Fire Pump Essentials - Derek Thompson

Embed Size (px)

Citation preview

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    1/62

    FIRE PUMP ESSENTIALS

    Chamco Industries

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    2/62

    FOUR TYPES/STYLES OF FIRE PUMPS

    Horizontal, split case. (250 usgpm - 5000 usgpm)

    Vertical Turbine. ( 250 usgpm - 5000 usgpm )

    End Suction. ( commercial )

    Vertical Inline. ( commercial )

    THE FIRE PUMPS

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    3/62

    FIRE PUMP TYPES

    ELECTRIC DRIVEN HORIZONTAL

    DIESEL DRIVEN HORIZONTAL

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    4/62

    FIRE PUMP TYPES

    JOCKEY PUMP

    VERTICAL TURBINE FIRE PUMP & ENGINE

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    5/62

    ENGINES

    Engines are UL or FM approved for Fire Service,

    and built by:

    Caterpillar ( full range, mostly above 200hp ) Cummins ( limited range, 100 - 300hp ) Clarke Engine ( best range, 50 - 700 hp )

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    6/62

    RIGHT ANGLE GEAR DRIVES

    Right Angle Gear Drives are FM approved for

    Fire Service, and built by:

    Randolph Manufacturing Amarillo Gear Johnson Gear

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    7/62

    FIRE PUMP CONTROLLERS

    Pump Control panels, for Electric and Diesel

    drives are UL or FM or ULC approved for Fire

    Service, and built by:

    Cutler Hammer Firetrol Metron

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    8/62

    FIRE PUMP CONTROLLERS

    Control panels for Diesel drives and Jockey Pumps:

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    9/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    10/62

    NFPA 20 Does not specify when or if a

    fire pump must be installed

    Specifies: How, Components,

    Equipment, Power Sourceare acceptable to use

    Provides the minimum

    requirements needed for

    satisfactory operation of

    listed fire pumps NFPA 20 covers every type of

    listed fire pump

    Most common is centrifugal

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    11/62

    Equivalency

    1.5 1.5.2

    NFPA 20 is not intended to prevent the use of

    systems, methods, or devices of equivalent or

    superior quality, strength, fire resistance,

    effectiveness, durability, and safety over those

    prescribed in this standard.

    AHJ has the final call

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    12/62

    NFPA 20 Terms Shall

    Mandatory requirement

    Should

    Indicates a

    recommendation that is

    advised but not required

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    13/62

    What Makes a Pump a Fire Pump

    4.2

    Stationary pumps shall be selected based on the

    conditions under which they are to be installed and

    used

    Capacities are based on calculated system demand, and

    pressures are based on available pressure from the water

    supply

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    14/62

    What Makes a Pump a Fire Pump 4.4.1 Unit Responsibility

    One supplier for pump, driver, controls

    Typically falls on the pump manufacturer

    SHOULDwas used not Shall Recommendation, having unit responsibility helps ensure that all

    components are compatible

    4.5 Certified Shop Test Needs to be furnished from the pump manufacturer to the

    purchaser, and must include head capacity and BHP

    Why? To verify that the fire pump was tested by themanufacturer prior to shipment and met the conditions.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    15/62

    What Makes a Pump a Fire Pump

    4.6.5 Head

    The Head available from a water supply shall be

    figured on the basis of a flow for 150% rated

    capacity. (EG: 1000GPM pump shall be able to reach

    a capacity of 1500GPM)

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    16/62

    What Makes a Pump a Fire Pump 4.7 Pumps, Drivers, and Controllers

    4.7.3

    A Pump shall not be equipped with more than one driver

    4.7.4

    Each pump shall have its own dedicated driver

    4.7.5

    Each driver shall have its own dedicated controller

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    17/62

    What Makes a Pump a Fire Pump 4.7.7 Maximum Pressure for Centrifugal Pumps

    4.7.7.1 The net pump shutoff pressure plus the maximum static

    suction pressure adjusted for elevation shall not exceed the

    pressure for which the system components are rated Ex: 1000Gpm @ 145psi, shut off pressure is 168psi, and suction

    pressure is 30psi. You need to have 250# fittings on the

    discharge side of the system.

    Dont over design the pump and use a throttle device to

    regulate pressure!!

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    18/62

    NFPA 204.8 Centrifugal Pump Capacities

    Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    19/62

    Automatic (circulation) Relief Valve

    4.11.1.3 The valve shall provide flow of sufficient water to

    prevent the pump form overheating when operating at shutoff. Up to

    2500GPM the nominal size shall be 3000GPM and higher shall be1

    Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    20/62

    Devices in Suction Piping

    4.14.9 Devices in Suction Piping.

    4.14.9.1 No device or assembly, unless identified in 4.14.9.2 that will stop,

    restrict the starting, or restrict the discharge of a fire pump or pump

    driver shall be installed in the suction piping. The purpose is to prohibit anything in the

    suction that would cause excess turbulence, friciton loss, or cut off the flow to the pump

    while running at 150% capacity. Cutting off the supply would cause catastrophic failure to the

    pump.

    Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    21/62

    Water Flow Test DevicesEvery fire pump needs a method for performing the acceptance test.

    1) Test Header Flows readings are usually taken with a Pitot tube

    3) Flowmeter A special pipe is run for the discharge back to the water

    supply with a flowmeter, control valve, and check valve in the line.

    4.20.1.1 A fire pump installation shall be arranged to allow the test of the pump

    at its rated conditions as well as the suction supply at the maximum

    flow available from the fire pump.

    Two objectives:

    1) To make sure the pump itself will function correctly

    2) Make sure the water supply can deliver the correct amount

    Under no circumstance may a fire pump be placed into service without an

    acceptance test!!!

    Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    22/62

    Automatic Air Release

    6.3.3 Automatic Air Release.

    6.3.3.1 Unless the requirements of 6.3.3.2 are met, pumps that are

    automatically controlled shall be provided with a listed float-operated

    air release valve having a normal 0.50 in. (12.7 mm) minimum

    diameter discharge to atmosphere.

    Air in the impeller can cause cavitation, dmage the impeller, and negatively

    impact pump perfomance!

    Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    23/62

    Listed Fire Pump Controllers

    10.1.2.1

    All controllers and transfer switches shall be

    specifically listed for electric motor driven Fire

    Pump Service

    12.1.3.1

    All controllers shall be specifically listed for diesel

    engine-driven fire pump

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    24/62

    Field Acceptance Testing 14.2.4 .1

    A copy of the manufacturers certified pump test

    characteristics curve shall be available for comparison of the

    results of the field acceptance test

    14.2.5.2.1

    The fire pump shall perform at minimum, rated, and peak loads

    without objectionable overheating of any component

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    25/62

    NFPA 20

    14.5.2.1

    Whenever a critical path component in a piece of

    centrifugal pump equipment is replaced, changed,

    or modified, a field/on-site retest shall be

    performed

    Table 14.5.2.4

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    26/62

    TESTING METHODS

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    27/62

    Courtesy of Proctor & Gamble, Cincinnati, OH

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    28/62

    Two hydrants are normally required to

    conduct a flow test of the water supply.

    This is the flow hydrant, the second hydrant

    will only have a pressure gauge and will be

    used to obtain a static (no flow) and residualpressure reading (while water is flowing).

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    29/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    30/62

    PUMP FLOWDETERMINATION

    WITH ( UL / FM )

    FLOW METER

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    31/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    32/62

    Short Play Pipe

    Underwriters Play Pipe

    1 Nozzle

    1 1/8 Nozzle

    PitotTube

    1

    Nozzle

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    33/62

    Maintenance

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    34/62

    Owner / Operators trained in required

    maintenance, weekly operation, required

    testing, and record keeping ?

    Did the pump distrbutor provide the required

    instruction manuals and a weekly check list for the

    required weekly testing, maintenance, and

    inspections of the pump, driver, and controller ?

    NFPA 20 14.3 NFPA 25 4.1 - 4.3

    If not, he is not doing his job!!!Weekly Check list should include those items required

    by NFPA 25 Chapter 8.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    35/62

    Review ALL Required Weekly/Annual Maintenance

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    36/62

    NOTE: Clean GreaseForced out of theDrain hole with

    PLUG REMOVED !!

    Check ForExcessGrease

    Review ALL Required Weekly/Annual Maintenance

    Annual

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    37/62

    AFTER alignment hasbeen re-checked(ANNUALLY) thecoupling should belubricated and re-assembled. Be sureto check the setscrews for tightness

    AnnualAlignment

    Check

    EMERGENCY

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    38/62

    # 1 C OOL IN G

    W A TE R

    # 2F UEL# 3

    C R A N K

    NOTE !

    SET at 120 % ofRated RPM **

    EMERGENCYMANUALSTARTINGPROCEDURE

    (11.6.6)

    BE SURE THAT YOUKNOW WHERE THEOVERSPEED RESETIS ON EVERY TYPEOF ENGINE THAT

    YOU SELL !!

    CUMMINS

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    39/62

    Develop a check listof your own forboth electric anddiesel Fire

    Pumps.-OR-

    Make a copy of

    NFPA 25, Chapter 8for use as a guideforweekly checks.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    40/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    41/62

    HAVE

    THESEFOLKS

    BEEN

    PROPERLYTRAINED?

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    42/62

    ?This is the ONLY WM case relief valveon record, that always had a tight shut offwith NO nuisance leakage - until the fire

    pump overheated and was destroyed !!

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    43/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    44/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    45/62

    Motor HP and current

    li it lti li d b

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    46/62

    NOTE: Automatic air release

    NFPA 20 (7.3.5.2.3) SHALL BE Located between the fire pump andthe discharge check valve. *

    limits, multiplied by

    the service factor,

    must not be exceeded

    under any condition of

    pump load . CHECK

    !

    NFPA 20 (9.5.2)*

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    47/62

    NOTE: Automatic air release SHALL BE

    Located in the highest point in the discharge

    line, between the fire pump and the discharge

    check valve. NFPA 20 (7.3.5.2.3) *

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    48/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    49/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    50/62

    NFPA 20( 7.4.3.7.2 )

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    51/62

    One degree of off-set is the preferredangle, per drive shaft manufacturers!!

    NFPA 20 (7.5.1.8.2)*

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    52/62

    NFPA 20 (7.6.1.3)*

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    53/62

    Top Shaft Nut is

    used to raise

    shaft and

    impellers

    approximately

    1/8 inch. (seeinstruction

    book)

    NFPA 20 (7.6.1.3)

    NFPA 20 2007

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    54/62

    Water Vel,2/sec Max

    Water Vel.

    1/sec Max

    Screen openings equal to 1sq. in. for every GPM(pump capacity at 150%)(at LOWEST Water LEVEL)NFPA 20 (5.14.8)*

    Confirm propersubmergence(Pump Length) *

    (7.2.2.2)

    NFPA 20 (A.7.2.2.2) (5.14.8)

    #12*

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    55/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    56/62

    Removable screens NFPA 20 (5.14.8.3)

    Intake size NFPA 20 (5.14.8.4)*

    With a vertical turbine fire

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    57/62

    NFPA 20 2003

    Zebra Mussel Infestation

    (5.14.8.12)

    pump a plugged screen will

    affect the water level in the

    sump and a plugged basket

    strainer on the bottom of thepump will reduce the total

    pump performance as the

    flow increases.

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    58/62

    VTFP INTAKE

    PROBLEMS..

    Removable screens NFPA 20 (5.14.8.3)Intake size ??? NFPA 20 (5.14.8.4)

    2 ft/sec and 1

    Sq. Inch per

    GPM at 150%

    Flow ?

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    59/62

    Pond

    Maintenance

    -OR-Lack of !!!

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    60/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    61/62

  • 8/14/2019 Fire Pump Essentials - Derek Thompson

    62/62