Upload
isanne
View
41
Download
0
Tags:
Embed Size (px)
DESCRIPTION
LHCb CO2 cooling kick-off meeting 28 May 2014 CERN. First look at the cooling requirements for the UT detector. Simone Coelli I.N.F.N . MILANO. Summary. Overview Cooling power requirements for the upgrade of the UT detector UT Detector cooling open issues - PowerPoint PPT Presentation
Citation preview
1
First look at the cooling requirements for the UT
detector
LHCb CO2 cooling kick-off meeting28 May 2014
CERN
Simone CoelliI.N.F.N. MILANO
2
• Overview
• Cooling power requirements for the upgrade of the UT detector
• UT Detector cooling open issues
• Open points and questions
Summary
3
• Four Planes of Silicon Strip Sensors• with ASICs readout• Support with integrated cooling
STAVE ELEMENTS
16 +16 +18 +18 = 68TOTAL NUMBER OF STAVES
3 STAVE FLAVOURS:8 + 8 + 52 = 68
LHCb UT detector upgradeOVERVIEW
4
THERMAL REQUIREMENTS
• POWER
ASICs READ-OUT Power electrical dissipation expected = 3200 W+ SELF-HEATING + POWER FLEX DISSIPATION =>4000 W OF DISSIPATED THERMAL LOAD TO BE REMOVED
Considering a margin to take into account the box and the transfer lines insulation..=> 4 to 5 kW cooling system power
• CO2 INLET TEMPERATURE
SENSOR OPERATING TEMPERATURE ALWAYS UNDER - 5 °CASICs OPERATING TEMPERATURE NOT EXCEEDING 40 °CStudies have been done on the thermal transfer, work is ongoing to limit the thermo-mechanical stress over the silicon sensor (100mm*100mm)
Þ Inlet CO2 liquid supply T from - 10 °C to - 35 °CWith the possibility to regulate the inlet fluid temperature
5
OTHER REQUIREMENTS
The detector is openablemade in two halves
=> the cooling connections should be attached on the two sides (symmetric flow division)
=> having the possibility to open the semi-detector assembly (about 800 mm) possibly relying on the transfer line flexibility
Actual UT
CLOSE POSITION(DATA-TAKING)
OPEN POSITION(MAINTENANCE)
6
UT Detector cooling open issues
7
• SNAKE PIPE DESIGN• BASELINE (BEST THERMAL PERFORMANCE)
Stave with a bended pipe embedded in the stave support passing underneath the ASICs
• 2 STRAIGHT PIPES DESIGN• OPTIONAL CONFIGURATION
Stave with two straight pipes running vertically parallel to the longitudinal stave axis
INTERNAL STAVE GEOMETRYHalf lenght stave represented here
8
Sensor attachment
Has an effect• on the stave thermal profile• on the thermo-mechanical behaviour (to guarantee allowed
deformation and stress)
Several sensor mechanics options un study
example
9
CO2 Boiling flow direction (upward/downward)
• To be decided what is the best option• Can be simulated using the CO2 code CoBRA?• Should be tested using a full scale prototype,
UTbX half-plane representation, for the snake pipe option
10
1 2 3 4 5 6 7 8 90
102030405060708090
HALF PLANEFLOW DISTRIBUTION
APPROXIMATE STAVE POWERDISTRIBUTIONTHE STAVES HAVE DIFFERENT THERMAL LOADS
GEOMETRY OF THE SERPENTINE FOR THE CENTRAL STAVEIS DIFFERENT:• 4 MORE BENDS• > TOTAL LENGHT
COOLING DISTRIBUTION SYSTEM DESIGN:
• DEDICATED COOLANT PRESSURE DROP AT EACH STAVE INLET
• INLET FLOW TROUGH CAPILLARIES WITH A DEDICATED CALIBRATION
• SYSTEM TEST FOR THIS SUBASSEMBLY TO VERIFY THE DESIGN
IN THIS SITUATION USING EVAPORATIVECOOLING:THERMO-HYDRAULIC INSTABILITIES CAN ARISE
Total cooling power ~ 500 W
11
Exhaust manifold :• Stainless steel• 8/9 welded pipe
fitting connections
Supposing snake pipes and an upward flow:
L3
L1
L2
Coolant inlet distribution:• Capillaries for
liquid flow distribution
• L1• L2• L3• Optimized
lengths
manifold conceptual sketch
12
flow re-balancing system using capillariesconnection to a common manifold?=> half detector: 34 CO2 supply lines3 inlet DP flavours: 4 * L1 + 4 * L2+ 26 * L3
manifold conceptual sketch
Exhaust outlet line
Supposing snake pipes and an upward flow:
CO2 supply line
24 FEB. 2014 13
A POSSIBLE HALF PLANE FLOW DISTRIBUTION TEST SET-UP
THE MOST UMBALANCED SITUATIONTO BE TESTED TO DEMONSTRATESTABILITY OF THE SYSTEM
Þ ONLY CENTRAL STAVE POWER ON
Þ TRACI COOLING SYSTEM COULD BE USED (POWER 100 W)
THERMO-HYDRAULIC CHARACTERIZATION OF THE SNAKE PIPE
14
Detector geometryone of the two half-detector unit
~ 1500 mm 45 mm
225 mm
45 mm
15
OPEN POINTS & QUESTIONS
• UT Detector responsibility (definition of points)• Transfer line is part of the cooling plant?
• Failure analysis: proposals• VELO/UT cooling plants: inter-connection or separated systems?
• How to proceed for the design• Cooling system simulation for design and optimization, CoBRA• Max pressure design for the piping system (MDP=10 Mpa starting
assumption)
16
Back-up slides
17
• Prototype testing• Single stave => blown system• Half-plane =>TRACI system• Full scale ..?
Electronics power dissipation=> Thermal loads
A1.T8 13 mW
A1.T7 17 mW
A1.T6 23 mW
A1.T5 34 mW
A1.T3 135 mW
A1.T4 58 mW
A1.T1No Grid distribution*= total 261 mW
A1.T2No Grid distribution*= total 171 mW
ASICs dissipated thermal power:0,768 mW / ASICThis half stave has on it a total 44 ASICs including both upstream & downstream faces=> 44 * 0,768 = 33,8 W total
Data-Power Flexbusdissipated thermal power:+ 2 W upstream face+ 2 W downstream face
SENSORS self-heatingthermal power:
upstream face downstream face
«central staves»• Number = 8• Cut-out for the the
beampipe• with 8 ASICs read-out• Higher thermal load
19
Flow regulation valve
20
UT DETECTOR THERMAL MANAGEMENT
SOME CONSIDERATIONS ON THE EXTIMATED TERMAL GRADIENTS COMING FROM THERMAL FINITE ELEMENT ANALYSIS
• ANALYSIS : STEADY-STATE FOR NOMINAL OPERATING CONDITION• BASED ON THE CENTRAL STAVE GEOMETRY MODEL – IT IS THE MAX POWERED STAVE• EXPLOITING AN IMPROVED DESIGN: USING ALL CARBON FOAM CORE• CALCULATION CLEARLY IS IN IDEAL CODITIONS: PERFECT ADHESION OF GLUE AND THERMAL
CONTACTS• CONDUCTIVE MATERIAL PROPERTIES USED ARE A GUESS• SENSITIVITY ANALYSIS HELP TO SEE THE EFFECTS OF INPUT CHANGE ON THE TEMP. SOLUTION• => SAFETY MARGIN SHOULD BE USED IN COOLING DESIGN TO ACCOUNT FOR SIMULATION
APPROXIMATION
TEMPERATURE REQUIREMENTS REMINDER
• SENSOR OPERATING TEMPERATURE ALWAYS UNDER -5 °C• ASICs OPERATING TEMPERATURE NOT EXCEEDING 40 °C
21
• THE THERMAL F.E. MODEL TAKES IN ACCOUNT ONLY THE THERMAL CONDUCTION• ACROSS THE STAVE MATERIALS• FROM THE THERMAL POWER SOURCES
• ASICs DISSIPATION• SENSOR SELF-HEATING • FLEX-BUS DISSIPATION
• TO THE COOLING PIPE EMBEDDED INTO THE STAVE AND SERVICING THE TWO STAVE FACES
• THE STAVE DESIGN GOAL IS TO MANAGE ALL THE THERMAL LOADS• EXPLOITING THE BEST THERMAL CONDUCTION IN THE STAVE UNTIL THE COOLING PIPE• THERMAL CONVECTION TOWARDS THE FLUID IN THE PIPE • PHASE CHANGE USING THE EVAPORATING COOLANT CO2
• THERE IS AN ADDITIONAL THERMAL CONVECTION WITH THE GAS FLOWING IN THE DETECTOR BOXTO CONTROL THE BOX ENVIRONMENT
• GAS INLET TEMPERATURE SHOULD BE LOWER THAN THE MEAN DETECTOR TEMPERATUREOTHERWISE THE DETECTOR COOLING SYSTEM WILL HAVE EXTRA WORK => T INLET GUESS: AROUND 0 °C=> MEAN SURFACE TEMPERATURE OF THE STAVES WILL BE CALCULATED FOR AN EVALUATION OF THIS EFFECT• GAS FLOWRATE MUST BE SUITABLY CHOOSEN - DEPENDING ON THE BOX AIR-TIGHTNESS
• REQUIREMENT: THE UT BOX DEW-POINT SHOULD BE ADEQUATELY LOW (LESS THAN - 40 °C)• THIS SETS THE MAX HUMIDITY ADMISSIBLE INSIDE THE BOX TO AVOID CONDENSATION ON THE COLD
PARTS• THIS DICTATES REQUIREMENTS ON:
• THE GAS FLOW PURITY • THE BOX AIR –TIGHTNESS
• PROPOSAL: USE NITROGEN FLOW IN A CLOSED LOOP WITH AN EXTERNAL COOLING, MEASURING BOX INTERNAL DEW-POINT
• HOT SPOTS (THE ASICs) WOULD DISSIPATE SOME THERMAL POWER TOWARDS THE GAS (MITIGATING TEMPERATURE PEAKS
22
• THERE IS ALSO A UNAVOIDABLE RADIATIVE THERMAL TRANSFER (INFRARED EMISSION)• HELPS HOT SPOTS (THE ASICs) TO DISSIPATE SOME THERMAL POWER TOWARD COLDER SURROUNDING
AND MITIGATING TEMPERATURE PEAKS• DETECTOR THERMAL EXCHANGE TAKES PLACE WITH THE SURFACES INCLOSING THE DETECTOR• DEPENDING MAINLY ON THE TEMPERATURE DIFFERENCE BETWEEN THE EXTERNAL DETECTOR PLANESAND THE CLOSING BOX SURFACES (THAT COULD BE NEAR TO THE AMBIENT TEMPERATURE)• RADIATION HEAT TRANSFER CALCULATION WOULD NEED A KNOWLEDGE OF MANY PARAMETERS (EXACT
GEOMETRY AND TEMP. DISTRIBUTION, VIEW FACTORS AND EMISSIVITY FACTORS)=> CALCULATION WILL BE DONE,=> A SAFETY MARGIN IN THE COOLING DESIGN SHOULD BE TAKEN
• FOLLOWS A SUM-UP OF THE RESULTS FOR THE TWO DESIGN :• THE SNAKE PIPE DESIGN• THE TWO STRAIGHT PIPES DESIGN
• TEMPERATURES OF:• SENSORS• ASICs
23
• SNAKE PIPE DESIGN
• STRAIGHT PIPES DESIGN
SENSOR TEMP. ASICs TEMP.
SENSOR TEMP.
INTERNAL STAVE GEOMETRY
INTERNAL STAVE GEOMETRY
ASICs TEMP.
TEMP. CONDUCTIVE GRADIENT RELATIVE TO THE COOLING PIPE INTERNAL SURFACE
Max SENSOR T ~ 11 °C
Max ASIC T ~ 30°C
Max ASIC T ~ 40°C
Max SENSOR T ~ 3 °C
24
NOTES ON THE RESULTS:
• COMMON TO THE TWO DESIGN OPTIONS
• SENSORS MAX TEMP. IS AFFECTED BY THE HOTTEST ASIC THAT TRANSMITS HEAT TO THE NEAR SENSOR GIVING RISE TO THE SENSOR HOT-SPOT
• ASIC-SENSOR DISTANCE AND FLEXBUS CONDUCTIVITY DRIVING THE EFFECT• ASIC HEAT IS TRANSFERRED ALSO TO THE OPPOSITE FACE SENSOR
• SNAKE PIPE DESIGN (COMPLICATION: PIPE BENDING)• ASICs TEMP. ARE RELATIVELY UNIFORM• DUE O THE SNAKE PIPE CONFIGURATION THAT IS DESIGNED TO PASS UNDERNEAT
EACH ASIC• ASICs THERMAL FIGURE OF MERIT VARYING FROM 10-20 °C/W/cm2• WORST ΔT over the sensor AROUND 3 °C
• TWO STRAIGHT PIPES DESIGN (COMPLICATION: INSERTS IMPLEMENTATION, DOUBLE PIPE CONNECTIONS)• TPG INSERTS (ARE USED WITH K = 900-900-10 UNDER THE ASICs• ASIC DISTANCE FROM THE PIPE DRIVING THE TEMP. PEAK• ASICs THERMAL FIGURE OF MERIT VARYING FROM 5-30 °C/W/cm2• WORST ΔT over the sensor AROUND 8 °C
=> GENERAL CONCLUSION: THE SNAKE PIPE DESIGN IS THE BEST TO BE PURSUED
THERMAL FIGURE OF MERIT ISBASED ON: • ASIC POWER ~ 0.768 W• ASIC SURFACE ~ 0.52 cm2
25
STARTING FROM THE THERMAL SIMULATION RESULTS:=> COOLING PIPE TEMPERATURE COULD BE SET TO STATISFY THE REQUIREMENTS
SENSOR OPERATING TEMPERATURE ALWAYS UNDER - 5 °CASICs OPERATING TEMPERATURE NOT EXCEEDING 40 °C
• SNAKE PIPE DESIGN => COOLING PIPE T ~ - 8 °C• TWO STRAIGHT PIPES DESIGN => COOLING PIPE T ~ - 16 °C• NOTE THIS IS WITHOUT MARGIN
REQUIRED INLET CO2 FLUID TEMPERATURE COULD THEN BE CALCULATEDTHE EFFECTS RELATED TO THE USE OF A TWO-PHASE COOLANT MUST BE TAKEN INTO ACCOUNT :
• PRESSURE DROP IN THE COOLING PIPE IS CAUSING A TEMPERATURE DROP (SATURATE FLUID)Þ INLET TEMPERATURE IS HIGHER THAN OUTLET (THE FIGURE DEPENDING ON THE PIPE AND ON
THEFLUID PARAMETERS )• INTERNAL HEAT TRANSFER COEFFICIENT (HTC) BETWEEN THE FLUID AND THE PIPE INTERNAL WALL ADDING A TEMPERATURE GRADIENT TO BE SUPERIMPOSED ON THE LOCAL FLUID TEMP.• ΔT convective contribution: temperature difference between fluid (bulk) and inner pipe wall• ΔT conductive contribution: temperature difference across the stave simulated by Finite Element Analysis
26
TO START THE DESIGN SOME HYPOTHESIS ON THESE THERMAL GRADIENTCAN BE MADEFIGURES BASED ON PREVIOUS EXPERIENCES AND SIMILAR DESIGN ARE AVAILABLEANY SUCH DESIGN NEEDS AN ITERATIVE PROCESS BECAUSE THE COOLING GEOMETRY AND THE THERMO-HYDRAULIC PROCESS ARE INTER-RELATEDDISCLAIMER:THESE CALCULATION NEED TO BE REFINED AND FOLLOWED-UP DURING THE COOLING SYSTEM DESIGN=> REAL SCALE TEST NEED TO BE MADE TO VALIDATE THE CALCULATIONS
NOTEGIVEN THE RESPECT OF THE CITED REQUIREMENTSTHE UT DETECTOR IS NOT VERY SENSITIVE TO A SMALL CHANGE (FEW DEGREES) IN THE OPERATIVE TEMPERATURE OF A SENSOR LOCATED ON THE INLET OR OUTLET PART OF THE STAVE
=> USING SOME MARGIN THE OPERATIVE INLET CO2 COOLANT TEMPERATURE COULD BE SUPPOSED TO BE FROM - 20 °C TO - 30 °CDEPENDING ON THE DESIGN CHOICE (SNAKE OR STRAIGHT PIPE)
THE FOLLOWING CONSIDERATIONS FOR THE COOLING SYSTEM ARE VALID IN GENERAL FOR BOTH THE DESIGN CASES
HALF STAVECENTRAL GEOMETRY
27
THE PURE CO2 SATURATION CURVEHEREAFTER CORRELATES TEMPERATURE AND PRESSURE INSIDE THE EVAPORATION CHANNEL
- 20 °C TO - 30 °C COOLING FLUID OPER. TEMP.
=> 10 TO 20 bar COOLING FLUIDOPER. PRESSURE
28
IN THE RANGE OF INTEREST DELTA H liq.=> vap. = 280 kJ/kg
THE LATENT HEAT OF VAPORIZATION FOR CO2 CAN BE KNOWN FROM THE CO2 PRESSURE-HENTALPY DIAGRAM
29
CONSIDERING FIRST WHAT HAPPENS IN A SINGLE STAVETHE CENTRAL STAVE TOTAL POWER TH THE COOLING PIPE HAS TO EXTRACT IS AROUND 85 W(TAKING INTO ACCOUNT SOME DISSIPATION IN THE FLEXBUS)
DESIGN OF THE COOLING SYTEMREQUIRES:• INLET CO2 LIQUID SUBCOOLED• BUT NEAR TO SATURATION• OUTLET VAPOUR FRACTION X OUT= 0.5
TO 0.6• TO AVOID THE DRY-OUT
MASS FLOWRATE
MASS FLOWRATE
TAKING X OUT = 50% MASS FLOWERATE NECESSARY CAN THEN BE EXTIMATED:
MASS FLOWRATE= 2 * POWER /DELTA HLIQ-VAP
= 2* 85 W / 280 kJ/kg = 0.6 g/s
LESS FLOWRATE IS TO BE AVOIDEDBECAUSE WILL BE GIVING A RISK OF DRYING-OUT
30
TO LIMIT THE TEMP.DECREASE => DESIGN CHANNEL PRESSURE DROP HAS TO BE LIMITEDACCEPTING FEW DEGREES MEANS ACCEPTABLE PRESSURE DROP AROUND 1 TO 2 BAR
MASS FLOWRATE
MASS FLOWRATE
CHANNEL
PRESSURE DROP IS DRIVEN MAINLY BY THE FLOWRATE, GEOMETRY (TOTAL LENGHT AND BENDS), INTERNAL ROUGHNESS, CHANNEL ORIENTATION
REAL CONDITION TEST IS NEEDED MEASURING ALL THE HYDRAULIC PARAMETERSFLOWRATEP, T INLET AND OUTLET
31
COURTESY OF BART VERLAAT (NIKHEF - CERN)
WHAT HAPPENS INSIDE THE CHANNEL
ALONG EVAPORATING CHANNEL:• DECREASING P• DECREASING T
TARGET DESIGN FOR THE THERMO-HYDRAULIC CONDITIONS IN THE DETECTOR COOLING CHANNEL
AVOID WITH, A SAFETY MARGIN, THE DRY-OUTX OUT < MAX
=> REQUIRES SUFFICIENT FLOWRATE
32
DETECTOR COOLING CO2 SYSTEM2PACL (2-Phase Accumulator Controlled Loop) (Verlaat et al. 2011)
UT DETECTOR COOLING CONFIGURATION SHOULD LOOK LIKE THIS:
This figure shows a simplified schematic of the circulation system which is used often in particle physics detector cooling.This method controls the system pressure and hence evaporation temperatures by a 2-phase accumulator which is heated or cooled. A heat exchanging concentric transfer line (2-3) brings the liquid in the inlet of the detector cooling pipes into saturation. Like this the evaporation in the detector cooling pipes is always happening at the pressure regulated in the accumulator. Experimental caverns are inaccessible during running of the LHC beam. All the active hardware of a 2PACL can be located in a safe zone (left side of figure 2). This area is always accessible for maintenance. In the experimental cavern preferably only passive piping is present.
33
Þ «CENTRAL» stave power ~ 90 W Þ «HALF PLANE»power ~ 500 W
To start thinking on the connectivity of the cooling system exploiting CO2 evaporation system
Proposal: use for each «half plane» • 1 lower inlet manifold,
distributing liquid CO2 to the staves
• 1 upper manifold, collecting hexaust CO2 (partially evaporated) from the staves
«right half plane»«left half plane»
CO2 (X = 0)
CO2 (~ 50%)
X := thermodynamic title Saturated liquid = 0%Saturated vapour =100%
Half planes areSupposed to move to open like in the actual tracker
DETECTOR COOLING LAY-OUT supposing to have a modularity with the four UT detector planes divided in:• 1 right half box (composed of 4 half planes)• 1 left half box (composed of 4 half planes)
34
The CO2 cooling plant should be a 2PACLsystem with cooling capacity: 4000 Watt@-30 °CÞ Need a specific plant
design Þ Similar to VELO UpgradeActual LHCb- VELOCooling capacity: 1500 W@-30°C
DETECTOR COOLING LAY-OUT
CONCEPTUAL BRANCHES LAY-OUT
35
ANOTHER POINT IS THE PRESSURE DROP OF THE OUTLETLINE Þ LIFTS UP THE TEMPERATURE PROFILE OF THE COOLING CHANNEL
For the study of long length cooling branches with CO2 a program is developed called CoBra Calculator (CO2 BRAnch Calculator)
DESIGN OF THE COOLING SYSTEM