Click here to load reader

GRAFIK Eye QS Control Unit - Lutron Electronics, Inc ... qsgrja.pdf · PDF fileSPECIFICATION SUBMITTAL Page ... intuitive lighting presets, and ... • Any zone on the GRAFIK Eye

  • View
    229

  • Download
    4

Embed Size (px)

Text of GRAFIK Eye QS Control Unit - Lutron Electronics, Inc ... qsgrja.pdf · PDF...

  • Job Name:

    Job Number:

    Model Numbers:

    PageSPECIFICATION SUBMITTAL

    GRAFIK Eye QS Control Unit

    LUTRON

    1

    2

    3

    4

    Off

    Preset

    Close

    Open

    DescriptionGRAFIK Eye QS is the premier energy-saving light and shade control. GRAFIK Eye QS includes an astronomic timeclock, intuitive lighting presets, and direct shade control. Additionally, the GRAFIK Eye QS is compatible with all Lutron wired QS products and systems, including Quantum.

    Mechanical Dimensions

    4$ in (119 mm)

    94 in (239 mm) 4 in

    (10 mm) 2 in (51 mm)

    Front View Side View

    Fits into a 4-gang U.S. backbox, 3` in (89 mm) deep; Lutron P/N 241-400.

    System Topology

    LUTRONLUTRON

    LUTRON LUTRON

    LUTRON

    LUTRON LUTRON

    LUTRON

    LUTRON

    LUTRON

    LUTRONLUTRON

    LUTRON LUTRON

    LUTRON

    LUTRON LUTRON

    LUTRON

    LUTRON

    LUTRON

    Example of Wired System

    QSE-CI-NWK-E

    Sivoia QS shade

    seeTouch QS

    seeTouch QS

    Wired occupancy

    sensor

    GRAFIK Eye QS GRAFIK Eye QS

    Wired QS link

    Quantum (optional)

    QS Sensor Module

    Energi Savr NodeTM

    Preset Dimming Controls

    369430 Rev. A 1 04.25.11

    100 V Control Unit

  • Job Name:

    Job Number:

    Model Numbers:

    PageSPECIFICATION SUBMITTAL

    FeaturesPushbuttonrecalloffourpresetlightingscenes,plusOff.

    Twelve(12)additionalscenesaccessiblethrough other QS devices, such as seeTouch QS wallstations.

    Optionalintegratedshadecontrolbuttons,whichcanalsobeaddedtotheunitafterinstallation.

    Masteroverridebuttonstoraiseandloweralllights.

    Allowssetupoflightingscenesandshadepresets using buttons on the control unit.

    Built-ininfrared(IR)receiver.ExternalIRconnection.Built-inastronomictimeclock. Infoscreenshowszonelightlevelpercentage,energysavings,zonelabeling,andprogramming.

    Lockoutoptionpreventsaccidentalchanges.Oneoccupancysensorinputand24V powerforoccupancysensor.

    QScommunicationlinkforseamlessintegrationoflights,motorizedwindowtreatments, occupancy sensors, wallstations, andintegrationinterfaces.

    CompatiblewithallLutronQSsystemcomponents.

    Backlitbuttonswithengravingmakeuniteasyto locate and operate.

    Availableinavarietyofcolorsandfinishes.

    LUTRON

    OK

    1 2 3 4 5 6

    Optional shade control keypad

    Zone control

    Infraredreceiver

    USB type mini B

    Infoscreen

    Lighting control keypad

    1

    2

    3

    4

    Off

    Off

    Preset

    Close

    1

    2

    3

    4

    Open

    Preset

    Close

    Open

    Note: General Engraving (-EGN) shown.

    Preset Dimming Controls

    369430 Rev. A 2 04.25.11

    100 V Control Unit

  • Model Numbers:

    PageSPECIFICATION SUBMITTAL

    Job Name:

    Job Number:

    Key Design FeaturesLightningstrikeprotectionmeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesofupto 6000 V andcurrentsurgesofupto3000A.

    Testedtowithstand16kVelectrostaticdischargewithout damage or memory loss.

    RTISSTM-equipped:Compensatesinrealtimeforincominglinevoltagevariations(novisibleflickerwith+/-2%changeinRMSvoltagepercycle,and+/-2%Hzchangeinfrequencypersecond).

    Powerfailurememoryretainsprogrammingandlightlevelsettingsforupto10yearsintheeventofapowerloss.

    TheGRAFIKEye QS supplies 3 Power Draw Units (PDUs) on the QS link. Forcompleteinformation,seePowerDrawUnitsonthe QS Link, Lutron PN 369405.

    Faceplateishingedatthetopandbottom,andstaysopenat180foreaseofaccess.

    Scene and Shade ButtonsLarge,roundedbuttonsareeasytouse.Backlitbuttonswithoptionalengravingmakeiteasytofindandtooperatethecontrolunitinlowlightconditions (backlight can be disabled).

    Optionalbuttonengravingisangleduptotheeyeforeasy reading.

    Predefinedlabelstickersareincludedforfieldlabeling.4presetlightingscenes,plusOff,areaccessiblefromthefrontofthecontrolunit.

    12additionalscenesarestoredinthecontrolunitandareaccessiblefromseeTouch QS wallstations and QSinterfaces.

    Lightlevelsfadesmoothlybetweenscenes.Fadetimecanbesetdifferentlyforeachscene:0to59seconds,or1to60minutes.MaximumfadetimefromOffis 3 seconds.

    Input Power100V 50/60Hz

    Environment32to104F(0to40C).Relativehumiditylessthan90%non-condensing.

    Lighting Sources/Load TypesControlsthefollowinglightingsourceswithasmooth,continuoussquarelawdimmingcurveoronafullconduction non-dim basis:

    IncandescentHalogenMagneticlow-voltagetransformerNeonandcoldcathodeNon-dim(incandescent,magneticlow-voltage,

    or neon/cold cathode) PleaserefertoCapacitiesformoreinformation.

    Controlsthefollowinglightingsourceswithasmooth,continuoussquarelawdimmingcurveoronafullconduction non-dim basis through separate Lutron power interfaces:

    Electroniclow-voltagetransformerNon-dim0-10V

    Capacities

    100 V 50 / 60 Hz

    Unit Capacity (watts) 1600

    MLV 1600 VA / 1200 W

    Zone Capacity (watts) 25 600

    MLV 25 600 VA / 25 480 W

    Load Type NotesAllelectroniclow-voltage(ELV)lightingusedwithaninterfacemustberatedforreversephasecontroldimming.BeforeinstallinganELVlightsource,verifywiththemanufacturerthattheirtransformercanbedimmed.Whendimming,anELVinterface(suchasthePHPM-PA-DV-WH) must be used with the control unit.

    Notallzonesmustbeconnected;however,connectedzonesmusthaveaminimumloadasspecifiedabove.

    Nozonemaybeloadedwithmorethanthecapacityspecifiedabove.Forhigherwattageapplications,useLutron power module PHPM-PA-JA or PHPM-SW-JA.

    System LimitsTheQSwiredcommunicationlinkislimitedto100devicesor100zones.

    Specifications

    Preset Dimming Controls

    369430 Rev. A 3 04.25.11

    100 V Control Unit

  • Job Name:

    Job Number:

    Model Numbers:

    PageSPECIFICATION SUBMITTAL

    Astronomic Timeclock Integraltoallunits.7dailyschedulesavailable.Oneavailableholidayscheduleisprogrammableby

    date up to one year in advance.25eventsperdaymaximum.TimeclockeventsareprogrammabletocontrolscenesthataffectanyEnergiSavrNodeTM unit connected on the QS link without changing the local scene on the GRAFIK Eye QS.

    Astronomictimesareprogrammablebyintegralcitydatabase or by entering latitude and longitude. Times automatically adjust throughout the year based on location.

    Localtimeclockeventscanactivateanyofthefollowingfeatures:

    -Scenes1to16andOff - Any available shade presets -StartandEndafterhoursmode -EnableandDisabledaylightingforallzones/groups -EnableandDisableoccupancyforoccupancy/

    vacancy sensors -EnableandDisableoccupiedeventsforalloccupancy

    sensors

    System Communications and CapacitiesLow-voltagetypeIECPELV/NEC Class 2 wiring connectscontrolunits,wallstations,motorizedshades,andcontrolinterfaces.

    AQSsystemcanhaveupto100devicesand100zones.

    Infrared Infrared(IR)receiverallowsinfraredtransmitterstoselect8scenes,raise/lowerlightingzones,orraise/lower shades.

    Transmitterbuttonsimitatebuttonsonfaceplate.50ft(15m)lineofsightrange.TerminalblockinfraredinputforconnectiontoawiredIRinputfromthird-partyequipment.

    IRcanbedisabledviaprogramming.WorkswithLutronGRX-ITandGRX-8ITinfraredremote

    controls.

    Shade ControlTheGRAFIKEye QS can include up to 3 shade button

    columns. Each column has backlit open, preset, close, and raise/lower buttons.

    Eachshadebuttoncolumncanbeprogrammedtooperateoneshadeoragroupofshades.(Shadesmaybe assigned to more than one shade button column).

    Faceplatesareavailablewith1,2and3shadebuttoncolumns.

    Zone ControlEachzonehasadedicatedraiseandlowerbuttontoadjustthezone.

    Eachzonehasadedicated7LEDbargraphforlevelstatus.Percentageoflightlevelandenergysavedisdisplayedontheinfoscreen.

    AllzoneinformationhasbluebacklitLEDs.Backlightturnsoffwhenidlefor30seconds.

    Info ScreenOLED(organicLED)screenisviewablefromallangles.Screenturnsoffwhenidlefor30seconds.Programmablezonelabels.Programmablescenelabels.Statusofreal-timezonepercentageandenergysavings.Programmabletimeclockschedules.Programmableshadelabels.

    Specifications

    Preset Dimming Controls

    369430 Rev. A 4 04.25.11

    100 V Control Unit

  • Job Name:

    Job Number:

    Model Numbers:

    PageSPECIFICATION SUBMITTAL

    SpecificationsAccessory Controls: seeTouch QS Wallstations (QSWS2)

    WiredseeTouchQSkeypadsprovidethefollowingfeatures:

    -Accesstooneormoreofthe16scenesontheGRAFIK Eye QS

    -Zonetoggle,partitioning,sequencing,finetune,panicmode, and timeclock enable/disable

    - Contact closure inputs -Certainfunctionsareonlyavailableonspecific

    wallstationconfigurations.RefertotheseeTouch QS specificationsubmittal.

    Accessory Controls: QS Sensor Module (QSMX-4W)TheQSSensorModuleprovidesameanstolinkwired

    occupancy and daylight sensors to a GRAFIK Eye QS via the wired QS link.

    - Occupancy sensors wired to a QS Sensor Module can be used by one or more GRAFIK Eye QS control units on the wired link.

    - Daylight sensors wired to a QS Sensor Module can be used by one or more GRAFIK Eye QS control units on the wired link.

    -Infraredsensorscancontroleitheroneormorezonesor scenes on the GRAFIK Eye QS. Functionality varies; refertothedocumentationfortheQSSensorModulefordetails.

    Accessory Controls: Contact Closure Input/Output Interface (QSE-IO)

    Recallspresetlightlevelsforthefollowingsetofsceneson the GRAFIK Eye QS:Scenes1-4andOff Scenes9-12andOff Scenes5-8andOff Scenes13-16andOff

    Sequencescenes5-16,Enable/DisableZoneLockout,Enable/Disable Scene Lockout, Enable/Disable Panic Mode, Enable/Disable Timeclock.

    OccupancySensors.Anindividualinputcountsas1occupancysensorfortheGRAFIKEye QS. Each input can be assigned to either Scene Control or Z