GILA-KNOB 230KV TRANSMISSION LINE REBUILD PHASE I (STRUCTURES 4/7 TO 5/2)
ARIZONA
SECTION C DESCRIPTION/SPECIFICATIONS
Spec. No. 883
Existing Gila-Knob structure 4/8, looking south
GILA-KNOB 230kV TRANSMISSION LINE REBUILD PHASE 1, (STRUCTURES 4/7 TO 5/2)
PROJECT DRAWINGS
A. GENERAL:
CONSTRUCTION STANDARD DRAWINGS: A complete set of standard drawings are available at https://www.wapa.gov/DoingBusiness/SellingToWestern/Pages/what-western-buys.aspx. Construction drawings are the specification drawings and any additional drawings required for use in construction. The construction drawings will be issued after contract award and may include amendment changes and other details, which make the drawings suitable to use for construction purposes.
PROJECT DRAWINGS: Project drawings included herein are reduced reproductions and are not to scale. Some project drawings show details of fabrication and other information not a part of the work. Disregard information and details, which are not applicable.
STANDARD DRAWINGS: Where details shown on standard drawings included herein differ from project drawings or text, the details of project drawings or text shall govern.
INFORMATIONAL DRAWINGS: Some project drawings have the words “FOR INFORMATION ONLY” appearing above the title block. These drawings show some information, which may be required for bidding purposes. These drawings do not show items to be furnished or work to be performed.
EXISTING INSTALLATION DRAWINGS: Some project drawings have the words “EXISTING INSTALLATION” appearing above the title block. These drawings show the existing installations prior to modifications and may show some new work to be performed.
REFERENCE DRAWINGS: Reference drawings referred to on project drawings and not included herein, are not necessary for bidding purposes.
CONTRACTOR'S RESPONSIBILITY: Check all drawings and advise Western of any errors or omissions.
B. LIST OF DRAWINGS:
LOCATION MAP:
1. GLA 0015 Rev. C – Location and Vicinity Map
EXISTING TRANSMISSION LINE STRUCTURES FOR REMOVAL:
2. 41 6006 REV. B (FIO) – Type HS 138KV and 161KV Suspension Structure (For Information Only)
3. 41 6013 REV. E (FIO) – Type 3A 138, 161, and 230KV Medium Angle Structure (For Information Only)
4. 41 6017 (FIO) – Type 3T 138KV and 161KV 3-Pole Tension Structure (For Information Only)
TRANSMISSION LINE PLAN AND PROFILES:
5. GLA-KNB T400 – Plan and Profile (FIO) (For Information Only)
6. GLA-KNB 4207 REV. A – Plan and Profile STR. 4/7 to STR. 5/2
7. GLA-KNB 4208 REV. A – Plan and Profile STR. 4/8R to STR. 4/10R
TRANSMISSION LINE ELECTRICAL:
8. GLA-KNB 1004 – Material Quantities
9. GLA-KNB 1005 – Vibration Dampers
TRANSMISSION LINE STEEL POLE STRUCTURE FOUNDATIONS:
10. GLA-KNB 2101 Rev. A – Type 266M Steel Pole Structures Foundations
11. GLA-KNB 2102 – Type 281N & 281S Steel Pole Structures Foundations
TRANSMISSION LINE STEEL POLE STRUCTURES:
12. 43 266M 2200 – 266M Pole Structures Outline and Design Loads
13. 43 281N 2200 Rev. A – 281N Steel Pole Structures Outline and Design Loads
14. 43 281S 2200 – 281S Pole Structures Outline and Design Loads 15. 43 2206 Rev. H – Maintenance Provisions Outlines
16. 43 2207 Rev. G – Maintenance Provisions Outlines
17. 43 2208 Rev. H – Maintenance Provisions Outlines 18. 43 2210 Rev. I – Maintenance Provisions Details
19. 41 9027 Rev. E – Aerial Patrol Mile Marker and Structure Number Signs 20. 41 2701 Rev. A – Fall Protection Anchorage Plates
GEOLOGY: 21. GLA-GNB 8000 – Site Plan and Boring Locations
22. GLA-GNB 8001 – Boring Log No. B-1 (Page 1 of 2)
23. GLA-GNB 8002 – Boring Log No. B-1 (Page 2 of 2)
24. GLA-GNB 8003 – Boring Log No. B-2 (Page 1 of 2) 25. GLA-GNB 8004 – Boring Log No. B-2 (Page 2 of 2)
26. GLA-GNB 8005 – Boring Log No. B-3 (Page 1 of 2)
27. GLA-GNB 8006 – Boring Log No. B-3 (Page 2 of 2) 28. GLA-GNB 8007 – Boring Log No. B-4 (Page 1 of 2)
29. GLA-GNB 8008 – Boring Log No. B-4 (Page 2 of 2)
1
K
K
K
2
KK
KK
K
KK KK KK
K
KK
K
K
3
KK
K
K
K
K
K
4
160+00 170+00 180+00 190+00 200+00 80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
PI 57°0
5'5
5"
PI 57°0
5'5
5"
PI -5
9°2
9'2
8"
GL
A-S
EW
69
KV
(W
AP
A)
16
3+
42
, E
X-4
/8
HS
-90
16
9+
27
, E
X-4
/9
80
-70
-80
3A
1199
PI -5
9°2
9'2
8"
PI -5
2°2
5'5
9"
17
6+
91
, E
X-4
/10
H
S-6
0
788 596 832
632
NG
A-H
AN
G2
5
00
-KV
(A
PS
)
NG
A-P
V
50
0-K
V (
AP
S)
NG
A-I
MP
5
00
-KV
(A
PS
)
PI -5
2°2
5'5
9"
PI 55°3
2'2
1"
18
5+
32
, E
X-4
/11
7
0-6
0-7
0 3
A
19
0+
74
, E
X-5
/1 H
S-5
5
19
6+
14
, E
X-5
/2
65
-55
-65
3T
-2
570
539
EX
-4/8
EX
-4/9
EX
-4/6
EX
-4/7
NO
RTH
GIL
A S
UB
(AP
S)
GILA GRAVITY CANAL
185 FT R-O-W
EX
-4/9
EX
-4/1
0
EX
-4/1
1
NORTH GILA SUB (APS)
T8S,R22W,SEC.11 YUMA CO., AZ
NG
A-H
AN
G2
500
-KV
(A
PS
)
NG
A-P
V
500
-KV
(A
PS
)
NG
A-IM
P
500-K
V (A
PS
)
100 FT R-O-W
EX
-4/1
1
EX
-5/1
EX
-5/2
T8S,R22W,SEC.11
YUM
A CO., AZ
4/8R 4/9R 4/10R
WESTERN AREA POWER ADMINISTRATION UNITED STATES DEPARTMENT OF ENERGY
C A
E
HEADQUARTERS - LAKEWOOD, COLORADO
PLS
CENTERLINE
APPROVED DESIGNED STEVE ROCK
ELECTRICAL ENGINEERING MANAGER
ALLEN TURNER
R-O-W EDGE
R-O-W EDGE
GILA - KNOB 161-KV TRANSMISSION LINE
ARIZONA
PLAN AND PROFILE
GLA-KNB
1" = 200' HORIZONTAL
1" = 40' VERTICAL
SCALE:
200' 0' 100'
40' 0' 20'
CONDUCTOR - 300 KCMIL 12-STRAND ANACONDA TYPE 178/R2 (HOLLOW "EYE-BEAM")
OGW - 7/16-INCH 7-STRAND HS STEEL
FOR INFORMATION ONLY
MARCH 25, 2016 T400
EXISTING STR. 4/7 TO EXISTING STR. 5/2
GL
A-K
NB
4-7
TO
5-2
.XY
Z
PA
TH
: S:\P
RO
JEC
TS
\TR
AN
SM
ISS
ION
LIN
ES
\GIL
A_K
NO
B.R
EB
UIL
D.2
015\
PLS
CA
DD
\XY
Z\ G
LA-K
NB
4-7
TO
5-2
.XY
Z
PLS
-CA
DD
PR
OJE
CT
LIN
E `
ED
IT`:
"A
PS
AP
PR
OA
CH
SP
AN
S; A
H &
BK
300
KC
MIL
CO
PP
ER
" T
HIS
SH
EE
T G
EN
ER
AT
ED
: 3/2
5/20
16 -
12:
23:4
7 P
LS-C
AD
D V
ER
SIO
N 1
4.00
X64
- A
TU
RN
ER
15
7+
59
, E
X-4
/7
9
5-8
5-9
5 3
T-2
5
60+00 70+00 80+00 90+00 100+00 60
80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
60
80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
PI
0°2
0'0
2"
GL
A-N
GA
69
KV
(W
AP
A)
EXISTING CO AND
PI
52°4
0'3
8"
EX
-4/6
ONDUCTOR OGW BACK
PI
52°4
0'3
8"
PI
-54°4
8'0
1"
EX
-4/7
95
-85
-95
3T
-2
GL
A-S
EW
69
KV
(W
AP
A)
EX
-4/8
HS
-90
4/7
2
81
N-7
0 (
BP
) S
TA
=6
1+
31
X
=4
72
92
4.7
3
Y=
63
50
75
.46
O
PG
W S
PL
ICE
1252, 1209
PI
-54°4
8'0
1"
PI
-47°4
3'1
4"
EX
-4/1
0 H
S-6
0
4/8
L
26
6M
-65
(B
P)
ST
A=
73
+3
9
X=
47
29
86
.19
Y
=6
36
28
2.4
3
WA
RN
ING
AR
RO
W "
UP
" L
OO
KIN
G A
HE
AD
O
PG
W L
EF
T
(S
OU
TH
) P
OL
E
4/9
L
26
6M
-45
(B
P)
ST
A=
81
+2
7
X=
47
23
66
.41
Y
=6
36
76
8.6
6
OP
GW
LE
FT
(
SO
UT
H)
PO
LE
788 596
NG
A-H
AN
G2
5
00
-KV
(A
PS
)
NG
A-P
V
50
0-K
V (
AP
S)
NG
A-I
MP
5
00
-KV
(A
PS
) T
HE
SE
EL
EV
`S.
OV
ER
GL
A-K
NB
O
PG
W
PI
-47°4
3'1
4"
PI
50°3
3'2
6"
EX
-4/1
1 7
0-6
0-7
0 3
A
EX
-5/1
HS
-55
4/1
0L
2
66
M-5
0 (
BP
) S
TA
=8
7+
23
X
=4
71
89
7.4
7
Y=
63
71
36
.55
W
AR
NIN
G A
RR
OW
"U
P"
LO
OK
ING
BA
CK
O
PG
W L
EF
T
(S
OU
TH
) P
OL
E
5/1
2
81
S-5
0 (
BP
) S
TA
=9
2+
87
X
=4
71
33
8.6
6
Y=
63
70
57
.19
M
ILE
MA
RK
ER
SIG
N
564 563
PI
50°3
3'2
6"
PI
0°0
2'1
7"
EX
-5/2
65
-55
-65
3T
-2
5/2
2
81
N-5
0 (
BP
) S
TA
=9
8+
51
X
=4
70
78
5.8
7
Y=
63
69
48
.42
O
PG
W S
PL
ICE
520
EXISTING CONDUCTOR AND OGW AHEAD
5/3
6
0-H
S
ST
A=
10
3+
71
X
=4
70
39
3.0
1
Y=
63
72
89
.35
R
N 49°45'46" W
EX
-4/6
EX
-4/7
N 2°54'55" E
N 6°45'37" E
46" W
EX
-4/7
EX
-4/8
EX
-4/9
NO
RTH G
ILA S
UB
(AP
S)
GILA GRAVITY CANAL
185 FT R-O-W N 52°9'16" W
N 51°53'6" W
EX
-4/9
EX
-4/1
0
EX
-4/1
1
NORTH GILA SUB (APS)
T8S,R22W,SEC.11 YUMA CO., AZ
NG
A-H
AN
G2
500-K
V (
AP
S)
NG
A-P
V
50
0-K
V (
AP
S)
NG
A-IM
P
50
0-K
V (A
PS
)
100 FT R-O-W S 80°23'29" W
S 76°37'56" W
S 78°52'7" W
EX
-4/1
1
EX
-5/1
EX
-5/2
E
X-5
/2
T8S,R22W
,SEC
.11
YUM
A C
O., AZ
N 49°2'54" W
EX
-5/2
EX
-5/2
EX
-5/3
PI 58+29.05 0°20'02"
PI 61+30.91 52°40'38"
PI 73+39.44 -54°48'01"
PI 87+23.22 -47°43'14"
PI 98+50.62 50°33'26"
PI 103+70.79 0°02'17"
4/7 4/8L 4/9L 4/10L 5/1 5/2 5/3
WESTERN AREA POWER ADMINISTRATION UNITED STATES DEPARTMENT OF ENERGY
C A
E
HEADQUARTERS - LAKEWOOD, COLORADO
PLS
CENTERLINE
APPROVED DESIGNED STEVE ROCK
ELECTRICAL ENGINEERING MANAGER
ALLEN TURNER
R-O-W EDGE
R-O-W EDGE
PLS-CADD SIGN CONVENTION: ( ) UNSIGNED: RT AH (-) NEG. SIGN: LT AH
COORDINATES AND BEARINGS ARE BASED ON THE ARIZONA STATE PLANE COORDINATE SYSTEM, WEST ZONE, NAD83 DATUM. UNITS ARE US SURVEY FEET.
GILA - KNOB 161-KV TRANSMISSION LINE
ARIZONA
PLAN AND PROFILE
GLA-KNB
1" = 200' HORIZONTAL
1" = 40' VERTICAL
SCALES:
200' 0' 100'
40' 0' 20'
* DESIGNED FOR 230-KV
PHASING
STR NO. 4/9L
Z Y X
LOOK. AH (NORTH)
PHASING
LOOKING AH STR NO. 4/7
A
B
C
Z
Y
X OPGW OGW
GLA-KNB (FUT.)
OPGW
PHASING
LOOKING AH STR NO. 5/2
C
B
A
X
Y
Z OPGW OGW
GLA-KNB (FUT.)
MARCH 25, 2016 A A7-AFT ADDED C/L BEARINGS AND MOVED STRS. 4/7, 5/1, 5/2.
4/19/16
C B A
C B A
PHASING
LOOKING AH STR NO. 5/3
PHASING
LOOKING AH STR NO. 4/5
4207
STR. 4/7 TO STR. 5/3
STRUCTURE RANGE, WIRE, RULING SPAN, INSTALLATION TENSION, DISPLAY CONDITION
GL
A-K
NB
4-7
TO
5-2
.XY
Z
NESC LIGHT LOADING COND. - 1272 KCMIL, 54/19 PHEASANT/ACSS/MA2 CURVE SHOWN AT 482 °F, FINAL CONDITIONS [4/8-4/9] 1334 KCMIL, 54/19 MARTIN ACCR-T13 CURVE SHOWN AT 410 °F, FINAL CONDITIONS OGW - 1/2-IN 7 STR. HS STEEL OPGW - AFL CC-57-465 CURVE SHOWN AT 20 °F, INITIAL CONDITIONS
MAX. ACSS DESIGN OPERATING TEMP. = 482 °F GROUND CLEARANCE = 24 FT. MINIMUM + / - 28 FT. SIDE PROFILES LIDAR AND IMAGERY SEP. 2011
PA
TH
: S
:\P
RO
JEC
TS
\TR
AN
SM
ISS
ION
LIN
ES
\GIL
A_K
NO
B.R
EB
UIL
D.2
015\P
LS
CA
DD
\XY
Z\
GLA
-KN
B 4
-7 T
O 5
-2.X
YZ
P
LS
-CA
DD
PR
OJE
CT
LIN
E `
ED
IT`:
"R
EB
UIL
D -
MIN
US
AP
S C
RO
SS
ING
S"
TH
IS S
HE
ET
GE
NE
RA
TE
D:
4/1
9/2
016 -
8:1
3:3
5 P
LS
-CA
DD
VE
RS
ION
14.2
0X
64 -
AT
UR
NE
R
STA. 55+54 - STA. 106+32
4/8L - 4/9L, ACCR_1351-T13_(MARTIN_ACCR)_V2.WIR, RULING SPAN 788 (FT), TENSION 9750 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 410 °F = 210 °C MAX SAG FE 4/7 - 4/8L, PHEASANT_ACSS.WIR, RULING SPAN 1214 (FT), TENSION 8430 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/7 - 4/8R, PHEASANT_ACSS.WIR, RULING SPAN 1245 (FT), TENSION 8441 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/9L - 4/10L, PHEASANT_ACSS.WIR, RULING SPAN 596 (FT), TENSION 8505 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/10L - 5/2, PHEASANT_ACSS.WIR, RULING SPAN 567 (FT), TENSION 8506 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/10R - 5/2, PHEASANT_ACSS.WIR, RULING SPAN 579 (FT), TENSION 8513 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/7 - 4/8L, CC-57-465.WIR, RULING SPAN 1204 (FT), TENSION 2250 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/8L - 4/9L, CC-57-465.WIR, RULING SPAN 781 (FT), TENSION 1700 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/9L - 4/10L, CC-57-465.WIR, RULING SPAN 590 (FT), TENSION 2250 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/10L - 5/2, CC-57-465.WIR, RULING SPAN 562 (FT), TENSION 2250 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/7 - 4/8R, 1_2-7_STRAND_HS_STEEL.WIR, RULING SPAN 1255 (FT), TENSION 2500 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/10R - 5/2, 1_2-7_STRAND_HS_STEEL.WIR, RULING SPAN 584 (FT), TENSION 3000 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE
160+00 170+00 180+00 190+00 200+00 80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
80
100
120
140
160
180
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
PI
56°3
1'2
0"
PI
56°3
1'2
0"
PI
-58°5
4'5
4"
EX
-4/7
95
-85
-95
3T
-2
GL
A-S
EW
69
KV
(W
AP
A)
EX
-4/8
HS
-90
1252, 1209
PI
-58°5
4'5
4"
PI
-51°1
2'4
8"
4/8
R
26
6M
-80
(B
P)
ST
A=
17
0+
10
X
=4
73
07
2.1
5
Y=
63
63
19
.11
W
AR
NIN
G A
RR
OW
"U
P"
LO
OK
ING
AH
EA
D
OG
W R
IGH
T
(N
OR
TH
) P
OL
E
4/9
R
26
6M
-45
(B
P)
ST
A=
17
8+
42
X
=4
72
41
5.1
7
Y=
63
68
29
.55
O
GW
RIG
HT
(
NO
RT
H)
PO
LE
832 632
NG
A-H
AN
G2
5
00
-KV
(A
PS
)
NG
A-P
V
50
0-K
V (
AP
S)
NG
A-I
MP
5
00
-KV
(A
PS
) T
HE
SE
EL
EV
`S.
OV
ER
GL
A-K
NB
N
PH
AS
E
NO OGW THIS SPAN
PI
-51°1
2'4
8"
PI
54°1
9'1
0"
EX
-5/1
HS
-55
4/1
0R
2
66
M-5
5 (
BP
) S
TA
=1
84
+7
3
X=
47
19
16
.39
Y
=6
37
21
7.0
8
WA
RN
ING
AR
RO
W "
UP
" L
OO
KIN
G B
AC
K
OG
W R
IGH
T
(N
OR
TH
) P
OL
E
563
599
N 2°54'55" E
N 6°45'37" E
N 49
°45'4
6" W
EX
-4/7
EX
-4/8
EX
-4/9
EX
-4/6
NO
RTH
GIL
A S
UB
(AP
S)
GILA GRAVITY CANAL
185 FT R-O-W N 52°9'16" W
N 51°53'6" W
EX
-4/9
EX
-4/1
0
EX
-4/1
1
NORTH GILA SUB (APS)
T8S,R22W,SEC.11 YUMA CO., AZ
NG
A-H
AN
G2
500-K
V (
AP
S)
NG
A-P
V
50
0-K
V (
AP
S)
NG
A-IM
P
50
0-K
V (A
PS
)
100 FT R-O-W
S 80°23'29" W
N 49°2'54" W
S 76°37'56" W S 78°52'7" W
EX
-4/1
1
EX
-5/1
EX
-5/2
E
X-5
/2
EX
-5/3
T8S,R
22W,S
EC.11
YU
MA C
O., A
Z
4/8R 4/9R 4/10R
WESTERN AREA POWER ADMINISTRATION UNITED STATES DEPARTMENT OF ENERGY
C A
E
HEADQUARTERS - LAKEWOOD, COLORADO
PLS
CENTERLINE
APPROVED DESIGNED STEVE ROCK
ELECTRICAL ENGINEERING MANAGER
ALLEN TURNER
R-O-W EDGE
R-O-W EDGE
PLS-CADD SIGN CONVENTION: ( ) UNSIGNED: RT AH (-) NEG. SIGN: LT AH
COORDINATES AND BEARINGS ARE BASED ON THE ARIZONA STATE PLANE COORDINATE SYSTEM, WEST ZONE, NAD83 DATUM. UNITS ARE US SURVEY FEET.
GILA - KNOB 161-KV TRANSMISSION LINE
ARIZONA
PLAN AND PROFILE
GLA-KNB
1" = 200' HORIZONTAL
1" = 40' VERTICAL
SCALE:
200' 0' 100'
40' 0' 20'
* DESIGNED FOR 230-KV
PHASING
LOOKING AH STR NO. 4/7
A
B
C
Z
Y
X OPGW OGW
GLA-KNB (FUT.)
PHASING
STR NO. 4/9R
A B C
LOOK. AH (NORTH)
PHASING
LOOKING AH STR NO. 5/2
C
B
A
X
Y
Z OPGW OGW
GLA-KNB (FUT.)
OGW (AH)
A A7-AFT ADDED CENTERLINE BEARINGS AND MOVED STRUCTURES 4/7, 5/1 AND 5/2.
4/15/16 MARCH 25, 2016 4208
STR. 4/8R TO STR. 4/10R
STRUCTURE RANGE, WIRE, RULING SPAN, INSTALLATION TENSION, DISPLAY CONDITION
GL
A-K
NB
4-7
TO
5-2
.XY
Z
NESC LIGHT LOADING COND. - 1272 KCMIL, 54/19 PHEASANT/ACSS/MA2 CURVE SHOWN AT 482 °F, FINAL CONDITIONS [4/8-4/9] 1334 KCMIL, 54/19 MARTIN ACCR-T13 CURVE SHOWN AT 410 °F, FINAL CONDITIONS OGW - 1/2-IN 7 STR. HS STEEL OPGW - AFL CC-57-465 CURVE SHOWN AT 20 °F, INITIAL CONDITIONS
MAX. ACSS DESIGN OPERATING TEMP. = 482 °F GROUND CLEARANCE = 24 FT. MINIMUM + / - 28 FT. SIDE PROFILES LIDAR AND IMAGERY SEP. 2011
PA
TH
: S
:\P
RO
JEC
TS
\TR
AN
SM
ISS
ION
LIN
ES
\GIL
A_K
NO
B.R
EB
UIL
D.2
015\P
LS
CA
DD
\XY
Z\
GLA
-KN
B 4
-7 T
O 5
-2.X
YZ
P
LS
-CA
DD
PR
OJE
CT
LIN
E `
ED
IT`:
"R
EB
UIL
D -
MIN
US
AP
S C
RO
SS
ING
S"
TH
IS S
HE
ET
GE
NE
RA
TE
D:
4/1
9/2
016 -
8:1
4:2
7 P
LS
-CA
DD
VE
RS
ION
14.2
0X
64 -
AT
UR
NE
R
STA. 154+82 - STA. 205+35
4/8R - 4/9R, ACCR_1351-T13_(MARTIN_ACCR)_V2.WIR, RULING SPAN 832 (FT), TENSION 7000 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 410 °F = 210 °C MAX SAG FE 4/7 - 4/8R, PHEASANT_ACSS.WIR, RULING SPAN 1245 (FT), TENSION 8441 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/9R - 4/10R, PHEASANT_ACSS.WIR, RULING SPAN 631 (FT), TENSION 8492 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/10R - 5/2, PHEASANT_ACSS.WIR, RULING SPAN 579 (FT), TENSION 8513 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 482 °F = 250 °C MAX SAG FE 4/7 - 4/8R, 1_2-7_STRAND_HS_STEEL.WIR, RULING SPAN 1255 (FT), TENSION 2500 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/9R - 4/10R, 1_2-7_STRAND_HS_STEEL.WIR, RULING SPAN 637 (FT), TENSION 3000 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE 4/10R - 5/2, 1_2-7_STRAND_HS_STEEL.WIR, RULING SPAN 584 (FT), TENSION 3000 (LBS) AT 60 (DEG F) INITIAL, DISPLAYED 30 °F AAMT INITIAL FE
8
9082 832 1 3 4/8 R 4/9 R
1205 1 3 4/7 4/8 L1237 1 3 4/7 4/8 R 596 1 3 4/9 L 4/10 L 631 1 3 4/9 R 4/10 R 558 2 3 4/10 L 5/2 573 2 3 4/10 R 5/2
788 1 3 4/8 L 4/9 L
1247 1 1 4/7 4/8 R 638 1 1 4/9 R 4/10 R 578 2 1 4/10 R 5/2
1195 781 590 553
1 1 4/8 L 4/9 L1 1 4/9 L 4/10 L2 1 4/10 L 5/2
1 1 4/7 4/8 L
10135 8887 8887 778410143 8871 8871 7797
9914 9309 9309 74319895 9349 9349 74279932 9279 9279 74419904 9337 9337 7428
12261 10980 10717 83847626 7458 6498
3337 2614 2614 25143827 3341 3341 29523814 3376 3376 2950
3410 2443 2358 20782615 1884 1826 15453108 2630 2551 18703091 2651 2577 1858
(545-570)(533-605)
(536-613)
(542-564)
9
11
12
13
14
15
16
17
18
19
20
SITE PLAN AND BORING LOCATIONS
Project Mngr:
Approved By:
Checked By:
Drawn By:
Project No.
Scale:
Date:
File No.Consulting Engineers and Scientists
4685 South Ash Avenue, Suite H-4 Tempe, AZ 85282FAX. (480) 897-1133PH. (480) 897-8200
Gila-Knob T/L Rebuild, Phase 1
12/16/2015
65155124.DWG
AS SHOWN
65155124
SDN
JRH
KLJ
JRH
EAST COUNTY 6th STREET and SOUTH AVENUE 8
1
2
E.
YUMA COUNTY, ARIZONA
EXHIBIT
A-1
NOTE: SITE IMAGE MAP PROVIDED USGS NATIONAL MAP VIEWER, 2015
N
N
O
R
T
H
G
I
L
A
S
U
B
S
T
A
T
I
O
N
E. COUNTY 6th ST
LEGEND:
APPROXIMATE BORING LOCATION (STRUCTURE #)
APPROXIMATE SCALE
1" =
0
FEET
200' 400'
400 Feet
B-4 (5/2)
B-3 (4-10L)
B-2 (4-8R)
B-1 (4/7)
S. A
VE
8 E
.
S. A
VE
8
1
2
E
.
21
7
1
1
2
4
110
92
NP
17-20
6-17
12-13-12N=25
12-13-15N=28
12-16
7.0
POORLY GRADED SAND WITH GRAVEL (SP), trace silt, brown,medium dense
POORLY GRADED SAND WITH SILT (SP-SM), trace gravel,brown, medium dense
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 1 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Borings backfilled with soil cuttings upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/4/2015
BORING LOG NO. B-1Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/4/2015
Exhibit: A-5
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
5
10
15
20
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.743526° Longitude: -114.488535°
Groundwater not encounteredWATER LEVEL OBSERVATIONS
22
3
2
2
2
103
5-5-6N=11
6-9-10N=19
10-12
9-13-29N=42
40.5
POORLY GRADED SAND WITH SILT (SP-SM), trace gravel,brown, medium dense (continued)
dense
Boring Terminated at 40.5 Feet
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 2 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Borings backfilled with soil cuttings upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/4/2015
BORING LOG NO. B-1Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/4/2015
Exhibit: A-5
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
25
30
35
40
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.743526° Longitude: -114.488535°
Groundwater not encounteredWATER LEVEL OBSERVATIONS
23
583
2
1
3
4
98
106
24-17-76-14
21-50/5"
17-25-30N=55
12-23-28N=51
20-30/3"
4.0
20.0
SANDY SILTY CLAY (CL-ML), light brown, very stiff, weakcementation
SILTY SAND WITH GRAVEL (SM), light brown, very dense, weakto moderate cementation
POORLY GRADED SAND WITH GRAVEL (SP), trace silt, brown tolight brown, very dense, no to weak cementation
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 1 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Backfilled with cement-bentonite grout upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/3/2015
BORING LOG NO. B-2Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/3/2015
Exhibit: A-6
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
5
10
15
20
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.746788° Longitude: -114.488083°
While drilling
WATER LEVEL OBSERVATIONS
24
2
13
15
50/4"
23-50/6"
19-44-50/3"
11-15-19N=34
40.5
POORLY GRADED SAND WITH GRAVEL (SP), trace silt, brown tolight brown, very dense, no to weak cementation (continued)
groundwater encountered at approximately 32 feet while drilling
dense
Boring Terminated at 40.5 Feet
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 2 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Backfilled with cement-bentonite grout upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/3/2015
BORING LOG NO. B-2Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/3/2015
Exhibit: A-6
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
25
30
35
40
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.746788° Longitude: -114.488083°
While drilling
WATER LEVEL OBSERVATIONS
25
97
2
1
2
19
98
108
76-25-51
2-2
6-7
6-7-7N=14
12-18
9-13-21N=34
6.0
11.0
19.0
POORLY GRADED SAND WITH GRAVEL (SP), trace silt, brown,very loose to loose
POORLY GRADED SAND WITH SILT (SP-SM), brown, mediumdense
POORLY GRADED SAND WITH GRAVEL (SP), trace silt, brown,medium dense
FAT CLAY (CH), brown, very stiff to hard
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 1 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Borings backfilled with soil cuttings upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/3/2015
BORING LOG NO. B-3Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/3/2015
Exhibit: A-7
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
5
10
15
20
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.749149° Longitude: -114.49197°
Groundwater not encounteredWATER LEVEL OBSERVATIONS
26
11297 21
23
20
2
98
101
14-21
14-19-23N=42
18-32/3"
20-35-37N=72
37.0
40.5
FAT CLAY (CH), brown, very stiff to hard (continued)
very dense
SILTY SAND WITH GRAVEL (SM), light brown, very dense,moderate cementation
Boring Terminated at 40.5 Feet
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 2 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Borings backfilled with soil cuttings upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/3/2015
BORING LOG NO. B-3Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/3/2015
Exhibit: A-7
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
25
30
35
40
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.749149° Longitude: -114.49197°
Groundwater not encounteredWATER LEVEL OBSERVATIONS
27
51
5
1
NP
5-10
5-7-10N=17
15-22
15-36-34N=70
12-15-19N=34
5.0
11.0
POORLY GRADED SAND WITH SILT AND GRAVEL (SP-SM),loose
POORLY GRADED SAND WITH SILT (SP-SM), trace gravel,medium dense
SILTY SAND (SM), trace gravel, dense to very dense, weak tomoderate cementation
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 1 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Borings backfilled with soil cuttings upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/4/2015
BORING LOG NO. B-4Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/4/2015
Exhibit: A-8
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
5
10
15
20
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.748832° Longitude: -114.495473°
Groundwater not encounteredWATER LEVEL OBSERVATIONS
28
2
20
20
20
94
92
16-30
10-13-17N=30
15-29
16-20-24N=44
28.0
40.5
SILTY SAND (SM), trace gravel, dense to very dense, weak tomoderate cementation (continued)
medium dense
FAT CLAY (CH), brown, hard
Boring Terminated at 40.5 Feet
Hammer Type: AutomaticStratification lines are approximate. In-situ, the transition may be gradual.
GR
AP
HIC
LO
G
TH
IS B
OR
ING
LO
G IS
NO
T V
ALI
D IF
SE
PA
RA
TE
D F
RO
M O
RIG
INA
L R
EP
OR
T.
G
EO
SM
AR
T L
OG
-NO
WE
LL 6
515
512
4.G
PJ
TE
RR
AC
ON
2015
.GD
T
12/1
6/15
SITE:
Page 2 of 2
Advancement Method:Hollow Stem Auger
Abandonment Method:Borings backfilled with soil cuttings upon completion.
4685 S. Ash Ave., Suite H-4Tempe, Arizona
Notes:
Project No.: 65155124
Drill Rig: CME-55
Boring Started: 12/4/2015
BORING LOG NO. B-4Civil Design & Engineering, Inc.CLIENT:Phoenix, Arizona
Driller: D&S Drilling
Boring Completed: 12/4/2015
Exhibit: A-8
See Exhibit A-2 for description of fieldproceduresSee Appendix B for description of laboratoryprocedures and additional data (if any).
See Appendix A for explanation of symbols andabbreviations.
North Gila Substation Near Yuma, Arizona
PROJECT: Gila-Knob T/L Rebuild
UN
CO
NF
INE
DC
OM
PR
ES
SIV
ES
TR
EN
GT
H (
psf)
PE
RC
EN
T F
INE
S
WA
TE
RC
ON
TE
NT
(%
)
DR
Y U
NIT
WE
IGH
T (
pcf)
ATTERBERGLIMITS
LL-PL-PI
SA
MP
LE T
YP
E
WA
TE
R L
EV
EL
OB
SE
RV
AT
ION
S
DE
PT
H (
Ft.)
25
30
35
40
FIE
LD T
ES
TR
ES
ULT
S
DEPTH
LOCATION See Exhibit A-1
Latitude: 32.748832° Longitude: -114.495473°
Groundwater not encounteredWATER LEVEL OBSERVATIONS
29