GLOBAL SECURE

Sustainable Energy through China-UK Research Engagement (SECURE)

Principal Investigator: Professor AP Roskilly

Project Duration: 12 Months

Funding Body: EPSRC

http://research.ncl.ac.uk/globalsecure/

Page 2: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

China-UK Seminar on Sustainable Energy & New Power-Train System Technologies

Beijing Institute of Technology (BIT) in China

23-24 March 2013

Organised by BIT, University of Newcastle Upon Tyne (UNEW) &

Chinese Society for Internal Combustion Engine (CSICE)

Page 3: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Theme 3 ‘Low Grade Heat Driven Cogeneration of Power & Cooling’

Dr Yaodong Wang, Dr Huashan Bao, Mr Constantinos Charalambous

Sir Joseph Swan Centre for Energy Research

Newcastle Institute for Research on Sustainability

Newcastle University

Prof Ruzhu Wang, Prof Liwei

Wang, Dr Zisheng LU

Institute of Refrigeration and

Cryogenics

Shanghai Jiao Tong University

Page 4: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Contents Introduction

Principle of LH Cogen system

Experimental test rig and initial results

1

2

3

Outcomes 4

Future work - project roadmap and 5

year engagement plan 6

Conclusion 5

Page 5: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

1. Introduction • Background The project is highly relevant to the priority areas of Energy and

Environmental Change issues.

Fossil fuels are the main sources of

energy we use today

Page 6: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

• Objective Demonstration of the combination of adsorption chiller and electrical

power generator using low grade heat from the sun or industries

refrigeration

power Low grade

heat

An adsorption-linear-

cogeneration system

(LH Cogen)

Page 7: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

• Project partners: • Shanghai Jiaotong University (working on cooling unit )

• Beijing Institute of Technology (working on linear expander unit )

Page 8: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

2. Principle of LH Cogen system

Power generation

process

Cooling

process

Page 9: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

3. Experimental test rig and initial results

Page 10: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Test setup in lab

Adsorption chiller in Lab Cooling tower outside the Lab

Data collection devices Control panel of chiller

Page 11: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Operating conditions of Cooling test Heating T(oC) Evaporation T(oC) Heat sink T(oC) Cycle time(min) Mass recovery time

135

0 20

10 1 min

13

30 sec

1 min

2 min

16 1 min

18 1 min

30 13 1 min

-5 20

10 1 min

13

30 sec

1 min

2 min

16 1 min

18 1 min

-10 20 13 1 min

145

-5

20 13 1 min -10

0

125

-5

20 13 1 min -10

0

110 0

20 13 1 min -5

100 0 20 13

1 min 16

Page 12: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Cooling test results

0

0.02

0.04

0.06

0.08

0.1

0.12

90 100 110 120 130 140

CO

P

Heating temperature (oC)

-5 oC

-10 oC

0 oC

0

0.02

0.04

0.06

0.08

0.1

0.12

10 11 12 13 14 15 16 17 18 19 20

CO

P

Cycle time (min)

0 oC

-5 oC

10+1

13+1 16+1

18+1

13+0.5

13+2

First test results: the average cooling power was 2.88 kW at evaporation

temperature -4.5 oC, with average COP and maximum COP values around 0.18

and 0.27 , respectively.

Page 13: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Scroll expander tested with compressed air

60

70

80

90

100

110

120

130

140

150

160

170

180

0 2 4 6 8 10 12 14 16 18 20

Ou

tpu

t p

ow

er

(W)

Time (min)

90 oC

60 oC

20 oC

Output power generated with compressed

air at different inlet temperature.

Temperature of

compressed air (oC)

Average

Power (W)

Average

Current (A)

Average

Voltage (V)

Increase rate of

power with

temperature

Increase rate of

voltage with

temperature

Increase rate of current

with temperature

20 107.0 1.11 98.0

60 124.52 1.20 112.65 16.37% 8.1% 14.95%

90 158.83 1.28 126.55 27.55% 6.7% 12.34%

Table 1. Average value of the

output

The compressed air pressure

remained around 3.0~4.0 bar;

Three different compressed air

temperature were 20 oC, 60 oC,

and 90 oC, respectively.

The flow rate was around

136.31 L/min when the air was

heated at 90 oC

Page 14: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Linear expander results

Peak power at different intake pressure

Power output at 6 bar intake pressure

Page 15: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

Integration with expander

Page 16: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

4. Outcomes

• A joint-paper draft has been produced:

Experimental study of the performance of a free piston

engine (linear expander) driven by high pressure air

• A report of experimental results from the tests of the

adsorption unit

Page 17: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

5. Conclusions

• Cooling effect is achieved

• Expansion with air driven for power generation using expander show that it is working

• Further tests on the LH Cogen unit required

Page 18: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

6. Future work - project roadmap report and 5 year engagement plan

• Project roadmap: • Further study by simulation and experiment will be carried on

• Economic and/or Life cycle analysis of LH Cogen system production, transportation and use

• Control and optimisation of LH Cogen system

• Application to different low grade heat sources and different applications

Page 19: GLOBAL SECURE - Newcastle Universityresearch.ncl.ac.uk/pro-tem/components/pdfs/material_disseminations...GLOBAL SECURE Sustainable Energy ... 5 Conclusion . 1. ... Adsorption chiller

5 year engagement plan:

• Further study by simulation and experiment will be carried on – work with Shanghai Jiaotong, Beijing Institute of Technology

• Economic and/or Life cycle analysis of LH Cogen system production, transportation and use: work with Shanghai Jiaotong

• Control and optimisation of LH Cogen system: work with Shanghai Jiaotong and BIT

• Application to different low grade heat sources and different applications: Shanghai Jiaotong