHED SHALL BE
DISCONNECTED, REMOVED AND DISPOSED OF BY ELECTRICAL CONTRACTOR. NO EQUIPMENT
(RACEWAYS, BOXES, CABLING, ETC.) SHALL BE ABANDONED IN PLACE AND COVERED BY NEW
CONSTRUCTION.
F. SCHEDULE ANY OUTAGES WITH OWNER PRIOR TO DE-ENERGIZATION OF ANY BRANCH CIRCUITS OR
FEEDERS.
G. DISCONNECTION/REMOVAL OF EXISTING COMMUNICATIONS SYSTEMS COMPONENTS SHALL BE
SCHEDULED WITH OWNER AND COORDINATED WITH THEIR VENDORS. UPON RECEIPT OF NOTICE TO
PROCEED, EC SHALL NOTIFY OWNER'S REPRESENTATIVE OF PLANNED TELECOMMUNICATIONS
ITEMS TO BE SALVAGED, AND PROVIDE COMPLETE LIST OF ALL ITEMS TO BE SUPPLIED BY OWNER.
H. SALVAGE ALL REMOVED COMPONENTS (SPEAKERS, GRILLES, TELEPHONE INSTRUMENTS, RADIO
HANDSETS, ETC.) SHALL BE SALVAGED TO THE OWNER.
I. INFORMATION SHOWN FOR LOAD DESCRIPTIONS ON EXISTING PANELS WAS GAINED FROM ORIGINAL
BUILDING ELECTRICAL PLANS AND SHALL BE FIELD VERIFIED. CONFIRM LOAD ON EACH CIRCUIT OF
ALL EXISTING PANELS AND PROVIDE UPDATED TYPEWRITTEN CIRCUIT DIRECTORY (IN PLASTIC
SLEEVE) FOR EACH EXISTING PANELBOARD.
J. ANY LOADS REMOVED DURING DEMOLITION SHALL HAVE CONDUCTORS REMOVED BACK TO NEXT
REMAINING DEVICE OR TO EXISTING PANELS. ABANDONED BREAKERS SHALL BE LABELED "SPARE".
K. PROVIDE BLANK FILLER PLATES IN DEADFRONTS OF EXISTING PANELBOARDS UPON COMPLETION OF
PROJECT WHERE BREAKERS HAVE BEEN REMOVED.
L. PROVIDE NEW PLASTIC, LAMINATED ENGRAVED NAMEPLATES FOR EACH EXISTING PANEL TO MATCH
NEW PANELS.
1
ELEVATION OF CANOPY CONDUIT
SCALE: NTS
(E) PULL-BOX 'PBC-03'
(E) 4" CONDUIT WITH POWER TO (E) PANEL 'R'.
REMOVE CONDUCTORS AND SALVAGE TO
DISTRICT. INTERCEPT EMPTY CONDUIT AND
EXTEND TO PULL-BOX 'PBC-05' (SEE E-101)
(E) 2" COMM.
CONDUIT TO (E)
'TCR1'
(E) 4" COMM. CONDUIT
FROM 'MDF' SHALL REMAIN
(E) PULL-BOX 'PBE-01'
(PULL-BOX FOR
RELOCATABLES TO REMAIN)
PROTECT IN PLACE
(E) 2" PWR. CONDUIT TO
REMAINING PORTABLE
CLASSROOMS. PROTECT IN PLACE
(E) PULL-BOX 'PBE-02' TO
BE RE-PURPOSED FOR
COMMUNICATIONS AS
'PBC-04'
(E) COMM.
PULL-BOX 'PBC-02'
(E) 4" CONDUIT AND PANEL
'R' FEEDER FROM 'MSB' TO
BE PARTIALLY REMOVED
(E) 4" CONDUIT WITH
PANEL 'R' FEEDER FROM
'MSB' TO BE PARTIALLY
REMOVED
(E) 4" CONDUIT. REMOVE PANEL
'R' FEEDER FROM 'MSB' TO
REPURPOSE CONDUIT FOR
LOW VOLTAGE SYSTEMS
TOWARDS 'MSB' & MDF
(E) 4" CONDUIT AND PANEL 'R'
FEEDER FROM 'MSB'. REMOVE
CONDUCOTRS AND RE-USE AS
LOW-VOLTAGE PATHWAY.
(N) 4" ELBOW FROM 'PBC-02' TO
INTERCEPT EXISTING CONDUIT,
PAINT TO MATCH (E) CANOPY.
(E) COMM.
PULL-BOX
'PBC-02'
1
1
1
(E)
960 SQ. F
TYPE V-
(E) STOR.
(E) STOR.
INTERCEPT (E) 4" CONDUIT
TO PANEL 'R' AND EXTEND
TO NEW COMM. PULL-BOX
AS SHOWN
(N) PULL-BOX
'PBE-03'
(E) 'PBC-04'
(E) 'PBC-03'
(E) 'PBE-01'
(E) 'PBC-02'
INTERCEPT (E) (1) 2"
CONDUIT TO 'TCR1' AND
EXTEND TO NEW COMM.
PULL-BOX AS SHOWN.
(E) PANEL 'J'
(N) PULL-BOX
'PBC-05'
(E) FEEDER FOR
RELOCATABLE
CLASSROOMS TO
REMAIN
(N) UNDERGROUND
CONDUITS WITH
ELECTRICAL FEEDERS.
SEE SINGLE LINE DIAGRAM
ON E-002
(E) 4" CONDUIT RE-ROUTED
FROM 'PBC-02'
(N) CONNECTION TO (E) PULL-BOX.
REFER TO 1/E-100
SO
UT
H H
ALC
YO
N R
D.
ALD
ER
S
TR
EE
T
PLAYGROUND
(E)
CLASSROOM
100
A-52009/1989
OCC. LOAD: 48
960 SQ. FT.
TYPE V-B
(E) MULTI-USE
010
A-12204/1954
A-49853/1988
A-101917/1999
OCC LOAD:
3500 SQ. FT.
TYPE V-B
(E) ADMIN
010
A-48858/1988
OCC LOAD:
1040 SQ. FT.
TYPE V-B
(E) CLASSROOM
140
A-59627/1993
OCC LOAD: 48
960 SQ. FT.
(E) PLAYGROUND
(E) PLAYGROUND
(E) PLAYGROUND
(E) SPORTS
COURTS
HARLOE ELEMENTARY
SCHOOL
901 FAIR OAKS AVENUE
ARROYO GRANDE, CA 93420
8.83 ACRES
APN# 077-283-002
DSA FILE # 40-39
(E)
ELEC.
(E) MEN
RR
(E) ELEC.
(E) GIRLS
RR
A# 03-103088
(E) BOYS
RR
A# 03-103088
(N) TEMP. CLASSROOM 1
BLDG GROUP: C
A# 100099
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(E) ELEC.
(E) CLASSROOM
BLDG: 060
A-12204/1954
A-49853/1988
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 080
A-17358/1958
A-101491/1999
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 070
A-17358/1958
A-101491/1999
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 050
A-12204/1954
A-49853/1958
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 090
A-47121/1986
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E)
ELECT.
(E)
I.T.
(E)
CLASSROOM
110
A-52009/1989
OCC. LOAD: 48
960 SQ. FT.
TYPE V-B
(E)
CLASSROOM
120
A-52009/1989
OCC. LOAD: 48
960 SQ. FT.
TYPE V-B
(E)
CLASSROOM
130
A-52009/1989
OCC. LOAD: 48
960 SQ. FT.
TYPE V-B
(E) BOYS
RR
(E)
GIRLS
RR
(E) KITCHEN
010
A-49853
OCC LOAD:
450 SQ. FT.
TYPE V-B
(E) CLASSROOM
150
A-59627/1993
OCC LOAD: 48
960 SQ. FT.
(E) CLASSROOM
160
A-65005/1996
OCC LOAD: 48
960 SQ. FT.
(E) STOR.
(E) ELEC.
(E) STOR.
(E)
ELEC.
(E) STOR.
(E) STOR.
(E) STOR.
(N) CLASSROOM
BLDG GROUP: A
ROOM #4:
PC# 02-113899
OCC LOAD: 45
874 SQ. FT.
TYPE V-B
(N) CLASSROOM
BLDG GROUP: A
ROOM #3:
PC# 02-113899
OCC LOAD: 45
891 SQ. FT.
TYPE V-B
(N) CLASSROOM
BLDG GROUP: A
ROOM #2:
PC# 02-113899
OCC LOAD: 45
890 SQ. FT.
TYPE V-B
(N) CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
OCC LOAD: 45
884 SQ. FT.
TYPE V-B
(N) CLASSROOM
BLDG GROUP: B
ROOM #3:
A# 02-113899
OCC LOAD: 45
873 SQ. FT.
TYPE V-B
(N) CLASSROOM
BLDG GROUP: B
ROOM #2:
A# 02-113899
OCC LOAD: 45
889 SQ. FT.
TYPE V-B
(N) CLASSROOM
BLDG GROUP: B
ROOM #1:
A# 02-113899
OCC LOAD: 45
889 SQ. FT.
TYPE V-B
(N)
BOY'S
RR
(N)
GIRL'S
RR
(N)
STF.
RR
(N)
STF.
RR
(E)
WOMEN
RR
(N) TEMP. CLASSROOM 2
BUILDING GROUP: C
A# 100099
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(N) TEMP. CLASSROOM 3
BUILDING GROUP: C
A# 03-61227
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(N) TEMP. CLASSROOM 4
BUILDING GROUP: C
A# 03-66135
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(N) TEMP. CLASSROOM 5
BUILDING GROUP: C
A# 03-66135
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(N) TEMP. CLASSROOM 6
BUILDING GROUP: C
A# 03-66135
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(N) TEMP. CLASSROOM 7
BUILDING GROUP: C
A# 03-66135
OCC. LOAD: 48
960 SQ. FT.
TYPVE V-B
(E) STAFF AND
VISITOR PARKING
LOT
A-49853
N
O P
AR
KIN
G - F
IR
E L
AN
E
ELEC.
DATA/I.T.
N89°59'13"W 548.15'
N0
°0
0'0
0"E
6
46
.8
4'
N0
°0
0'0
0"E
6
46
.8
3'
L=23.57'
D=89°59'13"
R=15.00'
L=23.56'
N
O P
AR
KIN
G - F
IR
E L
AN
E
N
O P
AR
KIN
G - F
IR
E L
AN
E
NO PARKING - FIRE LANE
NO PARKING - FIRE LANE
(E) CLASSROOM
BLDG: 050
A-12204/1954
A-49853/1958
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 050
A-12204/1954
A-49853/1958
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 070
A-17358/1958
A-101491/1999
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 070
A-17358/1958
A-101491/1999
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 090
A-47121/1986
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 090
A-47121/1986
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 080
A-17358/1958
A-101491/1999
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 080
A-17358/1958
A-101491/1999
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 060
A-12204/1954
A-49853/1988
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 060
A-12204/1954
A-49853/1988
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 040
A-12204/1954
A-49853/1988
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 040
A-12204/1954
A-49853/1988
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 040
A-12204/1954
A-49853/1988
OCC LOAD: 48
960 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 020
A-12204/1954
A-49853/1988
OCC LOAD: 67
1340 SQ. FT.
TYPE V-B
(E) CLASSROOM
BLDG: 030
A-17358/1958
A-101491/1999
OCC LOAD: 67
1340 SQ. FT.
TYPE V-B
N
O
P
A
R
K
I
N
G
1
2
3
4
'DPB'
'DPA'
6
9
11
12"MSB"
'THTC'
13
18
(E) 'FACP-1'
6
16
19
20
20
20
TYIPCAL ALONG
COVERED WALKWAY
21
MDF
(E)
'PBC-06'
'PBC-05'
'PBC-03'
14
'PBE-04'
CO
MM
.
PW
R.
PW
R.
PW
R.
PW
R.
10
'THP'
22
14
'MS'
9
'PBE-00'
9 'PBE-03'
27
1
-
13
'PBC-TH2'
9
'PBE-TH2'
7
'PBE-TH1'
'PBC-TH1'
1
E-103
23
23
(E) PNL 'J'
26'PBC-04'
25'PBE-01'
IDF
(N)
17
IDF
(N)
17
8
'XTH-D'
8'XTH-U'
14
24
2
-
6
6
6
'AC-B'
5
14CO42
CO42
ANN
15
5
19 'PBC-07'
CO52
CO32
14CO52
STUB, CAP,
AND MARK
CO42
19
'PBC-02'
20
(N) FIRE ALARM ANNUNCIATOR
'ANN' ADJACENT TO (E) FACP. SEE
FA-300
(N) FIRE ALARM CONTROL PANEL
'FACP-3', SEE FA-300
(N) FIRE ALARM CONTROL PANEL
'FACP-2', SEE FA-300
(E) 'PBC-01'
(E) 'PBC-00'
19
14
STUB, CAP,
AND MARK
CO42
14CO52
WP WP(E) (E)
WPWP
WPWP
WP
WP
WP
WP
28
(E) ELEC.
(E)
WOMEN
ROOM
(N) PADMOUNTED STEP-UP
TRANSFORMER 'XTH-U'
(N) (4) 2" CONDUITS,
(2) FOR SIGNAL, (1)
FOR FIRE ALARM
(N) 24"x24"x6" NEMA 3R
PULL-BOX MOUNTED
TO UNDERSIDE OF
CANOPY. PAINT TO
MATCH (E) CONDUIT
CONDITIONS
(E) (1) 4" CONDUIT
WITH SIGNAL
CONDUCTORS
FROM 'MDF'
(N) 24"x24"x6" NEMA 3R PULL-BOX MOUNTED
TO UNDERSIDE OF CANOPY. INTERCEPT (E)
4" CONDUIT AND PAINT TO MATCH (E)
CONDUIT CONDITIONS
(N) FEEDER TO 'XTH-U'. PROVIDE
90-DEGREE BEND AND ROUTE
OFF CANOPY DOWN TO XFMR ON
GROUND.
(E) (1) 4" CONDUIT WITH (N) ELECTRICAL FEEDER
FROM (N) 'TDISC'. SEE SINGLE LINE DIAGRAM
(N)
'PBE-TH1'
(N)
'PBC-TH1'
(E)
'PBC-07'
(N) SECONDARY FROM 'XTH-U'
PER SINGLE LINE DIAGRAM.
(N) UNDERGROUND
COMMUNICATIONS AND FIRE
ALARM CONDUITS FROM
CANOPY TO (N) 'THTC'
(E) (1) 4" POWER
CONDUIT TO BE
REMOVED
1
3
E-304
1
CHECKED: PM
DRAWN BY: JM
PROJECT NO.:
May 11, 2018
PR
OJE
CT
T
IT
LE
RE
VIS
IO
NS
15
1 W
est B
ra
nch
S
tre
et; S
uite
E
Arro
yo
G
ra
nd
e, C
A 9
34
20
(8
05
) 5
74
-1
55
0
1 2 3 4
EXPIRES: 06/30/19
THOMA #17-8124
San Luis O
bispo, C
A 93406
3562 E
mpleo S
t.
TH
OM
A E
LE
CT
RIC
, IN
C.
Phone: (805) 543-3850
Fax: (805) 543-3829
SHEET TITLE:
A
R
E
T
M
A
.
E
C
F
NO. 10757
E
L
T
S
O
E
A
T
E
SI
GE
R
I
W
L
T
L
I
E
A
R
O
L
I
C
RT
I
L
F
CA
A
I
N
H
O
M
N
A
RE
E
G
I
N
O
R
P
D
N
A
OI
EF
SS
L
Lucia M
ar U
nified S
chool D
istrict
HA
RLO
E E
LE
ME
NT
AR
Y S
CH
OO
L
90
1 F
AIR
O
AK
S A
VE
NU
E, A
RR
OY
O G
RA
ND
E, C
A 9
34
20
AP
N #
0
77
-2
83
-0
02
20
18
.0
5.1
1
E-101
ELECTRICAL
SITE PLAN
NORTH
SCALE:
ELECTRICAL SITE PLAN - POWER AND DATA/COMM.
1"=30'
REFERENCE NOTES
1. (N) UNDERGROUND PRIMARY PG&E SERVICE FROM (E) OVERHEAD UTILITY POLE TO (N) TRANSFORMER.
CONTRACTOR SHALL REFER TO PG&E HANDOUT PACKAGE AND PG&E GREENBOOK FOR EXACT
UNDERGROUND REQUIREMENTS AND DETAILS. EC SHALL BORE ACROSS ROAD AND PATCH AS
NECESSARY, WITH MINIMUM 36" COVER AND 12" UNDISTURBED EARTH ON EACH SIDE OF BORE.
2. (N) PAD MOUNT PG&E TRANSFORMER, REFER TO PG&E HANDOUT AND PG&E GREENBOOK FOR
INSTALLATION REQUIREMENTS, INCLUDING ADEQUATE CLEARANCES TO SIDEWALK AND FENCING.
COORDINATE WITH DISTRICT TO PROVIDE NEW FENCING, WITH EXTERNALLY OPERATED GATE
(ACCESSIBLE FROM PUBLIC ROADWAY).
3. (N) SECONDARY PG&E SERVICE TO DISTRIBUTION PANEL "MS", REFER TO SINGLE LINE DIAGRAM AND
PG&E HANDOUT PACKAGE.
4. (N) PAD MOUNTED DISTRIBUTION PANEL "MS". REFER TO SINGLE LINE DIAGRAM AND 5/E-303 FOR PAD
MOUNTING REQUIREMENTS.
5. ROUTE POWER IN UNDERGROUND CONDUIT TO PANEL "THP". SEE SINGLE LINE DIAGRAM FOR
CONDUIT/CONDUCTOR REQUIREMENTS.
6. (N) UNDERGROUND POWER FEEDERS TO NEW AND EXISTING STRUCTURES ON CAMPUS. SEE SINGLE LINE
DIAGRAM.
7. (N) ELECTRICAL PULL-BOX MOUNTED AT UNDERSIDE OF CANOPY FOR RELOCATABLE CLASSROOM POWER
FEED. INTERCEPT (E) 4" CONDUIT AT UNDERSIDE OF CANOPY AND EXTEND (N) FEEDER TO (N)
TRANSFORMER 'XTH-U' PER SINGLE LINE DIAGRAM.
8. (N) STEP-UP AND STEP-DOWN TRANSFORMERS FOR (N) PORTABLE CLASSROOMS ON CAMPUS, REFER TO
SINGLE LINE DIAGRAM FOR TRANSFORMER SIZING AND INSTALLATION REQUIREMENTS.
9. (N) 3'x5' PG&E #5 TRAFFIC RATED PULL BOX. PROVIDE LABEL FOR LID "ELECTRICAL". REFER TO DETAIL
5/E-301 FOR INSTALLATION REQUIREMENTS.
10. (N) RACK MOUNTED ELECTRICAL PANEL "THP" FOR PORTABLE CLASSROOMS, REFER TO SINGLE LINE
DIAGRAM E-002.
11. (N) RACK MOUNTED COMMUNICATIONS TERMINAL CABINET 'THTC'. REFER TO TELECOMMUNICATIONS
RISER DIAGRAM E-300.
12. (E) 600A, 120/208V, 3PH, 4W MAIN SWITCHBOARD 'MSB'. BACKFEED FROM NEW SERVICE VIA EXTERIOR
PULL-BOX MOUNTED AT ATTIC HEIGHT ABOVE (E) 'MSB', REFEED PER SINGLE LINE DIAGRAM.
13. (N) 2'x3' TRAFFIC RATED PULL-BOX FOR LOW-VOLTAGE COMMUNICATIONS. LABEL LID "COMMUNICATIONS".
REFER TO DETAIL 7/E-301 FOR INSTALLATION REQUIREMENTS.
14. (N) CONDUITS FOR LOW VOLTAGE SYSTEMS INCLUDING FIRE ALARM CONNECTIVITY. SEE LOW-VOLTAGE
CONDUIT SCHEDULE FOR UNDERGROUND CONDUIT COUNT. REFER TO TELECOMMUNICATIONS RISER
DIAGRAM ON E-300 FOR CONDUCTOR REQUIREMENTS. REFER TO FIRE ALARM RISER E-400 FOR
CONDUCTOR REQUIREMENTS FOR FIRE ALARM.
15. (N) CONDUITS FOR LOW-VOLTAGE TO RE-FEED PORTABLE CLASSROOM '100'. REFER TO
TELECOMMUNICATIONS RISER DIAGRAM E-300 FOR RE-FEED REQUIREMENTS OF (E) SYSTEMS.
16. (N) 3'x5' TRAFFIC RATED PULL-BOX FOR LOW-VOLTAGE COMMUNICATIONS. LABEL LID "COMMUNICATIONS".
REFER TO DETAIL 7/E-301 FOR INSTALLATION REQUIREMENTS.
17. (N) INTERMEDIATE DISTRIBUTION FRAME ('IDF'), REFER TO TELECOMMUNICATIONS RISER DIAGRAM E-300
FOR CONNECTIVITY DETAILS.
18. (N) UNDERGROUND FEEDER AND TRANSITION TO ATTIC HEIGHT ON BUILDING 'J' WING TO RE-CONNECT (E)
BUILDING 90 PANEL 'J' TO NEW SERVICE PER SINGLE LINE DIAGRAM. SAWCUT AND PATCH AS NECESSARY.
PAINT CONDUIT TO MATCH.
19. (E) PULL-BOXES MOUNTED TO UNDERSIDE OF (E) CANOPY STRUCTURE. TYPICAL ALONG COVERED
WALKWAY. PULL-BOX NAME SHOWN BESIDE KEYNOTE.
20. (E) 4" CONDUIT MOUNTED TO UNDERSIDE OF (E) CANOPY STRUCTURE. ROUTE NEW FIBER OPTIC CABLE
INSIDE (E) 2" INNER-DUCT AND FIRE ALARM IN REMAINDER OF 4" CONDUIT.
21. (E) LOW-VOLTAGE PULL-BOX ON WALL AT BUILDING 090.
22. (N) COMMUNICATIONS PULL-BOX MOUNTED AT UNDERSIDE OF (E) CANOPY. PROVIDE (N) CONDUITS FROM
(E) COMMUNICATIONS PULL-BOX AS SHOWN IN DETAIL 1 OF THIS SHEET FOR LOW-VOLTAGE
CONNECTIVITY, AND ROUTE DOWN CANOPY, UNDERGROUND CONDUIT, AND NEW PORTABLE
CLASSROOMS. REFER TO TELECOMMUNICATIONS RISER DIAGRAM E-300 FOR CONNECTIVITY DETAILS.
23. (N) SURFACE-MOUNTED DISTRIBUTION PANELBOARD (SQUARE-D "I-LINE") FOR (N) MODULAR BUILDINGS.
REFER TO ENLARGED FLOORPLANS AND SINGLE-LINE DIAGRAM FOR CONNECTIVITY DETAILS.
24. (E) IRRIGATION PUMP DISCONNECT SWITCH AND PUMP EQUIPMENT, TO BE RE-FED FROM (N) MAIN
SERVICE 'MS'. REFER TO SINGLE LINE DIAGRAM FOR CONDUIT AND CONDUCTOR SIZING OF (N) FEEDER.
EC SHALL FIELD VERIFY LOCATION OF PUMP CONTROLS PATHWAY/CONDUCTORS AND PROTECT IN PLACE.
25. EC SHALL FIELD VERIFY LOCATION OF FEEDER. (E) POWER FEEDER FOR RELOCATABLE CLASSROOMS TO
REMAIN, THROUGH PULL-BOX AT EXTERIOR OF BUILDING 'J'. EC SHALL PROTECT IN PLACE.
26. (E) ELECTRICAL PULL-BOX LOW ON WALL AT EXTERIOR OF BUILDING 'J' TO REMAIN. REMOVE (E) FEEDER
PER DEMO PLAN AND RE-USE AS COMMUNICATIONS PULL-BOX FOR LOW-VOLTAGE PATHWAY AS SHOWN.
27. (N) ACTIVE ZONE ENCLOSURE IN (N) BUILDING 'A'. REFER TO ENLARGED POWER/COMM. PLAN E-102 FOR
REQUIREMENTS.
28. (N) 1" CONDUIT FROM METER VESTIBULE IN (N) SERVICE 'MS' TO 'PBC-05'. ROUTE (N) OSP CAT6 CABLE
FROM (N) IDF IN (N) BUILDING 'B' TO BISCUIT TERMINATED AT NEW SERVICE PER PG&E GREENBOOK.
2
ENLARGED FLOORPLAN AT BUILDING 'J'
SCALE: NTS
1
ENLARGED FLOOR PLAN AT (E) 'MSB'
SCALE: NTS
LOW VOLTAGE CONDUIT SCHEDULE
NO. RACEWAY QUANTITY/SIZE
CO42
CO52
CO32
(N) (4) 2" CONDUITS - (3) 2" FOR COMMUNICATIONS, (1) 2" FOR FIRE ALARM
(N) (3) 2" CONDUITS - (2) 2" FOR COMMUNICATIONS, (1) 2" FOR FIRE ALARM
(N) (5) 2" CONDUITS - (4) 2" FOR COMMUNICATIONS, (1) 2" FOR FIRE ALARM
SEE GENERAL SITE PLAN NOTES ON E-001
1
UNISEX
STAFF
RR.
NEW
GIRL'S
RR
NEW
DATA/I.T.
NEW
ELECTRICAL
NEW
BOY'S
RR
UNISEX
STAFF
RR.
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
NEW CLASSROOM
BLDG GROUP: A
ROOM #1:
PC# 02-113899
"DPA"
14
AP
4
S
FR
ON
T
16
1
2
S
4
5
7
10
14
'DPB'
TYP. @ EACH
CLASSROOM
TYP. @ EACH
CLASSROOM
TYP. @ EACH
CLASSROOM
TO 'DPB'
APAP
AP AP AP AP
'CR4''CR3'
'CR2'
'CR7'
'CR6'
TO 'DPB'
3
TYP. @ EACH
CLASSROOM
J
J
TO 'DPB'
TO 'DPB''CR5'
TO 'DPA'
3
TYP. @ EACH
CLASSROOM
WP
S
4
WP
4
J
J
4
J
J
4
J
J
4
J
J
4
J
J
4
J
J
11
TYP. @ EACH
CLASSROOM
17
17
17
'PNL-B'
'FACP-2'
6
15
'MTTB'
8
BUILDING "A"
BUILDING "B"
S
WP
S
WP
4
4
TO 'DPA'TO 'DPA'
'CR1'
TO 'DPA'
'B-10'
SS
S S S S
12
13
12
13
'PBC-06'
'B'
18
1
E-302
1
E-302
1
E-302
1
E-302
1
E-302
1
E-302
1
E-302
12
12
'IDF'
9
17
21
'PBC-05'
19
20
'AC-B'
'TTB'
TO 'CR1'
ZE
21
J
C
C
C
C
88 8 8
888
TO 'PBE-03'
TO 'PBE-03'
'B-12'
'PNL-B'
12
TO ROOM
100
TO FUTURE
STUB
TO FUTURE
STUB
S
= (N) WEATHER PROOF (WP) VOIP ENABLED OUTDOOR SPEAKER & ENCLOSURE
DEVICE (PROVIDED BY DISTRICT, INSTALLED BY EC). EC SHALL PROVIDE (N) (1)
CAT6 CABLE PER DEVICE TERMINATED IN ACCESSIBLE CEILING SPACE (INSIDE
WALL) WITHIN 5'-0" OF DEVICE, PROVIDE MIN. 10' SERVICE LOOP. ALL MODULAR
JACKS, CABLE, AND PATCH CABLES SHALL BE BLUE. EC SHALL COORDINATE
WITH DISTRICT REPRESENTATIVE FOR FINISHED MOUNTING HEIGHT.
LEGEND
= INTERIOR WIRELESS ACCESS POINT (PROVIDED BY DISTRICT, INSTALLED BY
EC). PROVIDE (N) (2) CAT6A CABLES EACH TERMINATED IN 2-PORT BISCUIT IN
ACCESSIBLE CEILING. ALL MODULAR JACKS, CABLE, AND PATCH CABLES
SHALL BE WHITE.
AP
= DATA OUTLET AT LOCATION SHOWN IN PLAN. 'n' = NUMBER OF CAT6 DATA
DROPS. ALL MODULAR JACKS, CABLE, AND PATCH CABLES SHALL BE BLUE.
n
WP
= (N) VOIP ENABLED INDOOR SPEAKER DEVICE & ENCLOSURE DEVICE (PROVIDED
BY DISTRICT, INSTALLED BY EC). EC SHALL PROVIDE (N) (1) CAT6 CABLE
TERMINATED IN BISCUIT IN ACCESSIBLE CEILING SPACE PER DEVICE WITH
MINIMUM 10' SERVICE LOOP. ALL MODULAR JACKS, CABLE, AND PATCH CABLES
SHALL BE BLUE. EC SHALL COORDINATE WITH DISTRICT REPRESENTATIVE FOR
FINISHED MOUNTING HEIGHT.
S
C
= (N) FUTURE CAMERA LOCATION, PROVIDE 1-PORT BISCUIT MOUNTED IN
ACCESSIBLE CEILING AT LOCATION SHOWN IN PLAN. PROVIDE (N) (1) CAT6
DATA JACK TERMINATED IN BISCUIT. ALL MODULAR JACKS, CABLE, AND PATCH
CABLES SHALL BE BLUE.
= (N) BATTERY POWERED WALL MOUNTED CLOCK. COORDINATE WITH DISTRICT
REPRESENTATIVE FOR MOUNTING HEIGHT.
CHECKED: PM
DRAWN BY: JM
PROJECT NO.:
May 11, 2018
PR
OJE
CT
T
IT
LE
RE
VIS
IO
NS
15
1 W
est B
ra
nch
S
tre
et; S
uite
E
Arro
yo
G
ra
nd
e, C
A 9
34
20
(8
05
) 5
74
-1
55
0
1 2 3 4
EXPIRES: 06/30/19
THOMA #17-8124
San Luis O
bispo, C
A 93406
3562 E
mpleo S
t.
TH
OM
A E
LE
CT
RIC
, IN
C.
Phone: (805) 543-3850
Fax: (805) 543-3829
SHEET TITLE:
A
R
E
T
M
A
.
E
C
F
NO. 10757
E
L
T
S
O
E
A
T
E
SI
GE
R
I
W
L
T
L
I
E
A
R
O
L
I
C
RT
I
L
F
CA
A
I
N
H
O
M
N
A
RE
E
G
I
N
O
R
P
D
N
A
OI
EF
SS
L
Lucia M
ar U
nified S
chool D
istrict
HA
RLO
E E
LE
ME
NT
AR
Y S
CH
OO
L
90
1 F
AIR
O
AK
S A
VE
NU
E, A
RR
OY
O G
RA
ND
E, C
A 9
34
20
AP
N #
0
77
-2
83
-0
02
20
18
.0
5.1
1
E-102
ENLARGED
MODULAR PLAN -
POWER AND COMM
NORTH
SCALE:
ENLARGED MODULAR BUILDING PLAN - POWER AND COMMUNICATIONS
3/16"=1'-0"
REFERENCE NOTES
1. (N) CEILING MOUNT SPEAKERS FOR INTERCOM/BELLS. PROVIDE (N) (1) CAT6
CABLE TERMINATED IN BISCUIT AT EACH DEVICE. COORDINATE WITH DISTRICT
FOR FINAL PLACEMENT IN RELOCATABLE CLASSROOM.
2. WIRELESS ACCESS POINT HARDWARE TO BE PROVIDED BY DISTRICT STAFF,
INSTALLED BY ELECTRICAL CONTRACTOR. ROUTE (2) CAT6A CABLES TO BISCUIT
IN ACCESSIBLE CEILING SPACE AT THIS LOCATION. SEE DETAILS 1/E-301 &
4/E-301 FOR MOUNTING INSTRUCTIONS UNLESS OTHERWISE NOTED.
3. (N) RECESSED 5-INCH SQUARE BOX WITH HAND-HOLE FOR ACCESS TO CHASE
TO ACCESSIBLE CEILING. PROVIDE NEW (1) 1-1/4” CONDUIT STUB TO ACCESSIBLE
CEILING SPACE. COORDINATE WITH TELEVISION MOUNTING HARDWARE AND
SEEK OWNER APPROVAL FOR FINAL MOUNTING HEIGHT PRIOR TO ROUGH-IN.
CONTRACTOR TO LEAVE PULL-ROPE IN CONDUIT FOR FUTURE INSTALL OF
MEDIA CABLE. SEE DETAIL 1/E-302.
4. (N) OUTDOOR VOIP ENABLED SPEAKER WITH MANUFACTURER'S BACK-BOX
PROVIDED BY DISTRICT, INSTALLED BY CONTRACTOR. PROVIDE (N) (1) CAT6
TERMINATED IN ACCESSIBLE CEILING SPACE IN 1-PORT BISCUIT. PROVIDE
MINIMUM 10'-0" SERVICE LOOP. RISER DIAGRAM SHEET E-300.
5. NEW MAIN TELEPHONE TERMINAL BACKBOARD 'MTTB'. PROVIDE 3/4" THICK, 1-HR
FIRE RATED PLYWOOD BACKBOARD AS NECESSARY TO COVER DATA ROOM
WALLS. BOTTOM OF BACKBOARD SHALL START 6" AFF. PROVIDE GROUND BUS
BAR PER DETAIL 2/E-301.
6. (N) SURFACE MOUNT FIRE ALARM CONTROL PANEL 'FACP-2'. REFER TO SHEET
FA-300 FOR FIRE ALARM RISER DIAGRAM. PROVIDE DEDICATED 20A/1P CIRCUIT
FROM PANEL 'B' (IN MODULAR ELECTRICAL ROOM) WITH RED, LOCKABLE
BREAKER. EC SHALL USE (2) #12 THWN & (1) #12 GND.
7. (N) SECURITY CONTROLLER PROVIDED BY OTHERS.
8. (N) CLASSROOM ELECTRICAL PANEL PROVIDED BY MODULAR MANUFACTURER,
SHOW FOR REFERENCE ONLY, SEE MODULAR MANUFACTURER DRAWINGS FOR
EXACT LOCATIONS AND REQUIREMENTS. REFER TO SINGLE LINE DIAGRAM FOR
CONDUIT AND CONDUCTOR SIZE, FIELD LOCATE ELECTRICAL FEEDER STUBS TO
ATTIC (ROUTE FEEDERS OVERHEAD INSIDE BUILDING).
9. (N) DEDICATED RECEPTACLE AT +48" AFF. FOR IDF.
10. (N) TELECOMMUNICATIONS 19" 2-POST INTERMEDIATE DISTRIBUTION FRAME
(IDF) (CHATSWORTH P/N 48353-703) FOR NEW MODULAR BUILDING DATA
SYSTEMS. REFER TO COMMUNICATIONS RISER DIAGRAM E-300 FOR
CONNECTIVITY REQUIREMENTS AND DETAIL 5/E-302 FOR CABINET MOUNTING
REQUIREMENTS.
11. (N) 4-PORT DATA OUTLET WITH (4) DEDICATED CAT6 CABLES. PROVIDE 5"
SQUARE BACK-BOX WITH 1-GANG P-RING AND 1-1/4" CONDUIT TO ACCESSIBLE
CEILING SPACE PER COMMUNICATIONS PLAN NOTES (E-001).
12. CONTINUATION OF SITE LOW VOLTAGE CONDUIT SYSTEM. SEE SITE PLANS FOR
DETAILS.
13. (N) UNDERGROUND PULL-BOX FOR LOW VOLTAGE COMMUNICATIONS. REFER TO
SITE PLAN FOR SIZE, LOCATION AND CONTINUATION OF LOW VOLTAGE
PATHWAY. SEE 7/E-301
14. (N) BUILDING ELECTRICAL DISTRIBUTION PANELS 'DPA' AND 'DPB', MOUNT TO
BUILDING WALL PER 6/E-302.
15. (N) (5) 2" UNDERGROUND CONDUITS STUB INTO NEW DATA ROOM FROM
PULL-BOX 'PBC-06' PER PLAN. EC SHALL COORDINATE WITH MODULAR BUILDING
MANUFACTURER FOR STUB REQUIREMENTS.
16. (N) WALL-MOUNTED, BATTERY POWERED, GPS SYNCHRONIZED CLOCK.
17. (N) 1-PORT BISCUIT MOUNTED IN ACCESSIBLE CEILING SPACE FOR FUTURE
EXTERIOR CAMERAS. ROUTE (1) (N) CAT6 CABLES TO BUILDING IDF FROM (N)
BISCUIT.
18. (N) UNDERGROUND COMMUNICATIONS CONDUITS FROM BUILDING 'B' IDF TO
ACTIVE ZONE ENCLOSURE 'AC-B' IN BUILDING 'A' VIA TELEPHONE TERMINAL
BACKBOARD ABOVE ACCESSIBLE CEILING SPACE. REFER TO
TELECOMMUNICATIONS RISER DIAGRAM E-300.
19. (N) ACTIVE ZONE ENCLOSURE, LEVITON Z1000-AC4. PROVIDE (N) MODULAR
PATCH PANELS FOR INCOMING OSP RATED CAT6/6A, AND FOR (N) RISER RATED
STATION CABLING. PROVIDE (N) JUNCTION BOX WITH 1" CONDUIT TO NEAREST
PANEL IN ACCESSIBLE CEILING SPACE FOR FUTURE ENCLOSURE POWER
CONNECTION, INSTALL PER DETAIL 5/E-304. SEE E-300 FOR TELECOM RISER
DIAGRAM.
20. NEW BUILDING TELEPHONE TERMINAL BACKBOARD 'TTB' WITH FIRE ALARM
TERMINAL CABINET MOUNTED IN ACCESSIBLE CEILING SPACE TO INTERIOR
DEMISING WALL. PROVIDE 3/4" THICK, 1-HR FIRE RATED, PLYWOOD BACKBOARD
AS NECESSARY TO COVER INSTALLATION. SEE DETAIL 1/E-304.
21. CONTINUATION OF POWER-FEEDER. SEE SITE PLAN E-101 AND SINGLE LINE
DIAGRAM.
SEE GENERAL COMMUNICATION PLAN NOTES ON E-001
1
4
S
S
4
S
4
S
4
S
4
S
4
7
PANEL 'TH7'
AP
4
S
4
5
6
7
4
7
4
7
4
7
4
7
4
7
10
TYPICAL AT (7)
CLASSROOMS
12
3
11
S
WP
S
WP
S
WP
13
AP
AP
AP
AP
AP
AP
8
14
15
17
16'THTC'
'XTH-D'
'THP'
1
E-103
IDF
2
4
E-304
TYPICAL AT (7)
CLASSROOMS
TYPICAL AT (7)
CLASSROOMS
TYPICAL AT (7)
CLASSROOMS
9
9
9
1
J
4
4
E-304
1
4
E-304
1
4
E-304
1
4
E-304
1
3
E-301
TYPICAL AT (7)
CLASSROOMS
'FACP-3'
PANEL 'TH6'
PANEL 'TH5'
PANEL 'TH4'
PANEL 'TH3'
PANEL 'TH2'
PANEL 'TH1'
4
E-304
1
4
E-304
1
4
E-304
1
'TH7-8'
'TH7-11'
1
S
= (N) WEATHER PROOF (WP) VOIP ENABLED OUTDOOR SPEAKER & ENCLOSURE
DEVICE (PROVIDED BY DISTRICT, INSTALLED BY EC). EC SHALL PROVIDE (N) (1)
CAT6 CABLE PER DEVICE TERMINATED IN ACCESSIBLE CEILING SPACE (INSIDE
WALL) WITHIN 5'-0" OF DEVICE, PROVIDE MIN. 10' SERVICE LOOP. ALL MODULAR
JACKS, CABLE, AND PATCH CABLES SHALL BE BLUE. EC SHALL COORDINATE
WITH DISTRICT REPRESENTATIVE FOR FINISHED MOUNTING HEIGHT.
LEGEND
= INTERIOR WIRELESS ACCESS POINT (PROVIDED BY DISTRICT, INSTALLED BY
EC). PROVIDE (N) (2) CAT6A CABLES EACH TERMINATED IN 2-PORT BISCUIT IN
ACCESSIBLE CEILING. ALL MODULAR JACKS, CABLE, AND PATCH CABLES
SHALL BE WHITE.
AP
= DATA OUTLET AT LOCATION SHOWN IN PLAN. 'n' = NUMBER OF CAT6 DATA
DROPS. ALL MODULAR JACKS, CABLE, AND PATCH CABLES SHALL BE BLUE.
n
WP
= (N) VOIP ENABLED INDOOR SPEAKER DEVICE & ENCLOSURE DEVICE (PROVIDED
BY DISTRICT, INSTALLED BY EC). EC SHALL PROVIDE (N) (1) CAT6 CABLE
TERMINATED IN BISCUIT IN ACCESSIBLE CEILING SPACE PER DEVICE WITH
MINIMUM 10' SERVICE LOOP. ALL MODULAR JACKS, CABLE, AND PATCH CABLES
SHALL BE BLUE. EC SHALL COORDINATE WITH DISTRICT REPRESENTATIVE FOR
FINISHED MOUNTING HEIGHT.
S
C
= (N) FUTURE CAMERA LOCATION, PROVIDE 1-PORT BISCUIT MOUNTED IN
ACCESSIBLE CEILING AT LOCATION SHOWN IN PLAN. PROVIDE (N) (1) CAT6
DATA JACK TERMINATED IN BISCUIT. ALL MODULAR JACKS, CABLE, AND PATCH
CABLES SHALL BE BLUE.
= (N) BATTERY POWERED WALL MOUNTED CLOCK. COORDINATE WITH DISTRICT
REPRESENTATIVE FOR MOUNTING HEIGHT.
36"
TYPICAL
60" MAX.
COMPACTED
NATIVE
BACKFILL
NOTE:
MAINTAIN 48" CLEARANCE IN
FRONT OF EQUIPMENT.
CONTRACTOR TO USE MYERS
HUBS FOR ALL BOX ENTRANCES.
PROVIDE 1" CAP SCREW WITH 3/8"
SPRING NUT. (1) AT EACH CORNER OF
CABINET. TYPICAL AT (2) CABINETS, (8)
PER CABINET.
(N) NEMA 3R
ELECTRICAL
PANEL.
"THP"
CONCRETE FOOTING
(TYPICAL OF 2)
(N) TRANSFORMER
"XTH-D"
(BOD: 46"H x 31.3W"
x 24.1"D @ 875LBS.)
3
E-304
SITE COMM. AND
FIRE ALARM
CONDUITS
FEEDER
CONDUITS FOR
RELOCATABLE
CLASSROOMS
EC SHALL PROVIDE TRANSFORMER AND PAD
FOR MOUNTING. COORDINATE CONDUIT
STUB-UP WINDOWS WITH SUBMITTED AND
APPROVED TRANSFORMER. BASIS OF DESIGN
(BOD) IS SQUARE-D "EX112T3H".
PROVIDE (N) 3/4" PLYWOOD
BACKBOARD MOUNTED TO REAR
WALL OF CABINET FOR TERMINAL
STRIPS AND CABLE MANAGEMENT.
GRS CONDUIT WITH PVC TAPEWRAP FROM 6"
ABOVE GRADE TO 24" BELOW GRADE. TYPICAL.
FINISHED
GRADE
INSTALL (4) NEW P1000 UNISTRUT
CHANNELS TO POSTS. ATTACH TO NEW
POSTS WITH MINIMUM (2) 1/2"Ø A307
MACHINE BOLTS WITH NUTS AND
WASHERS PER CHANNEL (8 TOTAL).
3" SQUARE x 1/4" THK GALVANIZED
STEEL POST (TYPICAL OF 2)
(N) 24"x24"x10"D
NEMA 3R
TELECOM.
CABINET
"THTC"
(N) P1000 UNISTRUT CHANNELS TO
POSTS. TYPICAL OF (4)
6" MIN.
TYPICAL
14" Ø MIN.
TYPICAL
TRANSFORMER FEEDER,
SEE SINGLE LINE
DIAGRAM, E-002
'TH1' FEEDER,
SEE SINGLE
LINE DIAGRAM,
E-002
60" MAX.
(N) 480V, 3PH NEMA 3R
ENCLOSED CIRCUIT
BREAKER. MAX
WEIGHT 50 LBS.
MINIMUM 3/8"
THRU-BOLT DEVICE TO
DEVICE. PROVIDE AT
(4) CORNERS
1
CHECKED: PM
DRAWN BY: JM
PROJECT NO.:
May 11, 2018
PR
OJE
CT
T
IT
LE
RE
VIS
IO
NS
15
1 W
est B
ra
nch
S
tre
et; S
uite
E
Arro
yo
G
ra
nd
e, C
A 9
34
20
(8
05
) 5
74
-1
55
0
1 2 3 4
EXPIRES: 06/30/19
THOMA #17-8124
San Luis O
bispo, C
A 93406
3562 E
mpleo S
t.
TH
OM
A E
LE
CT
RIC
, IN
C.
Phone: (805) 543-3850
Fax: (805) 543-3829
SHEET TITLE:
A
R
E
T
M
A
.
E
C
F
NO. 10757
E
L
T
S
O
E
A
T
E
SI
GE
R
I
W
L
T
L
I
E
A
R
O
L
I
C
RT
I
L
F
CA
A
I
N
H
O
M
N
A
RE
E
G
I
N
O
R
P
D
N
A
OI
EF
SS
L
Lucia M
ar U
nified S
chool D
istrict
HA
RLO
E E
LE
ME
NT
AR
Y S
CH
OO
L
90
1 F
AIR
O
AK
S A
VE
NU
E, A
RR
OY
O G
RA
ND
E, C
A 9
34
20
AP
N #
0
77
-2
83
-0
02
20
18
.0
5.1
1
E-103
TEMP HOUSING
SITE PLAN -
ELEC. & COMM.
NORTH
SCALE:
TEMP HOUSING SITE PLAN - ELECTRICAL & COMMUNICATIONS
1/8"=1'-0"
REFERENCE NOTES
1. (N) (3) 2" CONDUITS SPANNED BETWEEN RELOCATABLE CLASSROOMS, (2) FOR
COMMUNICATIONS, AND (1) FOR FIRE ALARM. INSTALL PER DETAIL 4/E-304.
2. (N) WALL-MOUNTED TELECOMMUNICATIONS IDF (INTERMEDIATE DISTRIBUTION
FRAME). REFER TO DETAIL 2/E-302 FOR INSTALLATION REQUIREMENTS AND RISER
DIAGRAM E-300 FOR CONNECTIVITY REQUIREMENTS.
3. (N) 4-PORT DATA OUTLET WITH (4) DEDICATED CAT6 CABLES. PROVIDE
SURFACE-MOUNT PATHWAY (WIREMOLD 5000 SERIES OR EQUIVALENT) FROM
ACCESSIBLE CEILING SPACE TO SURFACE-MOUNT 4-PORT FACEPLATE. SEE 4 &
6/E-303 FOR NAMING CONVENTIONS.
4. ROUTE ELECTRICAL SERVICE IN UNDERGROUND CONDUIT FROM PANEL "THP" TO
EACH TEMP HOUSING RELOCATABLE CLASSROOM. REFER TO SINGLE LINE
DIAGRAM FOR CONDUIT AND CONDUCTOR SIZES. SEE 6/E-301.
5. ROUTE (N) (3) 2" COMMUNICATIONS CONDUIT UNDERGROUND FROM RACK
MOUNTED COMMUNICATIONS CABINET "THTC" TO RELOCATABLE CLASSROOM
JUNCTION BOX PER PLAN. REFER TO DETAIL 3/E-301 FOR RELOCATABLE
CLASSROOM ELEVATION. (2) 2" CONDUITS FOR SINGAL, (1) 2" CONDUIT SPARE. SEE
6/E-301.
6. ROUTE (N) (1) 2" CONDUIT FOR FIRE ALARM SERVICE UNDERGROUND FROM RACK
MOUNTED "THTC" CABINET TO (N) CABINET PER PLAN. REFER TO DETAIL 3/E-301
FOR RELOCATABLE CLASSROOM ELEVATION REQUIREMENTS.
7. ELECTRICAL PANEL PROVIDED BY RELOCATABLE CLASSROOM MANUFACTURER,
COORDINATE STUB-UP LOCATIONS WITH ACTUAL CONDITIONS OF RELOCATABLE
ELECTRICAL PANEL LOCATION. TYPICAL AT EACH CLASSROOM.
8. CONTINUATION OF SITE ELECTRICAL, DATA AND FIRE ALARM CONDUITS AND
CONDUCTORS. REFER TO ELECTRICAL SITE PLAN E-101.
9. (N) OUTDOOR VOIP ENABLED SPEAKER WITH MANUFACTURER'S BACK-BOX,
PROVIDED BY DISTRICT, INSTALLED BY CONTRACTOR. PROVIDE (N) (1) CAT6
TERMINATED IN ACCESSIBLE CEILING SPACE IN 1-PORT BISCUIT. PROVIDE
MINIMUM 10'-0" SERVICE LOOP.
10. (N) BATTERY POWERED GPS SYNCHRONIZED CLOCK MOUNTED TO WALL. TYPICAL
OF EACH CLASSROOM.
11. (N) CEILING MOUNT SPEAKERS FOR INTERCOM/BELLS. PROVIDE (N) (1) CAT6 CABLE
TERMINATED IN BISCUIT AT EACH DEVICE. COORDINATE WITH DISTRICT FOR FINAL
PLACEMENT IN RELOCATABLE CLASSROOM.
12. WIRELESS ACCESS POINT HARDWARE TO BE PROVIDED BY DISTRICT STAFF,
INSTALLED BY ELECTRICAL CONTRACTOR. ROUTE (2) CAT6A CABLES TO BISCUIT IN
ACCESSIBLE CEILING SPACE AT THIS LOCATION. SEE DETAILS 1/E-301 & 4/E-301
FOR MOUNTING INSTRUCTIONS UNLESS OTHERWISE NOTED.
13. (N) FIRE ALARM CONROL PANEL 'FACP-3' PANEL MOUNTED TO CLASSROOM WALL
PER MANUFACTURERS SPECIFICATIONS. SEE RISER DIAGRAM ON FA-300
14. (N) H-FRAME FOR ELECTRICAL POWER PANELBOARD AND COMMUNICATIONS
CABINET. SEE DETAIL 1 OF THIS SHEET FOR INSTALLATION DETAILS.
15. (N) STEP-DOWN PAD MOUNTED TRANSFORMER 'XTH-D' FOR TEMP HOUSING. SEE
SINGLE LINE DIAGRAM DETAIL 1 OF THIS SHEET.
16. (N) NEMA 3R COMMUNICATIONS AND FIRE ALARM TERMINAL CABINET 'THTC' FOR
(N) RELOCATABLE CLASSROOMS TELECOMMUNICATIONS AND FIRE ALARM. SEE
1/E-103.
17. (N) 400A, 120/208V, 3PH, 4W NEMA 3R SQUARE-D "I-LINE" DISTRIBUTION PANEL 'THP'
FOR (N) TEMP HOUSING ELECTRICAL SERVICE. SEE 1/E-103.
1
ELEVATION AT 'THP'
SCALE: NTS
SEE GENERAL COMMUNICATION PLAN NOTES ON E-001