203.743.6741 • 203.798.7313 www.preferred-mfg.com Instruments & Controls Catalog 25 Instruments & Controls 273 Low Boiler Efficiency Alarm Message and Contact Elevated stack temperature will indicate reduced boiler efficiency Every 40º F increase in flue gas temperature results in an approximate 1% decrease in boiler efficiency Burner Shutdown Contact and Message Dangerously high temperatures place the boiler at risk of serious overheating damage Provides additional protection against mud-filled low water cutout float switch failures “Three out of every four accidents are caused by overheating, and 80% of the overheating losses resulted from continued firing with low water levels; despite the fact that boilers, … are equipped with up-to-date controls.” (from M.P. Bragg and S.R. Laskey, “Low WaterAccidents,” The Hartford Steam Boiler Inspection and Insurance Co.) High Visibility Bargraph and Numeric Display 4 Digit Numeric Display 200 Segment Bargraph Bargraph Alarm Setpoint Markings High Intensity, Long Life LED Backlighting Field Adjustable using English-Language Menus Inputs: Type J or K Thermocouple 4-20 mADC Output Scaling Fahrenheit or Centigrade Bargraph Scaling Alarm Modes, Setpoints, Deadbands, and Time Delays NEMA 4 Front Panel Flexible Communications for Data Logging 4-20 mADC Temperature Re-transmission RS485 Modbus Interface FLUE GAS TEMPERATURE MONITOR & CUTOUT Model JC-15D RS485 Modbus Interface 4-20 mAdc Retransmit Output Typical Arrangement Description The JC-15D Flue Gas Temperature Monitor is a microprocessor-based indicating instrument for use with a heavy duty thermocouple assembly. Flue gas temperature is continuously displayed using a highly visible backlit LCD display. An intuitive bargraph display and alarm messages provide clear stack temperature status. Bargraph scaling, alarm setpoints, and time delays are all field selectable. All adjustments can be made directly from the faceplate of the instruments by scrolling through user friendly, English language menus. The Type J thermocouple assembly is constructed of a seal welded inconel sheath for corrosion protection, and can be directly installed in the boiler's flue gas outlet. The unit includes a ½" male NPT process connection, cast iron head with thermal block, and ½" female NPT electrical connection. JC-15D Faceplate and Display Thermocouple Assembly Model 104087D (20”) 104087E (12”)

FLUE GAS TEMPERATURE MONITOR & CUTOUT Low Boiler Efficiency Alarm Message and ... • Provides additional protection against mud-filled low ... FLUE GAS TEMPERATURE MONITOR & CUTOUT

  • Upload
    tranque

  • View
    214

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FLUE GAS TEMPERATURE MONITOR & CUTOUT Low Boiler Efficiency Alarm Message and ... • Provides additional protection against mud-filled low ... FLUE GAS TEMPERATURE MONITOR & CUTOUT

203.743.6741 • 203.798.7313www.preferred-mfg.com

Instruments & Controls

Catalog 25

Instruments &

Controls

273

LowBoilerEfficiencyAlarmMessageandContact• Elevatedstacktemperaturewillindicatereducedboiler

efficiency• Every40ºFincreaseinfluegastemperatureresultsin

anapproximate1%decreaseinboilerefficiency

BurnerShutdownContactandMessage• Dangerouslyhightemperaturesplacetheboileratrisk

ofseriousoverheatingdamage• Provides additional protection againstmud-filled low

watercutoutfloatswitchfailures• “Three out of every four accidents are caused by

overheating,and80%oftheoverheatinglossesresultedfrom continued firingwith lowwater levels; despitethe fact that boilers,…areequippedwithup-to-datecontrols.”(fromM.P.BraggandS.R.Laskey,“LowWaterAccidents,”TheHartfordSteamBoilerInspectionandInsuranceCo.)

HighVisibilityBargraphandNumericDisplay• 4DigitNumericDisplay• 200SegmentBargraph• BargraphAlarmSetpointMarkings• HighIntensity,LongLifeLEDBacklighting

FieldAdjustableusingEnglish-LanguageMenus• Inputs:TypeJorKThermocouple• 4-20mADCOutputScaling• FahrenheitorCentigrade• BargraphScaling• AlarmModes,Setpoints,Deadbands,andTimeDelays

NEMA4FrontPanel

FlexibleCommunicationsforDataLogging• 4-20mADCTemperatureRe-transmission• RS485ModbusInterface

FLUE GAS TEMPERATURE MONITOR & CUTOUTModelJC-15D

RS485 ModbusInterface

4-20 mAdc Retransmit Output

Typical Arrangement

DescriptionThe JC-15D Flue Gas Temperature Monitor is amicroprocessor-basedindicatinginstrumentforusewithaheavydutythermocoupleassembly.FluegastemperatureiscontinuouslydisplayedusingahighlyvisiblebacklitLCDdisplay.Anintuitivebargraphdisplayandalarmmessagesprovideclearstacktemperaturestatus.Bargraphscaling,alarmsetpoints,and timedelaysareall fieldselectable.Alladjustmentscanbemadedirectlyfromthefaceplateoftheinstrumentsbyscrollingthroughuserfriendly,Englishlanguagemenus.

TheType J thermocouple assembly is constructedof asealwelded inconelsheath forcorrosionprotection,andcanbedirectlyinstalledintheboiler'sfluegasoutlet.Theunitincludesa½"maleNPTprocessconnection,castironheadwith thermal block, and½" femaleNPTelectricalconnection.

JC-15D Faceplate and Display

Thermocouple Assembly Model 104087D (20”)

104087E (12”)

Page 2: FLUE GAS TEMPERATURE MONITOR & CUTOUT Low Boiler Efficiency Alarm Message and ... • Provides additional protection against mud-filled low ... FLUE GAS TEMPERATURE MONITOR & CUTOUT

203.743.6741 • 203.798.7313www.preferred-mfg.com

Instruments & Controls

Catalog 25

Inst

rum

ents

& C

ontro

ls

274

FLUE GAS TEMPERATURE MONITOR & CUTOUTModelJC-15D

Alarm SequenceBargraphandnumericdisplayscontinuouslyindicatethefluegastemperature.Ifthefluegastemperatureexceedsthewarningsetpointformorethan30seconds(adjustable),thebargraphblinks,the“warning”messageappears,andthe alarm relay energizes. If the flue gas temperaturecontinuestoincreaseandexceedstheshutdownsetpointformorethan30seconds(adjustable),thebargraphblinks,the“shutdown”messageappears,theshutdownrelayde-energizesandlatchesinto“manualreset”mode.TheburnershutsdowniftheJC-15D shutdownrelayiswiredintotheburnerinterlocks.Theshutdownrelayremainsde-energizedandthe“shutdown”messageremainsonthedisplayuntiltheoperatorpressesthe“reset”pushbutton.

Thealarmrelaycanbeusedtoactivateanexternalbellorhorn.Thealarmrelayde-energizeswhenthe“warning”and“shutdown”alarmsarebothinactive.Alternately,pressingtheJC-15D “alarmsilence”pushbutton,orenergizingthe120VACalarmsilenceinput,oraModbuscommandcande-energizethealarmrelayinordertosilenceanaudiblealarm.

Suggested SpecificationsProvidearemotereadingmicroprocessor-basedfluegastemperature alarmand indicating instrument anda fluegas temperature sensor assembly for each boiler.Theinstrumentshallprovideafluegastemperaturedisplayinengineeringunits,“inefficient”operationwarningindication,“overheat” operating condition indication and alarmcontacts.TheInstrumentshallcontinuouslyindicatefluegastemperatureonahighlyvisiblebacklitLCDdisplay.Provideanintegralorseparate4inch,0.5%resolution(minimum)bargraph display in engineering unitswith visual alarmsetpointindication.Providean“alarmsilence”and“manualreset”pushbuttonandtwo10ampererelays.Thehousingshallbepanelmountable,fullygasketedwithNEMA4frontface.Alladjustmentsshallbemadefromthefrontpaneldisplayinengineeringunits.Noexternalconfigurationtoolsshallberequired.TheInstrumentshallprovide:coldjunctioncompensationandupscalethermocouplebreakprotection.Theinstrumentshallincludealarmmessagesasfollows:Whenfluegastemperatureexceedsthe“warning”setpointformorethan30seconds(adjustable),thebargraphshallblink, and the “warning”message shall appear and an“alarm”relayenergizesandifwiredtoanalarmcircuitanalarmisactivated.Ifthefluegastemperaturecontinuestoincreaseandexceedsthe“shutdown”setpointformorethan30seconds(adjustable),thebargraphblinks,the“shutdown”messageappears,the“shutdown”relayde-energizesandlatches into the “manual reset”mode. If the “shutdown”relayiswiredintotheburnerinterlocks,theburnershutsdown.The “shutdown” relay remains de-energized andthe “shutdown”message remainon thedisplayuntil theoperatorpressestheintegral“reset”pushbutton.

ProvideaFlueGasTemperatureSensorassemblyforeachboiler.Thesensorassemblyshallinclude:iron/constantanISATypeJ thermocouple, inconelsheath,½"maleNPTprocess connection, cast iron headand a 20" insertionlength.Extensionleadwireshallbeonecontinuouslengthof20gaugesISATypeJXwithPVCinsulation.Theassemblyshallbeinstalledintheboileroutletbeforeanydamperorfaninaccordancewithmanufacturerssuggestedinstallationinstructions.TheinstrumentshallincludeaRS485Modbusnetworkinterfaceanda4-20mADCretransmitoutputtocommunicate toa futureDataAcquisitionSystem(DAS)or BuildingAutomationSystem (BAS).The Instrumentshall bemanufactured and labeled in accordancewithUL508requirements(CSAC22.2#14foruseinCanada).InspectionandlabelingshallbesupervisedbyULorotherOSHAapprovedNationallyRecognizedTestLab(NRTL).TheFlueGasTemperatureMonitoring,ControlandAlarmSystemshallbePreferredInstruments,Danbury,CT,Model JC-15D,with104087DThermocoupleAssembly.

Page 3: FLUE GAS TEMPERATURE MONITOR & CUTOUT Low Boiler Efficiency Alarm Message and ... • Provides additional protection against mud-filled low ... FLUE GAS TEMPERATURE MONITOR & CUTOUT

203.743.6741 • 203.798.7313www.preferred-mfg.com

Instruments & Controls

Catalog 25

Instruments &

Controls

275

FLUE GAS TEMPERATURE MONITOR & CUTOUTModelJC-15D

SpecificationsPanelPowerSupply:120VAC,+/-15%,50/60Hz,15VACaseSize: 8"Hx3.5"Wx7.5"DEnclosureType:NEMA4faceplateAmbientTemp.:+32°to122°FDisplays: HighContrastLCDDisplay

4"high,0.5%ResolutionBargraphBargraphRange: 0°-2000°FfieldadjustableAlarmSetpoints: Two(2)adjustablewithadjustable

timedelays

InputsInputTypes: TypeJorTypeKThermocouple,

fieldselectableAccuracy: 0.005%Resolution

0.07%AccuracyBreakProtection:Upscale

OutputsRelay: TwoSPDTRelays10Aresistive,

8FLA,½HP,120VACRetransmit: 4-20mADC,650ohmload

maximumNetwork: 1200-38400Baud;RS485Modbus,

ASCIIorRTUThermocouple

Assembly: TypeJungroundedProbeMaterial: InconelInsertionLength: 20"Connection: ½"MNPT

Ordering Information1. JC-15DInstrument2. 104087ETypeJThermocoupleAssembly12”3. 104087DTypeJThermocoupleAssembly20”4. 92088-J-B20PPShieldedtypeJthermocouplewire

(specifywirelengthinmultiplesof25feet)5. OptionalAccessories:

SDA-B6AlarmBell.85db,weather-proofSDA-VBRemoteAudible/VisualAlarm

C

JC-15D Mounting and Clearance Dimensions