Fire Dampers En

Embed Size (px)

Citation preview

  • 7/27/2019 Fire Dampers En

    1/33

    Halton fre damper range

    FDC FDE FDR BSD SSA FRH

    Nominal Size 160400 100...500 200x200

    1000x1000*)

    100500 150x150

    1000x1000 *)

    100200

    Fire Protection Standard

    Conormity

    EN 1366-2

    EN 13501-3

    EN 1366-2

    EN 13501-3

    EN 1366-2

    EN 13501-3

    BS 476

    NT FIRE 010

    BS 476

    NT FIRE 010

    BS 476

    Fire Classiication EIS 30 EIS

    120

    EIS15,ES90

    E120

    EIS 30

    EIS 120

    Tightness o the casing Class C

    EN 1751

    Class C

    EN 1751

    Class C

    EN 1751

    Class C

    EN 1751

    Class C

    EN 1751

    Tightness

    Smoke Protection Class

    Class S Class S

    Operation range 3100 Pa

    15 m/s

    3300 Pa 2800 Pa

    15 m/s

    Application

    Masonry & concrete wall

    Lightweight plasterboard wall

    Masonry & concrete ceiling

    X

    X

    X

    X

    X

    X

    X

    X

    X

    Power supply 24 VAC/VDC /

    230 VAC

    24 VAC/VDC

    / 230 VAC

    24 VAC/VDC

    / 230 VAC

    Other Inormation *) Circular

    ducts NS

    630..1000

    *) Modulated

    units or

    larger sizes

    Release at

    50 C or

    74 C

    Fire Dampers & Valves

  • 7/27/2019 Fire Dampers En

    2/330

    BSD - Fire Damper

    20/BSD/3500/0606/EN

    BSD

    Fire Damper

    Fire damper with non-insulated blade or circular

    ducts

    Available thermal uses: 50, 74, 65, 100, 120, 150

    or 200C

    Classiication o casing leakage EN 1751 class C

    Inlet and outlet spigots include integral rubber

    gaskets

    Fire tested to BS 476:part 20:1987 at the Warrington

    Fire Research Centre, Report No. WARRES 45434.

    Fire tested to NORDTEST NT FIRE 010 standard,

    which is the subject o the PAL 2864 a and b

    Research Reports o the Fire Technology Laboratory

    o the Technical Research Centre o Finland.

    Product model options and Accessories

    Model with stainless steel (AISI 316) design

    Model equipped with cleaning access panel Several automatic release and position indication

    options

    MATERIAL AND FINISHING

    PART MATERIAL NOTE

    Casing Galvanised steel Optional stainless steel AISI 6

    Blade Galvanised steel Optional stainless steel AISI 6

    Installation frame Galvanised steel Optional stainless steel AISI 6

    Closing springs Stainless steel

    Duct gaskets MS-polymer

  • 7/27/2019 Fire Dampers En

    3/33

    L1

    L

    D

    600

    NS L L D A

    00 0 60

    0 0

    60 0

    00 0

    0 0 00 0 6

    00 0 0

    00 60 600

    BSD - Fire Damper

    20/BSD/3500/0606/EN

    DIMENSIONS

    Product models and Accessories

    BSD -unit integrated with cleaning access panel RLA

    (BSD/R) enables removal o the ire damper and

    access to ductwork or cleaning.

    ACCESSORY CODE DESCRIPTION

    Installation frame GM

    Mesh on one side N

    Mesh on both sides N

    Fuse FU Thermal release at 0, 6, , 00, 0, 0 or 00 C

    Micro switch MS Closed position indication/enclosure class IP 6

    The ire damper can be equipped with a bipolar micro

    switch, which indicates the closing o the shut-o

    blade. The micro switch has potential ree points

    (no=normally open and nc=normally closed), which

    can be used to control other ire dampers equipped

    with an electric release e.g. triggering an alarm in the

    ire suppression system.

    The maximum operating voltage and current is 400 V,

    10A.

    Sizes 00 - 00 Size 600

  • 7/27/2019 Fire Dampers En

    4/33

    BSD - Fire Damper

    20/BSD/3500/0606/EN

    Electromagnetic operation

    The ire damper stays open, when the electric circuit

    is closed. The damper is shut by opening the circuit.

    Note: Interruption o power supply will close the

    damper. Uninterrupted power supply e.g. battery back-

    up system is recommended.

    Release types

    The ire damper is always equipped with thermal

    release. Additional release systems available:

    Electric signal release, solenoid operation

    Electromagnetic operation

    Pneumatic operation with pressurised gas (e.g. CO2).

    Solenoid operation

    The ire damper can be released with an electric

    signal, which is initiated by a smoke detector, micro

    switch or pressure switch etc. When the circuit is

    closed, the operating voltage is switched to the

    magnet and the damper closes.

    OPTION S S

    Power supply VDC 0 VAC

    Power consumption (design

    value)

    W 0 VA

    Enclosure IP class

    (minimum)

    IP 0 IP0

    ED 00 % 00 %

    OPTION EM

    Power supply VDC

    Wattage (design value) W

    Enclosure IP class (minimum) IP0

    ED 00 %

    Pneumatic operation

    The damper is connected to the ire suppressionsystem. When the system is activated, pressure

    acting on the pneumatic cylinder releases the spring,

    allowing the damper to close. The actuator is suitable

    or common pressure levels used in ire suppression

    systems. The lowest operating pressure o the

    actuator is 200 kPa.

    Pressure drop data

    Damper open

    BSD

  • 7/27/2019 Fire Dampers En

    5/33

    D+23

    12

    4

    3

    BSD - Fire Damper

    20/BSD/3500/0606/EN

    Function

    The BSD is a ire damper suitable or circular ducts.

    The device prevents the spread o ire and smoke

    in insulated ventilation ducts. In the case o a

    temperature rise in the ductwork, the thermal use

    releases allowing the springs to close the damper

    blades. The device can be set and test released,

    because the thermal use is reusable. The outer

    indicator handle also unctions as a position indicator.

    The BSD is set rom outside the device and can be

    installed in any direction. The nominal use release

    temperatures are +50C or +74C, but +65C, +100C,

    +120C, +150C or +200C are available or special

    cases.

    Installation

    CODE DESCRIPTION

    1 Fire damper

    2 Reusable use

    3 Installation rame

    4 Handle / position indicator

    The ire damper is ixed on a compartment wall or in

    a duct rom the installation lange, either directly or

    with the aid o the GM installation rame. There are no

    restrictions on the position o use.

    Check the unction o the ire damper beore

    installation.Clean the damper ater installation.

    Set the ire damper by turning the shut-o blade

    to the desired position with the aid o the indicator

    handle.

    Lock the damper by turning the use manually.

    Servicing

    A released damper can be reset once the use

    temperature is lower than the release temperature.

    I the shut-o blade does not lock, the use has be

    worn out and must be replaced.

  • 7/27/2019 Fire Dampers En

    6/33

    BSD - Fire Damper

    20/BSD/3500/0606/EN

    Suggested specifications

    The casing and blades o the ire damper shall be

    made o galvanised steel (or stainless steel AISI 316)

    The release spring shall be made o stainless steel.

    Thermal use release temperature shall be as

    speciied, (+50C, +65C, +74C +100C, +120C,

    +150C or +200C).

    The ire damper shall have means or opening and

    triggering the release externally.

    The ire damper shall comprise a position indicator.

    Where indicated the damper shall be supplied with

    the ollowing release option

    A. Electric signal release by closing circuit (initiated by

    e.g. smoke detector, micro- or pressure switch).

    Enclosure class o the electric release arrangement

    shall be IP 20 or better.B. Electromagnetic release by opening circuit

    C. Pneumatic release

    Product code

    BSD/S-D

    S = Model

    N Standard

    R With access panel RLA

    D = Diameter o duct connection

    100, 125, 160, 200, 250, 315, 400, 500

    Speciics and accessories

    FU = Fuse release temperature[C]

    50 C, 70 C, 74 C, 100 C, 120 C, 150 C,

    200 C

    RE = Release type

    NA Not assigned

    S1 Solenoid 24 VDC

    S2 Solenoid 230 VAC

    EM Electromagnetic, 24 VDC

    PN Pneumatic

    MA = Material

    CS Steel

    AS Stainless steel, AISI 316

    AC = Accessories

    GM Installation rame

    N1 Saety mesh 1 side

    N2 Saety mesh 2 sides

    MS Micro switch

    Code example

    BSD/N-100, FU=50,RE=NA,MA=CS

  • 7/27/2019 Fire Dampers En

    7/33

    FDC - Fire Damper or Circular Ducts

    20/FDC/3500/0606/EN

    FDC

    Fire Damper or Circular Ducts

    Type-approved and compliant with the EN 1366-2

    and EN 13501-3 standards

    For installation in separating concrete and masonry

    walls and ceilings o ire compartments with ire

    resistance class EIS 30 EIS 120

    Also or installations on lightweight plasterboard

    walls with a ire resistance class o EIS 30

    EIS 120

    Manuactured in accordance with the ISO 9001

    quality system

    VTT, the Technical Research Centre o Finland, is

    responsible or external quality control

    For installation in circular ducts with diameter

    160500 mm

    Double sealing, ensuring that the blades are tight

    when the ire damper is closed beore and during a

    ire

    Fire damper casing complying with the tightness

    requirements or Class C, EN 1751

    Fire damper tightness meeting smoke damper

    requirement S o standard EN 1366-2

    Suitable or use in ducts with a maximum pressure

    o 3100 Pa

    Damper closing tests perormed at 15 m/s duct

    velocity

    Product models and Accessories

    Models equipped with either manual or electric

    actuators

    Installation rame (GM) or lightweight plasterboard

    walls

  • 7/27/2019 Fire Dampers En

    8/336

    D

    -1

    560

    342 218 D + 50

    143

    600

    D = 160, 200, 250, 315, 400

    D = 500

    D

    60

    00

    0

    00

    00

    FDC - Fire Damper or Circular Ducts

    20/FDC/3500/0606/EN

    DIMENSIONS

    When the damper is installed on concrete and

    masonry walls or ceilings, the size o the installation

    hole is D+50 mm

    When it is installed on lightweight walls, consult the

    Installation Instructions or the size o the installation

    holes.

    Material and finishing

    The FDC ire damper casing, installation lange and

    installation rame are made o galvanised steel. The

    closing blade is made o calcium silicate and equipped

    with a lexible silicone seal as well as a graphite mass

    seal.

    Product options and Accessories

    Actuators

    Manual actuator, MA (spring return)

    Belimo BF 24-T2 HI, operating voltage AC/DC 24 V

    (72 C, contains a microswitch), B1 (Sizes D400D500)

    Belimo BF 230-T2 HI, operating voltage AC 230 V

    (72 C, contains a microswitch), B2 (Sizes D400D500)

    Belimo BLF24-T2 HI, operating voltage AC/DC 24 V

    (72 C, contains a microswitch), B3 (Sizes D160D315)

    Belimo BLF230-T2 HI, operating voltage AC 230 V

    (72 C, contains a microswitch), B4 (Sizes D160D315)

    Accessories

    Saety mesh on one side, N1

    Saety mesh on both sides, N2

    For lightweight wall installation (WT=L), the installation

    rame (GM) is included in the delivery.

    Manual actuator accessories

    Fuse release temperatures, FU = 50 C, 65 C, 72 C,

    100 C

    Limit switches, open and closed position, MS

  • 7/27/2019 Fire Dampers En

    9/33

    f / [Hz] 0 00 k k k k

    kok - - - -

    l / dB +/- +/- +/- +/- +/- +/- +/-

    FDC - Fire Damper or Circular Ducts

    20/FDC/3500/0606/EN

    Function

    The FDC is a circular ire damper o ire resistance

    class EIS 30-EIS 120, which prevents ire and smoke

    rom spreading in ventilation ducts The ire damper is

    equipped with either a motorised actuator or manual

    actuation arrangement. In both options, a use reacts

    to a rise in temperature, causing a spring-return

    blade to close. I the power in the motorised actuator

    system is switched o, the blade closes automatically.

    The ire damper is made o ireproo materials. Once

    the ire damper has closed, the double sealing closes

    the duct tightly, eectively preventing the spreading

    o lue gases in the ventilation ductwork. The lexible

    seal o the double sealing system operates at lower

    temperatures, while the graphite mass seal expands

    to insulate the system at temperatures above 150 C.The ire damper is delivered complete with a spring-

    return actuator and a use that is activated at 72 C.

    The ire damper can also be delivered as a manually

    operated unit. Both actuators have a visual position

    indicator. The FDC ire damper can be connected to

    the MSH control and testing system or ire dampers.

    The MSH enables the use o smoke detectors in the

    ductwork or rooms. The FDC ire damper can also

    be connected to other common building automation

    systems.

    Pressure drop and sound data

    Sound power level Lw, in in each ocatve band is

    computed bu adding the corresponding correction

    actor, Kok, to the sound pressure level in the

    selection chart according to the ollowing equation.

    Lw = LpA + Kok

    The corresponding actor Kok is the average o the

    FDC operating area.

  • 7/27/2019 Fire Dampers En

    10/33

    5 80

    1 2 S1

    S2

    S3

    S4

    S5

    S6

    1 2 3 4 5 6 7 8 9 10

    BF24 BLF24BF230 BLF230 IP54

    24 VAC / VDC230 VAC

    (-)N

    (+)L1

    M

    K1K1K1

    FDC - Fire Damper or Circular Ducts

    20/FDC/3500/0606/EN

    Installation

    Installation on concrete and masonry walls

    When the ire damper is installed on concrete

    and masonry walls and ceilings between ire

    compartments, the blade shat is always horizontal.

    An opening is always let in the separating element

    or the ire damper, and the product is subsequently

    grouted into this.

    To make installation easier, all products come with

    an installation lange, which is used to asten the ire

    damper to the concrete surace with screws beore

    grouting.

    During installation, the ire damper and actuator must

    be protected with, e.g., a plastic cover.

    The correct operation o the ire damper must be

    ensured beore and ater grouting.When the damper is installed on concrete and

    masonry walls or ceilings, the size o the installation

    hole is D+50 mm.

    Installation on lightweight plasterboard walls

    When the ire damper is installed on lightweight

    plasterboard walls between ire compartments,

    an opening or the ire damper must be let on

    the plasterboard in which the installation rame

    (accessory) is irst mounted.

    The blade shat must always be horizontal.

    To make installation easier, the ire damper comes

    with an installation lange, which is used to asten the

    ire damper to, e.g., the steel rame o the panel wall.

    The space between the ire damper and the

    installation rame is illed with a ire prevention mastic.

    During installation, the ire damper and actuator must

    be protected with, e.g., a plastic cover.

    The correct operation o the ire damper must beensured ater application o the ire prevention mastic.

    For lightweight walls, the size o the installation hole

    varies according to the product in question.

    The size should be chosen on the basis o the size o

    the installation rame (accessory).

    Detailed installation instructions, as well as an

    installers installation certiicate orm, are supplied

    with each product. See also the Installation

    Instructions.

    Electric actuator wiring diagram

    Manual actuator wiring diagram (limit switches,

    MS)

    Damper open Damper driving Damper closed

    K: / closed K: / open K:/ open

    K: / open K:/ closed K:/ closed

    Limit switch K and K: Pizzato, type FR -HO

  • 7/27/2019 Fire Dampers En

    11/33

    FDC - Fire Damper or Circular Ducts

    20/FDC/3500/0606/EN

    Suggested specifications

    The ire damper o class EIS 30EIS 120 shall

    have a double sealing solution that ensures ire-gas

    resistance at all temperatures when the ire damper is

    closed.

    The use shall be located inside the damper, and it is

    possible to replace it rom the outside.

    In motorised models, the use shall be activated at

    +72 C.

    In the manually operated system, the use activation

    temperature corresponds to the speciications (50, 65,

    72, 100 C).

    The ire damper shall have means or external opening

    / triggering o the release and closing.

    The ire damper shall include a position indicator.

    The ire damper shall be suitable or vertical andhorizontal installations on concrete and masonry walls

    and ceilings or lightweight plasterboard walls between

    ire compartments (EIS 30...EIS 120).

    The technical properties o the type-approved ire

    damper shall conorm to the EN 1366-2 and EN 13501-

    3 standards.

    The internal quality control o the ire damper

    manuacturer shall be based on the ISO 9001 quality

    system.

    VTT, the Technical Research Centre o Finland, is

    responsible or external quality control.

    Product code

    FDC/S-D

    S = Model

    E Europe

    S Sweden

    R Russia

    D = Size o duct connection

    160, 200, 250, 315, 400, 500

    Speciics and Accessories

    WT = Wall type

    C Concrete wall

    L Lightweight wall(installation rame GM)

    RE = Release type

    MA Spring release

    B1 BF-24-T2 HI use 72C (Belimo)

    (D400...D500)

    B2 BF-230-T2 HI use 72C (Belimo)

    (D400...D500)

    B3 Belimo BLF24-T2 HI, operating

    voltage AC/DC 24 V (72 C, contains a

    microswitch), (Sizes D160D315)

    B4 Belimo BLF230-T2 HI, operating

    voltage AC 230 V (72 C, contains a

    microswitch), (Sizes D160D315)

    FU = Fuse release temperature [C ]

    50 C, 65 C, 72 C, 100 C

    AC = Accessories

    N1 Saety mesh, 1 side

    N2 Saety mesh, 2 sides

    MS Limit switches

    Code example

    FDC/E-160, WT=C,RE=MA,FU=72

  • 7/27/2019 Fire Dampers En

    12/330

    FDE - Fire Damper or Circular Ducts

    20/FDE/3500/0606/EN

    FDE

    Fire Damper or Circular Ducts

    Type-approved and compliant with the EN 1366-2

    and EN 13501-3 standards

    Installation in separating concrete or masonry walls

    and ceilings

    Possibility o installation on lightweight plasterboard

    walls

    Fire resistance classes EIS 15, ES 90 and E120.

    External quality control management by VTT, the

    Technical Research Centre o Finland

    Installation in circular ducts with diameter

    100500 mm

    Manuacture in accordance with the ISO 9001

    quality standard

    Fire damper casing complying with the tightness

    requirements or Class C, EN 1751

    Inlet and outlet spigots that include integral rubber

    gaskets

    Suitability or use in ducts with a maximum pressure

    o 3300 Pa

    Product models and Accessories

    Several automatic release and position indication

    options

    Models equipped with either manual or electrical

    actuators (various types available)

    Manual uses available (spring release): 50, 65, 72,

    100, 120, 150 or 200 C

    MATERIAL AND FINISHING

    PART MATERIAL

    Casing Galvanised steel

    Blade Galvanised steel

    Blade gaskets Ceramic cloth

    Installation frame Galvanised steel

    Closing springs Stainless steel

    Duct gaskets C-polyurethane hybrid

  • 7/27/2019 Fire Dampers En

    13/33

    L

    D

    L3

    L3

    L1 L2

    NS D L L L L

    00 0 0 0

    0 0 0

    60 0 0 0

    00 0 0 0

    0 0 0 0

    0 0 00 0 0

    00 0 60

    f / [Hz] 0 00 k k k k

    kok - - -0 -

    l / dB +/- +/- +/- +/- +/- +/- +/-

    FDE - Fire Damper or Circular Ducts

    20/FDE/3500/0606/EN

    DIMENSIONS

    When the damper is installed on a concrete or

    masonry wall or ceiling, the size o the installation

    hole is about D + 50 mm.

    Detailed installation instructions, as well as an

    installers installation certiicate orm, are supplied

    with each product.

    Pressure drop and sound data

    Sound power level Lw, in in each ocatve band is

    computed bu adding the corresponding correctionactor, Kok, to the sound pressure level in the

    selection chart according to the ollowing equation.

    Lw = LpA + Kok

    The corresponding actor Kok is the average o the

    FDE operating area.

  • 7/27/2019 Fire Dampers En

    14/33

    FDE - Fire Damper or Circular Ducts

    20/FDE/3500/0606/EN

    The ire damper can be equipped with a bipolar

    microswitch, which indicates the closing o the shut-

    o blade. The microswitch has potential-ree contacts

    (no=normally open and nc=normally closed), which

    can be used to control other ire dampers equipped

    with an electric release (e.g., triggering an alarm in the

    ire suppression system).

    The maximum operating voltage and current is 400 V,

    10 A.

    Actuators

    Manual actuator, MA (spring return)

    Belimo BLF24-T2 HI, operating voltage AC/DC 24 V (72

    C, contains a microswitch), B1

    Belimo BLF230-T2 HI, operating voltage AC 230 V (72

    C, contains a microswitch), B2

    ACCESSORIES

    ACCESSORY CODE DESCRIPTION

    Mesh on one side N

    Mesh on both sides N

    Fuse FU Thermal release at 0, 6, , 00, 0, 0 or 00 C

    Microswitch MS Closed position indication, enclosure class IP 6

    OPTION S S

    Power supply VDC 0 VAC

    Power consumption (design

    value)

    W 0 VA

    Enclosure IP class

    (minimum)

    IP 0 IP0

    ED 00 % 00 %

    OPTION EM

    Power supply VDC

    Wattage (design value) W

    Enclosure IP class (minimum) IP0

    ED 00 %

    Release types

    The ire damper always has thermal release operation

    (a use). Additional release systems available:

    Electric signal release, solenoid operation.

    Electromagnetic operation.

    Pneumatic operation with pressurised gas (e.g.,

    CO2).

    Solenoid operation

    The ire damper can be released with an electrical

    signal, which is initiated by a smoke detector,

    microswitch / pressure switch or similar. When the

    circuit is closed, the operating voltage is switched to

    the magnet and the damper closes.

    Electromagnetic operation

    The ire damper stays open when the electrical circuit

    is closed. The damper is shut by opening the circuit.

    Note: Interruption o the power supply closes the

    damper. An uninterrupted power supply (e.g., a battery

    backup system) is recommended.

    Pneumatic operation

    The damper is connected to the ire suppression

    system. When the system is activated, pressure

    acting on the pneumatic cylinder releases the spring,

    allowing the damper to close. The actuator is suited

    or common pressure levels used in ire suppression

    systems. The lowest operating pressure or the

    actuator is 200 kPa.

  • 7/27/2019 Fire Dampers En

    15/33

    1

    FDE - Fire Damper or Circular Ducts

    20/FDE/3500/0606/ENFunction

    The FDE unit is a circular ire damper o ire resistance

    class EIS 15, ES 90 and E120, which prevents ire and

    smoke rom spreading in ventilation ducts. The ire

    damper is equipped with either a motorised actuator

    or a manual actuation arrangement. Under both

    options, a use reacts to a rise in temperature, causing

    a spring-return blade to close. I the power in the

    motorised actuator system is switched o, the blade

    closes automatically. The FDE can be installed in any

    direction, and setting is perormed rom outside the

    device.

    The ire damper is made o ireproo materials. Once

    the ire damper has closed, the blade and sealing

    close the duct tightly, eectively preventing the

    spreading o lue gases.

    The ire damper is delivered complete with a spring-

    return actuator and a use that is activated at 72 C.

    Alternatively, the ire damper can be delivered as a

    manually operated unit. The nominal use release

    temperature is 50 or 72 C, but 65, 100, 120, 150 and

    200 C are available or special cases.

    The FDE ire damper can be connected to the MSH

    control and testing system. The MSH enables the

    use o smoke detectors in ductwork or in rooms. The

    FDE ire damper can also be connected to common

    building automation systems.

    Installation

    There are no restrictions on the position o use.

    Check the unctioning o the ire damper beore

    installation.

    Clean the damper ater installation.Set the ire damper by turning the shut-o blade

    to the desired position with the aid o the indicator

    handle. Lock the damper by turning the use manually.

    Installation on masonry walls

    1 Screw and ixing plug

    D1 Product size + about 50 mm

    When the ire damper is installed on a concrete or

    masonry wall or ceiling between ire compartments,

    there are no restrictions on the position o use.

    An opening is always let in the separating element

    or the ire damper, and the product is subsequently

    grouted into this.

    To make installation easier, all products come with

    an installation lange, which is used to asten the ire

    damper to the concrete surace with screws beore

    grouting.

    During installation, the ire damper and actuator must

    be protected with, e.g., a plastic cover.

    The correct operation o the ire damper must be

    ensured beore and ater grouting.When the damper is installed on a concrete or

    masonry wall or ceiling, the size o the installation

  • 7/27/2019 Fire Dampers En

    16/33

    5

    2

    34

    1

    230 VACL1

    S1 S2 S3

    BLF230-HI

    Tf1 Tf2 Tf3 BAE72A-S

    < 5

    S4 S5 S6

    < 80

    1 2

    AC 2 4 VDC 24 V+

    Connect viasafety isolatingtransformer!!

    ~

    S1 S2 S3

    BLF24-HI

    Tf1 Tf2 Tf3 BAE72A-S

    < 5

    S4 S5 S6

    < 80

    1 2

    N

    K1K1

    FDE - Fire Damper or Circular Ducts

    20/FDE/3500/0606/EN

    hole is about D+50 mm.

    Installation on lightweight plasterboard walls

    D1 Product size + about 5 mm

    1 Fireproo sealing mass

    2 Steel rame3 Plasterboard

    4 Mineral wool

    5 Screw

    When the ire damper is installed on a lightweight

    plasterboard wall between ire compartments, a

    small opening or the ire damper must be let in the

    plasterboard walls.

    There are no restrictions on the position o use.

    To make installation easier, the ire damper comes

    with an installation lange, which is used to asten the

    ire damper to, e.g., the steel rame o the panel wall.

    The space between the ire damper and the

    plasterboard wall is grouted with ire prevention

    mastic. During installation, the ire damper and

    actuator must be protected with, e.g., a plastic cover.

    The correct operation o the ire damper must be

    ensured ater application o the ire prevention mastic.

    Set the ire damper manually by turning the shut-

    o blade to the desired position with the aid o the

    indicator handle. Lock the damper by turning the use

    manually. I the shut-o blade does not lock, the use

    is worn out and must be replaced.

    Detailed installation instructions, as well as an

    installers installation certiicate orm, are supplied

    with each product. See also Installation Instructions.

    Electric actuator wiring diagram

    Manual FDE actuator wiring diagram (limit switch,

    MS)

    Damper open Damper closed

    K: / closed K: / open

    / open / closed

  • 7/27/2019 Fire Dampers En

    17/33

    FDE - Fire Damper or Circular Ducts

    20/FDE/3500/0606/EN

    Servicing

    A released damper can be reset ater the use

    temperature has allen below the release temperature.

    I the shut-o blade does not lock, the use is worn

    out and must be replaced.

    Suggested specifications

    The casing and blades o the ire damper shall be

    made o galvanised steel.

    The release spring shall be made o stainless steel.

    The thermal use release temperature shall be as

    speciied, (50, 65, 72, 100, 120, 150 or 200 C).

    The ire damper shall have means or opening and

    triggering the release externally.

    The ire damper shall include a position indicator.

    Where indicated, the damper shall be supplied with

    the ollowing release options:

    A. Electric signal release by closing circuit (initiated by,

    e.g., a smoke detector or a microswitch or pressure

    switch); the enclosure class o the electric release

    arrangement shall be IP 54 or better.

    B. Electromagnetic release by opening circuit.

    C. Pneumatic release.

    Product code

    FDE-D

    D = Diameter o duct connection

    100, 125, 160, 200, 250, 315, 400, 500

    Speciics and accessories

    FU = Fuse release temperature

    50 50 C

    65 65 C

    72 72 C

    100 100 C

    120 120 C150 150 C

    200 200 C

    RE = Release type

    MA Spring return

    B1 BLF24-T2 HI use, 72 C (Belimo)

    B2 BLF230-T2 HI use, 72 C (Belimo)

    RS = Release type or spring release

    NA Not assigned

    S1 Solenoid, 24 VDC

    S2 Solenoid, 230 VAC

    EM Electromagnetic, 24 VDC

    PN Pneumatic

    MA = Material

    CS Galvanised steel

    AC = Accessories

    N1 Saety mesh, 1 side

    N2 Saety mesh, 2 sides

    MS Microswitch

    Code example

    FDE D-100, FU=50, RE=MA, MA=CS

  • 7/27/2019 Fire Dampers En

    18/336

    FDR - Fire Damper or Circular and Rectangular Ducts

    20/FDR/3500/0606/EN

    FDR

    Fire Damper or Circular and Rectangular Ducts

    Type-approved and compliant with the EN 1366-2

    and EN 13501-3 standards

    For installation in separating concrete and masonry

    walls and ceilings o ire compartments with ire

    resistance class EIS 30 EIS 120

    For installations on lightweight plasterboard walls

    with a ire resistance class o EIS 30 EIS 120.

    Manuactured in accordance with the ISO 9001

    quality system

    VTT, the Technical Research Centre o Finland, is

    responsible or external quality control

    For installation in rectangular and circular ducts with

    diameter 6301,000 mm

    Available with motorised or manual actuator

    Double sealing, ensuring that the blades are tight

    when the ire damper is closed beore and during a

    ire

    Fire damper casing complying with the tightness

    requirements or Class C, EN 1751

    Fire damper tightness meeting smoke damper

    requirement S o standard EN 1366-2

    Suitable or use in ducts with a maximum pressure

    o 2800 Pa

    Damper closing tests perormed at 15 m/s duct

    velocity

    Product models and Accessories

    Models equipped with either manual or electric

    actuators

    Installation rame (GM) or lightweight plasterboard

    walls

  • 7/27/2019 Fire Dampers En

    19/33

    FDR BxH D- La Lb C L L+xC

    60 600x600 6 66 60

    00 00x00 66 0 6

    000 000x000 66 00 6

    f / [Hz] 0 00 k k k k

    kok 0 0 - - - -0

    l / dB +/- +/- +/- +/- +/- +/- +/-

    FDR - Fire Damper or Circular and Rectangular Ducts

    20/FDR/3500/0606/EN

    DIMENSIONS

    B/H: 200, 250, 300, 400, 500...1000

    When the damper is installed on concrete and

    masonry walls or ceilings, the size o the installation

    hole is B/H + 100 mm

    When the damper is installed on lightweight walls, the

    size o the installation hole is B/H + 110 mm

    Pressure drop and sound data

    Sound power level Lw, in in each octave band is

    computed bu adding the corresponding correction

    actor, Kok, to the sound pressure level in the

    selection chart according to the ollowing equation.

    Lw = LpA + Kok

    The corresponding actor Kok is the average o the

    FDR operating area.

  • 7/27/2019 Fire Dampers En

    20/33

    FDR - Fire Damper or Circular and Rectangular Ducts

    20/FDR/3500/0606/EN

    Material and finishing

    The FDR ire damper casing, installation lange and

    installation rame are made o galvanised steel. The

    closing blade is made o calcium silicate and equipped

    with a lexible silicone seal as well as a graphite mass

    seal that expands at high temperatures.

    Product options and Accessories

    Actuators

    Manual actuator, MA (spring return)

    Belimo BF 24-T2 HI, operating voltage AC/DC 24 V

    (72 C, contains a microswitch), B1

    Belimo BF 230-T2 HI, operating voltage AC 230 V

    (72 C, contains a microswitch), B2

    Accessories

    Saety mesh on one side, N1

    Saety mesh on both sides, N2

    For lightweight wall installation (WT=L), the installation

    rame (GM) is included in the delivery.

    Manual actuator accessories

    Fuse release temperatures, FU = 50 C, 65 C, 72 C,

    100 C

    Limit switches, open and closed position, MS

    Function

    The FDR is a ire damper o class EIS 30.EIS 120 or

    circular or rectangular ducts, which prevents ire and

    smoke rom spreading in ventilation ducts. The ire

    damper is equipped with either a motorised actuator

    or manual actuation arrangement. In both options, a

    use reacts to a rise in temperature, causing a spring-

    return blade to close. I the power in the motorised

    actuator system is switched o, the blade closes

    automatically.

    The ire damper is made o ireproo materials. Once

    the ire damper has closed, the double sealing closes

    the duct tightly, eectively preventing the spreading

    o lue gases in the ventilation ductwork. The lexible

    seal o the double sealing system operates at lower

    temperatures, while the graphite mass seal expandsto insulate the system at temperatures above 150 C.

    The ire damper is delivered complete with a spring-

    return actuator and a use that is activated at 72 C.

    The ire damper can also be delivered as a manually

    operated unit. Both actuators have a visual position

    indicator. The FDR ire damper can be connected to

    the MSH control and testing system or ire dampers.

    The MSH enables the use o smoke detectors in the

    ductwork or rooms. The FDR ire damper can also

    be connected to other common building automation

    systems.

  • 7/27/2019 Fire Dampers En

    21/33

    5 80

    1 2 S1

    S2

    S3

    S4

    S5

    S6

    1 2 3 4 5 6 7 8 9 10

    BF24BF230 IP42

    24 VAC / VDC230 VAC

    (-)N

    (+)L1

    M

    K1K1K1

    FDR - Fire Damper or Circular and Rectangular Ducts

    20/FDR/3500/0606/EN

    Installation

    Installation on masonry walls

    When the ire damper is installed on concrete

    and masonry walls and ceilings between ire

    compartments, the blade shat is always horizontal.

    An opening is always let in the separating element

    or the ire damper, and the product is subsequently

    grouted into this.

    To make installation easier, all products come with

    an installation lange, which is used to asten the ire

    damper to the concrete surace with screws beore

    grouting.

    During installation, the ire damper and actuator must

    be protected with, e.g., a plastic cover.

    The correct operation o the ire damper must be

    ensured beore and ater grouting.When the damper is installed concrete and masonry

    walls and ceilings, the size o the installation hole is

    B/H + 100 mm

    Installation on lightweight plasterboard walls

    When the ire damper is installed on lightweight

    plasterboard walls between ire compartments,

    an opening or the ire damper must be let on

    the plasterboard in which the installation rame

    (accessory) is irst mounted. The blade shat must

    always be horizontal. To make installation easier, the

    ire damper comes with an installation lange, which

    is used to asten the ire damper to, e.g., the steel

    rame o the panel wall. The space between the ire

    damper and the installation rame is illed with a ire

    prevention mastic. During installation, the ire damper

    and actuator must be protected with. e.g.. a plastic

    cover. The correct operation o the ire damper must

    be ensured ater application o the ire preventionmastic.

    For lightweight walls, the size o the installation hole is

    B/H+110 mm. The size should be chosen on the basis

    o the size o the installation rame (accessory).

    Detailed installation instructions, as well as an

    installers installation certiicate orm, are supplied

    with each product.

    Electric actuator wiring diagram Manual actuator wiring diagram (limit switches,

    MS)

    Damper open Damper driving Damper closed

    K: / closed K: / open K:/ open

    K: / open K:/ closed K:/ closed

    Limit switch K and K: Pizzato, type FR -HO

  • 7/27/2019 Fire Dampers En

    22/330

    FDR - Fire Damper or Circular and Rectangular Ducts

    20/FDR/3500/0606/EN

    Suggested specifications

    The ire damper o class EIS 30EIS 120 shall

    have a double sealing solution that ensures ire-gas

    resistance at all temperatures when the ire damper

    is closed. The use shall be located inside the damper,

    and it is possible to replace it rom the outside.

    In motorised models, the use shall be activated at

    +72 C.

    In the manually operated system, the use activation

    temperature corresponds to the speciications (50, 65,

    72, 100 C).

    The ire damper shall have means or external opening /

    triggering o the release and closing. The ire damper shall

    include a position indicator.

    The ire damper shall be suitable or vertical and

    horizontal installations on concrete and masonry walls

    and ceilings or lightweight plasterboard walls between

    ire compartments (EIS 30...EIS 120).

    The technical properties o the type-approved ire

    damper shall conorm to the EN 1366-2 and EN 13501-

    3 standards.

    The internal quality control o the ire damper

    manuacturer shall be based on the ISO 9001 quality

    system.

    VTT, the Technical Research Centre o Finland, is

    responsible or external quality control.

    Product code

    FDR/S-A-W-H

    S = Model

    E Europe

    S Sweden

    R Russia

    A = Type o duct connections

    R Rectangular

    A Duct connection 630

    B Duct connection 800

    C Duct connection 1000

    W = Width

    A=R: 200, 250, 300, 400, 500, 600, 700, 800,

    900, 1000

    A=A: 600A=B: 800

    A=C: 1000

    H = Height

    A=R: 200, 250, 300, 400, 500, 600, 700, 800,

    900, 1000

    A=A: 600

    A=B: 800

    A=C: 1000

    Speciics and Accessories

    WT = Wall type

    C Concrete wall

    L Lightweight wall

    (installation rame GM)

    RE = Release type

    MA Spring release

    B1 BF-24-T2 HI use 72C (Belimo)

    B2 BF-230-T2 HI use 72C (Belimo)

    FU = Fuse release temperature [C ]

    50 C, 65 C, 72 C, 100 C

    AC = AccessoriesN1 Saety mesh, 1 side

    N2 Saety mesh, 2 sides

    MS Limit switches

    Code example

    FDR/E-R-200-200, WT=C,RE=MA,FU=72

  • 7/27/2019 Fire Dampers En

    23/33

    FRH - Fire Valve

    20/FRH/3500/0606/EN

    FRH

    Fire Valve

    Combined exhaust valve with adjustable pressure

    loss and ire damper or circular ducts

    Prevents the spread o ire and lue gases into

    ventilation ductwork

    Airlow rate adjustment and measurement acility

    Release temperature o the use is +50C or +74C

    Fire tested to BS 476:part 22:1987 by the Loss

    Prevention Council, the subject o FIRTO Technical

    Evaluation No. TE 6643

    Research Reports PAL 3147 and PAL 2268 o the

    Fire Technology Laboratory o the Technical

    Research Centre o Finland.

    Accessories

    Installation rame options

    Wall protection ring

    MATERIAL AND FINISHING

    PART MATERIAL NOTE

    Collar Steel

    Central cone Steel Melting fuse

    Gasket Polyurethane

    Installation frame Galvanised steel

    Protection ring Steel

    Finishing Epoxy-painted White RAL 00 Special colour available

  • 7/27/2019 Fire Dampers En

    24/33

    W

    77

    H

    D

    NS W H D

    00

    6

    0 60 00

    00

    FRH - Fire Valve

    20/FRH/3500/0606/EN

    DIMENSIONS

    ACCESSORIES

    ACCESSORY CODE DESCRIPTION

    Installation frame LF Installation frame without gasket, height 0 mm

    Installation frame GF Installation frame with gasket, height 0 mm

    Installation frame DF Installation frame with duct dimensions, can be installed direct to duct parts (bend,

    T-branch, etc.)

    Protection ring CS For protection of the installation surface from smudging

    QUICK SELECTION

    qv l/s 0 0 0 0 60 0 0 0 00

    m/h 0 0 0 6 60

    FRH-00 LpA 0 6 0

    DPtot 6 6 0

    dP_t 6 -

    FRH- LpA

    DPtot dP_t 0 6 -

    FRH-0 LpA 6 6

    DPtot 66 0

    dP_t 0 0 -

    FRH-60 LpA 6

    DPtot 6

    dP_t 6 60 -

    FRH-00 LpA 6

    DPtot 0

    dP_t 0 -

    LpA values presented with room attenuation dB (red 0m -

    sab). When using room attenuation dB (red 0m

    - sab):LpA - dB.

    LpA A-weighted sound pressure level, reduced by total

    equivalent absorption surface of 0m

    , dB(A) red0m - sab

    DPtot Total pressure drop, Pa

    dP_t Maximum DPtot (Pa), when a-weighted sound

    pressure level (Lp) is dB(A)

  • 7/27/2019 Fire Dampers En

    25/33

    q = k pv m$*

    FRH - Fire Valve

    20/FRH/3500/0606/EN

    Function

    The valve throttles the exhaust airlow and attenuates

    the duct noise. The pressure drop is dependant on

    the position o the central cone. The desired exhaust

    airlow rate is adjusted during the balancing o the

    airlows in a ductwork system.

    The ire damper contains a thermal use, which

    releases the cone to the closed position with the help

    o a spring. The thermal use is released at +50C or

    at +74C .

    Installation

    The exhaust valve is mounted with the aid o a

    separate installation rame LF, GF or DF. Push the

    installation rame into the duct and ix it. Push the

    valve into the installation rame and turn until it is

    irmly attached.

    Technical data

    Please reer to URH in the Halton Air Distribution

    brochure

    Adjustment

    The valve is adjusted by rotating the central cone.

    Measure the opening (A) position (in mm) o the

    central cone. Set a probe inside the valve and

    measure the dierential pressure with a manometer.

    The airlow rate is calculated using the ormula below.

    Ater the adjustment, lock the central cone with the

    locking nut.

    Servicing

    CODE DESCRIPTION

    1 Central cone

    2 Locking nut

    3 Collar

    Loosen the valve rom the ductwork by turning anti-

    clockwise. Note the adjusted opening position o the

    central cone.

    Wipe the parts with a damp cloth, instead o

    immersing in water. Reassemble valve in reverse

    order ater cleaning.

    Note: Do not use hot water or hot temperatures

    during cleaning as this may cause unnecessaryrelease o the use.

  • 7/27/2019 Fire Dampers En

    26/33

    FRH - Fire Valve

    20/FRH/3500/0606/EN

    Suggested specifications

    The ire valve shall have an adjustable central cone

    and collar made o epoxy-painted steel, with white

    (RAL 9010) as standard colour.

    The installation rame shall be equipped with a sealing

    gasket.

    The ire valve shall be equipped with a thermal use

    and release spring.

    The opening position o the central cone shall be

    adjusted during balancing in order to achieve required

    pressure loss and airlow rate.

    Ater balancing the central cone shall be locked into

    the selected adjustment position.

    Product code

    FRH-D

    D = Diameter o duct connection

    100, 125, 150, 160, 200

    Speciics and accessories

    CO = Colour

    W White

    X Special colour

    FU = Fuse release temperature[C]

    50 C, 74 C

    Code example

    FRH-100, CO=W,FU=50

    Sub products

    DF Installation rame or duct parts

    GF Installation rame

    LF Installation rame

  • 7/27/2019 Fire Dampers En

    27/33

    SSA - Fire Damper

    20/SSA/3500/0606/EN

    SSA

    Fire Damper

    Rectangular curtain ire damper with non-insulated

    olding blades

    Available uses: +50, +72, +65, +100, +150 or

    +200 C

    Classiication o casing leakage EN 1751 Class C

    Hot galvanised steel design

    Fire tested to BS 476:part 20:1987 at the Warrington

    Fire Research centre, Report No. WRCSI 31470/A

    SSA-D2 and WRCSA 31470/B SSA

    Fire tested to NORDTEST NT FIRE 010 standard,

    which is the subject o the PAL 2876/73, No

    PAL 3132 b, No PAL 3132 c Research Reports o

    the Fire Technology Laboratory o the Technical

    Research Centre o Finland.

    Product models and Accessories

    Several automatic release and position indication

    options

    Circular duct connections; inlet and outlet spigots

    include integral rubber gaskets

    Large sizes are available with modular design

    MATERIAL

    PART MATERIAL NOTE

    Casing Galvanised steel

    Curtain blades Galvanised steel

    Closing springs Stainless steel

    External gaskets EPDM rubber Only with circular connections D, D

    Thermal release fuse Brass Different release temperature options

  • 7/27/2019 Fire Dampers En

    28/336

    H-7

    H+43

    75

    145

    W+43

    W-7

    145

    75

    W1

    NS W

    00

    60

    00

    0

    00

    00

    60 6

    00

    000 0

    W H

    00,0,...,000 0,00,...,000

    SSA - Fire Damper

    20/SSA/3500/0606/EN

    DIMENSIONS

    Special dimensions

    The maximum nominal size is 1000x1000 mm.

    It is possible to have a continuous grille o modular

    design when the installation length is greater than

    1000 mm. The maximum total length is 20 m.

    Models with circular duct connections

    SSA/C, CT=D1 & SSA/C CT=D2

    The SSA ire damper can be equipped with a bipolar

    microswitch (MS), which indicates the closing o the

    ire damper. The microswitch has potential-ree

    contacts (no=normally open and nc=normally closed),

    which can be used to control other ire dampers

    equipped with an electric release, e.g., triggering an

    alarm in the ire suppression system.

    The maximum operating voltage and current is 400 V,

    10A.

    ACCESSORIES AND PRODUCT MODELS

    ACCESSORY CODE DESCRIPTION

    Installation frame GM

    Mesh on one side N

    Mesh on both sides N

    Fuse FU Thermal release at 0, 6, , 00, 0 or 00 C

    Microswitch MS MS Closed position indication/ enclosure class IP 6

    Position Indicator PI

    Fastening flange FL One side

    Fastening flanges, pcs FL Both sides

  • 7/27/2019 Fire Dampers En

    29/33

    SSA - Fire Damper

    20/SSA/3500/0606/EN

    Electromagnetic operation

    The ire damper stays open when the electric circuit is

    closed. The damper is shut by opening the circuit.

    Note: Interruption o the power supply will close

    the damper. An uninterrupted power supply - e.g., a

    battery backup system - is recommended.

    Release types

    The ire damper always has a thermal release.

    Additional release arrangements available:

    Solenoid operation, electric signal release, contact;

    normally open (no)

    Electromagnetic operation, contact; normally closed

    (nc)

    Pneumatic operation with pressurised gas (e.g., CO2)

    Manual release (wire rope)

    Solenoid operation

    The ire damper can be released with an electric

    signal, which is initiated by a smoke detector,

    microswitch or pressure switch etc. When the circuit

    is closed, the operating voltage is switched to the

    solenoid and the damper closes.

    OPTION S S

    Power supply VDC 0 VAC

    Power consumption (design

    value)

    W 0 VA

    Enclosure IP class

    (minimum)

    IP 0 IP0

    ED 00 % 00 %

    OPTION EM

    Power supply VDC

    Wattage (design value) W

    Enclosure IP class (minimum) IP0

    ED 00 %

    Pneumatic operation

    The damper is connected to the ire suppression

    system. When the system is activated, pressure

    acting on the pneumatic cylinder releases the spring,

    allowing the damper to close. The actuator is suitable

    or common pressure levels used in ire suppression

    systems. The lowest operating pressure o the

    actuator is 200 kPa.

    Manual operation

    Manual release, options or wire rope release.

    Pressure drop data

  • 7/27/2019 Fire Dampers En

    30/33

    SSA - Fire Damper

    20/SSA/3500/0606/ENFunction

    The SSA is a ire damper suitable or rectangular and

    circular ducts. The damper prevents the spread o ire

    and smoke in insulated ventilation ducts. The SSA is

    suitable or installation either horizontally or vertically

    so that the blades close downwards. Various release

    mechanisms are possible.

    A temperature increase in a ventilation duct causes a

    thermal use release, allowing the springs to close the

    damper blades. The bottom blade is locked ater the

    curtain has closed, preventing accidental reopening.

    The standard nominal use release temperatures are

    +50 and +72 C, but release temperatures o +65,

    +100, +150 and +200 C are available.

    Installation

    Install the damper with the blades in horizontal

    or vertical position in the ductwork. For vertical

    installation, note that the blades are to close

    downwards.

    Fasten the damper in the ductwork using slip joints or

    using astening langes.

    Use a seal between the langes in order to tighten the

    seam.

    Fasten the circular connections by riveting or

    screwing.

    The damper is installed on a compartment wall or

    in a duct by use o the astening lange (AC=FL) or

    in conjunction with an installation rame (AC=GM,

    AC =FL) and is set with the aid o the indicator

    handle (see details in drawing below). When the

    required dimension exceeds 1000 mm, the damper is

    constructed in modular orm. Modular installations are

    constructed with a GM rame with the size o the duct

    opening and FL modules. See the drawing below.

    To enable checking, cleaning and setting, an inspection

    panel has to be positioned close to the ire damper.

    The use can be changed by opening the quick-release

    astener and attaching the new usible link in the

    astener.

  • 7/27/2019 Fire Dampers En

    31/33

    SSA - Fire Damper

    20/SSA/3500/0606/EN

    Product code

    SSA/S-W-H-D

    S = Type o duct connection

    R Rectangular connections

    C Circular connections

    W = Width

    S=R: 100,+50,..,10000

    S=C and D=100: 150

    S=C and D=125: 150

    S=C and D=160: 200

    S=C and D=200: 200

    S=C and D=250: 250

    S=C and D=315: 400

    S=C and D=400: 400S=C and D=500: 500

    S=C and D=630: 600

    S=C and D=800: 800

    S=C and D=1000: 1000

    S=C: 150

    H = Height

    S=R: 150,+50,..,10000

    S=C: W

    D = Diameter o duct connection

    S=C: 100, 125, 160, 200, 250, 315, 400, 500,

    630, 800, 1000

    Speciics and accessories

    CT = Type o circular connection

    D1 1 circular connection

    D2 2 circular connections

    FU = Fuse release temperature[C]

    50 C, 65 C, 72 C, 100 C, 150 C, 200 C

    RE = Release type

    NA Not assigned

    MA Manual

    S1 S1=Solenoid 24 VDCS2 Solenoid 230 VAC

    EM Electromagnetic 24 VDC

    PN Pneumatic

    MA = Material

    CS Steel

    AC = Accessories

    MS Micro switch

    GM Installation rameN1 Saety mesh one side

    N2 Saety mesh two sides

    PI Position indicator

    FL Fastening lange

    Code example

    SSA/R-150-150, FU=50,RE=NA,MA=CS

  • 7/27/2019 Fire Dampers En

    32/330

    MSH - Fire Damper Management System

    20/MSH/3500/0606/EN

    MSH

    Fire Damper Management System

    Used with motorised ire dampers FDR, FDC and

    FDE (operating voltage: 24 V)

    Controls the shut-o operation o ire dampers when

    a ire breaks out

    Enables time-controlled, external or manual testing

    o ire damper operation

    Smoke detectors able to be directly connected to

    the MSH management units

    Locks the an during testing o operation and in ire

    scenarios

    Outputs or remote ire and service alarm indication

    Local alarm indication or ire and service alarm

    conditions

    Easy implementation

    Control unit models

    Control unit or eight (8) or sixteen (16) ire

    dampers

    Control unit with or without smoke detectoroperation

    Smoke detectors can be connected to models MSH/2

    and MSH/4. Transormer and ire indication rom ire

    alarm system o the buiding or power supply are

    included in the delivery.

    Smoke sensors

    Smoke detectors or duct and room installation

    Smoke detectors equipped with optical or ionising

    unction

    TypeMax. Number of

    dampers

    Max. Number of smoke

    detectors

    MSH/ -

    MSH/ 0

    MSH/ 6 -

    MSH/ 6 0

    Smoke detector, room installation

    Smoke detector, duct installation

    Code Type Manufacturer Model

    MSH/A Smoke detector:

    duct, optical

    Calectro ST-P-DA,

    L= 600 mm

    MSH/B Smoke detector:

    room, optical

    Calectro UG--O

    MSH/C Smoke detector:

    duct, ionising

    Calectro ST-I-DA,

    L = 600 mm

    MSH/D Smoke detector:

    room, ionising

    Calectro UG--J

  • 7/27/2019 Fire Dampers En

    33/33

    MSH 1-8-8-MC

    Test

    Total

    Reset Set SetHour Min

    Day

    Fire

    Service

    Closed Fan

    Open

    20/MSH/3500/0606/ENOperation

    The MSH ire damper management system has three

    important unctions:

    1. close the ire dampers when a ire breaks out

    2. regularly test the ire dampers to ensure that they

    are in operational condition

    3. ensure that the ire dampers are open in normal

    conditions and that ventilation can operate as planned

    Fire

    Each ire damper is equipped with a thermal use,

    which closes the damper when the temperature rises

    above 72 C. I any o the thermal uses is released,

    all the ire dampers connected to the MSH unit are

    immediately closed. I the system is equipped with

    smoke detectors, all ire dampers connected to the

    MSH unit in question are immediately closed to the

    saety position when the smoke detector indicates an

    early ire.

    Testing of fire dampers

    The MSH system regularly tests the operation o the

    ire dampers to ensure that they operate correctly

    should a ire break out. The testing can be time-

    controlled and set to take place at desired intervals (1

    to 9 days) or example, every other day.

    To test the system, the MSH unit sends a switch-o

    command to the air handling unit control system.

    When the an stops, the MSH unit closes the ire

    dampers to the saety position and ensures that all

    the ire dampers are closed. Ater that, all dampers are

    reopened and the an is able to start again. I an error

    is detected in the operation o any o the dampers,

    the MSH system issues a service alarm.

    User interface

    The operational status o the ire dampers and any

    alarms are visible on the MSH units operator panel at

    a single glance. The operator panel is also used to set

    the time-controlled testing parameters, start manualtesting and acknowledge service notiication as well

    as operation in the event o a ire.

    Product codes

    MSH/S

    S = Construction / component

    1 = Unit or eight (8) ire dampers, no smoke

    detector connection

    2 = Unit or eight (8) ire dampers, smoke

    detector connection Calectro ABAV-S3

    3 = Unit or sixteen (16) ire dampers, no

    smoke detector connection

    4 = Unit or sixteen (16) ire dampers, smoke

    detector connection Calectro ABAV-S3

    A = Smoke detector: duct, optical Calectro:

    ST-P-DA, L= 600 mm

    B = Smoke detector: room, optical Calectro:

    UG-2-O

    C = Smoke detector: duct, ionising Calectro:

    ST-I-DA, L = 600 mm

    D = Smoke detector: room, ionising

    Calectro: UG-2-J