www.smith-eng.com 1 Flipping Chilled Water Optimization: Train Operators First Princeton and MIT Case Studies

Flipping Chilled Water Optimization: Train Operators First

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com1

Flipping Chilled Water Optimization: Train

Operators First

Princeton and MIT Case Studies

Page 2: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com2

CHILLED WATER PLANT OPTIMIZATION

• Chilled Water plant

optimization finds lowest

energy balance of all

components

• Typically training occurs at end

of project

• We recommend training first

Page 3: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com3

WHY TRAIN FIRST?

Page 4: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com4

REASON #1: MUST UNDERSTAND THE SYSTEM

• Most often simple issues keep system from working

properly, that can only be found through survey

• Tribal knowledge can be

key to success

• Training facilitates dialogue

between operators

Page 5: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com5

EXAMPLE: MIT SYSTEM BOTTLENECKS

Page 6: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com6

CLOGGED START-UP STRAINER

Page 7: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com7

MORE CLOGGED STRAINERS-

60#

48#

38#

112# 118#

78#

126#

122#

10# DROP

6.9#

Page 8: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com8

READING PRESSURE GAUGES AT ELEVATION

Page 9: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com9

REASON #2: COMPLEX PLANTS PARTIAL AUTOMATION

• Many plants do not want full automation

• Especially plants

with mix of steam

and electric assets

• Steam turbine

chillers

Page 10: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com10

STEAM TURBINE CHILLERS

MIT: 5000 Ton York OM500 Princeton: 4500 Ton Carrier 17DA

Page 11: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com11

EXAMPLE: MIT COOLING TOWERS

CT9 CT8

CT7

CT13

CT12

CT1

0

CT11

• Uneven

cooling

tower basin

levels

Page 12: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com12

REASON #3: GAIN OPERATOR’S TRUST AND ADDRESS

MISCONCEPTIONS

• If operators do not trust the optimization, THEY WILL

OVERRIDE IT

• There are common

misconceptions that

are counter to

principles of

optimization

Page 13: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com13

EXAMPLE: CW TEMPERATURE ON TRANE CHILLERS

PU CW Operation – CW Control Valve – CH-2

Page 14: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com14

EXAMPLE: CHILLER SURGE

Ways to get out of surge:

1. Increase CW Flow

2. Lower CWST

3. Increase Evap Flow

4. Raise CHWST (sometimes)

Page 15: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com15

CHILLER FUNDAMENTALS

M

T

120F

HOT

GAS

85F

CWS

95F

CWR

97F

WARM

LIQUID

42F

COLD

LIQUID

50F

COOL

GAS

54F

CHWR

44F

CHWS

90F

AIR78F

WB AIR

90F

DB AIR55F AIR

100% RH

90F OA

70% RH

CONDENSEREVAPORATOR

COMPRESSOR

EXPANSION

VALVE

Page 16: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com16

CHILLER FUNDAMENTALS – APPROACH AND LIFT

85F

CWS

95F CWR

54F

CHWR

44F

CHWS

Cond Approach = Cond

Refrig Temp - Leaving

CW Temp

97F-95F = 2F

Evap Approach = Leaving

CHW Temp -Evap Refrig

Temp

44F – 42F = 2F

Lift =

Cond Pressure – Evap

Pressure

118.3 – 36.6 = 81.7psig

Or

Cond Temp – Evap Temp

97F – 42F = 55F

Page 17: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com17

EXAMPLE: MIT HAND VALVE OPTIMIZATION

Page 18: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com18

OPTIMIZATION – STEAM CHILLER

Page 19: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com19

OPTIMIZATION – STEAM CHILLER

Page 20: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com20

OPTIMIZATION – STEAM CHILLER

Page 21: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com21

REASON #4: GET SAVINGS WITH PARTIAL OPTIMIZATION

• An operator

“Cheat Sheet”

can often get

you half the

way to fully

optimized

Page 22: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com22

REASON 5: OPERATOR INTERFACE MUST HAVE BUY-IN

The pump control sequence

is designed to automatically

control the number of running

pumps and the speed that

the pumps run to:

A. Maintain the differential

pressure at the plant

wall, and

B. Stage the number of

pumps running so that

the pumps are close as

possible to their best

efficiency point

Page 23: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com23

REASON #6: POST OPTIMIZATION DRIFT

• Systems change over time. Operators must know how

to respond

• Getting operator buy-

in so that they see the

process and

understand, allows

them to

Page 24: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com24

EXAMPLE: PRINCETON PUMP STAGING

Page 25: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com25

Design Operation350 Ft2500 GPM

PUMP PRINCIPLES

Page 26: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com26

P-1 (On)

TDH: 135’ FLOW: 2621 GPM Ƞ : 56%

TDH:

135’

Total FLOW:

7,863 GPM

Ƞ:

56%

Total kW:

375

TDH: 135’ FLOW: 2621 GPM Ƞ : 56%

TDH: 135’ FLOW: 2621 GPM Ƞ : 56%

TDH: 0’ FLOW: 0 GPM Ƞ : 0%

P-2 (On)

P-3 (On)

P-4 (Off)

3 CHW

Pumps

Page 27: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com27

P-1 (On)

TDH: 133’ FLOW: 1965 GPM Ƞ : 76%

TDH:

133’

Total FLOW:

7,863 GPM

Ƞ:

76%

Total kW:

259

kW Reduction:

115

TDH: 133’ FLOW: 1965 GPM Ƞ : 76%

TDH: 133’ FLOW: 1965 GPM Ƞ : 76%

TDH: 133’ FLOW: 1965 GPM Ƞ : 76%

P-2 (On)

P-3 (On)

P-4 (On)

4 CHW

Pumps

Page 28: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com28

CHW PUMP OPTIMIZATION

Page 29: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com29

SUMMARY: WHY TRAIN FIRST?

1. Must understand the system and capture tribal knowledge

2. Complex plants likely do not want full automation

3. Process must gain operator’s trust

4. Partial Optimization can be achieved with operator cheat sheet

5. Operator Interface must have operator buy-in and context

6. Optimization will drift if operators are not on board

Page 30: Flipping Chilled Water Optimization: Train Operators First

www.smith-eng.com30

Thank You