Name : Hemal DesaiJob Title : Head TechnologyCompany : Endress+Hauser India
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Agendag• Drivers for NE 107• Challenges faced by Operators TodayChallenges faced by Operators Today• Foundation Fieldbus & NAMUR• Benefits of NAMUR NE 107• Summarized NE 107
© 2011 Fieldbus Foundation
Dark Agesg
Must be rightTx says so ?????????
A l Si l
16mA
Analogue Signal
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
The Middle Agesg
What are
Endress+HauserDeltabar S
What would you liketo know ??
you ????
Communication requestusing Hand held deviceusing Hand held device
Master Slave
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
TodayyThe Here and Now
Endress+HauserDeltabar S
Your Pump may soon need some maintenance!maintenance!
Foundation FieldbusPeer to Peer
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Diagnostic Information from DevicesgTravel DeviationCycle CounterValve Signature
Electronics FailureSensor FailureProcess ConditionValve Signature
Step ResponseDynamic Error BandDrive SignalOutput Signal
Process ConditionConfiguration WarningRTD DriftRTD Life Estimationetc...
Electronics FailureSensor Failure
Output Signaletc...
etc...
Electronics FailureS F ilSensor Failure
Process ConditionConfiguration WarningPlugged Impulse Linesetc
Sensor FailureReverse FlowEmpty PipeCalibration ErrorProcess Conditionetc...
pH Electrode AgingGlass Electrode FailureReference Electrode Failure
Process ConditionConfiguration Warningetc...
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Reference Electrode FailureReference Electrode CoatingReference Electrode Poisoningetc...
ResultOver range Reverse Flow
Sensor Fail
Electrode coated
OverwhelmedIgnoreSuppress
Empty Tube Sensor disconnect
Sensor failureLeakage Valve stuck Travel Deviation
FrictionRTD failure
Coil openPl d li
High Temperature
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Plugged lines
The Status Todayy• Large part of the Production & Quality losses are
primarily result of operator error which can beprimarily result of operator error which can be prevented by ensuring that right information is available to the right person at right time.g p g
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Challenges Faced by Operators Todayg y p y• Difficult to get overview status of the process.• Operators are bombarded with Nuisance alarmsOperators are bombarded with Nuisance alarms• Inconsistencies in diagnostics information from
different vendors & product classes.p• Different applications, terminals, interfaces with
unsynchronized dataO i l f l l d• Operators are integral part of control loops and need to take decisions in critical situations.
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Foundation Fieldbus and NAMUR
• May 2006 Foundation Fieldbus announced co operation with NAMUR Working Group 2.6 Fieldbus for development of device diagnostic profiles to further enhance FF technologyprofiles to further enhance FF technology.
• Sept 2008 Foundation Fieldbus released final Diganostic Profile specification based onDiganostic Profile specification based on NAMUR Working Group 2.6
• Adopted NAMUR NE 107 recommendation for “Self Monitoring & Diagnostics of Field Devices”
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
NAMUR Organizationg
© 2011 Fieldbus Foundation
What is NAMUR?• NAMUR is an international association of users
of automation in process industriesof automation in process industries. – manufacturers of chemical or pharmaceutical
products– users of process plants– providers of services to chemical/pharmaceutical
f tmanufacturers– organizations with a technical or scientific purpose,
e.g. scientific bodies, associations, universities etc.e.g. scientific bodies, associations, universities etc.
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
NAMUR Organizationg
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
What does NAMUR do?• NAMUR promotes the interests of the process
industry (users) in the field of automation e gindustry (users) in the field of automation e.g. – instrumentation with sensors and actuators, – electrical engineering– communication between process control equipment, – batch control, advanced process control, plant and process
monitoring,– DCS, MES– process management, plant asset management– Logistic systems and Supply Chain ManagementLogistic systems and Supply Chain Management
NAMUR Recommendations NE NAMUR Worksheets NA
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Objective of NAMUR NE 107j• It is Standardization of diagnostics information
form field devices integrated via e g Foundationform field devices integrated via e.g. Foundation Fieldbus
• Improved Operator Efficiencyp p y• Improve Productivity• Reduce cost
M k i ffi i• Make maintenance more efficient.
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
What are NAMUR 107 Benefits• What does NAMUR 107 implementation do?
• Bring Reliable & Viewable status diagnostics fromBring Reliable & Viewable status diagnostics from field devices
Status will be forwarded to the right person at right• Status will be forwarded to the right person at right time (fewer spurious alarms)
• Actionable Diagnostics
• Allocation of status signals in field devices.Allocation of status signals in field devices. Independent of DCS!
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Summarized NAMUR - NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
NAMUR Recommendation NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
NAMUR Recommendation NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
5 Categories of Status signalsg g
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
NAMUR Recommendation NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
NAMUR Recommendation NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Status to Operatorsp
M i R i dMaintenance Required.
Leakage??
PCV -101
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
PCV 101
NAMUR Recommendation NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Context of Applicationpp
MaintenanceConsole
Operator’sConsole
SD_MAINT_ALM
ActiveActive
SD_MAINT_ACTIVE
Clogged Pressure Sensor
H1
SD_RECOMMENDED_ACTION
Clean Sensor
© 2011 Fieldbus FoundationFFIC : Automation 2011 ‐Mumbai
Context of ApplicationppMaintenance
ConsoleOperator’s
Console
SD_FAIL_ALM
Active
SD RECOMMENDED ACTION
SD_FAIL_ACTIVE
Pressure sensor failure
H1
SD_RECOMMENDED_ACTION
Change Sensor
© 2011 Fieldbus Foundation
NAMUR Recommendation NE 107NE107:“Self-Monitoring and Diagnosis of Field Devices”Devices
– Diagnosis results must be reliable– Internal diagnosis categorized into 5 standard status signals– Configuration should be flexible depending on the user's
requirements– The plant operator should only see these status signals– The diagnosis results must always be viewed in the context
of the application– Detailed information available for device specialistp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Details to Expertsp
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
FF 912 SpecificationpFF 912 - Field Diagnostic Profile
The technical specification which describes theThe technical specification which describes the implementation of the NE 107 into Foundation Fieldbus
Endress+Hauser was part of the specialist team which defined the FF 912
Failure Function Ch kFailure Check
Out of Specification
Maintenance Required
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
FF 912 ExplanationpMust be implemented in the Resource
Block since ITK 6.0
The same parameters are available for The same parameters are available for
all manufacturer. The parameterization
for the FMCS categorization is similar
for all vendors.
Can be implemented if additional
diagnostic bit are needed
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Manufacturer specific
Endress+Hauser Committed to NE107E+H Group
Wide
Advanced
Diagnostic
Hardware
-
Software Wide
Standard for
g-
Testing
Logistic
Products Platform With NE 107
FMP 5x – GWR*
TMT 82*
E 200 - Coriollis *E 200 - Coriollis * Presently Released with HART Only, Ff expected
DCS / PLC
IntegrationDTMs
© 2011 Fieldbus Foundation
DTMs
Example E200 Coriolisp
2 Event page
• Icon/text according NE 107
(F,M,C,S)
1. Measurement page with warning
2. Event page
3. Info page
• An event occurred.
Depending on event status
the status symbol for the
event level is shown
© 2011 Fieldbus Foundation
• Diagnostic event page.
• Maintenance instructions
Challengesg• Time by which device & host vendors will
become compliantbecome compliant.• Vendors having products manufactured at
different production centers (acquired p ( qcompanies)
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Summaryy
• Clear Harmonized information Independent ofClear Harmonized information Independent of source of data
• Good overview of Process & Status
All l i f i il bl i• All relevant information available in easy to use environment.
© 2011 Fieldbus Foundation
FFIC : Automation 2011 ‐Mumbai
Thank You