FOUNDATION FIELDBUS ITK6

Instructions for start-up

Page 2: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

2

List of updates

Index Date Modification Written

by: Checked

by: Approved

by :

B 22/09/16 Typo corrections T. Milan A. Delannes B. Prost

A 11/12/15 Document creation based on NR1157 T. Milan D. Schwebel F. Bayle

Page 3: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

3

Summary

List of updates 2

Summary 3

1. INTRODUCTION 4

2. SPECIFICATIONS 4

3. FOUNDATION FIELDBUS INTERFACE 5 3.1. Hardware description 5 3.2. Cable requirements 5 3.3. Fieldbus connection 5 3.4. Intellibus Set-up 6 3.5. Display indication of fieldbus communication status 6 3.6. Emergency supply 7

4. Fundational FIELDBUS TECHNICAL OVERVIEW 7 4.1. Foundation Fieldbus communication 7

4.1.1. Link Active Scheduler (LAS) 7 4.1.2. Function Block 7 4.1.3. Transducer Block 8 4.1.4. Ressource block 8 4.1.5. Device description 8

4.2. Foundation Fieldbus technology 8 4.2.1. Fieldbus Signaling 8 4.2.2. Maximum cable length 8 4.2.3. Terminator 10 4.2.4. Number of devices possible on the Fieldbus 10 4.2.5. Repeaters 10

5. CONTROLS AND INDICATIONs 11 5.1. Actuator controls 11 5.2. Actuator feedback indications 15

6. TRANSDUCER BLOCK 20

7. FUNCTION BLOCK PID 24

8. FIELD DIAGNOSTIC PARAMETERS 25

Page 4: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

4

1. INTRODUCTION

Foundation Fieldbus is an industrial fieldbus which allows connecting actuators and other devices (sensors, etc.) to a Distributed Control System (DCS) or a Programmable Logic Controller (PLC). Many actuators and other devices can be connected on a fieldbus line provided they are all equipped with a compatible Foundation Fieldbus interface.

Foundation Fieldbus uses standard Function Blocks.

A Function Block could be:

digital output (DO) such as commands “open” and “close”,

digital input (DI) such as feedback status “valve open”, “valve closed”.

analog output (AO) and analog input (AI) for signals as position signals.

Proportionnal / Integral / Derivative (PID) control may be performed by the field through the use of Function Blocks.

The Foundation Fieldbus interface described in this document has been specially designed for the Bernard actuators with INTELLI+ control.

Control box with inside Foundation Fieldbus interface could be supplied to connect other equipment.

Please make sure to get and read the INTELLI+ instructions for start-up (ref. NR1151) prior going further with the setting of the INTELLIBUS FF interface.

2. SPECIFICATIONS

Physical requirements

The INTELLIBUS FF interface is powered directly from the fieldbus and is fully isolated from the actuator.

Supply voltage (from the Fieldbus) 9 to 32V Consumption 20mA

A loss of actuator power supply does not lead to a fieldbus disruption.

Temperature working range is the same as the actuator one.

Compliance requirements

CE Conformity.

The INTELLIBUS FF interface has successfully completed rigorous testing by the Fieldbus Foundation and has received registration.

Device Description files (named Bernard Controls - Intelli+ FF Interface) available on request and on the website www.fieldbus.org

Technical requirements

The INTELLIBUS FF interface is a Link Master device and is capable of becoming a Link Active Scheduler (LAS)

Function block execution time:

DI, DO, AI, AO blocks = 50 ms;

PID block = 100ms

Channels numbers

Channel1 = AI 1 “Position %”

Channel7 = “DI 4”

Channel2 = AI 2 “Torque %”

Channel8 = “DI 5”

Channel3 = “AO” Channel9 = “DO 1”

Channel4 = “DI 1” Channel10 = “DO 2”

Channel5 = “DI 2” Channel11 = “DO 3”

Channel6 = “DI 3” Channel12 = “DO 4”

Page 5: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

5

3. FOUNDATION FIELDBUS INTERFACE

3.1. Hardware description

The Fieldbus module “INTELLIBUS FF” located in the actuator is plugged onto the main Intelli+ board. No access is required.

3.2. Cable requirements

The cable must be specified for Foundation Fieldbus type A.

An example of a cable below:

Cable Characteristics

Belden 3076F

1 pair 18 AWG

Resistance: 5.86 ohms/1000ft @20°C

Nominal mutual capacitance @ 1kHz:

80pF/m (24pF/ft)

Shielding : shielding braid or

foil

Fieldbus cable must be installed according to the following requirements:

A distance of 20 cm must be kept with other cables

It must follow a specific cable path and be connected to the earth

All actuators using Fieldbus must be at the same earth electrical potential

3.3. Fieldbus connection

Fieldbus is connected according to the following schema:

Common cable shielding is connected to a terminal of the actuator (34 here)

Cables are connected on 2 terminals of the actuator (35 & 36 here). Corresponding input and output cables are connected on the same terminal.

A termination has to be installed at each end of line. This termination is not built in the actuator.

Terminals number may not match ones mentioned here. Please check your wiring diagram to get the correct ones.

Shield

34

Previous actuator

Next

actuator

Actuator

35 36

Page 6: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

6

3.4. Intellibus Set-up

The INTELLIBUS module is selected in the menu:

How to set-up Intellibus

1) With the local control knob of the actuator, select Change, then Fieldbus, then Card FF present.

2) Validate with Yes.

3) Confirm with the red knob.

4) To save, select return in each submenu until reading RETURN (Change OK?) Then confirm OK with the red button.

When the Fieldbus card is selected, the menu shows 2 other settings:

Lost communication This settings allows to configure actuator behaviour in case of communication loss

o Which position the actuator goes to closed position, open position or stays in position. Default setting is Stayput.

o Controls state: in case of loss of communication, all controls are reset. For example, if the auxiliary control AUX1 is set on Local control inhibit when communication is lost, local controls are available again.

Cmd by fieldbus The default setting is Yes. If No is selected, then no command is taken into account through the Fieldbus. Only indications are transmitted.

3.5. Display indication of fieldbus communication status

An indication of the fieldbus communication status is available on the actuator display.

No data exchange (empty square)

Data exchange (rotating triangle)

Intellibus module fault (blinking cross)

(x) can have the following values :

O: On/Off mode command from DO blocs

A: Auto-mode command from AO blocs

Blanc: No FF command only wired command

FF(x)

FF(x)

FF(x)

Page 7: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

7

3.6. Emergency supply

The actuator Intelli+ is normally supplied by the mains but in case of loss of power supply an emergency supply could be used to continue to communicate through the Fieldbus. This emergency supply needs 24V DC 4W.

The optional extra battery is also an alternative to be able to read the display during power off period but also to update the position in case of a change. The right position is then updated through the Fieldbus communication.

4. Fundational FIELDBUS TECHNICAL OVERVIEW

4.1. Foundation Fieldbus communication

4.1.1. Link Active Scheduler (LAS)

The INTELLIBUS FF interface can communicate with Distributed Control System (DCS), Programming Logic Controller (PLC), Personnal Computer (PC) or other devices from various suppliers equipped with Foundation Fieldbus.

Communication on the Fieldbus is managed by a Link Active Scheduler (LAS).

Characteristics of the LAS

The LAS has a list of the devices connected and sends cyclic messages to all devices. It also sends a Pass Token message, allowing an actuator to transmit unscheduled messages.

Any Link Master device may becoming a LAS.

The Fieldbus may have multiple Link Masters. If the current LAS fails, one of the Link Masters will become the LAS and the operation fieldbus will continue.

The actuator with INTELLIBUS FF could be a LAS.

Actuator address

There is no address configuration to the actuator level. This is performed automatically by the Link Active Scheduler (LAS). New actuators may be added to the Fieldbus anytime. The LAS periodically sends Probe Node (PN) messages to the addresses not in the live list. If an actuator is present at the addresses and receives the PN, it immediately returns a Probe Response message. If the actuator answers with a PR, the LAS adds the actuator to the live list and confirms its addition by sending the actuator a Node Activation message.

4.1.2. Function Block

A function block is like a black box inside the INTELLIBUS FF interface with input and output parameters. Function Block is used by the control system to communicate through the Fieldbus.

Function block name:

Discrete input (DI) (input in a fieldbus view) - for example: valve is open

Discrete output (DO) - for example: close the valve

Analog input (AI) - for example: valve is 50% open

Analog output (AO) - for example: close the valve at 30%

Page 8: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

8

In each function block there is a list of parameters available (see §5).

Another Function Block is the Proportional / Integral / Derivative (PID) to perform control loop (see §7).

4.1.3. Transducer Block

The Transducer Block contains information not used for the process such as manufacture date, dead band setting, and opening and closing torque/position curve. (see §6)

4.1.4. Ressource block

The Resource Block contains data specific to the hardware associated with the resource. This includes the device type and revision, manufacturer ID, serial number and resource state.

The resource block contain also the Field Diagnostic parameter (see §8)

4.1.5. Device description

To achieve interoperability Device Description (DD) technology is used. The DD is like a “driver” for a printer. Bernard Controls supply the Device Description for the INTELLIBUS FF interface.

4.2. Foundation Fieldbus technology

4.2.1. Fieldbus Signaling

The transmitting device delivers +/- 10mA at 31.25 kbit/s into a 50 ohm equivalent load to create a 1.0 V peak-to-peak voltage modulated on top of the direct current supply voltage. The DC voltage can range from 9 to 32V.

The maximum DC current available depends of the fieldbus power supply.

4.2.2. Maximum cable length

The Fieldbus cable coming from a PLC is connected to the first actuator then the Fieldbus cable links this actuator with the next one and so on. All actuators are connected to the line one after the other until the last one. No return to the PLC is required.

The 31.25 kbit/s fieldbus allows ramifications or “spurs” but with restrictions

Cable length = Trunk length + total spur lengths

Maximum length = 1900m (6200ft) with “Type A” cable

Devices Max total spur length

25-32 No spur No spur

19-24 30m 100ft

15-18 60m 200ft

13-14 90m 300ft

1-12 120m 400ft

Page 9: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

9

Possible number of devices possible on the Fieldbus will vary depending on the power consumption of each device. The INTELLIBUS FF consumption is 20mA and the minimum voltage allowed is 9V. It is necessary to check the available voltage at each actuator.

Example

With a cable type Belden 3076F - 23 ohm/km at 70°C (46 ohm for 2 wires) INTELLIBUS consumption 20mA, minimum voltage 9V. Fieldbus supply voltage 24V The drop in voltage due to the consumption is calculated by Drop in voltage = Cable resistance × Current. Results are summarized in the following table.

Length Nb of actuators supplied

Current (mA) Drop in voltage Segment m ft

200 656 5 100 0.92

50 164 4 80 0.18

50 164 1 20 0.05

70 230 3 60 0.19

70 230 2 40 0.13

60 197 1 20 0.06

700 2297 1 20 0.64

Total 1200 3937

Total fieldbus length ( to sum) is less than 1900m.

Spurs length ( + ) is less than 120m

The last actuator has a supply voltage of:

24V − − − − − = 22V (> 9V) that is enough to work.

PLC

Spurs

End of line

Terminator

Note: The PLC is also at the end of the main trunk cable and needs a

terminator

Main trunk Main trunk

Page 10: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

10

4.2.3. Terminator

A terminator must be connected at each end of the main trunk cable. Note: There is no end of line terminator inside the actuator. This terminator is made with a capacity in a series with a resistor.

4.2.4. Number of devices possible on the Fieldbus

The number of devices depends of the power supply of the Fieldbus. With a supply of 24V 350mA it is possible to connect until 17 actuators (each actuator needs 20mA)

4.2.5. Repeaters

Adding repeaters modules allows to increase both the number of actuator on the line and total line length. Each repeater allows to lengthen the line by 1900m. See §4.2.2 to know the possible device number and maximum length for each segment.

According to the type of repeater, it is possible to use until 4 repeaters. Take also into account the repeater consumption on the fieldbus (usually 30mA). The important advantage of the repeater compared to other repeater-free technologies is to keep the communication speed unaffected and therefore to get a very short response time.

Bernard Controls can supply weatherproof or explosion proof repeaters.

PLC Repeater

Repeater power

supply End of line Terminator

Segment 1 Segment 2

100 Ohms

1 µF

Page 11: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

11

5. CONTROLS AND INDICATIONs

With Foundation Fieldbus system, controls and indications are organized in Function Blocks. For actuator controls (§4.1) there is Function Block Discrete Output (DO) or Analog Output (AO). Output is a Fieldbus view: output of the Fieldbus. For actuator indications (§4.2) there is Function Block Discrete Input (DI) or Analog Input (AI). These data are mainly use for the processing. For configuration, setting and maintenance the data are brought together in the Transducer Block (§5)

5.1. Actuator controls

Actuator control by Foundation Fieldbus is possible only if the actuator rotating selector is on the "remote" position.

Conditions which can prevent a command to be executed:

Actuator rotating selector on "local" or "OFF"

Alarm tripped (motor thermal overload)

Emergency command received (ESD)

Actuators controls are located at the Function Block Discrete Output (DO) in the INTELLIBUS module. These controls are:

Function Block DO(1)

Bit n° Value Description

Bit 0 0 No command

1 Close command

Bit 1 0 No command

1 Open command

Bit 2 0 Stop ( or maintained command mode)

1 No stop (or Pulse command mode)

Bit 3 0 No command

1 Auxiliary command 1

Bit 4 0 No command

1 Auxiliary command 2

Bit 5 0 Relay 1 contact open

1 Relay 1 contact closed

Bit 6 0 Relay 2 contact open

1 Relay 2 contact closed

Bit 7 0 Relay 3 contact open

1 Relay 3 contact closed

Remark: If a Function Block is only one bit writable, then use DO(1), DO(2),DO(3) to reach the controls Open, Close and Stop. In other case Function Block DO(1) is sufficient for controls Open,

Close and Stop

Page 12: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

12

OPEN / CLOSE (Open and close command)

According to the actuator configuration, it is possible to select a priority to the opening or to the closing command (refer to NR1151). By default there is no priority given to either opening or closing.

Priority can be used to:

Allow to reverse the actuator rotation direction during a manoeuvre without having to use the stop command. In this case, it is necessary to set a priority to the opening or to the closing direction.

Give priority to one or the other rotation direction: if the actuator receives the open and close commands simultaneously and the priority has been given to the opening, the actuator will run the open position.

STOP If this command is maintained at 0 (most common case), the open and close commands have to be maintained. If this command is set to 1, a short duration open / close command pulse is sufficient to drive the valve to the open or closed position. In this case, the stop command (0) can be used to stop the actuator during the travel in its current position.

AUXILIARY COMMANDS

By default, auxiliary command 1 is assigned to local control (actuator selector) inhibited.

By default, auxiliary command 2 is not assigned to a Fieldbus command but to an emergency command (ESD): this command is hardwired (separate wiring) and directly connected to the control box main strip.

These commands depend of actuator configuration (refer to NR1151) and can be assigned to the following functions.

LOCAL / REMOTE Substitutes for the local/remote selector of the actuator and is used to remotely enable either remote control or local control.

LOCAL+REMOTE / REMOTE: same as previous but local and remote control can be enabled simultaneously.

LOCAL COMMAND INHIBIT The local command inhibit is remotely controlled. It inhibits the local opening and closing commands, and enables remote commands, even if the Local/Remote selector of the actuator is set to Local.

OPEN, CLOSE INHIBIT: this command is used to inhibit opening or closing of the actuator.

AUTO/ON-OFF For an actuator used in modulation with positioner function, it is possible to issue remote commands via proportional control (equivalent to 4-20mA) or via opening/closing/stop commands. The auto/on-off command is used to switch over from one type of command to another.

ESD CLOSE, OPEN, STOP The ESD (Emergency Shut Down) is an emergency remote command, which overrides all other commands. According to the valve operation, the emergency command will be an opening, closing or intermediate stop. This ESD command is assigned to a Fieldbus command for auxiliary command 1 and assigned to a hardwired (separate wiring) for auxiliary command 2.

Note: The hardwired ESD has a higher priority than Fieldbus ESD. The emergency command is not possible when the Local/Remote selector is set to "OFF".

PARTIAL STROKE This command performs automatically a test to confirm that the actuator is still operational. The test consists to operate the actuator on a partial stroke and return. The start position and the stroke % can be configured. An alarm is emitted if the stroke is not performed in a predetermined delay. This delay is worked out from the rated operating time.

RELAYS The relays could be used to have an output indication (wired as a non fieldbus actuator) or to drive outside devices through Fieldbus. These optional relays could be configured in Intelli+ menu for actuator indication or output controls.

Page 13: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

13

Function Block DO(2)

Bit n° Value Description

Bit 0 0 No command

1 Open command

Bit 1 0 No command

1 Close command

Bit 2 0 Stop ( or maintained command mode)

1 No stop (or Pulse command mode)

Bit 3 0 No command

1 Auxiliary command 1

Bit 4 0 No command

1 Auxiliary command 2

Bit 5 0 Relay 1 contact open

1 Relay 1 contact closed

Bit 6 0 Relay 2 contact open

1 Relay 2 contact closed

Bit 7 0 Relay 3 contact open

1 Relay 3 contact closed

The same controls are available in various Function Blocks

Function Block DO(3)

Bit n° Value Description

Bit 0 0 Stop (or Maintained command mode)

1 No stop (or Pulse command mode)

Bit 1 0 Relay 1 contact open

1 Relay 1 contact closed

Bit 2 0 Relay 2 contact open

1 Relay 2 contact closed

Bit 3 0 Relay 3 contact open

1 Relay 3 contact closed

Bit 4 0 Relay 4 contact open

1 Relay 4 contact closed

Bit 5 0 Relay 5 contact open (optional)

1 Relay 5 contact closed (optional)

Bit 6 0 Relay 6 contact open (optional)

1 Relay 6 contact closed (optional)

Bit 7 0 Relay 7 contact open (optional)

1 Relay 7 contact closed (optional)

Page 14: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

14

Function Block DO(4)

Bit n° Value Description

Bit 0 0 No command

1 Auxiliary command 1

Bit 1 0 No command

1 Auxiliary command 2

Bit 2 0 No command

1 Close command

Bit 3 0 No command

1 Open command

Bit 4 0 Relay 1 contact open

1 Relay 1 contact closed

Bit 5 0 Relay 2 contact open

1 Relay 2 contact closed

Bit 6 0 Relay 3 contact open

1 Relay 3 contact closed

Bit 7 0 Relay 4 contact open

1 Relay 4 contact closed

The actuator proportional control is located at the Function Block Analog Output (AO) in the INTELLIBUS module. This indication is:

Function Block AO(1)

Proportional control (set-point) 0.0% to 100.0% (1000 points), 0.0=closed, 100.0=open

To choose between proportional and ON-OFF control, assign an auxiliary command to the function AUTO/ON-OFF then select the control mode required from the control room (see above Function Block DO).

Page 15: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

15

5.2. Actuator feedback indications

The actuator feedback indications are located at the Function Block Discrete Intput (DI) in the INTELLIBUS module. These indications are:

Function Block DI(1)

Bit n° Value Description

Bit 0 0 Valve not closed

1 Valve closed

Bit 1 0 Valve not open

1 Valve Open

Bit 2 0 The actuator is not running

1 Actuator running

Bit 3 0 Actuator not closing

1 Actuator closing

Bit 4 0 Actuator not opening

1 Actuator opening

Bit 5 0 Selector not to remote position

1 Selector to remote position

Bit 6 0 Selector not to OFF position

1 Selector to OFF position

Bit 7 0 Selector not to local position

1 Selector to local position

Valve OPEN/CLOSE: confirms the valve is open or closed

Actuator running: the actuator is operated in opening or closing direction

Actuator Opening/Closing: the actuator is operated in opening/closing direction

Selector to remote: no command allowed from Local controls.

Selector to OFF: no command allowed in local or from Fieldbus. Indications are always available.

Selector to Local: no command allowed from Fieldbus. Indications are always available.

Page 16: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

16

Function Block DI(2)

Bit n° Value Description

Bit 0 0 Valve not open

1 Valve Open

Bit 1 0 Valve not closed

1 Valve closed

Bit 2 0 Actuator not closing

1 Actuator closing

Bit 3 0 Actuator not opening

1 Actuator opening

Bit 4 0 Selector not to remote position

1 Selector to remote position

Bit 5 0 Actuator available

1 Actuator fault indication

Bit 6 0 No ESD command

1 Actuator receives an emergency command ESD

Bit 7 0 No valve jammed alarm

1 Valve jammed

Actuator fault indication

The actuator is not available due to a following event:

Motor thermal overload, lost phase (in case of 3ph supply), locked rotor.

Including additional faults (refer to NR1151 to configure):

Selected option: selector in local, selector in off.

Options: jammed valve, emergency command, command inhibit, over-travel.

If the actuator is power off, then the Intellibus interface is power off and there is no communication on Fieldbus (except with the optional extra battery or the emergency supply).

Actuator receives an emergency command ESD: the actuator is not available because it receives

an emergency command which overrides all other commands

Valve jammed: actuation could not be completed due to excess torque.

Page 17: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

17

Function Block DI(3)

Bit n° Value Description

Bit 0 0 Selector not to remote position

1 Selector to remote position

Bit 1 0 Selector not to OFF position

1 Selector to OFF position

Bit 2 0 selector not to local position

1 Selector to local position

Bit 3 0 No action

1 Torque limiter action in open direction

Bit 4 0 No action

1 Torque limiter action in close direction

Bit 5 0 No locked motor open alarm

1 Locked motor open

Bit 6 0 No locked motor close alarm

1 Locked motor close

Bit 7 0 No overtravel alarm

1 Overtravel alarm

Torque limiter action OPEN/CLOSE: torque limiter action in opening/closing direction even if the valve stops normally on torque.

Locked motor OPEN/CLOSE: motor is locked in the opening/closing direction.

Overtravel alarm: position overshoot >5% after motor shut down.

Page 18: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

18

Function Block DI(4)

Bit n° Value Description

Bit 0 0 Actuator available

1 Actuator fault indication

Bit 1 0 No motor thermal overload alarm

1 Motor thermal overload

Bit 2 0 No indication active on terminal 8

1 Indication active on terminal 8

Bit 3 0 No indication active on terminal 9

1 Indication active on terminal 9

Bit 4 0 No partial stroke in progress

1 Partial stroke in progress

Bit 5 0 No PST fault

1 PST fault

Bit 6 0 No battery fault or not present

1 Battery low

Bit 7 0 No handwheel action

1 Handwheel action

(*) The connection depends of actuator type. Refer to the actuator wiring diagram

Motor thermal overload: the motor thermal contact tripped. The actuator will be again available

as soon as the motor will cool.

Indication on terminal 8 & 9 is active (option): indications of hardwired inputs (allows to

communicate through Fieldbus, indications coming from outside devices).

Battery low or is not present: in case of battery option the battery should be replaced because of too low voltage or the battery is missing.

Handwheel action: the handwheel has been actuated since the last electrical operation

PST: partial stroke test is a test on a part of the stroke.

PST fault: a fault occured during the partial stroke test.

Page 19: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

19

Function Block DI(5)

Bit n° Value Description

Bit 0 0 The actuator is not running

1 Actuator running

Bit 1 0 No stop mid travel

1 Stop mid travel

Bit 2 0 Power off

1 Power on

Bit 3 0 No lost phase alarm

1 Lost phase

Bit 4 0 No lost signal

1 Lost signal

Bit 5 0 No position sensor power supply fault

1 Position sensor power supply fault

Bit 6 0 No torque sensor power supply fault

1 Torque sensor power supply fault

Bit 7 0 No active on terminal 12

1 Indication is active on terminal 12 (ESD by default)

(*)The connection depends of actuator type. Refer to the actuator wiring diagram

Actuator running: the actuator is operated in opening or closing direction

Stop mid travel: the actuator is at a stop, neither open nor closed.

Power on: the actuator is normally powered.

Lost phase: in 3 phase, a phase is missing. No start allowed.

Lost signal: 4 to 20mA lost signal (In case of analogue and hardwired input signal)

Position or torque power supply fault: Intelli+ receives no information from the position or torque sensor.

Indication

By default this terminal is assigned to a hardwired emergency command (ESD) and an ESD command is present.

The actuator feedback position and torque are located at the Function Block Analog Intput (AI) in the INTELLIBUS module. These indications are:

o Function Block AI(1) Actuator position feedback: 0.0% to 100.0% (1000 points) Actuator position feedback: actuator position in % of opening - 0%= closed, 100%= open

o Function Block AI(2): running torque 0 to 150%.

o Running torque: indication of the instantaneous torque. 100% is the maximum actuator rated torque.

Page 20: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

20

6. TRANSDUCER BLOCK

Available data through FIELDBUS in the Transducer Block

N° Data Value Number

of bytes

Type

1 Operating class 1: On-Off 2: Modulating Class III 3: Modulating Class II

1 Read only

2 Nut thread (If linear system)

In mm (To calculate the stroke but only during set-up). Value is zero if no linear system.

1 Read only

3 Locked motor timing In seconds 1 Read only

4 Motor supply type 0: 3 phases 1: single phase or DC

1 Read only

5 Reverse delay time (unit 50ms) - Ex. 3 = 150ms 1 Read only

6 Closing mode 0: Close on position 1: Close on torque 3: Open and close on torque

1 Read only

7 Stroke unit 1: Number of turns 2: Degrees 3: mm

1 Read only

8

Set-up for auxiliary command 1

() Bit state for active command (see 4.1)

0: Not used 1: Local(0) / Remote(1) 2: Local+Remote(0) /Remote(1) 3: Local command inhibit(1) 4: Open inhibit(1) 5: Close inhibit(1) 6: On-Off(0) / Auto(1) 7: Fieldbus emergency closing (1) 8: Fieldbus emergency opening (1) 9: Fieldbus emergency stop (1) 10: Partial stroking (1) 11: FF command (0) / wired command (1)

1 Read/Write

9

Set-up for auxiliary command 2 coming through the fieldbus but for emergency commands wired separately from the fieldbus.

0: Not used 1: Local(0)/remote(1) 2: Local+Remote(0) /Remote(1) 3: Local command inhibit(1) 4: Open inhibit(1) 5: Close inhibit(1) 6: On-Off(0) / Auto(1) 7: Wired emergency closing (1) 8: Wired emergency opening (1) 9: Wired emergency stop (1) 10: Partial stroking (1) 11: FF command (0) / wired command (1)

1 Read/Write

Page 21: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

21

10 Local stop also inhibited with a local command inhibit

0: No, local stop is possible 1: Yes, local stop and off inhibited

1 Read/Write

11 Dead band for positioner function

Unit 0.1% Mini value: 2 (0.2%) Maxi value: 50 (5%)

1 Read/Write

12 Timing control 0: No timing control ; 1: Timing control 1 Read/Write

13 Start of closing temporised zone

0 to 100 % 1 Read/Write

14 End of closing temporised zone

0 to 100 % (lower than start value) 1 Read/Write

15 Start of opening temporised zone

0 to100 % 1 Read/Write

16 End of opening temporised zone

0 to 100 % (higher than start value) 1 Read/Write

17 Timer open time expected In seconds 2 Read/Write

18 Timer close time expected In seconds 2 Read/Write

19 Operating time without timer

In seconds 2 Read only

20 No local stop in remote mode

0= Local stop possible 1= No local stop

1 Read/Write

21 Fail safe position in case of loss of communication

0= Stayput 1= Closing 2= Opening

1

Read/Write

22 Open priority 0= No priority ; 1= Open priority 1 Read/Write

23 Close priority 0= No priority ; 1= Close priority 1 Read/Write

24 In case of emergency command, torque limit is 100%

0= No 1= Yes

1 Read/Write

25 In case of emergency command, thermal overload is by- passed

0= No 1= Yes

1 Read/Write

26 External gear ratio (format: 1/ ) – ex.: 200 = 1/200 2 Read only

27 Actuator number ASCII characters 16 Read only

28 Manufacture date ASCII characters 12 Read only

29 Software version ASCII characters – ex.:1.03 6 Read only

30 Stroke measured during set-up

For stroke unit see address 7 2 Read only

31 Opening torque curve

Torque in % Data 1 = Closed position Data 2= 1% open Data 101= 100% open

101 Read only

32 Closing torque curve

Torque in % Data 1 = closed position Data 2= 1% open Data 101= 100% open

101 Read only

33 Open breakout max torque during the last electrical actuation

in % 1 Read only

Page 22: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

22

34 Close tight max torque during the last electrical actuation

in % 1 Read only

35 Opening max torque during the last electrical actuation

in % 1 Read only

Page 23: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

23

36 Closing max torque during the last electrical actuation

in % 1 Read only

37 Starts last 12 hours 2 Read only

38 Total number of starts 4 Read only

39 Total running time Unit is 1/10 sec 4 Read only

40 Partial number of starts (since the last reset)

4 Read only

41 Partial running time (since the last reset)

Unit is 1/10 sec 4 Read only

42 Locked motor open 0= No fault, 1= Fault 1 Read only

43 Locked motor close 0= No fault, 1= Fault 1 Read only

44 Torque sensor 0= No fault, 1= Fault 1 Read only

44 Position sensor 0= No fault, 1= Fault 1 Read only

46 Closing direction of rotation discrepant

0= No fault, 1= Fault 1 Read only

47 Opening direction of rotation discrepant

0= No fault, 1= Fault 1 Read only

48 Overtravel 0= No fault, 1= Fault 1 Read only

49 Too many starts 0= No fault, 1= Fault 1 Read only

50 Lost phase 0= No fault, 1= Fault 1 Read only

51 Lost signal 0= No fault, 1= Fault 1 Read only

52 Thermal overload 0= No fault, 1= Fault 1 Read only

53 Pumping 0= No fault, 1= Fault 1 Read only

54 Config. memory 0= No fault, 1= Fault 1 Read only

55 Activity memory 0= No fault, 1= Fault 1 Read only

56 Base memory 0= No fault, 1= Fault 1 Read only

57 24V auxiliary 0= No fault, 1= Fault 1 Read only

58 User pass word ASCII characters - "000" to "999" 3 Read/Write

59 Valve tag number ASCII characters - ex: "MOV55VV" 8 Read/Write

60 Open breakout torque setting

40 to 100%, 101% if no limitation 1 Read/Write

61 Close tight torque setting 40 to 100% 1 Read/Write

62 Opening torque setting 40 to 100% 1 Read/Write

63 Closing torque setting 40 to 100% 1 Read/Write

64 Partial stroke% 1 to 100% 1 Read/Write

65 Partial stroke start position 0= Close, 1= Open 1 Read/Write

66 Partial stroke fault 0= No fault, 1= Fault 1 Read only

67 Partial stroke in progress 1= In progress 1 Read only

68 FF command signaling 0= FF command, 1= Wired command 1 Read only

69 Handwheel action 0=No action, 1=Action 1 Read only

Page 24: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

24

7. FUNCTION BLOCK PID

The Function Block PID is used to achieve a Proportional/Integral/Derivative control loop. Function Blocks can be built into fieldbus devices as needed to achieve the desired device functionality. For example, a simple temperature transmitter may contain an AI function block.

The control valve actuator might contain a PID function block as well as the expected AO block. Thus a complete control loop can be built using only a simple transmitter and a control valve actuator. This function block PID is located in the actuator but is operational only if the links with others function blocks (inside or outside the actuator) have been achieved with a Foundation Fieldbus configurator.

The PID located inside the actuator is not obliged to drive it. It could be used to drive another device.

Page 25: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

25

8. FIELD DIAGNOSTIC PARAMETERS

According to Namur NE-107 recommandation, Bernard Controls actuators comply with the field diagnostic parameters requirements. Those parameters are included inside the resource block and can be configured in the 4 categories

The table below describes the field diagnostics, their recommended categories and their recommended action.

Field diagnostic signal

Categories

Recommended action Maintenance

required Out of

specification Function

check Failure

Overtravel alarm X

Intelli+: Travel is too short, set a correct travel.

Intelli+ SIL2: Position feedback fault. Check the position feedback supply.

Position sensor fault X

Position sensor failed or is disconnected.

- Check the position sensor connection.

- Contact Bernard Controls customer support department

Torque sensor fault X

Torque sensor failed or is disconnected.

- Check the torque sensor connection

- Contact Bernard Controls customer support department

Motor locked alarm in opening direction X Actuator was intended to move and did not. Contact Bernard Controls customer support.

Motor locking alarm in locking direction X Actuator was intended to move and did not. Contact Bernard Controls customer support.

Motor thermal relay has tripped X Motor overheating, this actuator is not designed for this operating class. Wait untill the signal disappears.

Lost phase X A phase is missing check power supply connection.

Battery low X

For Intelli +: Change the Intelli+ battery.

For Intelli+ SIL2: Emergency supply is missing. Check emergency supply or disable it in Intelli+ SIL2 settings.

Opening direction of rotation discrepant X

Intelli+: Check the connection between separated control box and actuator.

Intelli+ SIL2: Check the phases order.

Page 26: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

26

Closing direction of rotation discrepant X

Intelli+:

Check the connection between separated control box and actuator.

Intelli+ SIL2:

ESD command fault. Check ESD command.

Lost 24V Aux X Check the wiring on terminals 6 & 7.

Too many starts X This actuator is not designed for this operating class. Wait at least 1 hour without starting, untill the signal disappears. The actuators is still available.

Partial stroke fault X

The partial stroke is failling:

- Check the start position

- Check the load apply to the actuator

Base memory fault X The manufacturer configuration is altered. Contact Bernard Controls customer support.

Configuration memory fault X The user configuration is altered. Contact Bernard Controls customer support.

Activity memory fault X The activity memory is altered. The actuator is still available. Contact Bernard Controls customer support, to delete the default.

Intelli+ communication fault X Contact Bernard Controls customer support.

Actuator fault signaling X

Intelli+:

The fault relay is tripped, the actuator is not available. Refer to Intelli+ Manual.

Intelli+ SIL2:

The actuator is not available due to a following event: Valve blocked, not on remote position, default SIL relay, and torque sensor alarm. Including additional faults (please refer to Intelli+ SIL manual).

Valve jammed X Actuation could not be completed due to excess torque.

Actuator hunting X Actuation could not be completed due to excess torque.

No FF command X Only wired commands are available.

Only Indications is available by FF.

Handwheel action X The handwheel has been actuated since the last electrical Operation

Page 27: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

27

Page 28: FOUNDATION FIELDBUS ITK6 - BERNARD CONTROLS

Invest in confidence

Instructions for start-up – Fieldbus foundation ITK6 - NR1313_A

28

AFRIQUE DU SUD A-Q-RATE AUTOMATION CC [email protected] BERTSHAM Tél. : +27 11 432 58 31

ALLEMAGNE

BERNARD CONTROLS DEUFRA GMBH [email protected] TROISDORF Tél. : +49 22 41 98 340

AUTRICHE IPU ING PAUL UNGER [email protected] VIENNE Tél. : +43 1 602 41 49

BELGIQUE BERNARD CONTROLS BENELUX SA [email protected] NIVELLES Tél. : +32 (0)2 343 41 22

BRÉSIL JCN [email protected] SAO PAULO Tél. : +55 11 39 02 26 00

CHINE BERNARD CONTROLS CHINA [email protected] PEKIN

Tél. : +86 (0) 10 6789 2861

CORÉE DU SUD RENTEC CO Ltd (Marché de l’eau) [email protected] GYEONGGI-DO Tél. : +82 31 399 73 23

CORÉE DU SUD YOO SHIN E&I Co. Ltd (Marché du Pétrole & Gaz) [email protected] SEOUL Tél. : +82 2 406 62 78

DANEMARK ARMATEC A/S [email protected] GLOSTRUP www.armatec.dk Tél. : +45 46 96 00 00

ÉGYPTE ATEB [email protected]

ALEXANDRIE Tél. : +203 582 76 47

ESPAGNE BERNARD CONTROLS SPAIN [email protected] MADRID Tél. : +34 91 30 41 139

Émirats Arabes Unis EMIRATES HOLDINGS [email protected] ABU DHABI Tél. : +97 12 644 73 73

États -Unis/Canada/Mexique BERNARD CONTROLS Inc [email protected] HOUSTON - TEXAS

Tél. : +1 281 578 66 66

FINLANDE Tallberg Tech Oy Ab [email protected] ESPOO www.tallberg.fi/tallbergtech Tél. : +358 0 207 420 740

GRÈCE PI&MS Entreprises Ltd [email protected] HALANDRI Tél. : +30 210 608 61 52

HONGRIE APAGYI TRADEIMPEX KFT

[email protected] BUDAPEST Tél. : +36 1 223 1958

IRAN ASIA INSTRUMENTS Co. Ltd. [email protected] TÉHÉRAN www.asiainstrumentsltd.com Tél. : +98 21 8850 3065

ITALIE BERNARD CONTROLS ITALIA [email protected] MILAN Tél. : +39 02 931 85 233

MALAISIE ACTUATION & CONTROLS ENGINEER

[email protected]

JOHOR BAHRU Tél. : +60 7 23 50 277 / 23 50 281

MAROC AQUATEL sarl [email protected] CASABLANCA Tél. : +212 22 66 55 71

MOYEN-ORIENT BERNARD CONTROLS MIDDLE-EAST [email protected] DUBAI - U.A.E. Tél. : +971 4 39 80 7 KSB LINDFLATEN AS [email protected] LYSAKER Tél. : +476 71 29 900

NOUVELLE ZéLANDE MRCTransmark NZ LTD [email protected] Auckland Tél. : +64 9 276 4149

PAYS-BAS BERNARD CONTROLS BENELUX NV

[email protected] AN ZWAAG Tél. : +31 (0)229-298083

POLOGNE MARCO [email protected] VARSOVIE Tél. : +48 22 864 55 43

TURQUIE OTKONSAS sales@otk

Liste complète des agents et distributeurs réactualisée sur notre site

www.bernardcontrols.com

FIN