  • TRANSISTORIZED INVERTERFR-E500

    FR-E520-0.1KN to 7.5K-KN

    INSTRUCTION MANUAL

    OUTLINE

    PARAMETERS

    SPECIFICATIONS

    INSTALLATIONAND WIRING

    OPERATION/CONTROL

    PROTECTIVEFUNCTIONS

    Chapter 6

    Chapter 5

    Chapter 4

    Chapter 3

    Chapter 2

    Chapter 1

  • A - 1

    Thank you for choosing the Mitsubishi Transistorized inverter.

    This instruction manual gives handling information and precautions for use of this

    equipment.

    Incorrect handling might cause an unexpected fault. Before using the inverter,

    please read this manual carefully to use the equipment to its optimum.

    Please forward this manual to the end user.

    This section is specifically about safety mattersDo not attempt to install, operate, maintain or inspect the inverter until you have readthrough this instruction manual and appended documents carefully and can use theequipment correctly.

    Do not use the inverter until you have a full knowledge of the equipment, safetyinformation and instructions.

    In this manual, the safety instruction levels are classified into "WARNING" and"CAUTION".

    Assumes that incorrect handling may cause hazardousconditions, resulting in death or severe injury.

    Assumes that incorrect handling may cause hazardousconditions, resulting in medium or slight injury, or maycause physical damage only.

    Note that even the CAUTION level may lead to a serious consequence according toconditions. Please follow the instructions of both levels because they are importantto personnel safety.

    WARNING

    CAUTION

  • A - 2

    SAFETY INSTRUCTIONS

    1. Electric Shock Prevention

    WARNING! While power is on or when the inverter is running, do not open the front cover.

    You may get an electric shock.! Do not run the inverter with the front cover removed. Otherwise, you may access

    the exposed high-voltage terminals or the charging part of the circuitry and get anelectric shock.

    ! If power is off, do not remove the front cover except for wiring or periodicinspection. You may access the charged inverter circuits and get an electricshock.

    ! Before starting wiring or inspection, switch power off, wait for more than 10minutes, and check for residual voltage with a meter (refer to chapter 2 for furtherdetails) etc.

    ! Earth the inverter.! Any person who is involved in the wiring or inspection of this equipment should be

    fully competent to do the work.! Always install the inverter before wiring. Otherwise, you may get an electric shock

    or be injured.! Operate the switches and potentiometers with dry hands to prevent an electric

    shock.! Do not subject the cables to scratches, excessive stress, heavy loads or pinching.

    Otherwise, you may get an electric shock.! Do not change the cooling fan while power is on.

    It is dangerous to change the cooling fan while power is on.! While power is on, do not move the station number and baudrate setting switches.

    Doing so can cause an electric shock.

    2. Fire Prevention

    CAUTION! Mount the inverter and brake resistor on an incombustible surface. Installing the

    inverter directly on or near a combustible surface could lead to a fire.! If the inverter has become faulty, switch off the inverter power. A continuous flow

    of large current could cause a fire.! When a brake resistor is used, use an alarm signal to switch power off.

    Otherwise, the brake resistor will overheat abnormally due a brake transistor orother fault, resulting in a fire.

    ! Do not connect a resistor directly to the DC terminals P (+), N (−). This couldcause a fire.

  • A - 3

    3. Injury Prevention

    CAUTION! Apply only the voltage specified in the instruction manual to each terminal to

    prevent damage etc.! Ensure that the cables are connected to the correct terminals. Otherwise,

    damage etc. may occur.! Always make sure that polarity is correct to prevent damage etc.! While power is on and for some time after power-off, do not touch the inverter or

    brake resistor as they are hot and you may get burnt.

    4. Additional instructions

    Also note the following points to prevent an accidental failure, injury, electric shock, etc.

    (1) Transportation and installation

    CAUTION! When carrying products, use correct lifting gear to prevent injury.! Do not stack the inverter boxes higher than the number recommended.! Ensure that installation position and material can withstand the weight of the

    inverter. Install according to the information in the Instruction Manual.! Do not operate if the inverter is damaged or has parts missing.! Do not hold the inverter by the front cover or operation panel; it may fall off.! Do not stand or rest heavy objects on the inverter.! Check the inverter mounting orientation is correct.! Prevent screws, wire fragments or other conductive bodies or oil or other

    flammable substance from entering the inverter.! Do not drop the inverter, or subject it to impact.! Use the inverter under the following environmental conditions:

    Ambienttemperature

    Constant torque : -10°C to +50°C (non-freezing)

    Ambient humidity 90%RH or less (non-condensing)Storagetemperature

    -20°C to +65°C*

    AmbienceIndoors (free from corrosive gas, flammable gas, oil mist, dustand dirt)E

    nviro

    nmen

    t

    Altitude, vibrationMaximum 1000m above sea level for standard operation. Afterthat derate by 3% for every extra 500m up to 2500m (91%).5.9m/s2 or less (conforming to JIS C 0400)

    *Temperatures applicable for a short time, e.g. in transit.

  • A - 4

    (2) Wiring

    CAUTION! Do not fit capacitive equipment such as a power factor correction capacitor,

    radio noise filter or surge suppressor to the output of the inverter.! The connection orientation of the output cables U, V, W to the motor will affect

    the direction of rotation of the motor.

    (3) Trial run

    CAUTION! Check all parameters, and ensure that the machine will not be damaged by a

    sudden start-up.

    (4) Operation

    WARNING! When you have chosen the retry function, stay away from the equipment as it

    will restart suddenly after an alarm stop.! The load used should be a three-phase induction motor only. Connection of any

    other electrical equipment to the inverter output may damage the equipment.! Do not modify the equipment.

  • A - 5

    CAUTION! The electronic overcurrent protection does not guarantee protection of the motor

    from overheating.! Do not use a magnetic contactor on the inverter input for frequent

    starting/stopping of the inverter.! Use a noise filter to reduce the effect of electromagnetic interference. Otherwise

    nearby electronic equipment may be affected.! Take measures to suppress harmonics. Otherwise power harmonics from the

    inverter may heat/damage the power capacitor and generator.! When parameter clear or all clear is performed, each parameter returns to the

    factory setting. Re-set the required parameters before starting operation.! The inverter can be easily set for high-speed operation. Before changing its

    setting, fully examine the performances of the motor and machine.! In addition to the inverter's holding function, install a holding device to ensure

    safety.! Before running an inverter which had been stored for a long period, always

    perform inspection and test operation.

    (5) Emergency stop

    CAUTION! Provide a safety backup such as an emergency brake which will prevent the

    machine and equipment from hazardous conditions if the inverter fails.

    (6) Maintenance, inspection and parts replacement

    CAUTION! Do not carry out a megger (insulation resistance) test on the control circuit of the

    inverter.

    (7) Disposing of the inverter

    CAUTION! Treat as industrial waste.

    (8) General instructionsMany of the diagrams and drawings in this instruction manual show the inverterwithout a cover, or partially open. Never operate the inverter in this manner. Alwaysreplace the cover and follow this instruction manual when operating the inverter.

  • CONTENTS

    I

    1 OUTLINE 1

    1.1 Pre-Operation Information ..........................................................................................1

    1.1.1 Precautions for operation .....................................................................................1

    1.2 Basic Configuration.....................................................................................................3

    1.2.1 Basic configuration ...............................................................................................3

    1.3 Structure .....................................................................................................................4

    1.3.1 Appearance and structure ....................................................................................4

    1.3.2 Functions..............................................................................................................5

    1.3.3 Inverter communication specifications..................................................................5

    1.3.4 CC-Link Ver. 1.10.................................................................................................6

    1.3.5 Communication with remote devices....................................................................6

    1.3.6 Removal and reinstallation of the front cover .......................................................7

    1.3.7 Removal and reinstallation of the wiring cover .....................................................8

    1.3.8 Removal and reinstallation of the accessory cover ..............................................9

    1.3.9 Exploded view ....................................................................................................10

    2 INSTALLATION AND WIRING 11

    2.1 Installation.................................................................................................................11

    2.1.1 Instructions for installation..................................................................................11

    2.2 Wiring........................................................................................................................13

    2.2.1 Terminal connection diagram .............................................................................13

    2.2.2 Wiring of the Main Circuit ...................................................................................16

    2.2.3 Wiring of the control circuit .................................................................................20

    2.2.4 Wiring of CC-Link communication signals ..........................................................23

    2.2.5 Connection to the PU connector.........................................................................26

    2.2.6 Connection of stand-alone option units ..............................................................29

    2.2.7 Design information .............................................................................................31

    2.3 Other Wiring..............................................................................................................32

    2.3.1 Power supply harmonics ....................................................................................32

    2.3.2 Japanese harmonic suppression guideline ........................................................33

    2.3.3 Inverter-generated noise and reduction techniques ...........................................36

    2.3.4 Leakage currents and countermeasures ............................................................40

    2.3.5 Peripheral devices ..............................................................................................41

    Co

    nte

    nts

  • II

    2.3.6 Instructions for compliance with U.S. and Canadian Electrical Codes ...............45

    2.3.7 Instructions for compliance with the European standards ..................................46

    3 OPERATON/CONTROL 48

    3.1 Inverter Setting..........................................................................................................48

    3.1.1 Pre-operation checks..........................................................................................48

    3.1.2 Inverter station number setting ...........................................................................49

    3.1.3 Setting of the transmission baudrate setting switch ...........................................50

    3.1.4 Power on ............................................................................................................50

    3.1.5 Confirmation of the operation mode ...................................................................51

    3.2 Function Overview ....................................................................................................52

    3.2.1 Function Block Diagram .....................................................................................52

    3.2.2 Function overview...............................................................................................53

    3.3 Communication Specifications..................................................................................55

    3.3.1 I/O signal list .......................................................................................................55

    3.3.2 Assignment of remote registers..........................................................................57

    3.3.3 Instruction Codes ...............................................................................................58

    3.4 Programming Examples............................................................................................59

    3.4.1 Reply code definitions ........................................................................................59

    3.4.2 Program example for reading the inverter status................................................60

    3.4.3 Operation mode setting program example .........................................................61

    3.4.4 Program example for setting the operation commands......................................62

    3.4.5 Program example for monitoring the output frequency ......................................62

    3.4.6 Parameter reading program example.................................................................63

    3.4.7 Parameter writing program example...................................................................64

    3.4.8 Running frequency setting program example .....................................................65

    3.4.9 Alarm definition reading program example.........................................................66

    3.4.10 Inverter resetting program example..................................................................67

    3.4.11 Instructions .......................................................................................................68

    4 PARAMETERS 69

    4.1 Parameter List...........................................................................................................69

    4.1.1 Parameter list .....................................................................................................69

    4.1.2 List of parameters classified by purpose of use .................................................75

    4.1.3 Parameters recommended to be set by the user ...............................................76

  • III

    4.2 Parameter Function Details ......................................................................................77

    4.2.1 Torque boost (Pr. 0, Pr. 46)................................................................................77

    4.2.2 Output frequency range (Pr. 1, Pr. 2, Pr. 18)......................................................78

    4.2.3 Base frequency, base frequency voltage (Pr. 3, Pr. 19, Pr. 47) .........................79

    4.2.4 Multi-speed operation (Pr. 4, Pr. 5, Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)...80

    4.2.5 Acceleration time (Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45) .............................81

    4.2.6 Electronic overcurrent protection (Pr. 9, Pr. 48) .................................................83

    4.2.7 DC injection brake (Pr. 10 to Pr. 12)...................................................................84

    4.2.8 Starting frequency (Pr. 13) .................................................................................85

    4.2.9 Load pattern selection (Pr. 14) ...........................................................................85

    4.2.10 Stall prevention (Pr. 22, Pr. 23, Pr. 66).............................................................87

    4.2.11 Acceleration/deceleration pattern (Pr. 29) ........................................................89

    4.2.12 Regenerative brake duty (Pr. 30, Pr. 70) ..........................................................90

    4.2.13 Frequency jump (Pr. 31 to Pr. 36) ....................................................................91

    4.2.14 Speed display (Pr. 37) ......................................................................................92

    4.2.15 Up-to-frequency sensitivity (Pr. 41) ..................................................................93

    4.2.16 Output frequency detection (Pr. 42, Pr. 43)......................................................93

    4.2.17 Monitor display (Pr. 52) ....................................................................................94

    4.2.18 Automatic restart after instantaneous power failure (Pr. 57, Pr. 58).................96

    4.2.19 Shortest acceleration/deceleration mode (Pr. 60 to Pr.63)...............................97

    4.2.20 Retry function (Pr. 65, Pr. 67 to Pr. 69) ............................................................99

    4.2.21 Applied motor (Pr. 71) ....................................................................................101

    4.2.22 PWM carrier frequency (Pr. 72, Pr. 240) ........................................................102

    4.2.23 Reset selection/disconnected PU detection/PU stop selection (Pr. 75) .........103

    4.2.24 Parameter write disable selection (Pr. 77)......................................................105

    4.2.25 Reverse rotation prevention selection (Pr. 78) ...............................................106

    4.2.26 Operation mode selection (Pr. 79)..................................................................107

    4.2.27 General-purpose magnetic flux vector control selection (Pr. 80).........................108

    4.2.28 Offline auto tuning function (Pr. 82 to Pr. 84, Pr. 90, Pr. 96) ..........................109

    4.2.29 Computer link operation (Pr. 117 to Pr. 124, Pr. 342) ....................................115

    4.2.30 Output current detection function (Pr. 150, Pr. 151).......................................127

    4.2.31 Zero current detection (Pr. 152, Pr. 153)........................................................128

    4.2.32 Stall prevention (Pr. 156)................................................................................129

    4.2.33 User group selection (Pr. 160, Pr. 173 to Pr. 176) .........................................131

    4.2.34 Actual operation hour meter clear (Pr. 171) ...................................................132

    Co

    nte

    nts

  • IV

    4.2.35 Input terminal (remote output) function selection (Pr. 180 to Pr. 183)............132

    4.2.36 Output terminal (remote input) function selection (Pr. 190 to Pr. 192) ...........134

    4.2.37 Cooling fan operation selection (Pr. 244) .......................................................135

    4.2.38 Slip compensation (Pr. 245 to Pr. 247)...........................................................136

    4.2.39 Ground fault detection at start (Pr. 249) .........................................................137

    4.2.40 Stop selection (Pr. 250) ..................................................................................138

    4.2.41 Output phase failure protection selection (Pr. 251) ........................................139

    4.2.42 Communication error "E.OPT" operation selection (Pr. 500 to Pr. 502) .........140

    5 PROTECTIVE FUNCTIONS 142

    5.1 Errors (Alarms)........................................................................................................142

    5.1.1 Operation at Alarm Occurrence........................................................................142

    5.1.2 Error (alarm) definitions ....................................................................................143

    5.1.3 To know the operating status at the occurrence of alarm.................................149

    5.1.4 Correspondence between digital and actual characters...................................150

    5.1.5 Resetting the inverter .......................................................................................150

    5.1.6 How to Check for Error using the LEDs............................................................151

    5.2 Troubleshooting ......................................................................................................154

    5.2.1 Motor remains stopped.....................................................................................154

    5.2.2 Motor rotates in opposite direction ...................................................................154

    5.2.3 Speed greatly differs from the setting...............................................................154

    5.2.4 Acceleration/deceleration is not smooth...........................................................155

    5.2.5 Motor current is large........................................................................................155

    5.2.6 Speed does not increase..................................................................................155

    5.2.7 Speed varies during operation..........................................................................155

    5.2.8 Operation mode unswitched to CC-Link operation mode.................................156

    5.2.9 Inverter unstarted in CC-Link operation mode..................................................156

    5.2.10 Parameter write cannot be performed............................................................156

    5.3 Precautions for Maintenance and Inspection..........................................................157

    5.3.1 Precautions for maintenance and inspection....................................................157

    5.3.2 Check items......................................................................................................157

    5.3.3 Periodic inspection ...........................................................................................158

    5.3.4 Insulation resistance test using megger ...........................................................158

    5.3.5 Pressure test ....................................................................................................158

    5.3.6 Daily and Periodic Inspection ...........................................................................159

  • V

    5.3.7 Replacement of parts .......................................................................................162

    5.3.8 Measurement of main circuit voltages, currents and powers............................164

    6 SPECIFICATIONS 166

    6.1 Standard Specifications ..........................................................................................166

    6.1.1 Model specifications .........................................................................................166

    6.1.2 Common specifications ....................................................................................167

    6.1.3 Outline dimension drawings .............................................................................169

    APPENDIX 173

    APPENDIX 1 Data Code List ........................................................................................173

    Co

    nte

    nts

  • C H A P T E R 1

    O U T L I N E

    This chapter gives information on the basic "outline" of this

    product.

    Always read the instructions before using the equipment.

    1.1 Pre-Operation Information .......................................... 1

    1.2 Basic Configuration..................................................... 3

    1.3 Structure ..................................................................... 4

    ! PU

    Parameter unit (FR-PU04)! Inverter

    Mitsubishi transistorized inverterFR-E500 series

    ! Pr.Parameter number

    ! CC-LinkControl & Communication Link

    CHAPTER 1

    OUTLINE

    Chapter 1

    Chapter 2

    Chapter 3

    Chapter 4

    Chapter 5

    Chapter 6

  • OUTLINE

    1

    1.1 Pre-Operation Information

    1 OUTLINE1.1 Pre-Operation Information1.1.1 Precautions for operation

    This manual is written for the FR-E500 series Control & Communication Link (hereafterreferred to as "CC-Link") type transistorized inverters.Incorrect handling may cause the inverter to operate incorrectly, causing its life to bereduced considerably, or at the worst, the inverter to be damaged. Handle the inverterproperly in accordance with the information in each section as well as the precautionsand instructions of this manual to use it correctly.For handling information on the parameter unit (FR-PU04), stand-alone options, etc.,refer to the corresponding manuals.

    (1) Unpacking and product check

    Unpack the inverter and check the capacity plate on the front cover and the rating plateon the inverter side face to ensure that the product agrees with your order and theinverter is intact.

    1) Inverter type

    Inverter type Serial number

    Capacity plate

    Rating plateCapacity plate

    Rating plate

    FR-E520-0.1KN/

    Inverter typeInput rating

    Output rating

    Serial number

    MITSUBISHIMODEL

    INVERTER

    FR-E520-0.1KN INPUT :

    OUTPUT :

    SERIAL :

    XXXXX

    XXXXX

    PASSED

    Productssupporting CC-LinkVer.1.10 has a logo.

    " Inverter type

    FR E520 0.1 K N

    Symbol Voltage class

    200V class

    CC-Link type

    E520

    InverterIndicates capacity

    "kW".

    2) AccessoryInstruction manual

    If you have found any discrepancy, damage, etc., please contact your salesrepresentative.

  • OUTLINE

    2

    (2) Preparation of instruments and parts required for operation

    Instruments and parts to be prepared depend on how the inverter is operated. Prepareequipment and parts as necessary. (Refer to page 48.)

    (3) Installation

    To operate the inverter with high performance for a long time, install the inverter in aproper place, in the correct direction, with proper clearances. (Refer to page 11.)

    (4) Wiring

    Connect the power supply, motor and operation signals (control signals) to the terminalblock. Note that incorrect connection may damage the inverter and peripheral devices.(See page 13.)

    (5) Grounding

    To prevent an electric shock, always use the motor and inverter after grounding them.The ground cable provided for reduction of induction noise from the power line of theinverter is recommended to be run by returning it up to the ground terminal of theinverter. (Refer to page 39)

    1

  • OUTLINE

    3

    1.2 Basic Configuration

    1.2 Basic Configuration

    1.2.1 Basic configuration

    The following devices are required to operate the inverter. Proper peripheral devicesmust be selected and correct connections made to ensure proper operation. Incorrectsystem configuration and connections can cause the inverter to operate improperly, itslife to be reduced considerably, and in the worst case, the inverter to be damaged.Please handle the inverter properly in accordance with the information in each sectionas well as the precautions and instructions of this manual. (For connections of theperipheral devices, refer to the corresponding manuals.)

    AJ61BT11

    CPU

    (MC)

    (NFB) or

    (ELB)

    Ground

    Ground

    DC reactor(FR-BEL)

    AC reactor(FR-BAL)

    Earth leakagecircuit breakeror no-fuse breaker

    Power supply

    Magneticcontactor

    Inverter

    Manuals for CC-Link master station

    Master station

    Terminal resistor

    CC-Link dedicated cable

    Up to 42 inverters can be connected.

    Terminal resistor

    AJ61BT11/A1SJ61BT11 Control & Communication Link System Master/Local module User's Manual ... IB-66721

    AJ61QBT11/A1SJ61QBT11 Control & Communication Link System Master/Local module User's Manual ... IB-66722

    QJ61BT11 Control & Communication Link System Master/Local module User's Manual ... IB-080016

    Po

    wer

    supply

    Japanese Harmonic Suppression GuidelineThe "harmonic suppression guideline for household appliance and general-purposeproducts" issued by Ministry of Economy, Trade and Industry (formerly Ministry ofInternational Trade and Industry) in September, 1994 applies to 3-phase 200V classinverters of 3.7kW or less. By installing the power factor improving reactor (FR-BELor FR-BAL), inverters comply with the "harmonic suppression techniques fortransistorized inverters (input current 20A or less)" established by the JapanElectrical Manufacturers' Association.

  • OUTLINE

    4

    1.3 Structure

    1.3 Structure

    1.3.1 Appearance and structure

    (1) Front view

    POWER lamp (yellow)

    Accessory cover

    ALARM lamp (red)

    Operating statusindicator LEDs

    Rating plate

    Front cover

    Capacity plate

    Wiring cover

    (2) Without accessory cover and front cover

    POWER lamp (yellow)

    Operating status indicator LEDs

    Control logic changing connector

    Control circuit terminal block

    PU connector*

    ALARM lamp (red)

    Transmission baud rate setting switchCC-Link terminal blockMain circuit terminal block

    Wiring cover

    Station number setting switches

    * Use the PU connector for the FR-PU04 (option) and RS-485 communication.

    1

  • OUTLINE

    5

    1.3.2 Functions

    Name FunctionStation number settingswitches

    ×10

    0987 654

    32

    1

    ×1

    0987 654

    32

    1Used to set the inverter station numberbetween 1 and 64.For details, refer to page 49.

    Transmission baudrate setting switch

    Switch used to set the transmission speed.For details, refer to page 50.

    POWER lamp (yellow) Lit to indicate that power is input (present).ALARM lamp (red) Lit to indicate that a protective function is activated.Operating statusindicator LEDs

    L.RUN : Lit to indicate normal receipt of refresh data. Extinguishedwhen data is interrupted for some time.

    SD : Extinguished to indicate that send data is "0".RD : Lit to indicate detection of carrier in receive data.L.ERR : Lit to indicate the communication error of the station itself.

    Flickers to indicate that the switch or other setting waschanged while power is on.

    1.3.3 Inverter communication specifications

    Form Terminal block connection system (disconnectable frominverter front)

    Number of units connected Maximum 42 units (1 station/unit occupied), other modelsmay also be used.

    Terminal block connected 6-terminal block (M2×6 screws)Cable size 0.75 to 2mm2

    Station type Remote device stationNumber of stations occupied One inverter occupies one stationConnection cable CC-Link dedicated cable, CC-Link Version 1.10 compatible

    CC-Link dedicated cable

  • OUTLINE

    6

    1.3.4 CC-Link Ver. 1.10

    The conventional CC-Link products, whose inter-station cable lengths have equallybeen changed to 20cm (7.87 inch) or more to improve the inter-station cable lengthrestriction, are defined as CC-Link Ver. 1.10. In comparison, the conventional productsare defined as CC-Link Ver. 1.00.Refer to the CC-Link Master Module Manual for the maximum overall cable lengths andinter-station cable lengths of CC-Link Ver. 1.00 and Ver. 1.10.

    (1) CC-Link Ver. 1.10 compatibility conditions1) All modules that comprise a CC-Link system should be compatible with CC-Link Ver.

    1.10.2) All data link cables should be CC-Link Ver. 1.10 compatible, CC-Link dedicated

    cables. (CC-Link Ver. 1.10 compatible cables have a logo or Ver. 1.10indication.)

    Note: In a system that uses the CC-Link Ver. 1.00 and Ver. 1.10 modules andcables together, the maximum overall cable length and inter-station cablelength are as specified for CC-Link Ver. 1.00.

    (2) How to confirm the CC-Link Ver. 1.10 compatible productsOnly the FR-E520-KN units manufactured in and after September 2001 are CC-LinkVer. 1.10 compatible.1) Product having SERIAL of numbers shown below or later on its body and shipping

    carton(The shipping carton has only three upper digits of the six-digit control number.)

    Type SERIALFR-E520-0.1KN X19 FR-E520-0.2KN, 0.4KN Y19 FR-E520-0.75KN Z19 FR-E520-1.5KN, 2.2KN X19 FR-E520-3.7KN V19 FR-E520-5.5KN, 7.5KN W19

    X 1 9 Symbol Year Month Control number

    SERIAL number

    2) Product having a logo on its bodyRefer to page 1 for the SERIAL and logo positions on the body.

    1.3.5 Communication with remote devices

    (1) When the CPU has automatic refresh function (example: QnA seriesCPU)Through communication with the corresponding devices using sequence ladderlogic, data is automatically transferred to/from the refresh buffer of the masterstation at the execution of the END instruction to perform communication with theremote devices.

    (2) When the CPU does not have automatic refresh function (example:AnA series CPU)Data is transferred to/from the refresh buffer of the master station directly bysequence ladder logic to perform communication with the remote devices.

    1

  • OUTLINE

    7

    1.3.6 Removal and reinstallation of the front cover

    """" Removal

    (For the FR-E520-0.1KN to 3.7KN)

    The front cover is secured by catches in positions A and B as shown below.Push either A or B in the direction of arrows, and using the other end as asupport, pull the front cover toward you to remove.

    1) 2) 3)

    AB

    (For the FR-E520-5.5KN, 7.5KN)

    The front cover is fixed with catches in positions A, B and C.Push A and B in the directions of arrows at the same time and remove thecover using C as supporting points.

    1) 2) 3)

    C

    B

    C

    A

    """" Reinstallation

    When reinstalling the front cover after wiring, fix the catches securely.With the front cover removed, do not switch power on.

  • OUTLINE

    8

    Note:1. Make sure that the front cover has been reinstalled securely.2. The same serial number is printed on the capacity plate of the front cover

    and the rating plate of the inverter. Before reinstalling the front cover, checkthe serial numbers to ensure that the cover removed is reinstalled to theinverter from where it was removed.

    1.3.7 Removal and reinstallation of the wiring cover

    """" Removal

    The wiring cover is fixed by catches in positions 1) and 2).Push either 1) or 2) in the direction of arrows and pull the wiring coverdownward to remove.

    1) 2)

    Wiring hole

    """" Reinstallation

    Pass the cables through the wiring hole and reinstall the cover in the originalposition.

    1

  • OUTLINE

    9

    1.3.8 Removal and reinstallation of the accessory cover

    """" Removal

    Hold down the portion A indicated by the arrow and lift the right hand sideusing the portion B indicated by the arrow as a support, and pull out theaccessory cover to the right.

    1) 2) 3)

    A

    B

    """" Reinstallation

    Insert the mounting catch (left hand side) of the accessory cover into themounting position of the inverter and push in the right hand side mountingcatch to install the accessory cover.

    Mounting position

    Accessory cover

    Catch

    2)1)A

    3)

  • OUTLINE

    10

    1.3.9 Exploded view

    Accessory cover

    Front cover

    Wiring cover

    Note: Do not remove any parts other than the accessory cover, front cover andwiring cover. 1

  • 1

    C H A P T E R 2INSTALLATIONAND

    WIRING

    This chapter gives information on the basic "installation and

    wiring" for use of this product.

    Always read the instructions in this chapter before using the

    equipment.

    2.1 Installation ....................................................................11

    2.2 Wiring ...........................................................................13

    2.3 Other Wiring .................................................................32

    CHAPTER 2INSTALLATION AND

    WIRING

    Chapter 1

    Chapter 2

    Chapter 3

    Chapter 4

    Chapter 5

    Chapter 6

  • 2.1 InstallationINSTALLATION AND WIRING

    11

    2 INSTALLATION AND WIRING2.1 Installation2.1.1 Instructions for installation

    When mounting any of the FR-E520-0.1KN to 0.75KN, remove the accessory cover,front cover and wiring cover.

    1) Handle the unit carefully.The inverter uses plastic parts. Handle it gently to protect it from damage.Also, hold the unit with even strength and do not apply too much strength to the frontcover alone.

    2) Install the inverter in a place where it is not affected by vibration easily (5.9m/s2

    maximum.).Note the vibration of a cart, press, etc.

    3) Note on ambient temperature.The inverter life is under great influence of ambient temperature. In the place ofinstallation, the ambient temperature must be within the permissible range -10°C to+50°C. Check that the ambient temperature is within the permissible range in thepositions shown in Fig. 3).

    4) Install the inverter on a non-combustible surface.The inverter will be very hot (maximum about 150°C). Install it on a non-combustiblesurface (e.g. metal). Also leave sufficient clearances around the inverter.

    5) Avoid high temperatures and high humidity.Avoid direct sunlight and places of high temperature and high humidity.

    6) Avoid places where the inverter is exposed to oil mist, flammable gases, fluff, dust,dirt etc.Install the inverter in a clean place or inside a "totally enclosed" panel which doesnot accept any suspended matter.

  • INSTALLATION AND WIRING

    12

    7) Note the cooling method when the inverter is installed in an enclosure.When two or more inverters are installed or a ventilation fan is mounted in anenclosure, the inverters and ventilation fan must be installed in proper positions withextreme care taken to keep the ambient temperatures of the inverters with thepermissible values. If they are installed in improper positions, the ambienttemperatures of the inverters will rise and ventilation effect will be reduced.

    8) Install the inverter securely in the vertical direction with screws or bolts.

    3) Note on ambienttemperatures

    Measurement position

    Measurement position

    5cm 5cm

    5cm

    FR-E500

    4) Clearances around the inverter

    FR-E500

    10cm or more

    10cm or more

    Leave sufficient clearances above and under the inverter to ensure adequate ventilation.

    Cooling fan built in the inverter

    1cm or more*

    1cm or more*

    Cooling air

    *5cm or more for 5.5K and 7.5KThese clearances are also necessary for changing the cooling fan.

    7) For installation in an enclosure

    Inverter

    Ventilation fan

    (Correct example) (Incorrect example)Position of Ventilation Fan

    Inverter

    Built-in cooling fan

    (Correct example)

    Inverter Inverter

    When more than one inverter is contained(Incorrect example)

    Inverter

    Inverter

    8) Vertical mounting

    2

  • 2.2 WiringINSTALLATION AND WIRING

    13

    2.2 Wiring

    2.2.1 Terminal connection diagram

    """" 3-phase 200V power input

    RST

    MRS

    RES

    SD

    SD

    P24

    P24A

    B

    C

    UVW

    P1

    (+)P

    PR

    (−)N(Note 1)

    (Note 2)

    (Note 2)

    DA

    DB

    DG

    FG

    DA

    DB

    DG

    SLD

    SW1 SW2

    SW3

    SINK

    SOURCE

    POWER LED

    ALARM LED

    L.RUN LED

    SD LED

    RD LED

    L.ERR LED

    3-phase AC power supply

    NFB

    Output stop

    Reset

    Control input signals (no voltage input allowed)

    JumperRemove this jumper when using the optional power-factor improving DC reactor.

    Brake resistor connection

    Motor

    IM

    Ground

    Alarm output

    Main circuit terminalControl circuit input terminalControl circuit output terminal

    GroundPU connector(RS-485)

    Sink inputcommons

    Source inputcommons

    CC-Link communication signals

    PLC CC-Linkmaster unit

    Station numbersetting

    Baudrate setting

    Sink-sourcechanging

    (Indicator)

    (L1)(L2)(L3)

    MC

    SLD

    SLD

    Note:1. 0.1K and 0.2K do not contain a transistor.2. Terminals SD and P24 are common terminals. Do not earth them to the

    ground.

  • INSTALLATION AND WIRING

    14

    (1) Description of the main circuit terminals

    Symbol Terminal Name Description

    R, S, T

    (L1, L2, L3)AC power input

    Connect to the commercial power supply. Keep these terminals

    unconnected when using the high power factor converter.

    U, V, W Inverter output Connect a three-phase squirrel-cage motor.

    P (+), PRBrake resistor

    connection

    Connect the optional brake resistor across terminals P-PR (+-PR)

    (not for 0.1K and 0.2K).

    P (+), N (−) Brake unit connection Connect the optional brake unit or high power factor converter.

    P (+), P1Power factor improving

    DC reactor connection

    Disconnect the jumper from terminals P-P1 (+-P1) and connect the

    optional power factor improving DC reactor.

    Ground For grounding the inverter chassis. Must be earthed.

    (2) Description of the control circuit terminals

    Type Symbol Terminal Name Description

    MRS Output halt

    Turn on the MRS signal (20ms or longer) to

    stop the inverter output.

    Used to shut off the inverter output to bring

    the motor to a stop by the electromagnetic

    brake.

    Setting of Pr. 183

    "MRS terminal (RY9)

    function selection"

    changes the terminal

    function.

    RES Reset

    Used to reset the protective circuit activated. Turn on the RES

    signal for more than 0.1 second, then turn it off. The signal can

    always be reset with the factory setting.

    Setting Pr. 75 enables reset only at an inverter alarm occurrence.

    (Refer to page 103.)

    P24Contact input

    common (source)

    Common terminal for contact inputs for use in the source input

    mode.

    In the source input mode, connection with this terminal switches the

    signal on and disconnection switches it off.

    Input si

    gnals

    Conta

    cts,

    e.g

    . st

    art

    and s

    ynch

    ronous

    sele

    ctio

    n

    SDContact input

    common (sink)

    Common terminal for contact inputs for use in the sink input mode.

    In the sink input mode, connection with this terminal switches the

    signal on and disconnection switches it off.

    Outp

    ut si

    gnals

    Conta

    ct

    A, B, C

    (note)Alarm output

    Contact output indicating that the output has

    been stopped by the inverter protective

    function activated. 230VAC 0.3A, 30VDC

    0.3A. Alarm: discontinuity across B-C

    (continuity across A-C), normal: continuity

    across B-C (discontinuity across A-C).

    Output terminal

    (remote input)

    function choices

    (Pr. 190 to Pr. 192)

    change the terminal

    functions.

    Note : Wire the cables for application of voltages to the contact outputs so that theymay be separated from the PLC power at the no-fuse breaker etc. If they areconnected to the same power supply as is used by the PLC, the inverter cannotbe changed during CC-Link communication.

    2

  • INSTALLATION AND WIRING

    15

    (3) CC-Link communication signals

    Terminal Symbol Terminal Name Description

    DA

    DB

    DG

    SLD

    SLD

    FG

    CC-Link

    communication

    signals

    Connected with the master station and other local stations to make

    CC-Link communication.

    (4) RS-485 communication

    Name Description

    PU connector

    Communication can be made by the PU connector in accordance with RS-485.

    ! Compliant standard: EIA Standard RS-485

    ! Transmission form: Multidrop link system

    ! Communication speed: Maximum 19200bps

    ! Overall distance: 500m

  • INSTALLATION AND WIRING

    16

    2.2.2 Wiring of the Main Circuit

    (1) Wiring instructions

    1) It is recommended to use insulation-sleeved solderless terminals for power supplyand motor wiring.

    2) Power must not be applied to the output terminals (U, V, W) of the inverter.Otherwise the inverter will be damaged.

    3) After wiring, wire off-cuts must not be left in the inverter.Wire off-cuts can cause an alarm, failure or malfunction. Always keep the inverterclean.When drilling mounting holes in a control box or the like, be careful so that chips andothers do not enter the inverter.

    4) Use thick cables to make the voltage drop 2% or less.If the wiring distance is long between the inverter and motor, a main circuit cablevoltage drop will cause the motor torque to decrease, especially at the output of alow frequency. (A selection example for the wiring length of 20m is shown on page18.)

    5) For long distance wiring, the overcurrent protection may be activated improperly orthe devices connected to the output side may misoperate or become faulty underthe influence of a charging current due to the stray capacitance of the wiring.Therefore, the maximum overall wiring length should be as indicated in the followingtable. If the wiring length exceeds the value, it is recommended to set "1" in Pr. 156to make the fast-response current limit function invalid. (When two or more motorsare connected to the inverter, the total wiring length should be within the indicatedvalue.)

    Inverter Capacity 0.1K 0.2K 0.4K 0.75K1.5K ormore

    Non-low acoustic noise mode 200m 200m 300m 500m 500mLow acoustic noise mode 30m 100m 200m 300m 500m

    Overall wiring length (1.5K or more)

    500m maximum

    300m

    300m

    300m+300m=600m

    2

  • INSTALLATION AND WIRING

    17

    6) Connect only the recommended optional brake resistor between the terminalsP-PR (+-PR). Keep terminals P-PR (+-PR) of 0.1K or 0.2K open.These terminals must not be shorted.0.1K and 0.2K do not accept the brake resistor. Keep terminals P-PR (+-PR) open.Also, never short these terminals.

    7) Electromagnetic wave interferenceThe input/output (main circuit) of the inverter includes harmonic components, whichmay interfere with the communication devices (such as AM radios) used near theinverter. In this case, install the FR-BIF optional radio noise filter (for use in the inputside only) or FR-BSF01 or FR-BLF line noise filter to minimize interference.

    8) Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIFoption) in the output side of the inverter.This will cause the inverter to trip or the capacitor and surge suppressor to bedamaged. If any of the above devices are installed, immediately remove them.(When using the FR-BIF radio noise filter with a single-phase power supply, connectit to the input side of the inverter after isolating the T phase securely.)

    9) When rewiring after operation, make sure that the POWER lamp has gone off, andwhen more than 10 minutes has elapsed after power-off, check with a meter etc.that the voltage is zero. After that, start rewiring work. For some time after power-off,there is a dangerous voltage in the capacitor.

    Notes on Grounding

    " Leakage currents flow in the inverter. To prevent an electric shock, the inverterand motor must be grounded.

    " Use the dedicated ground terminal to ground the inverter. (Do not use the screwin the case, chassis, etc.)

    " The ground cable should be as thick as possible. Its gauge should be equal to orlarger than those indicated in the following table. The grounding point should beas near as possible to the inverter to minimize the ground cable length.

    To meet the Low Voltage Directive, use PVC insulated cables larger thanspecified size in brackets ( ).

    " Ground the motor on the inverter side using one wire of the 4-core cable.

    (Unit: mm2)

    Ground Cable GaugeMotor Capacity

    200V class

    2.2kW or less 2 (2.5)

    3.7kW 3.5 (4)

    5.5kW, 7.5kW 5.5 (6)

  • INSTALLATION AND WIRING

    18

    (2) Terminal block layout

    FR-E520-0.1KN, 0.2KN, 0.4KN, 0.75KN

    P1N/- P/+ PR

    R/L1 S/L2 T/L3 U V W

    TB1Screw size (M3.5)

    Screw size (M3.5)

    FR-E520-1.5KN, 2.2KN, 3.7KN

    P1

    P/+

    PRT/L3 U V W

    Screw size(M4)

    N/-

    R/L1 S/L2TB2Screw size(M4)

    TB1Screw size(M4)

    FR-E520-5.5KN, 7.5KN

    P1N/- P/+ PRR/L1 S/L2 T/L3 U V W

    Screw size(M5)

    TB1Screw size(M5)

    (3) Cables, crimping terminals, etc.

    The following table lists the cables and crimping terminals used with the inputs (R (L1),S (L2), T (L3)) and outputs (U, V, W) of the inverter and the torques for tightening thescrews:

    """" FR-E520-0.1KN to 7.5KN

    CablesPVC insulated

    CablesCrimpingTerminals

    mm2 AWG mm2Applicable

    Inverter Type

    TerminalScrewSize

    Tight-ening

    TorqueN⋅⋅⋅⋅m R, S, T

    (L1, L2, L3)U, V, W

    R, S, T(L1, L2, L3)

    U, V, WR, S, T

    (L1, L2, L3)U, V, W

    R, S, T(L1, L2, L3)

    U, V, W

    FR-E520-0.1KN-0.75KN

    M3.5 1.2 2-3.5 2-3.5 2 2 14 14 2.5 2.5

    FR-E520-1.5KN, 2.2KN

    M4 1.5 2-4 2-4 2 2 14 14 2.5 2.5

    FR-E520-3.7KN

    M4 1.5 5.5-4 5.5-4 3.5 3.5 12 12 4 2.5

    FR-E520-5.5KN

    M5 2.5 5.5-5 5.5-5 5.5 5.5 10 10 6 4

    FR-E520-7.5KN

    M5 2.5 14-5 8-5 14 8 6 8 16 6

    Note:1. The cables used should be 75°C copper cables.2. Tighten the terminal screws to the specified torques.

    Undertightening can cause a short or misoperation.Overtightening can cause the screws and unit to be damaged, resulting in ashort or misoperation.

    2

  • INSTALLATION AND WIRING

    19

    (4) Connection of the power supply and motor

    """" Three-phase power input

    Three-phase power supply 200V

    R S T

    R S T

    No-fuse breaker

    The power supply cables must be connectedto R, S, T. (L1, L2, L3) If they are connected to U, V, W, the inverter will be damaged.(Phase sequence need not be matched.)

    U V W

    U V W

    Connect the motor to U, V, W. In the aboveconnection, turning on the forward rotation switch (signal) rotates the motor in the counterclockwise (arrow) directionwhen viewed from the load shaft.

    (L1) (L2) (L3)

    (L1) (L2) (L3)

    Motor

    Ground

    Groundterminal

    Note: To ensure safety, connect the power input to the inverter via a magneticcontactor and earth leakage circuit breaker or no-fuse breaker, and use themagnetic contactor to switch power on-off.

  • INSTALLATION AND WIRING

    20

    2.2.3 Wiring of the control circuit

    (1) Wiring instructions1) Terminals SD are common terminals for I/O signals. These common terminals must

    not be earthed to the ground.

    2) Use shielded or twisted cables for connection to the control circuit terminals and runthem away from the main and power circuits (including the 200V relay sequencecircuit).

    3) The frequency input signals to the control circuit are micro currents. When contactsare required, use two or more parallel micro signal contacts or a twin contact toprevent a contact fault.

    4) It is recommended to use the cables of 0.3mm2 to 0.75mm2 gauge for connection tothe control circuit terminals.

    5) When bar terminals and solid wires are used for wiring, their diameters should be0.9mm maximum If they are larger, the screw threads may be damaged duringtightening.

    (2) Terminal block layoutIn the control circuit of the inverter, the terminals are arranged as shown below:Terminal screw size: M2.5

    Terminal layout of control circuit

    P24P24SDSD

    MRSRESNCNCABC

    **

    *: Keep NC unconnected.

    2

  • INSTALLATION AND WIRING

    21

    (3) Wiring method

    1) For wiring the control circuit, use cables after stripping their sheaths.Refer to the gauge printed on the inverter and strip the sheaths to the followingdimensions. If the sheath is stripped too much, its cable may be shorted with theadjoining cable. If the sheath is stripped too little, the cable may come off.

    7mm±1mm

    2) When using bar terminals and solid wires for wiring, their diameters should be0.9mm maximum. If they are larger, the threads may be damaged during tightening.

    3) Loosen the terminal screw and insert the cable into the terminal.

    4) Tighten the screw to the specified torque.Undertightening can cause cable disconnection or misoperation. Overtightening cancause damage to the screw or unit, leading to short circuit or misoperation.

    Tightening torque: 0.25 N⋅m to 0.49 N⋅m* Use a size 0 screwdriver.

    Note : When routing the stripped cables, twist them so that they do not become loose.In addition, do not solder it.

    (4) Control logic changing

    The input signal logic is factory-set to the sink mode.To change the control logic, the position of the connector beside the control circuitterminal block must be changed.

    1) Using tweezers etc. to remove the connector in the sink logic position and fit it in thesource logic position.Do this position changing before switching power on.

  • INSTALLATION AND WIRING

    22

    Note:1. Make sure that the front cover has been installed securely.2. The front cover has a capacity plate and the inverter a rating plate on it.

    Since these plates have the same serial numbers, always reinstall theremoved cover to the inverter from where it was removed.

    3. Always install the sink-source logic changing connector in either of thepositions. If two connectors are installed in these positions at the same time,the inverter may be damaged.

    2) Sink logic type! In this logic, a signal switches on when a current flows out of the corresponding

    signal input terminal.Terminal SD is common to the contact input signals.Terminal SE is common to the open collector output signals.

    R

    RCurrentMRS

    RES

    SD

    AX40

    SE

    RUN

    24VDC

    R

    1

    9

    R

    • Current flow related to RUN signal Inverter

    3) Source logic type! In this logic, a signal switches on when a current flows into the corresponding signal

    input terminal.Terminal P24 is common to the contact input signals.Terminal SE is common to the open collector output signals.

    R

    R

    Current

    RES

    MRS

    P24AX80

    24VDC

    RUN

    SE

    1

    9

    R

    R

    • Current flow related to RUN signal Inverter

    2

  • INSTALLATION AND WIRING

    23

    2.2.4 Wiring of CC-Link communication signals

    (1) Terminal block wiring

    The terminals for CC-Link communication signals are arranged in the inverter asshown below.Terminal screw size: M2.5

    DA

    DB

    DG

    SLD

    SLD

    FG

    (2) Wiring of inverter and PLC

    UR (L1)

    VS (L2)

    WT (L3)

    DADADADBDBDGDGSLDSLDFG

    PLC CC-Linkmaster module

    Powersupply

    Inverter

    Motor

  • INSTALLATION AND WIRING

    24

    (3) Connection of two or more inverters

    Factory Automation can be applied to several inverters which share a link system asCC-Link remote device stations and are controlled and monitored by PLC userprograms.

    DA

    DB

    DG

    SLD

    FG

    Inverter

    DA

    DB

    DG

    SLD

    FG

    DA

    DB

    DG

    SLD

    FG

    InverterMaster module

    Terminal resistor*

    Terminal resistor*

    Shielded twisted cable

    Shielded twisted cable

    *Use the terminal resistors supplied with the PLC.

    1) Maximum number of units connected to one master station42 units (when only inverters are connected)

    If there are other units, the following conditions must be satisfiedsince the number of stations occupied changes with the unit:

    {(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≤ 64a: Number of units occupying 1 stationb: Number of units occupying 2 stationsc: Number of units occupying 3 stationsd: Number of units occupying 4 stations

    {(16 × A) + (54 × B) + (88 × C)} ≤ 2304A: Number of remote I/O station ≤ 64B: Number of remote device stations ≤ 42C: Number of local, standby master

    and intelligent device stations ≤ 26

    (4) Wiring method

    1) 1) Use twisted cables (three wire type) after stripping the cable sheaths and twistingthe wires. If the sheath is stripped too long, the cable may contact with the adjacentcable, causing a short circuit. If the sheath is stripped too short, the cable may bedisconnected. Use the recommended cables. For the specifications and availabilityof the CC-Link dedicated cable, refer to the CC-Link catalog.Recommended tightening torque: 0.22 N⋅m to 0.25 N⋅mUse a small flat-blade screwdriver (tip thickness: 0.6mm/full length: 3.5mm).

    6.5mm ±0.5mm

    2

  • INSTALLATION AND WIRING

    25

    (5) Recommendation of bar terminals

    For wiring of the CC-Link communication signals, two CC-Link dedicated cables mustbe twisted together and connected to one terminal block.When using bar terminals, the following terminals and tool are recommended.

    1) Recommended bar terminal, crimping tool! Company: Phoenix Contact Co., Ltd.! Bar terminal type: AI-TWIN2×0.5-8WH! Crimping tool type: CRIMPFOX UD6, ZA3

    2) Connection of terminal resistorConnect a terminal resistor between terminals DA-DB of the inverter located at theend.Work the resistor attached to the master unit of the PLC for use as the terminalresistor.

    Cut.Cut the tube.

    Tube

    Note: When there is no resistor attached to themaster unit, use a commercially available110Ω, 1/2W resistor.

    3) Connection of shield wire of the CC-Link dedicated cableTwist the shield wire of the CC-Link dedicated cable and connect it to terminal SLD.

    Shield wire

    Note: The two SLD terminals are connected in the inverter.

  • INSTALLATION AND WIRING

    26

    2.2.5 Connection to the PU connector

    (1) When connecting the parameter unit using a cable

    Use the option FR-CB2# or the following connector and commercially available cable:

    ! Connector : RJ45 connector

    Example 5-554720-3, Tyco Electronics Corporation,! Cable : Cable conforming to EIA568 (e.g. 10BASE-T cable)

    Example: SGLPEV 0.5mm×4P (Twisted pair cable, 4 pairs),MITSUBISHI CABLE INDUSTRIES, LTD.

    ! Parameter unit (FR-PU04): 20m

    (2) For RS-485 communication

    By removing the accessory cover and using the PU connector, communicationoperation can be performed from a personal computer etc.

    Viewed from the inverter (receptacle side) front

    8) to 1)

    1) SG2) P5S3) RDA4) SDB

    5) SDA6) RDB7) SG8) P5S

    Note:1. Do not connect the PU connector to a computer's LAN board, FAX modemsocket or telephone modular connector. Otherwise, the product may bedamaged due to electrical specification differences.

    2. Pins 2 and 8 (P5S) provide power to the control panel or parameter unit. Donot use these pins for RS-485 communication.

    3. Refer to page 115 for the communication parameters.

    1) When a computer having a RS-485 interface is used with several inverters

    PU connector

    (Note 1)

    Computer

    RS-485

    interface/terminal

    Computer

    10BASE-T cable (Note 2)

    Distribution

    terminal

    Station 1

    Inverter

    Station 2

    Inverter

    Station n

    Inverter

    Termination

    resistor

    PU connector

    (Note 1)

    PU connector

    (Note 1)

    2

  • INSTALLATION AND WIRING

    27

    Use the connectors and cables which are available on the market.Note:1. Connector: RJ45 connector

    Example: 5-554720-3, Tyco Electronics Corporation2. Cable : Cable conforming to EIA568 (such as 10BASE-T cable)

    Example: SGLPEV 0.5mm × 4P (Twisted pair cable, 4 pairs),Mitsubishi Cable Industries, Ltd.(Do not use pins 2) and 8) (P5S).)

    2) When a computer having a RS-232C interface is used with inverters

    Computer

    RS-232CconnectorRS-232Ccable

    RS-485terminal

    Max. 15m

    Converter*

    Terminationresistor

    Distributionterminal

    *Commercially available converter is required. (Note 3)

    10BASE-T cable (Note 2)

    PU connector(Note1)

    Station 1

    Inverter

    PU connector(Note1)

    Station 2

    Inverter

    PU connector(Note1)

    Station n

    Inverter

    Use the connectors, cables and converter which are available on themarket.

    Note:1. Connector: RJ45 connectorExample: 5-554720-3, Tyco Electronics Corporation

    2. Cable : Cable conforming to EIA568 (such as 10BASE-T cable)Example: SGLPEV 0.5mm × 4P (Twisted pair cable, 4 pairs),Mitsubishi Cable Industries, Ltd.(Do not use pins 2) and 8) (P5S).)

    3. *Commercially available converter examplesModel: FA-T-RS40ConverterNagoya Sales Office, Mitsubishi Electric Engineering Co., Ltd.

  • INSTALLATION AND WIRING

    28

    1) Wiring of one RS-485 computer and one inverter

    SDB

    SDA

    RDB

    RDA

    FG

    SG

    CSB

    CSA

    RSB

    RSARDB

    RDA

    SDB

    SDA

    SG

    (Note 1)

    Computer Side Terminals

    Signal name Description

    Receive data

    Receive data

    Send data

    Send dataRequest to send

    Request to send

    Clear to send

    Clear to send

    Signal ground

    Frame ground

    Cable connection and signal direction

    10 BASE-T Cable

    InverterPU connector

    0.3mm or more2

    2) Wiring of one RS-485 computer and "n" inverters (several inverters)

    SDB

    SDA

    RDB

    RDA

    FG

    SG

    CSB

    CSA

    RSB

    RSA

    (Note 1)

    SG

    RD

    B

    RD

    A

    SD

    B

    SD

    A

    SG

    RD

    B

    RD

    A

    SD

    B

    SD

    A

    SG

    RD

    B

    RD

    A

    SD

    B

    SD

    A

    Computer

    Station 1 Station 2 Station n

    Inverter Inverter Inverter

    Terminationresistor(Note 2)

    Cable connection and signal direction

    10 BASE-T Cable

    Note:1. Make connections in accordance with the instruction manual of thecomputer used.Fully check the terminal numbers of the computer as they differ betweenmodels.

    2. There may be the influence of reflection depending on the transmissionspeed and/or transmission distance. If this reflection hinderscommunication, provide a termination resistor. If the PU connector is usedto make a connection, use the distributor as a termination resistor cannot befitted.Connect the termination resistor to only the inverter remotest from thecomputer. (Termination resistor: 100Ω)

    2

  • INSTALLATION AND WIRING

    29

    2.2.6 Connection of stand-alone option units

    The inverter accepts a variety of stand-alone option units as required.Incorrect connection will cause inverter damage or an accident. Connect and operatethe option unit carefully in accordance with the corresponding option unit manual.

    (1) Connection of the dedicated external brake resistor (option)(Cannot be connected to 0.1K and 0.2K)

    Connect a brake resistor across terminals P (+) and PR. Connect a dedicated brakeresistor only.(For the positions of terminals P (+) and PR, refer to the terminal block layout (page 18.)

    PR

    P

    Brake resistor

    P PRBrake resistor

    P1N

    FR-E520-0.4KN, 0.75KN, 5.5KN, 7.5KN FR-E520-1.5KN to 3.7KN

    (2) Connection of the BU brake unit (option)

    Connect the BU brake unit correctlyas shown on the right. Incorrectconnection will damage the inverter.

    MCR (L1)S (L2)T (L3)

    UVW

    Motor

    IM

    Inverter

    HCHBHA TB

    HC HB ONBrake unit

    MCMC

    OFF

    (+)P

    (−)N

    POCR

    Discharge resistor

    Remove jumpers.

    PR

    OCR

    +

    BU brake unit N

    NFB

    Constant-voltage power supply

    Comparator

    PC

    Note:1. The wiring distance between the inverter, brake unit and discharge resistorshould be within 2m. If twisted wires are used, the distance should be within 5m.

    2. If the transistors in the brake unit should fail, the resistor will be extremelyhot, causing a fire. Therefore, install a magnetic contactor on the inverter'spower supply side to shut off current in case of failure.

  • INSTALLATION AND WIRING

    30

    (3) Connection of the FR-HC high power factor converter (option unit)(In the case of single-phase power input, the FR-HC cannot be connected.)When connecting the high power factor converter (FR-HC) to suppress powerharmonics, wire as shown below. Wrong connection will damage the high power factorconverter and inverter.

    Inverter(FR-E500)

    IM

    High power factor converter

    (FR-HC)External box(FR-HCB)

    Reactor 2(FR-HCL02)

    R(L1)

    Resistor

    Reactor 1(FR-HCL01)

    Powersupply

    Filter capacitor

    Phase detection

    S(L2)T(L3)

    P(+)N(−)MRSRESSD

    UVW

    PN

    RDYRSO

    SERST

    R4S4T4

    R3S3T3

    R3S3T3MC

    R2S2T2

    R2S2T2

    RST

    MCNFB

    MC1MC2

    Motor

    Resistor MC1MC2

    R4S4T4

    Note:1. The power input terminals R, S, T (L1, L2, L3) must be open.Incorrect connection will damage the inverter. Reverse polarity of terminalsN (−), P (+) will damage the inverter.

    2. The voltage phases of terminals R, S, T (L1, L2, L3) and terminals R4, S4,T4 must be matched before connection.

    3. If the load capacity is less than half of the high power factor convertercapacity, satisfactory harmonic suppression effects cannot be produced.

    (4) Connection of the power factor improving DC reactor (option)

    Connect the FR-BEL power factorimproving DC reactor betweenterminals P1-P (+). In this case, thejumper connected across terminalsP1-P (+) must be removed.Otherwise, the reactor will notfunction.

    P1 PFR-BEL

    Remove the jumper.

    P1

    P

    FR-BEL

    Remove the jumper.

    FR-E520-1.5KN to 3.7KN

    FR-E520-0.1KN to 0.75KN,

    5.5KN,7.5KN

    PRN

    Note:1. The wiring distance should be within 5m.2. The size of the cables used should be equal to or larger than that of the

    power supply cables (R (L1), S (L2), T (L3)).

    2

  • INSTALLATION AND WIRING

    31

    2.2.7 Design information

    1) Provide electrical and mechanical interlocks for MC1 and MC2 which are used forcommercial power supply-inverter switch-over.When there is a commercial power supply-inverter switch-over circuit as shownbelow, the inverter will be damaged by leakage current from the power supply due toarcs generated at the time of switch-over or chattering caused by a sequence error.

    2) If the machine must not be restarted when power is restored after a power failure,provide a magnetic contactor in the inverter's primary circuit and also make up asequence which will not switch on the start signal.If the start signal (start switch) remains on after a power failure, the inverter willautomatically restart as soon as the power is restored.

    3) Since the input signals to the control circuit are on a low level, use two or moreparallel micro signal contacts or a twin contact for contact inputs to prevent a contactfault.

    4) Do not apply a voltage to the contact input terminals of the control circuit.

    5) Always apply a voltage to the alarm output signal terminals (A, B, C) via a relay coil,lamp, etc.

    6) Make sure that the specifications and rating match the system requirements.

    1) Commercial power supply-inverterswitch-over

    UVW

    R(L1)S(L2)T(L3)

    IMPower supply

    InverterLeakage current

    MC2

    MC1

    Interlock

    3) Low-level signal contacts

    Low-level signal contacts Twin contact

  • 2.3 Other WiringINSTALLATION AND WIRING

    32

    2.3 Other Wiring

    2.3.1 Power supply harmonics

    Power supply harmonics may be generated from the converter section of the inverter,affecting the power supply equipment, power capacitor etc. Power supply harmonicsare different in generation source, frequency band and transmission path from radiofrequency (RF) noise and leakage currents. Take the following measures.

    """" The differences between harmonics and RF noises are indicated below:

    Item Harmonics RF Noise

    FrequencyNormally 40 to 50th degreesor less (up to 3kHz or less)

    High frequency (several 10kHz to 1GHzorder)

    EnvironmentTo wire paths, powerimpedance

    Across spaces, distance, laying paths

    Quantitativeunderstanding

    Logical computation ispossible

    Occurs randomly, quantitativeunderstanding is difficult.

    Generated amountApproximately proportionalto load capacity

    According to current fluctuation rate(larger with faster switching)

    Immunity of affecteddevice

    Specified in standards foreach device.

    Differs according to maker's devicespecifications.

    Examples ofsafeguard

    Install a reactor. Increase the distance.

    """" Countermeasures

    The harmonic current generated from theinverter to the power supply differsaccording to various conditions such as thewiring impedance, whether a power factorimproving reactor is used or not, and outputfrequency and output current on load side.For the output frequency and output current,the adequate method is to obtain themunder rated load at the maximum operatingfrequency.

    Note: A power factor improving capacitor and surge suppressor on the inverter'soutput side may overheat or be damaged due to the harmonics of the inverteroutput. Also, when an overcurrent flows in the inverter, the overcurrentprotection is activated. Hence, when the motor is driven by the inverter, donot install a capacitor or surge suppressor on the inverter's output side. Toimprove the power factor, insert a power factor improving reactor in theinverter's input or DC circuit. For details, refer to the FR-A500/E500 seriestechnical information.

    NFB

    IM

    Power factor

    improving AC

    reactor

    Inve

    rter

    Power factor

    improving DC

    reactor

    Motor

    Do not insert power

    factor improving capacitor

    2

  • INSTALLATION AND WIRING

    33

    2.3.2 Japanese harmonic suppression guideline

    Harmonic currents flow from the inverter to a power receiving point via a powertransformer. The harmonic suppression guideline was established to protect otherconsumers from these outgoing harmonic currents.1) "Harmonic suppression guideline for household appliances and general-purpose

    products"This guideline was issued by Ministry of Economy, Trade and Industry (formerlyMinistry of International Trade and Industry) in September, 1994 and applies to 3-phase 200V class inverters of 3.7kW or less. By installing the FR-BEL or FR-BALpower factor improving reactor, inverters comply with the "harmonic suppressiontechniques for transistorized inverters (input current 20A or less)" established by theJapan Electrical Manufacturers' Association. Therefore install the optional reactor forthe 3-phase 200V class, 3.7kW or less inverter.

    2) "Harmonic suppression guideline for specific consumers"This guideline sets forth the maximum values of harmonic currents outgoing from ahigh-voltage or specially high-voltage consumer who will install, add or renewharmonic generating equipment. If any of the maximum values is exceeded, thisguideline requires that consumer to take certain suppression measures.

    Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power

    Received Power Voltage 5th 7th 11th 13th 17th 19th 23rd Over23rd6.6kV 3.5 2.5 1.6 1.3 1.0 0.9 0.76 0.7022 kV 1.8 1.3 0.82 0.69 0.53 0.47 0.39 0.3633 kV 1.2 0.86 0.55 0.46 0.35 0.32 0.26 0.24

    (1) Application of the harmonic suppression guideline for specificconsumers

    Not more thanreference capacity

    New installation/addition/renewal of equipment

    Calculation of equivalentcapacity sum

    Sum of equivalentcapacities

    Over referencecapacity

    Calculation of outgoing harmonic current

    Is outgoing harmoniccurrent equal to or lowerthan maximum value?

    Not more than maximum value

    Harmonic suppression technique is not required.

    Over maximum value

    Harmonic suppressiontechnique is required.

  • INSTALLATION AND WIRING

    34

    Table 2 Conversion Factors for FR-E500 Series

    Class Circuit Type Conversion Factor (Ki)Without reactor K31 = 3.4With reactor (AC side) K32 = 1.8With reactor (DC side) K33 = 1.8

    33-phase bridge(Capacitor-smoothed)

    With reactors (AC, DC sides) K34 = 1.4

    5 Self-exciting 3-phase bridgeWhen high power factorconverter is used

    K5 = 0

    Table 3 Equivalent Capacity Limits

    Received Power Voltage Reference Capacity6.6kV 50 kVA22/33 kV 300 kVA66kV or more 2000 kVA

    Table 4 Harmonic Contents (Values at the fundamental current of 100%)

    Reactor 5th 7th 11th 13th 17th 19th 23rd 25thNot used 65 41 8.5 7.7 4.3 3.1 2.6 1.8Used (AC side) 38 14.5 7.4 3.4 3.2 1.9 1.7 1.3Used (DC side) 30 13 8.4 5.0 4.7 3.2 3.0 2.2Used (AC, DC sides) 28 9.1 7.2 4.1 3.2 2.4 1.6 1.4

    1) Calculation of equivalent capacity (P0) of harmonic generating equipmentThe "equivalent capacity" is the capacity of a 6-pulse converter converted from thecapacity of consumer's harmonic generating equipment and is calculated with thefollowing equation. If the sum of equivalent capacities is higher than the limit inTable 3, harmonics must be calculated with the following procedure:

    P0=Σ (Ki × Pi) [kVA]Ki : Conversion factor (refer to Table 2)Pi : Rated capacity of harmonic

    generating equipment* [kVA]i : Number indicating the conversion

    circuit type

    *Rated capacity: Determined by the capacityof the applied motor and found in Table 5. Itshould be noted that the rated capacity usedhere is used to calculate a generatedharmonic amount and is different from thepower supply capacity required for actualinverter drive.

    2) Calculation of outgoing harmonic currentOutgoing harmonic current = fundamental wave current (value converterd from received

    power voltage) × operation ratio × harmonic content• Operation ratio: Operation ratio = actual load factor × operation time ratio

    during 30 minutes• Harmonic content: Found in Table 4.

    2

  • INSTALLATION AND WIRING

    35

    Table 5 Rated Capacities and Outgoing Harmonic Currents for Inverter Drive

    Fundamental Wave Current Converted from 6.6kV

    (No reactor, 100% operation ratio)Applied

    Motor

    (kW)

    200V class

    Rated

    Current [A]

    6.6kV

    Equivalent of

    Fundamental

    Wave Current

    (mA)

    Rated

    Capacity

    (kVA) 5th 7th 11th 13th 17th 19th 23rd 25th

    0.4 1.61 (Note) 49 0.57 31.85 20.09 4.165 3.773 2.107 1.519 1.274 0.882

    0.75 2.74 (Note) 83 0.97 53.95 34.03 7.055 6.391 3.569 2.573 2.158 1.494

    1.5 5.50 (Note) 167 1.95 108.6 68.47 14.20 12.86 7.181 5.177 4.342 3.006

    2.2 7.93 (Note) 240 2.81 156.0 98.40 20.40 18.48 10.32 7.440 6.240 4.320

    3.7 13.0 (Note) 394 4.61 257.1 161.5 33.49 30.34 16.94 12.21 10.24 7.092

    5.5 19.1 579 6.77 376.1 237.4 49.22 44.58 24.90 17.95 15.05 10.42

    7.5 25.6 776 9.07 504.4 318.2 65.96 59.75 33.37 24.06 20.18 13.97

    Note: When a motor of 3.7kW or less capacity is driven by a transistorized inverter ofmore than 3.7kW. For example, when a 3.7kW or less motor is driven by a5.5kW transistorized inverter, the transistorized inverter is not the target of thehousehold appliances/general-purpose products guideline, but because theymust be included in the calculation of the harmonic current of the guideline, thefundamental wave input currents are indicated.

    3) Harmonic suppression technique requirementIf the outgoing harmonic current is higher than; maximum value per 1kW (contractpower) × contract power, a harmonic suppression technique is required.

    4) Harmonic suppression techniques

    No. Item Description

    1Reactor installation(ACL, DCL)

    Install a reactor (ACL) in the AC side of the inverter or a reactor(DCL) in its DC side or both to suppress outgoing harmoniccurrents.

    2

    High power factorconverter(FR-HC)

    The converter circuit is switched on-off to convert an inputcurrent waveform into a sine wave, suppressing harmoniccurrents substantially. The high power factor converter (FR-HC)is used with the standard accessory.

    3Installation of powerfactor improvingcapacitor

    When used with a series reactor, the power factor improvingcapacitor has an effect of absorbing harmonic currents.

    4Transformer multi-phase operation

    Use two transformers with a phase angle difference of 30° as in-∆, ∆-∆ combination to provide an effect corresponding to 12

    pulses, reducing low-degree harmonic currents.

    5AC filter A capacitor and a reactor are used together to reduce

    impedances at specific frequencies, producing a great effect ofabsorbing harmonic currents.

    6

    Passive filter(Active filter)

    This filter detects the current of a circuit generating a harmoniccurrent and generates a harmonic current equivalent to adifference between that current and a fundamental wave currentto suppress a harmonic current at a detection point, providing agreat effect of absorbing harmonic currents.

  • INSTALLATION AND WIRING

    36

    2.3.3 Inverter-generated noise and reduction techniques

    Some noises enter the inverter causing it to incorrectly operate, and others areradiated by the inverter causing misoperation of peripheral devices. Though theinverter is designed to be insusceptible to noise, it handles low-level signals, so itrequires the following basic measures to be taken. Also, since the inverter chops theoutput at high carrier frequencies, it could generate noise. If these noises causeperipheral devices to misoperate, measures should be taken to suppress noise. Themeasures differ slightly depending on noise propagation paths.

    1) Basic measures! Do not run the power cables (I/O cables) and signal cables of the inverter in

    parallel with each other and do not bundle them.! Use twisted shield cables for the detector connecting and control signal cables

    and connect the sheathes of the shield cables to terminal SD.! Ground the inverter, motor, etc. at one point.

    2) Measures against noise which enters and causes misoperation of the inverterWhen devices which generate noise (devices which use magnetic contactors,magnetic brakes, many relays, for example) are installed near the inverter, theinverter may misoperate due to noise. The following measures must be taken:! Provide surge suppressors for devices that generate noise to suppress noise.! Fit data line filters to signal cables. (Refer to page 39)! Ground the shields of the detector connection and control signal cables with cable

    clamp metal.2

  • INSTALLATION AND WIRING

    37

    3) Measures against noises which are radiated by the inverter causing misoperation ofperipheral devices.Inverter-generated noises are largely classified into those radiated by the cablesconnected to the inverter and inverter main circuit (I/O), those electromagneticallyand electrostatically inducted to the signal cables of the peripheral devices close tothe main circuit power supply, and those transmitted through the power supplycables.

    Inverter-generated noise

    Air-propagated noise

    Path 2)

    Path 1)

    Path 4), 5)

    Path 6)

    Path 8)

    Path 7)

    Magnetic induc-tion noise

    Static induction noise

    Cable Propaga-ted noise

    Noise directly radiated by inverter

    Noise radiated by power cables

    Noise radiated by motor cables

    Noise propagated through power cables

    Leakage noise from groundcable due to leakage current

    Path 3)

    Inverter

    IMMotorSensor

    7) 2)

    1)

    3)4)

    5)

    7)

    2)6)

    3)

    8)

    Telephone

    Sensor power supply

    Receiver

    Instrument

  • INSTALLATION AND WIRING

    38

    Noise Path Measures

    1), 2), 3)

    When devices which handle low-level signals and are susceptible tomisoperation due to noise (such as instruments, receivers and sensors)are installed near the inverter and their signal cables are contained in thesame panel as the inverter or are run near the inverter, the devices maybe misoperated by air-propagated noise and the following measures mustbe taken:(1) Install easily affected devices as far away as possible from the

    inverter.(2) Run easily affected signal cables as far away as possible from the

    inverter.(3) Do not run the signal cables and power cables (inverter I/O cables) in

    parallel with each other and do not bundle them.(4) Insert line noise filters onto I/O and radio noise filters into inputs to

    suppress cable-radiated noises.(5) Use shielded cables for signal cables and power cables and run them

    in individual metal conduits to further reduce effects.

    4), 5), 6)

    When the signal cables are run in parallel with or bundled with the powercables, magnetic and static induction noises may be propagated to thesignal cables causing misoperation of the devices and the followingmeasures must be taken:(1) Install easily affected devices as far away as possible from the

    inverter.(2) Run easily affected signal cables as far away as possible from the

    inverter.(3) Do not run the signal cables and power cables (inverter I/O cables) in

    parallel with each other and do not bundle them.(4) Use shielded cables for signal cables and power cables and run them

    in individual metal conduits to further reduce effects.

    7)

    When the power supplies of the peripheral devices are connected to thepower supply of the inverter within the same line, inverter-generated noisemay flow back through the power supply cables causing misoperation ofthe devices and the following measures must be taken:(1) Install the radio noise filter (FR-BIF) to the power cables (input cables)

    of the inverter.(2) Install the line noise filter (FR-BLF, FR-BSF01) to the power cables

    (I/O cables) of the inverter.

    8)

    When a closed loop circuit is formed by connecting the peripheral devicewiring to the inverter, leakage current may flow through the ground cableof the inverter causing misoperation of the device. In such a case,disconnection of the ground cable of the device may cause the device tooperate properly.

    2

  • INSTALLATION AND WIRING

    39

    """" Data line filter

    Noise entry can be prevented by providing a data line filter for the detector or othercable.

    """" Data examples

    By decreasing the carrier frequency, thenoise terminal voltage* can be reduced.Use Pr. 72 to set the carrier frequency toa low value (1kHz).Though motor noise increases at a lowcarrier frequency, selection of Soft-PWMwill make it unoffending.

    By using shielded cables as signal cables,induction noise can be reduced greatly (1/10 to1/100). Induction noise can also be reduced bymoving the signal cables away from the inverteroutput cables.(Separation of 30cm reduces noise to 1/2 to 1/3.)By fitting the FR-BSF01 or BLF on the inverteroutput side, induction noise to the signal cablescan be reduced.

    Differences between noise terminalvoltages at different carrier frequencies

    0

    20

    40

    60

    80

    100

    120

    0.1 1 10Noise frequency (MHz)N

    ois

    e t

    erm

    inal v

    olta

    ge (

    dB

    )

    ConditionsAverage terminal voltage 0dB=1µV 120dB=1V

    Carrier frequency 10kHz

    Carrier frequency 1kHz

    Noise induced to signal cables by inverter outputcables

    5cm

    Line-to-line distance d (cm)

    20

    40

    60

    80

    100

    100 20 30 40 50

    Induct

    ion v

    olta

    ge

    (dB

    )

    d(cm) Motor

    Measuring instrument

    Terminal

    Inverter

    FR-BLFFR-BSF01

    (4T)

    Conditions• Inverter: FR-E520-3.7KN• Motor: FR-JR 4P 3.7kW• Output frequency: 30Hz• Noise form: Normal modeParallel cable

    Twisted pair cable

    Coaxial cable

    * Noise terminal voltage: Represents the magnitude of noise propagated from theinverter to the power supply.

    """" Example of measures against noise

    Inverter

    FR-BIF

    Sensor

    Use 4-core cable for motor power cable and use one wire as earth cable.

    Power supply

    for sensor

    Use twisted pair shielded cable.

    Inverter power supply

    Control power supply

    Do not ground shield but connect it to signal common cable.

    Do not ground control box directly.Do not ground control cable.

    Separate inverter and power line 30cm or more (at least 10cm) from sensor circuit.

    Install filter FR-BIF to inverter input side.

    Control box Reduce carrier frequency.

    Motor

    IMFR-BSF01FR-

    BSF01

    FR-BLFFR-BSF01

    Install filter to

    inverter input side.

    FR-BLFFR-BSF01

    Install filter to

    inverter output side.

  • INSTALLATION AND WIRING

    40

    2.3.4 Leakage currents and countermeasures

    Due to the static capacitance existing in the inverter I/O wiring and motor, leakagecurrents flow through them. Since their values depend on the static capacitance, carrierfrequency, etc., take the following measures.

    (1) To-ground leakage currents

    Leakage currents may flow not only into the inverter's own line but also into the otherlines through the ground cable, etc. These leakage currents may operate earth leakagecircuit breakers and earth leakage relays unnecessarily.

    """" Countermeasures

    ! If the carrier frequency setting is high, decrease the carrier frequency (Pr. 72) ofthe inverter.Note that motor noise increases. Selection of Soft-PWM (Pr. 240) will make itunoffending.

    ! By using earth leakage circuit breakers designed for harmonic and surgesuppression (e.g. Mitsubishi's Progressive Super Series) in the inverter's own lineand other line, operation can be performed with the carrier frequency kept high(with low noise).

    """" To-ground leakage current

    ! Note that a long wiring length will increase leakage currents. Decrease the carrierfrequency of the inverter to reduce leakage currents.

    ! Higher motor capacity leads to larger leakage currents.

    (2) Line-to-line leakage currents

    Harmonics of leakage currents flowing in static capacities between the inverter outputcables may operate the external thermal relay unnecessarily.

    InverterPower supply

    IM

    Thermal relay

    Line static capacitances

    N