GRUNDFOS DATA BOOKLET

Grundfos Direct Sensors™Vortex flow sensors

GPipes
Stamp
Page 2: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Ta

ble

of c

on

ten

ts

2

Grundfos Direct Sensors™

1. Vortex flow sensors 3Introduction 3

2. Vortex flow sensor, industry (VFI) 4VFI general data 4VFI 0.3-6 DN 18, technical data 6VFI 0.6-12 DN 25, technical data 7VFI 1.3-25 DN 32, technical data 8VFI 2-40 DN 40, technical data 9VFI 3.2-64 DN 50, technical data 10VFI 5.2-104 DN 65, technical data 11VFI 8-160 DN 80, technical data 12VFI 12-240 DN 100, technical data 13

3. Vortex flow sensor, standard 14VFS general data 14VFS 1-20, technical data 16VFS 2-40, technical data 17VFS 5-100, technical data 18VFS 10-200, technical data 19VFS 20-400, technical data 20VFS 1-12 QT, technical data 21VFS 1-15 QT, technical data 22VFS 2-40 QT, technical data 23VFS 5-100 QT, technical data 24VFS 10-200 QT, technical data 25

4. Product range 26VFI sensor 26VFS sensor 27Sensor selection 27

5. Accessories 28Sensor interface, type SI 001 PSU 28Sensor interface, type SI 010 CNV 28

6. Appendix 29Installation of VFI sensor 29Minimum flow rate 30Pressure drop curves 31

7. Further product documentation 32WebCAPS 32WinCAPS 33

Page 3: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

ors

Grundfos Direct Sensors™ 1

1. Vortex flow sensors

IntroductionThis data booklet comprises an overview of the

Grundfos vortex flow sensor range and related products.

Fig. 1 Grundfos vortex flow sensors

The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos group.

The Grundfos vortex flow sensor is an integrated flow and temperature measurement system designed and validated for harsh aqueous environments. The flow measurement is based on the vortex principle. The system elements include a flow pipe with an integrated bluff body and a differential pressure detector.

Fig. 1 Bluff body inside a vortex flow sensor

When a bluff body is placed in a flow inside a pipe, a series of vortices will be generated periodically on each side of the bluff body. These vortices propagate down stream giving rise to periodic pressure variations, which can be detected by the differential pressure detector. The frequency of the pressure variations is proportional to the volume flow through the pipe.

Fig. 2 Operating principle

The bluff body is designed to optimise the pulse strength of the pressure variations at the position of the differential pressure detector. The bluff body is an integrated part of the injection moulded flow pipe, or supplied as a composite insert solution.

Flow ranges are determined by the pipe diameter and the signal processing parameters. The differential pressure detector key elements are a bulk micromachined silicon chip and a microprocessor-based signal-conditioning circuit, both on the same PCB. The conditioning circuit converts the pressure reading to a signal proportional to the flow through the pipe.

The electronics are protected by an IP44 composite housing.

The chip has a square membrane, which deflects due to pressure. Strain gauges are incorporated in a Wheatstone bridge configuration on stress intensive positions on the membrane. The pressure and temperature sensitive area (the membrane region) is coated on both sides by an extremely corrosion and diffusion resistive thin film (Silicoat®). The coating provides direct environmental robustness of the chip. The separation of the media and media-free zones is provided by O-ring sealing.

TM

04

73

62

16

10

, T

M0

5 4

73

9 2

41

2 &

TM

05

47

46

24

12

TM

04

92

36

37

10

TM

04

71

55

16

10

PipeBluff body

Flow direction

3

Page 4: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, in

du

stry

(VF

I)

4

Grundfos Direct Sensors™2

2. Vortex flow sensor, industry (VFI)

VFI general data

Vortex flow sensor, industry

Fig. 3 VFI sensor

Technical overview The VFI is the industrial version of the Grundfos vortex flowmeter range. The VFI is based on the principle of vortex shedding behind a bluff body. The VFI has no moving parts and is built into a stainless steel pipe. The rugged design allows the VFI to be used in a wide range of applications as a cost-effective and accurate flow sensor.The flow sensors are supplied with flanges or with threaded ends for use with union nuts.

Fig. 4 Bluff body in a VFI sensor

Applications• Water treatment and distribution

• light chemical industry

• water management

• pool and water resorts

• heating

• air-conditioning

• cooling towers

• condensing units

• solar collectors.

Features• Flow range from 0.3 to 240 m3/h

• based on the vortex principle

• compact and well-proven design

• approved for drinking water

• wide temperature range.

Benefits• No moving parts

• compatible with wet, aggressive media

• cost-effective and robust design

• system solution with Grundfos pumps.

Approvals• WRAS

• KTW

• ACS

• NSF 61.

Markings

Electrical connections

Fig. 5 Electrical connections

Power supply: 12.5 - 30 V (screened cable)

Type: Loop-powered, 2-wire

TM

04

73

62

22

10

TM

04

92

28

37

10

CE c, CSA, us C-Tick

TM

04

71

56

16

10

PIN 1 2 3 4

Wire colour Brown White Blue Black

Output 4-20 mA

+ -

���

1

3

4

2

Page 5: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

in

du

str

y (

VF

I)

Grundfos Direct Sensors™ 2

Type key

Type designation VFI -··0.3-6 m -1 -C -M 5.000 X -FG6 -SG -30 F -A··1

Product group:VFI: Vortex flow sensor, industry

Range:0.3-6

Unit:m: m3/h

Generation:1: 1st generation

Electrical output type:C: 4-20 mA, 2-wire

Sensor connector or cable type and cable connector in sensor end:M: M12x1, female straight, screened 4-wire cable

Cable length5.000= 5 m

Cable connector opposite sensor:X: Open-ended

Sealing material and class:First letter:E: EPDM (drinking-water approved)F: FKM (for use in oily media)Second letter:G: Gel-filledThird letter:6: IP67

Material:B: BrassC: CompositeG: Cast ironQ: Stainless steel flow pipe with composite insert (QT)S: Stainless steel

Dimension of mechanical connection:30: DIN PN25/40 DN18/25/32, ANSI B16.5 Class 300 - 1¼"

Mechanical connection type:F: Flange

Packaging:A: Set with pre-assembled components1: 1 piece

5

Page 6: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, in

du

stry

(VF

I)

6

Grundfos Direct Sensors™2

VFI 0.3-6 DN 18, technical data

Vortex flow sensor, industry, 0.3 - 6 m³/h

Fig. 6 VFI 0.3-6 sensor

Dimensions

Fig. 7 Dimensions VFI sensor with flanges

Flanges are compatible with DN 25/32 flanges sizes.

Fig. 8 Dimensions VFI sensor with thread

The VFI sensor with threaded ends must be mounted with union nuts.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 9 Flow response

TM

04

71

42

17

10

/ T

M0

4 4

25

0 1

71

0T

M0

4 7

15

4 1

61

0

Flange material

FlangeA

[mm]B

[mm]C

[mm]D

[mm]Weight

[kg]

Cast iron DN 25/32 (PN 40)

200 18 120 1404.38

Stainless steel 4.44

TM

04

71

53

16

10

MaterialThread

sizeA

[mm]B

[mm]C

[mm]Weight

[kg]

Stainless steel G1 1/4" 200 18 120 1.39

Flow

Measuring range 0.3 - 6 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.0075 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4-20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20-2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

Page 7: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

in

du

str

y (

VF

I)

Grundfos Direct Sensors™ 2

VFI 0.6-12 DN 25, technical data

Vortex flow sensor, industry, 0.6 - 12 m³/h

Fig. 10 VFI 0.6-12 sensor

Dimensions

Fig. 11 Dimensions VFI sensor with flanges

Flanges are compatible with DN 25/32 flanges sizes.

Fig. 12 Dimensions VFI sensor with thread

The VFI sensor with threaded ends must be mounted with union nuts.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 13 Flow response

TM

04

71

43

17

10

/ T

M0

4 4

25

1 1

71

0T

M0

4 7

15

4 1

61

0

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN 25/32 (PN 40)

200 18 124 1404.52

Stainless steel 4.58

TM

04

71

53

16

10

MaterialThread

sizeA

[mm]B

[mm]C

[mm]Weight

[kg]

Stainless steel G1 1/4" 200 18 124 1.53

Flow

Measuring range 0.6 - 12 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.015 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20-2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

7

Page 8: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, in

du

stry

(VF

I)

8

Grundfos Direct Sensors™2

VFI 1.3-25 DN 32, technical data

Vortex flow sensor, industry, 1.3 - 25 m³/h

Fig. 14 VFI 1.3-25 sensor

Dimensions

Fig. 15 Dimensions VFI sensor with flanges

Flanges are compatible with DN 25/32 flanges sizes.

Fig. 16 Dimensions VFI sensor with thread

The VFI sensor with threaded ends must be mounted with union nuts.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 17 Flow response

TM

04

71

44

17

10

/ T

M0

4 4

25

2 1

71

0T

M0

4 7

15

4 1

61

0

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN 25/32 (PN 40)

200 18 128 1404.47

Stainless steel 4.53

TM

04

71

53

16

10

MatreialThread

sizeA

[mm]B

[mm]C

[mm]Weight

[kg]

Stainless steel G 1 1/2" 200 19 128 1.31

Flow

Measuring range 1.3 - 25 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.03125 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe stainless steel 1.4408

Bluff body stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20-2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

Page 9: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

in

du

str

y (

VF

I)

Grundfos Direct Sensors™ 2

VFI 2-40 DN 40, technical data

Vortex flow sensor, industry, 2 - 40 m³/h

Fig. 18 VFI 2 - 40 sensor

Dimensions

Fig. 19 Dimensions VFI sensor with flanges

Flanges are compatible with DN 40 flanges sizes.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 20 Flow response

TM

04

71

45

17

10

TM

04

71

54

16

10

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN 40 (PN 40)

200 18 131 1505.58

Stainless steel 6.45

Flow

Measuring range 2 - 40 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.05 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30-120 °C, non-freezing

Liquid temperature -30-120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

9

Page 10: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, in

du

stry

(VF

I)

10

Grundfos Direct Sensors™2

VFI 3.2-64 DN 50, technical data

Vortex flow sensor, industry, 3.2 - 64 m³/h

Fig. 21 VFI 3.2 - 64 sensor

Dimensions

Fig. 22 Dimensions VFI sensor with flanges

Flanges are compatible with DN 50 flanges sizes.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 23 Flow response

TM

04

71

46

17

10

TM

04

71

54

16

10

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN 50 (PN 40)

200 22 138 1656.94

Stainless steel 5.94

Flow

Measuring range 3.2 - 64 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.08 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

Page 11: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

in

du

str

y (

VF

I)

Grundfos Direct Sensors™ 2

VFI 5.2-104 DN 65, technical data

Vortex flow sensor, industry, 5.2 - 104 m³/h

Fig. 24 VFI 5.2 - 104 sensor

Dimensions

Fig. 25 Dimensions VFI sensor with flanges

Flanges are compatible with DN 65 flanges sizes.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 26 Flow response

TM

04

71

47

17

10

TM

04

71

54

16

10

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN 65 (PN 40)

200 25 145 1859.31

Stainless steel 9.9

Flow

Measuring range 5.2 - 104 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.13 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

11

Page 12: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, in

du

stry

(VF

I)

12

Grundfos Direct Sensors™2

VFI 8-160 DN 80, technical data

Vortex flow sensor, industry, 8 - 160 m³/h

Fig. 27 VFI 8 - 160 sensor

Dimensions

Fig. 28 Dimensions VFI sensor with flanges

Flanges are compatible with DN 80 flanges sizes.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 29 Flow response

TM

04

71

48

17

10

TM

04

71

54

16

10

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN80 (PN40)

200 25 152 23511,51

Stainless steel 16

Flow

Measuring range 8 - 160 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.2 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 28 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

Page 13: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

in

du

str

y (

VF

I)

Grundfos Direct Sensors™ 2

VFI 12-240 DN 100, technical data

Vortex flow sensor, industry, 12 - 240 m³/h

Fig. 30 VFI 12 - 240 sensor

Dimensions

Fig. 31 Dimensions VFI sensor with flanges

Flanges are compatible with DN 100 flanges sizes.

Specifications

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s

Sensor output signals

Fig. 32 Flow response

TM

04

71

49

17

10

TM

04

71

54

16

10

Flange material

Flange size

A[mm]

B[mm]

C[mm]

D[mm]

Weight[kg]

Cast iron DN 100 (PN 16)

250 25 163 22013.56

Stainless steel 14.00

Flow

Measuring range 12 - 240 m³/h*

Accuracy (±1σ), 0 - 100 °C

± 1.5 % FS*

Response time < 1 s

Resolution 0.30 m³/h

Media and environment

Liquid types See appendix Minimum flow rate

Liquid max. pressure 16 barLiquid temperature (operation) -30 - 120 °C, non-freezing

Liquid temperature -30 - 120 °C, non-freezing

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature –55 - 70 °C

Storage temperature –55 - 70 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure 60 bar

Electrical data

Power supply 12.5 - 30 VDC (± 5 %)

Output signals - cut off

4 - 20 mA21 mA

Power consumption Max. 660 mW

Load impedance

Max. 60 Ω at 12.5 VDCMax. 100 Ω at 13.3 VDCMax. 600 Ω at 24 VDCMax. 900 Ω at 30 VDC

Sensor materials

Measurement element Silicon-based MEMS sensor

Packing material EPDM or FKM rubber

Sensor housing Stainless steel 1.4404

Flow pipe Stainless steel 1.4408

Bluff body Stainless steel 1.4401

Wetted materialsCorrosion-resistant coating

EPDM or FKM rubberStainless steel 1.4401/04/08

Environmental standards

Enclosure class IP67

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

TM

04

75

34

12

10

21 mA

4 mA

Qmin Qmax

Signal cut off

13

Page 14: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, s

tan

da

rd

14

Grundfos Direct Sensors™3

3. Vortex flow sensor, standard

VFS general data

Vortex flow sensor, standard

Fig. 33 VFS and VFS QT Sensors

Technical overview Grundfos Direct Sensors™, type VFS, is a series of combined flow- and temperature sensors (two-in-one) based on the principle of vortex shedding behind a bluff body. The VFS sensors are designed for high-volume production and are fully compatible with wet, aggressive media. The VFS sensor utilises MEMS sensing technology in combination with a novel packaging concept using corrosion-resistant coating on the MEMS sensor element. This makes the VFS sensor very robust and ideal for high-volume OEM applications.

Applications• Thermal management in solar heating systems

• industrial process flow control

• flow rate detection for pump controls

• monitoring of pumps, valves and filters

• temperature control

• domestic hot-water systems

• heat metering indication (solar heat pumps).

Features• Flow ranges: 1-12, 1-15, 1.3-20, 2-40, 5-100,

10-200 and 20-400 l/min.

• designed to operate in glycol mixture

• based on vortex shedding

• voltage output (ratiometric, ideal for use with microprocessor and PLC)

• compact and robust design

• approved for drinking water: WRAS, KTW, W270, ACS

• SiliCoat® technology.

Benefits• No moving parts

• flow- and temperature sensor in one package (two-in-one sensor)

• quick temperature response (direct media contact)

• compatible with wet, aggressive media

• cost-effective and robust construction.

Type key

For more information. see http://www.grundfos.com/directsensors.

Electrical connections

Fig. 34 Electrical connections

Power supply requirements

• 5 VDC ±5%

• max. 10 mV ripple, 50 Hz

• min. output current 10 mA

• separated from hazardous live circuitry by double or reinforced insulation

• power limitation: 150 VA; current limitation: 8 A.

Directives

The Grundfos Vortex flow sensors are in conformity with these Council directives on the approximation of the laws of the EC member states:

• Low Voltage Directive (2006/95/EC)

– Standards used: EN 61010-1:2001

• EMC Directive (2004/108/EC)

– Standards used: EN 61326-1:2006 and 61326-2-3:2006

The Grundfos Vortex flow sensors fall under Article 3, §3 of PED Directive 97/23/EEC and are therefore not required to be CE-marked according to this directive.

TM

05

47

45

24

12

96xxxxxx - XX - XXXX XXXXX

Product number

Version

Production year and week

Consecutive number

TM

04

71

56

16

10

Pin configuration Colour

1 Temperature signal (0.5 to 3.5 V relative to pin 3) Yellow

2 Flow signal (0.5 to 3.5 V relative to pin 3) White

3 GND (0 V), PELV Green

4 Power supply (+ 5 V DC) Brown

V

V

4321

PE

Temperature signal

Flow signal

Electrical connector

Pin No

Pipe system

Page 15: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

sta

nd

ard

Grundfos Direct Sensors™ 3

VFS Sensors

Fig. 35 VFS family

VFS flow sensors consist of a composite flow pipe and a sensor with cable.

The VFS are available in 1-20, 2-40, 5-100, 10-200, 20-400 l/min versions.

VFS QT sensors

Fig. 36 VFS QT family

VFS QT flow sensors consist of a composite insert, a stainless steel outer pipe and a sensor with cable.

The VFS QT are availiable in 1-12, 1-15, 2-40, 5-100, 10-200 l/min versions.

Sensor and cable connection

Fig. 37 Sensor and cableT

M0

5 4

74

4 2

51

2T

M0

5 4

74

3 2

51

2

TM

05

47

49

25

12

15

Page 16: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, s

tan

da

rd

16

Grundfos Direct Sensors™3

VFS 1-20, technical data

Vortex flow sensor, standard, 1-20 l/min

Fig. 38 VFS 1-20 sensor

Dimensions

Fig. 39 Dimensional sketches of sensing element

Fig. 40 Dimensional sketch of flow pipe

Sensor output signals

Fig. 41 Flow response

Fig. 42 Temperature response

Specifications

TM

05

47

51

25

12

TM

05

46

69

25

12

TM

03

82

05

08

07

TM

03

82

06

08

07

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

1.3 - 20 l/min1.3 - 20 l/min

Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)

±1.5 % FS± 5 % FS (typical ±3% FS)

Response time (63.2 %) < 1s

Resolution 0.1 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80 °C ±1 °C

Accuracy (±1σ), 0 - 100 °C ±2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (± 5 %). Grounding of the sensor

supply is recommended (PELV)

Output signals Ratiometric

Flow signal 0.35 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Flow pipe PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM,

PPS, PPA 40-GF

Environmental standards

Enclosure class IP44 (Not overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Flow pipe 82 x 39 x 25 mm

Temperature (°C)

Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

Page 17: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

sta

nd

ard

Grundfos Direct Sensors™ 3

VFS 2-40, technical data

Vortex flow sensor, standard, 2-40 l/min

Fig. 43 VFS 2-40 sensor

Dimensions

Fig. 44 Dimensional sketches of sensing element

Fig. 45 Dimensional sketch of flow pipe

Sensor output signals

Fig. 46 Flow response

Fig. 47 Temperature response

Specifications

TM

05

47

49

25

12

TM

05

46

69

25

12

TM

03

82

04

08

07

TM

03

82

16

08

07

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

2 - 40 l/min 2 - 40 l/min

Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)

±1.5 % FS± 5 % FS (typical ±3% FS)

Response time (63.2 %) < 1 s

Resolution 0.2 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80°C ±1 °C

Accuracy (±1σ), 0 - 100°C ±2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak)

–55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (± 5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Flow pipe PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM, PPS,

PPA 40-GF

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Flow pipe 88 x 39 x 25 mm

Temperature (°C)

Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

17

Page 18: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, s

tan

da

rd

18

Grundfos Direct Sensors™3

VFS 5-100, technical data

Vortex flow sensor, standard, 5-100 l/min

Fig. 48 VFS 5-100 sensor

Dimensions

Fig. 49 Dimensional sketches of sensing element

Fig. 50 Dimensional sketch of flow pipe

Sensor output signals

Fig. 51 Flow response

Fig. 52 Temperature response

Specifications

TM

05

47

48

25

12

TM

05

46

69

25

12

TM

03

82

19

08

07

TM

03

82

17

08

07

2xISO 228/1-G 1A

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

5 - 100 l/min5 - 100 l/min

Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)

±1.5 % FS± 5 % FS (typical ±3% FS)

Response time (63.2 %) < 1 s

Resolution 0.5 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80 °C ±1 °C

Accuracy (±1σ), 0 - 100 °C ±2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak)

–55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (±5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Flow pipe PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM, PPS,

PPA 40-GF

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Flow pipe 129 x 37 x 32 mm

Temperature (°C)

Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

Page 19: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

sta

nd

ard

Grundfos Direct Sensors™ 3

VFS 10-200, technical data

Vortex flow sensor, standard, 10-200 l/min

Fig. 53 VFS 10-200 sensor

Dimensions

Fig. 54 Dimensional sketches of sensing element

Fig. 55 Dimensional sketch of flow pipe

Sensor output signals

Fig. 56 Flow response

Fig. 57 Temperature response

SpecificationsTM

05

47

47

25

12

TM

05

46

69

25

12

TM

03

82

04

08

07

TM

03

82

16

08

07

2xISO 228/1-G 1¼ A

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

10 - 200 l/min10 - 200 l/min

Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)

±1.5 % FS± 5 % FS (typical ±3% FS)

Response time (63.2 %) < 1.0 s

Resolution 1.0 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (± 1σ), 25 - 80 °C ± 1 °C

Accuracy (± 1σ), 0 - 100 °C ± 2 °C

Response time (63.2 %) 250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 VDC (± 5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Flow pipe PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM, PPS,

PPA 40-GF

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawings

Flow pipe 137 x 45 x 41 mm

Temperature (°C)Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

19

Page 20: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, s

tan

da

rd

20

Grundfos Direct Sensors™3

VFS 20-400, technical data

Vortex flow sensor, standard, 20-400 l/min

Fig. 58 VFS 20-400 sensor

Dimensions

Fig. 59 Dimensional sketches of sensing element

Fig. 60 Dimensional sketch of flow pipe

Sensor output signals

Fig. 61 Flow response

Fig. 62 Temperature response

SpecificationsTM

05

47

46

25

12

TM

05

46

69

25

12

TM

04

29

54

33

08

TM

03

82

18

08

07

2xISO 228/1-G 1½

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

100 200 300 400

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

20 - 400 l/min20 - 400 l/min

Accuracy:In water (±1σ), (0 - 100 °C)Tyfocor LS (±1σ), (0 - 100 °C)

±1.5 % FS± 5 % FS (typical ±3% FS)

Response time (63.2 %) < 1.0 s

Resolution 2.0 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (± 1σ), 25 - 80 °C ± 1 °C

Accuracy (± 1σ), 0 - 100 °C ± 2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 VDC (± 5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Flow pipe PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM, PPS,

PPA 40-GF

Environmental standards

Enclosure class IP44 (Non-overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawings

Flow pipe 180 x 54 x 48 mm

Temperature (°C)Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

Page 21: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

sta

nd

ard

Grundfos Direct Sensors™ 3

VFS 1-12 QT, technical data

Vortex flow sensor, standard, 1-12 l/min

Fig. 63 VFS 1-12 sensor

Dimensions

Fig. 64 Dimensional sketches of VFS QT

Sensor output signals

Fig. 65 Flow response

Fig. 66 Temperature response

Specifications

TM

05

47

42

25

12

TM

00

5 4

67

1 2

51

2T

M0

05

46

70

25

12

TM

03

24

65

21

08

0 1 2 3 4 5 6 7 8 9 10 11 12

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

1 - 12 l/min1 - 12 l/min

Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)

± 1.5 % FS± 5.0 % FS (typical 3%)

Response time (63.2 %) < 3 sec.

Resolution 0.06 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80 °C ± 1 °C

Accuracy (±1σ), 0 - 100 °C ± 2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 4 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (± 5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.25 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Vortex tube 1.4408

Insert PPA 40 GF

Wetted materialsCorrosion-resistant coating

EPDM, PPS, PPA 40-GF, 1.4408

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Vortex tube 110 x 29.8 x 31.5 mm

Insert 63.9 x 16 x 15.4 mm

Temperature (°C)

Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

21

Page 22: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, s

tan

da

rd

22

Grundfos Direct Sensors™3

VFS 1-15 QT, technical data

Vortex flow sensor, standard, 1-15 l/min

Fig. 67 VFS 1-15 sensor

Dimensions

Fig. 68 Dimensional sketches of VFS QT

Sensor output signals

Fig. 69 Flow response

Fig. 70 Temperature response

Specifications

TM

05

47

42

25

12

TM

00

5 4

67

1 2

51

2T

M0

05

46

70

25

12

TM

05 3

706

16

12

0 5 10

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

15Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

1 - 15 l/min1 - 15 l/min

Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)

± 1.5 % FS± 5.0 % FS (typical 3%)

Response time (63.2 %) < 1 sec.

Resolution 0.075 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80 °C ± 1 °C

Accuracy (±1σ), 0 - 100 °C ± 2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (± 5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.25 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Vortex tube 1.4408

Insert PPA 40 GF

Wetted materialsCorrosion-resistant coating

EPDM, PPS, PPA 40-GF, 1.4408

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Vortex tube 110 x 29.8 x 31.5 mm

Insert 63.9 x 16 x 15.4 mm

Temperature (°C)

Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

Page 23: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

sta

nd

ard

Grundfos Direct Sensors™ 3

VFS 2-40 QT, technical data

Vortex flow sensor, standard, 2-40 l/min

Fig. 71 VFS 2-40 sensor

Dimensions

Fig. 72 Dimensional sketches of VFS QT

Sensor output signals

Fig. 73 Flow response

Fig. 74 Temperature response

Specifications

TM

05

47

41

25

12

TM

00

5 4

67

1 2

51

2T

M0

05

46

70

25

12

TM

03

82

16

08

07

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

TM

03

81

49

06

07

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

2 - 40 l/min

Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)

± 1.5 % FS± 5.0 % FS (typical 3%)

Response time (63.2 %) < 1 sec.

Resolution 0.2 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80 °C ±1 °C

Accuracy (±1σ), 0 - 100 °C ±2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm²/s).

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (±5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Housing Composites (PPS, PA66)

Vortex tube 1.4408

Insert PPA 40 GF

Wetted materialsCorrosion-resistant coating, EPDM,

PPS, PPA 40-GF, 1.4408

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Vortex tube 110 x 29.8 x 31.5 mm

Insert 63.9 x 16 x 15.4 mm

Temperature (°C)Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

23

Page 24: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rtex

flow

se

ns

or, s

tan

da

rd

24

Grundfos Direct Sensors™3

VFS 5-100 QT, technical data

Vortex flow sensor, standard, 5-100 l/min

Fig. 75 VFS 5-100 sensor

Dimensions

Fig. 76 Dimensional sketches of VFS QT

Sensor output signals

Fig. 77 Flow response

Fig. 78 Temperature response

Specifications

TM

05

47

40

25

12

TM

00

5 4

67

2 2

51

2T

M0

3 8

21

7 0

80

7T

M0

3 8

14

9 0

60

7

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

Temperature (°C)Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

5 - 100 l/min

Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)

± 1.5 % FS± 5.0 % FS (typical 3%)

Response time (63.2 %) < 1 s

Resolution 0.5 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (±1σ), 25 - 80 °C ±1 °C

Accuracy (±1σ), 0 - 100 °C ±2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % (relative), non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 V DC (±5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Vortex tube 1.4408

Insert PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM,

PPS, PPA 40-GF, 1.4408

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawing

Vortex tube 129 x 37 x 32 mm

Insert 99.2 x 23.4x 21.9 mm

Page 25: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Vo

rte

x f

low

se

ns

or,

sta

nd

ard

Grundfos Direct Sensors™ 3

VFS 10-200 QT, technical data

Vortex flow sensor, standard, 10-200 l/min

Fig. 79 VFS 10-200 sensor

Dimensions

Fig. 80 Dimensional sketches of VFS QT

Sensor output signals

Fig. 81 Flow response

Fig. 82 Temperature response

Specifications

TM

05

47

39

25

12

TM

00

5 4

67

3 2

51

2T

M0

3 8

21

8 0

80

7T

M0

3 8

14

9 0

60

7

Flow (l/min)

Flo

w o

utp

ut

sig

na

l (V

)

Temperature (°C)Tem

pe

ratu

re o

utp

ut

sig

na

l (V

)

Flow

Measuring range:In water (0 - 100 °C)Tyfocor LS (30 - 100 °C)

10 - 200 l/min

Accuracy:In water (±1σ), (0 - 100 °C) Tyfocor LS (±1σ), (0 - 100 °C)

± 1.5 % FS± 5.0 % FS (typical 3%)

Response time (63.2 %) < 1.0 s

Resolution 1.0 l/min

Temperature

Measuring range 0 - 100 °C

Accuracy (± 1σ), 25 - 80 °C ± 1 °C

Accuracy (± 1σ), 0 - 100 °C ± 2 °C

Response time (63.2 % at 50 % FS flow)

250 ms

Resolution 0.35 °C

Media and environment

Media typesThe sensor is compatible with liquids

(kinematic viscosity ≤ 2 mm2/s)

Media temperature (operation)Water: 0 - 100 °C

Tyfocor LS: 30 - 100 °C

Media temperature (peak)–25 °C, non-freezing

120 °C for 5 minutes, up to 3 weeks in sensor lifetime

Ambient air temperature (operation)

–25 - 60 °C

Ambient air temperature (peak) –55 - 90 °C

Humidity 0 - 95 % RH, non-condensing

System burst pressure > 16 bar

Electrical data

Power supply5 VDC (± 5 %). Grounding of the sensor

supply is required (PELV)

Output signals Ratiometric

Flow signal 0.5 - 3.5 V (Zero at 0.35 V)

Temperature signal 0.5 - 3.5 V

Power consumption < 50 mW

Load impedance > 10 kΩ

Sensor materials

Sensing element Silicon-based MEMS sensor

Seal (sensor to housing) EPDM rubber

Vortex tube 1.4408

Insert PPA 40-GF

Wetted materialsCorrosion-resistant coating, EPDM,

PPS, PPA 40-GF, 1.4408

Environmental standards

Enclosure class IP44 (Non overmoulded IP20)

Temperature cycling IEC 68-2-14

Vibration (non-destructive) 20 - 2000 Hz, 10G, 4h

Electromagnetic compatibility EN 61326-1

Dimensions

Sensing element 47 x 40 x 20 mm, see drawings

Vortex tube 137 x 45 x 41 mm

Insert 104.2 x 30.4 x 28.9 mm

25

Page 26: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Pro

du

ct ra

ng

e

26

Grundfos Direct Sensors™4

4. Product range

VFI sensorScope of delivery:

• Sensor tube with sensor

• flanges (only for flange versions)

• union nuts (for threaded versions)

• 5 m cable with M12 connection in one end

• quick guide.

Complete product Flow rangePipe size

O-ring Connection typeProduct numberEPDM FKM

Cast iron flange

Stainless steel flange

Thread

VFI-··0.3-6m-1-C-M5.000X-FG6-SG-30F-A··1

0.3-6 m3/h DN 18

97686127

VFI-··0.3-6m-1-C-M5.000X-FG6-SG-30F-A··1 97686128

VFI-··0.3-6m-1-C-M5.000X-EG6-SS-30F-A··1 97688293

VFI-··0.3-6m-1-C-M5.000X-FG6-SS-30F-A··1 97688294

VFI- 0.3-6m-1-C-M5.000X-EG6-SS-07P-A 1 97688334

VFI-··0.3-6m-1-C-M5.000X-FG6-SS-07P-A··1 97688342

VFI-·0.6-12m-1-C-M5.000X-EG6-SG-30F-A··1

0.6-12 m3/h DN 25

97686129

VFI-·0.6-12m-1-C-M5.000X-FG6-SG-30F-A··1 97686130

VFI-·0.6-12m-1-C-M5.000X-EG6-SS-30F-A··1 97688295

VFI-·0.6-12m-1-C-M5.000X-FG6-SS-30F-A··1 97688296

VFI-·0.6-12m-1-C-M5.000X-EG6-SS-07P-A··1 97688335

VFI-·0.6-12m-1-C-M5.000X-FG6-SS-07P-A··1 97688343

VFI-·1.3-25m-1-C-M5.000X-EG6-SG-30F-A··1

1.3-25 m3/h DN 32

97686141

VFI-·1.3-25m-1-C-M5.000X-FG6-SG-30F-A··1 97686142

VFI-·1.3-25m-1-C-M5.000X-EG6-SS-30F-A··1 97688297

VFI-·1.3-25m-1-C-M5.000X-FG6-SG-30F-A··1 97688298

VFI-·1.3-25m-1-C-M5.000X-EG6-SS-09P-A··1 97688336

VFI-·1.3-25m-1-C-M5.000X-FG6-SS-09P-A··1 97688344

VFI-···2-40m-1-C-M5.000X-EG6-SG-31F-A··1

2-40 m3/h DN 40

97686143

VFI-···2-40m-1-C-M5.000X-FG6-SG-31F-A··1 97686144

VFI-···2-40m-1-C-M5.000X-EG6-SS-31F-A··1 97688299

VFI-···2-40m-1-C-M5.000X-FG6-SS-31F-A··1 97688300

VFI-·3.2-64m-1-C-M5.000X-EG6-SG-32F-A··1

2-64 m3/h DN 50

97686145

VFI-·3.2-64m-1-C-M5.000X-FG6-SG-32F-A··1 97686146

VFI-·3.2-64m-1-C-M5.000X-EG6-SS-32F-A··1 97688301

VFI-·3.2-64m-1-C-M5.000X-FG6-SS-32F-A··1 97688302

VFI-5.2-104m-1-C-M5.000X-EG6-SG-33F-A··1

5.2-104 m3/h DN 65

97686147

VFI-5.2-104m-1-C-M5.000X-FG6-SG-33F-A··1 97686148

VFI-5.2-104m-1-C-M5.000X-EG6-SS-33F-A··1 97688303

VFI-5.2-104m-1-C-M5.000X-FG6-SS-33F-A··1 97688304

VFI-··8-160m-1-C-M5.000X-EG6-SG-35F-A··1

8-160 m3/h DN 80

97686149

VFI-··8-160m-1-C-M5.000X-FG6-SG-35F-A··1 97686150

VFI-··8-160m-1-C-M5.000X-EG6-SS-35F-A··1 97688305

VFI-··8-160m-1-C-M5.000X-FG6-SS-35F-A··1 97688306

VFI-·12-240m-1-C-M5.000X-EG6-SG-37F-A··1

12-240 m3/h DN 100

97686151

VFI-·12-240m-1-C-M5.000X-FG6-SG-37F-A··1 97686152

VFI-·12-240m-1-C-M5.000X-EG6-SS-37F-A··1 97688308

VFI-·12-240m-1-C-M5.000X-FG6-SS-37F-A··1 97688309

Page 27: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Pro

du

ct

ran

ge

Grundfos Direct Sensors™ 4

VFS sensor

Sensor selectionGrundfos offers a wide range of custom-built variants of the VFS sensorthat can be customized to meet individual requirements.

Due to the large variation of VFS sensors, all VFS sensors cannot be listed in one table. Therefore, the tables below give a point of selection to choose from. Be aware that not all combinations are possible. Therefore, if you have any questions regarding selection, please contact Grundfos Sensors.

Example of a type key:

VFS -·20-400L-1-D-C1.200E-·G4-CS-25P-W··1

1. Product group

2. Product range and units:

3. Generation:

4. Electrical output type:

5. Cable and connectors:

– Middle letters: 1.200 is cable length in m

– First and last letters: Cable connector

6. Sealing material and enclosure class

– Material:The first letter represents the flow pipe, the second represents the mechanical connection part.

7. Dimension of mechanical connection

8. Mechanical connection type

9. Packaging

1 2 3 4 5 6 7 8 9 10

VFS 20 - 400 L 1 D C1.200E G4 CS 25 P W··1

Product range Range of unit

20-400 L: litres/min.

Code Generation

1 1st generation

2 2nd generation

3 3rd generation

Code Output

B 0-10 V

C 4-20 mA, 2 wires

D 0.5-3.5 V

E 0.5-4.5 V

F 2 x 0-10 V

G 4-20 mA, 3 wires

Code Cable connector description

B FCI 90312-004LF/77138-101

C CKM 42010107/42010311, tin plated

D AMP 103648-3/104479-9

E Molex 51004-0400/50011-8000

F AMP 172167-1/0-170365-1

G Tyco Val-U-Lok 794954-4/794958-2, gold plated

J JST XHP-4/SXH-001T-P0.6

L Lumberg 3510-04 K02

N Lumberg 3510-04 K03

PMolex 43025-0400/43030-0005, 43030-001/ Cembre 1910M16

Q Molex 43025-0400/43030-0006

R Molex 51004-0400/50011-8000/ Cembre 1900M12

X Open ended

Code Sealing description

E EPDM (drinking water approved)

F FPM (for use in oily media)

G Gel-filled

Code Enclosure class

2 IP20

4 IP44

5 IP55

6 IP67

Code Material description

B Brass

C Composite

G Cast iron

Q Stainless steel flow pipe with composite insert (QT)

S Stainless steel

Code Dimension Code Dimension

03 G ½" 17 7/16"

04 G ¾" 19 18.75mm

05 G1" 21 21.5mm

06 6mm 24 1/8 - 27

07 G 1¼" 25 3/4 - 14

08 8mm 26 1 - 11.5

09 G 1½" 27 1 ¼ - 11.5

10 G 1½" 51 f1" - G ¾

11 G 2½" 52 f1¼" - G 1

12 G 3" 63 G ½ with ventilation opening

13 G4"

Code Description

B BSPT (ISO 7/1)

C Compression

F Flange

G Flange and BSPP (ISO 228/1)

K Clips

M NPSM

N NPT

P BSPP (ISO 228/1)

S Sweat

T Tube

U UNF

Code Description of packaging

A Set with pre-assembled components

P Spare parts set

S Set

V Service set

W Blister pack, standard Grundfos cardboard

N Blister pack, white cardboard

1 1 piece

10 Bulk 10

25 Bulk 25

50 Bulk 50

100 Bulk 100

500 Bulk 500

27

Page 28: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Ac

ce

ss

orie

s

28

Grundfos Direct Sensors™5

5. Accessories

Sensor interface, type SI 001 PSUSI 001 PSU from Grundfos Direct Sensors™ is an external power supply for Grundfos sensors and other transmitters with 24 VDC supply voltage.

The power supply is to be used where the distance between the transmitter and the controller exceeds 30 m.

Fig. 83 Sensor interface, SI 001 PSU

Specification:

• Voltage range: 110-400 VAC

• frequency range: 50-60 Hz

• ambient temperature: -20 to +50°C

• enclosure class: IP54.

Sensor interface, type SI 010 CNVSI 010 CNV from Grundfos Direct Sensors™ is an external power supply, signal amplifier and signal converter for Grundfos sensors.

SI 010 CNV has built-in precision resistors enabling the transmitter to give 4-20 mA, 1-5 V and 2-10 V output signals.

SI 010 CNV should be used in applications where sensors from the standard product range are used, but the controller requires a 4-20 mA input signal.

Fig. 84 Sensor interface, SI 010 CNV

Specification:

• Voltage range: 115-230 VAC± 10% or 24 VDC

• frequency range: 50-60 Hz

• power consumption: Max. 2.5 W

• ambient temperature: -20 to +50°C

• enclosure class: IP20.

TM

04

41

94

08

09

Part Product No.

Sensor interface, SI 001 PSU 96915820

TM

04

48

82

22

09

Part Product No.

Sensor interface, SI 010 CNV 96983684

Page 29: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Ap

pe

nd

ix

Grundfos Direct Sensors™ 6

6. Appendix

Installation of VFI sensor

TM

05

23

06

48

11

min. 10 x D 1 min. 5 x D 1

D

0 bar

min. 20 x D 1 -0,05 bar (0.725 PSI)

D

-30 to 120 °C (-22 to 248 °F)

-25 to 60 °C(-13 to 140 °F)

Max. 28 bar(406 PSI) IP67

29

Page 30: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Ap

pe

nd

ix

30

Grundfos Direct Sensors™6

Minimum flow rate

Minimum flow rate as a function of the kinematic viscosity

The minimum detectable flow rate (Qmin.) for the VFI sensors depends on the kinematic viscosity of the liquid. The chart below shows Qmin as a function of the kinematic viscosity.

*Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s.

TM

04

80

01

27

10

0.1 1 100.4

0.9

1.3

1.8

2.2

2.63.13.54.0

9

13

18

22

26313539

4.5

44

88

132

176

220

GPM

Kinematic Viscosity [cSt]

DN100

DN80

DN65

DN50

DN40

DN32

DN25

DN18

*

Page 31: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Ap

pe

nd

ix

Grundfos Direct Sensors™ 6

Pressure drop curves

Reference condition:

- Liquids at 20 °C, 1013 mbar, ρ = 998 kg/m3, v = 1 x 10-6 m2/s.

TM

04

93

90

43

10

00.30.3 0.4 0.6 0.8 11 1.2 1.5 2 3 4 5 6 8 1010 12 15 20 30 40 50 60 80 100100 150 200 300Q [m³/h]

0.01

0.02

0.03

0.04

0.050.06

0.08

0.10.1

0.2

0.3

0.4

0.50.6

0.8

1.001.00

2.00

3.00

4.00

5.006.00

[psi]p

1010 20 30 40 50 60 80 100100 200 300 400 Q [US GPM]

DN100

DN18

DN25

DN32

DN40 DN50DN65

DN80

31

Page 32: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Fu

rthe

r pro

du

ct d

oc

um

en

tatio

n

32

Grundfos Direct Sensors™7

7. Further product documentation

WebCAPSWebCAPS is a Web-based Computer Aided Product Selection program available on www.grundfos.com.

WebCAPS contains detailed information on more than 185,000 Grundfos products in more than 20 languages.

In WebCAPS, all information is divided into 6 sections:

• Catalogue

• Literature

• Service

• Sizing

• Replacement

• CAD drawings.

Catalogue

This section is based on fields of application and pump types, and contains

• technical data• curves (QH, Eta, P1, P2, etc.) which can be adapted to the

density and viscosity of the pumped liquid and show the number of pumps in operation

• product photos• dimensional drawings• wiring diagrams• quotation texts, etc.

Literature

In this section you can access all the latest documents of a given pump, such as

• data booklets• installation and operating instructions• service documentation, such as Service kit catalogue and

Service kit instructions• quick guides• product brochures.

Service

This section contains an easy-to-use interactive service catalogue. Here you can find and identify service parts of both

existing and discontinued Grundfos pumps.Furthermore, this section contains service videos showing you

how to replace service parts.

Page 33: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

Fu

rth

er

pro

du

ct

do

cu

me

nta

tio

n

Grundfos Direct Sensors™ 7

WinCAPS

Fig. 85 WinCAPS CD-ROM

WinCAPS is a Windows-based Computer Aided Product Selection program containing detailed information on more than 185,000 Grundfos products in more than 20 languages.

The program contains the same features and functions as WebCAPS, but is an ideal solution if no Internet connection is available.

WinCAPS is available on CD-ROM and updated once a year.

Sizing

This section is based on different fields of application and installation examples, and gives easy step-by-step instructions in

how to• select the most suitable and efficient pump for your installation• carry out advanced calculations based on energy

consumption, payback periods, load profiles, life cycle costs, etc.

• analyse your selected pump via the built-in life cycle cost tool• determine the flow velocity in wastewater applications, etc.

Replacement

In this section you find a guide to selecting and comparing replacement data of an installed pump in order to replace the

pump with a more efficient Grundfos pump. The section contains replacement data of a wide range of pumps

produced by other manufacturers than Grundfos.

Based on an easy step-by-step guide, you can compare Grundfos pumps with the one you have installed on your site.

When you have specified the installed pump, the guide will suggest a number of Grundfos pumps which can improve both

comfort and efficiency.

CAD drawings

In this section it is possible to download 2-dimensional (2D) and 3-dimensional (3D) CAD drawings of most Grundfos pumps.

These formats are available in WebCAPS:

2-dimensional drawings:• .dxf, wireframe drawings• .dwg, wireframe drawings.

3-dimensional drawings:• .dwg, wireframe drawings (without surfaces)• .stp, solid drawings (with surfaces)• .eprt, E-drawings.

0 1

33

Page 34: GRUNDFOS DATA BOOKLET - Daparak · Sensor selection 27 5. Accessories 28 Sensor interface, type ... The trademark Grundfos Direct Sensors™ is owned and controlled by the Grundfos

GRUNDFOS A/S . DK-8850 Bjerringbro . DenmarkTelephone: +45 87 50 14 00www.grundfos.com

The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.

Being responsible is our foundationThinking ahead makes it possible

Innovation is the essence

97790189 0912 GBRepl.

GPipes
Stamp