D1 CURTAIN FIRE DAMPERS CURTAIN FIRE DAMPERS Nailor Industries Inc.

Fire Damper Nailor

Embed Size (px)

Citation preview

Page 1: Fire Damper Nailor

D1

CU

RTA

IN F

IRE

DA

MPER

SCU

RTA

IN F

IRE

DA

MPER

S

NailorIndustries Inc.

Page 2: Fire Damper Nailor

ContentsPage No.

Product Overview D3

Curtain Fire Damper Basics D8

Dynamic U.L. Minimum /Maximum Sizes D9

Static U.L. Minimum /Maximum Sizes D10

Dynamic Fire DampersD0100 Series • 1 1/2 Hour • Standard 4 1/4" (108) Frame D12D0114 Series • 1 1/2 Hour • Integral Sleeve D14D0114HY Series • 1 1/2 Hour • Hybrid with Integral Sleeve D16D0500 Series • 3 Hour • Standard 4 1/4" (108) Frame D18D0100G Series • 1 1/2 Hour • Integral Sleeve for Grille Mount D20D0110GOW Series • 1 1/2 Hour • Out of Wall Mounting D22Selection Procedures for Dynamic Fire Dampers D24

Static Fire Dampers0100 Series • 1 1/2 Hour • Standard 4 1/4" (108) Frame D260114 Series • 1 1/2 Hour • Integral Sleeve D260200 Series • 1 1/2 Hour • 2" (51) Thinline Frame D300310 Series • 1 1/2 Hour • 6" (152) Wide Frame D320500 Series • 3 Hour • Standard 4 1/4" (108) Frame D340570 Series • 3 Hour • 2" (51) Thinline Frame D360540 Series • 3 Hour • 6" (152) Wide Frame D380100G Series • 1 1/2 Hour • Integral Sleeve for Grille Mount D400200G Series • 1 1/2 Hour • Thinline Damper with Integral Sleeve for Grille Mount D420110GOW Series • 1 1/2 Hour • Out of Wall Mounting D440130GC Series • 1 1/2 Hour • Garbage Chute Fire Damper D46

Sizing ChartsFor Standard 4 1/4" (108) Frame Fire Dampers D48For Thinline 2" (51) Frame Fire Dampers D49For Wide Frame 6" (152) Fire Dampers D50

Options & VariablesOptions/Variables Model Codes D51How to Order Curtain Fire Dampers D51Sleeve Options D52Sleeve Lengths /Gauges D53HM1/HM2 Hemmed Ends D53Retaining AnglesQS1/QS2 'Quick-Set' Retaining Angles D54Type C Damper SealingLP/HP Low Pressure/High Pressure Caulking D55Closure DevicesFL Fusible Links D55EML Easy Maintenance Link D56ETL Electro-Thermal Link D57Closure Temperatures D58Pull-Tab ReleasePT Pull-Tab Release for Horizontal Dampers D58Microswitch Status IndicatorsMS/MSE Microswitches D59Flanged SleeveTDF1/TDF2 TDF Flanges D60

D2

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

Revised May 5, 2005

Page 3: Fire Damper Nailor

MODEL SERIES D0110/D0114DYNAMIC • 1 1/2 HOURThe Nailor D0100 Series dynamic curtain fire dampers areUL approved for use where building codes require protectionof HVAC ductwork penetrations in walls, partitions or floorsthat have a fire resistance rating of 2 hours or less. Classifiedfor use in dynamic systems where the HVAC system remainsoperative in the event of a fire, the D0100 Series featuresstainless steel closure springs for assured damper closureunder airflow. Model Series D0114 includes an integralsleeve to make jobsite installation fast and simple.

MODEL SERIES D0500DYNAMIC • 3 HOURThe Nailor D0500 Series dynamic curtain fire dampers areUL approved for use where building codes require protectionof HVAC ductwork penetrations in walls, partitions or floorsthat have a fire resistance rating of 4 hours or less. Classifiedfor use in dynamic systems where the HVAC system remainsoperative in the event of a fire, the D0500 Series featuresstainless steel closure springs for assured damper closureunder airflow, corrosion resistant steel frame and blades forlasting performance, and choice of transition styles andfactory installed sleeves to suit duct size, making installationfast and simple.

Since 1971, Nailor Industries fire dampers have been an intrinsic part of HVAC systems in commercial and industrial buildings.As an industry leader, Nailor’s commitment to quality construction and product development has helped limit property damageand make buildings safer for occupants all over the world by restricting the passage of flame and smoke. Building codes requirefire dampers to maintain the fire resistance ratings of walls, partitions and floors which have been penetrated by ducts or othersimilar openings. Nailor provides a variety of dampers to suit the wide array of structures that require protection, whether adynamic (fans operate during emergency) or static (fans shut down) type HVAC system is utilized. All Nailor dynamic firedampers have been tested to minumum 2000 fpm (10.16 m/s) @ 4” w.g. (1 kPa) as per the latest UL 555 Safety Standard.

D3

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

S

Model D0510

Model D0110

Revised May 5 2005

MODEL SERIES D0110GINTEGRAL SLEEVE FOR USE WITH GRILLEDYNAMIC • 1 1/2 HOURDesigned for use in conjunction with a steel grille whenductwork terminates at an opening in a fire ratedwall/partition. This unique product utilizes special grillemounting flanges on the sleeve that eliminate therequirement for unsightly retaining angles which commonlyprotrude from behind the grille. The steel grille installs overand completely conceals the mounting flanges for a clean,aesthetic finish. The fire damper is offset in the sleeve toaccommodate a single or double deflection supply air grille,single deflection supply air register or a return air grille orregister. Countersunk screw holes in the the grille frame willmatch to mounting flanges when Nailor grille is ordered inconjunction with the damper assembly.

Model D0110G

GENERAL PRODUCT OVERVIEW

Page 4: Fire Damper Nailor

D4

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

MODEL SERIES 0110/0114STATIC • 1 1/2 HOURThe Nailor 0100 Series curtain fire dampers, for use in static"fans off" systems where the HVAC system shuts down inthe event of a fire, are UL approved to provide protection ofHVAC ductwork penetrations in walls, partitions or floors thathave a fire resistance rating of 2 hours or less. The 0100Series features corrosion resistant steel frame and bladesfor performance that lasts, and a choice of transition stylesto suit duct size. Model Series 0114 includes an integralsleeve to make jobsite installation fast and easy.

MODEL SERIES 0200THINLINE FRAME • STATIC • 1 1/2 HOURThinline curtain fire dampers are UL approved for use wherebuilding codes require the protection of HVAC ductworkpenetrations in walls, partitions or floors that have a fireresistance rating of 2 hours or less. The 0200 Series isclassified for use only in static "fans off" systems where theHVAC system is automatically shut down in the event of a firealarm. The 0200 Series Thinline dampers are only 2" (51) deepmaking them ideal for installation in narrow fire rated partitions,transfer duct openings, behind grilles or in any other applicationwhere space is limited.

Model 0110H

Model 0210V

Revised May 5 2005

Model D0110GOW

MODEL D0110GOWOUT OF WALL • INTEGRAL SLEEVE FOR GRILLEDYNAMIC • 1 1/2 HOURThe Model D0110GOW is an "out of wall or floor" integralsleeve dynamic curtain type fire damper, specificallydesigned for supply or return ducts that terminate at a grilleor register. For use where local building codes require theprotection of HVAC ductwork penetrations in walls, partitionsor floors that have a fire resistance rating of up to two hours.The D0110GOW design provides sufficient damper off-set toaccommodate most commercial grille/register designs whileensuring an approved installation in any fire partition or wall nomatter how narrow. This model is particularly suited for use incommon steel stud drywall partition designs, as narrow as 31/2" (89) where a traditional "within the plane of the wall" firedamper installation is not possible.

GENERAL PRODUCT OVERVIEW

Page 5: Fire Damper Nailor

D5

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

S

MODELS 0510, 0520 AND 0530STATIC • 3 HOURThe Nailor 0500 Series standard frame curtain fire dampers,for use in static "fans off" systems where the HVAC systemshuts down in the event of a fire, are UL approved to provideprotection of HVAC ductwork penetrations in walls, partitionsor floors that have a fire resistance rating of 4 hours or less.The 0500 Series features corrosion resistant steel frame andblades for performance that will last, and a choice oftransition styles and factory installed sleeves to suit ductsize, making installation fast and simple.

MODELS 0570, 0580 AND 0590THINLINE FRAME • STATIC • 3 HOURModels 0570, 0580, and 0590 thinline curtain fire dampersare UL approved for use where building codes require theprotection of HVAC ductwork penetrations in vertical fireseparations (walls or partitions) that have a fire resistancerating of 4 hours or less. The 0500 Thinline Series isclassified for use in static "fans off" systems where theHVAC system is automatically shut down in the event of afire alarm. These thinline dampers are only 2" (51) deepmaking them ideal for installation in narrow fire ratedpartitions, transfer duct openings, behind grilles or any otherapplication where room is limited. They feature corrosionresistant steel frame and blades for lasting performance, anda choice of transition styles and factory installed sleeves tosuit duct size, making installation fast and simple.

Model 0510H

Model 0570V

MODEL 0310WIDE FRAME • STATIC • 1 1/2 HOURThe Nailor Model 0310 Wide Frame curtain fire damper is ULapproved for use where local building codes require theprotection of HVAC ductwork penetrations in walls, partitionsor floors that have a fire rating of 2 hours or less. The 0310is classified for use only in static "fans off" systems wherethe HVAC system is automatically shut down in the event ofa fire alarm. The wide frame allows for less blades and alarger free area.

Model 0540V

Revised May 5 2005

GENERAL PRODUCT OVERVIEW

Page 6: Fire Damper Nailor

D6

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

Model 0110G

Model 0210G

MODEL SERIES 0100GINTEGRAL SLEEVE FOR USE WITH GRILLE STATIC • 1 1/2 HOURDesigned for use in conjunction with a steel grille whenductwork terminates at an opening in a fire ratedwall/partition. The 0100G Series is 1 1/2 hour UL labeled foruse in 2 hour fire separations or less and is classified for usein static "fans off" systems where the HVAC system shutsdown in the event of a fire alarm. This unique product utilizesspecial grille mounting flanges on the sleeve that eliminatethe requirement for unsightly retaining angles whichcommonly protrude from behind the grille. The steel grilleinstalls over and completely conceals the mounting flangesfor a clean, aesthetic finish.

MODEL SERIES 0200GINTEGRAL SLEEVE FOR USE WITH GRILLETHINLINE FRAME • STATIC • 1 1/2 HOURThinline Series integral sleeve fire dampers are designed foruse in conjunction with a steel grille when ductwork terminatesat an opening in a fire rated wall/partition. The 0200G ThinlineSeries is 1 1/2 hour UL labeled for use in 2 hour fireseparations or less and is classified for use in static "fans off"systems where the the HVAC system shuts down in the eventof a fire alarm. This unique product utilizes special grillemounting flanges on the sleeve that eliminate the requirementfor unsightly retaining angles which commonly protrude frombehind the grille. The steel grille installs over and completelyconceals the mounting flanges for a clean, aesthetic finish.The 2" (51) deep thinline fire damper is offset in the sleeve toaccommodate a single or double deflection grille or register.

Revised May 5 2005

MODEL 0540WIDE FRAME • STATIC • 3 HOURThe Nailor Model 0540 wide frame curtain fire damper is ULapproved for use where building codes require the protectionof HVAC ductwork penetrations in vertical fire separations(walls or partitions) that have a fire resistant rating of 4 hoursor less. The 0540 is classified for use in static "fans off"systems where the HVAC system is automatically shut downin the event of a fire alarm.The 0540 is ideal for use when maximum free area is desiredin situations where space or design does not yield room fora Type B damper style. Featuring corrosion resistant steelframe and blades for lasting performance, the Nailor Model0540 is available with factory installed sleeve for fast andsimple installation.Model 0540V

GENERAL PRODUCT OVERVIEW

Page 7: Fire Damper Nailor

D7

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

Let Nailor Simplify Your Fire Damper Installation!Labor saving options such as factory fitted sleeves, TDF proprietary flange duct/sleeve connections, factory supplied"Quick-Set" retaining angles, and grille mounting tab sleeves help speed and simplify jobsite installation, saving time andmoney.

Additional available features that simplify testing and maintenance procedures include Pull-Tab release for horizontaldampers, Nailor’s innovative Easy Maintenance Link and microswitch damper status indicators. Nailor’s completepackage will simplify your fire damper installation!

GENERAL PRODUCT OVERVIEW

Model 0130GC

MODEL 0130GCGARBAGE CHUTE CURTAIN FIRE DAMPERThe Nailor Model 0130GC has been specially designed forgarbage chute applications. The damper casing is oversizedto ensure that the blade stack, fusible link and closuresprings are unobstructed from falling waste. The round collaris slightly oversized for direct attachment to the outside ofthe garbage chute. The 100% free area 0130GC alsofeatures corrosion resistant steel construction and isavailable in three standard sizes, 20" dia. (508), 22" dia.(559) and 24" dia. (610), as well as custom sizes. Damperhas a 1 1/2 hour fire rating.

Model 0110GOW

MODEL 0110GOWOUT OF WALL • INTEGRAL SLEEVE FOR GRILLESTATIC • 1 1/2 HOURThe Model 0110GOW is an "out of wall or floor" integral sleevecurtain type fire damper, specifically designed for supply orreturn ducts that terminate at a grille or register. For use wherelocal building codes require the protection of HVAC ductworkpenetrations in walls, partitions or floors that have a fireresistance rating of up to two hours. The 0110GOW is classifiedfor use only in static “fans off” systems where the HVAC systemis automatically shut down in the event of a fire alarm. The0110GOW design provides sufficient damper off-set toaccommodate most commercial grille/register designs whileensuring an approved installation in any fire partition or wall nomatter how narrow. This model is particularly suited for use incommon steel stud drywall partition designs, as narrow as 3 1/2"(89) where a traditional "within the plane of the wall" fire damperinstallation is not possible.

Page 8: Fire Damper Nailor

D8

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SCURTAIN FIRE DAMPER BASICS

CURTAIN FIRE DAMPER BASICS

DEFINITION OF A FIRE DAMPER:The National Fire Protection Association (NFPA) Standard 90A defines a fire damper as "a device, installed inan air distribution system, that is designed to close automatically upon detection of heat, to interrupt migratoryairflow, and to restrict the passage of flame."

Although curtain fire dampers restrict flame and airflow passage as described in the NFPA definition, they arevirtually transparent to heat and therefore ineffective for use in openings in fire-rated ceiling assemblies. SeeCeiling Damper Basics for more details.

TYPES OF CURTAIN FIRE DAMPERSCurtain type fire dampers are generally available in three configuration as follows:

TYPE 'A' TYPE 'B' TYPE 'C'

Openings in vertical fire separations ie: walls and partitions, require a vertical mount fire damper (duct runshorizontally). Gravity causes the blades to drop closed (static rated dampers).Openings in horizontal fire separations ie: floors, require a horizontal mount fire damper (duct runs vertically).Horizontal mount fire dampers utilize springs to pull the blades closed.Dynamic rated fire dampers utilize closure springs in both vertical and horizontal applications to ensure theblades close fully under airflow conditions.

STATIC RATED VS. DYNAMIC RATED FIRE DAMPERS:Static fire dampers were designed for use in HVAC systems that shut down (fans off) in the event of a firealarm. They have not been tested to ensure closure while air is moving in the duct.Dynamic fire dampers have been tested under specific airflow and static pressure conditions in order toensure that the damper will close in today’s HVAC designs that utilize 'fans on' smoke management systems.See Dynamic Fire Damper Selection Procedures in this section.Generally, a dynamic rated damper can be used in both static (fans off) or dynamic (fans on) type systems, buta static rated fire damper can only be used in a 'static' system (fans shut down during alarm).

DID YOU KNOW?....• Fire dampers must be mounted in a steel sleeve. The damper/sleeve assembly is held in place in the wall,

partition or floor by use of retaining angles on each side of the wall etc. Ductwork shall connect to the sleeveon either side, as required, providing a connection that can 'break away' should the ductwork fall during a fire.This allows the damper/sleeve assembly to remain in the wall etc., maintaining the integrity of the fire barrier.

• NFPA 90A requires that fire barriers of less than 3 hours utilize a 1 1/2 hour rated fire damper. Fire barriers of3 hours or more require a 3 hour rated fire damper.

• All fire dampers must be installed as per manufacturer’s instructions.

Blades and frame in the airstream. Blades out of the airstream; With bladesout of airstream, provides better freearea and resulting pressure dropcharacteristics than Type 'A', especiallyon smaller size dampers.

Blades and frame out of the airstream;used mainly for transitioning to round oroval duct. Provides optimum pressuredrop characteristics with blades andframe out of airstream.

H

W

H

W

D W

H

Revised July 1, 2004

Page 9: Fire Damper Nailor

D9

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SDYNAMIC FIRE DAMPERS • MIN./MAX. SIZES

DYNAMIC CURTAIN TYPE FIRE DAMPERS(For use in dynamic systems.)

MINIMUM AND MAXIMUM UL CLASSIFIED SIZES

Damper Types: Type A: Blades and frame in airstream. Type B: Blades out of airstream for minimal restriction of airflow. Type CR: Round enclosure withblades and frame out of airstream for maximum free area. Type CO: Oval enclosure with blades and frame out of airstream for maximum free area. Type CSR: Square or rectangular enclosure with blades and frame out of airstream for maximum free area.

Note: Larger sizes may become available as they are tested and approved by Underwriters Laboratories. Contact your Nailor representative or consultwww.nailor.com for the latest available sizes.

Maximum individual sections not to exceed 18" x 24" (457 x 610).1

SINGLE SECTION MULTIPLE SECTION ASSEMBLY

MINIMUM SIZE MAXIMUM SIZE MAXIMUM SIZE

INSTALLATION INSTALLATION INSTALLATION

VERTICAL HORIZONTAL VERTICAL HORIZONTAL VERTICAL HORIZONTAL

72" x 24" or 36" x 48"D0110 A

6" x 6" 6" x 6" 24" x 24" 24" x 24"(1829 x 610 or Contact Factory

(152 x 152) (152 x 152) (610 x 610) (610 x 610)914 x 1219)

72" x 21" or 36" x 45"D0120 B

6" x 4" 6" x 4" 24" x 21" 24" x 21"(1829 x 533 or Contact Factory

(152 x 102) (152 x 102) (610 x 533) (610 x 533)914 x 1143)

D0130 Round CR 4" dia. (102) 4" dia. (102) 20" dia. (508) 20" dia. (508) 34" dia. (864) Contact Factory5" x 4" 5" x 4" 22" x 20" 22" x 20" 70" x 20"

D0130 Oval CO(127 x 102) (127 x 102) (559 x 508) (559 x 508) (1778 x 508)

Contact Factory

4" x 4" 4" x 4" 22" x 20" 22" x 20" 70" x 20"D0140 Sq./Rect. CSR

(102 x 102) (102 x 102) (559 x 508) (559 x 508) (1778 x 508)Contact Factory

6" x 6" 6" x 6" 24" x 24" 24" x 24"D0114-12/14/16 A

(152 x 152) (152 x 152) (610 x 610) (610 x 610)— —

6" x 4" 6" x 4" 24" x 21" 24" x 21"D0124-12/14/16 B

(152 x 102) (152 x 102) (610 x 533) (610 x 533)— —

D0134-12/14/16 CR 4" dia. (102) 4" dia. (102) 20" dia. (508) 20" dia. (508) — —72" x 60"

D0114HY A See Page D16 — — —(1829 x 1524)

72" x 54"D0124HY B See Page D16 — — —

(1829 x 1372)—

D0134HY CR See Page D16 — — — 53" dia. (1346) —

70" x 53"D0134HY CO See Page D16 — — —

(1778 x 1346)—

D0100G A,B,CR 6" x 6" 6" x 6" 24" x 24" 24" x 24"(152 x 152) (152 x 152) (610 x 610) (610 x 610)

— —

6" x 6" 6" x 6" 24" x 24" 24" x 24" 36" x 24"D0110GOW A

(152 x 152) (152 x 152) (610 x 610) (610 x 610) (914 x 610)—

72" x 24" or 36" x 48"D0510 A

6" x 6" 6" x 6" 24" x 24" 24" x 24"(1829 x 610 or Contact Factory

(152 x 152) (152 x 152) (610 x 610) (610 x 610)914 x 1219)

72" x 21" or 36" x 45"D0520 B

6" x 4" 6" x 4" 24" x 21" 24" x 21"(1829 x 533 or Contact Factory

(152 x 102) (152 x 102) (610 x 533) (610 x 533)914 x 1143)

D0530 Round CR 4" dia. (102) 4" dia. (102) 20" dia. (508) 20" dia. (508) 34" dia. (864) Contact Factory5" x 4" 5" x 4" 22" x 20" 22" x 20" 70" x 20"

D0530 Oval CO(127 x 102) (127 x 102) (559 x 508) (559 x 508) (1778 x 508)

Contact Factory

4" x 4" 4" x 4" 22" x 20" 22" x 20" 70" x 20"D0530 Sq./Rect. CSR

(102 x 102) (102 x 102) (559 x 508) (559 x 508) (1778 x 508)Contact Factory

1

1

SERIES/MODELTYPE

Revised April 21, 2005

Page 10: Fire Damper Nailor

D10

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

SINGLE SECTION MULTIPLE SECTION

ASSEMBLY

MINIMUM SIZE MAXIMUM SIZE MAXIMUM SIZE

INSTALLATION INSTALLATION INSTALLATION

VERTICAL HORIZONTAL VERTICAL HORIZONTAL VERTICAL HORIZONTAL

0110 A 4" x 4" 4" x 4" 60" x 60" 60" x 60" 120" x 120" 102" x 60"(102 x 102) (102 x 102) (1524 x 1524) (1524 x 1524) (3048 x 3048) (2591 x 1524)

0120 B 4" x 3" 4" x 4" 60" x 54" 60" x 54" 120" x 114" 102" x 54" or 90" x 60"(102 x 76) (102 x 102) (1524 x 1372) (1524 x 1372) (3048 x 2896) (2591 x 1372) or (2286 x 1524)

0130 Round CR 3" dia. (76) 4" dia. (102) 53" dia. (1346) 53" dia. (1346) 112" dia. (2845) 53" dia. (1346)

0130 Oval CO 4" x 3" 5" x 4" 58" x 53" 58" x 53" 118" x 112" 100" x 53"(102 x 76) (127 x 102) (1473 x 1346) (1473 x 1346) (2997 x 2845) (2540 x 1346)

0140 Sq./Rect. CSR 3" x 3" 4" x 4" 58" x 53" 58" x 53" 118" x 112" 100" x 53"(76 x 76) (102 x 102) (1473 x 1346) (1473 x 1346) (2997 x 2845) (2540 x 1346)

0114-12/14/16 A 4" x 4" 4" x 4" 48" x 48" 48" x 48"— —(102 x 102) (102 x 102) (1219 x 1219) (1219 x 1219)

0124-12/14/16 B4" x 3" 4" x 4" 48" x 43" 48" x 43"

— —(102 x 76) (102 x 102) (1219 x 1092) (1219 x 1092)

0134-12/14/16 CR 3" dia. (76) 4" dia. (102) 42" dia. (1067) 42" dia. (1067) — —

0100G A, B, CR 4" x 4" 4" x 4" 24" x 24" 24" x 24"— —(102 x 102) (102 x 102) (610 x 610) (610 x 610)

0200G A, B, CR 4" x 4" 4" x 4" 24" x 24" 24" x 24" — —(102 x 102) (102 x 102) (610 x 610) (610 x 610)

0110GOW A 4" x 4" 4" x 4" 36" x 24" 36" x 24" — —(102 x 102) (102 x 102) (914 x 610) (914 x 610)

0210 A4" x 4" 4" x 4" 41" x 36" or 36" x 60" 41" x 36" — —(102 x 102) (102 x 102) (1041 x 914) or (1041 x 914)

(914 x 1524)

0220 B 4" x 3" 4" x 3" 41" x 30" or 36" x 50" 41" x 30" — —(102 x 76) (102 x 76) (1041 x 762) or (1041 x 762) (914 x 1270)

0230 Round CR 3" dia. (76) 3" dia. (76) 34" dia. (864) 34" dia. (864) — —

0230 Oval CO 4" x 3" 4" x 3" 39" x 29" 39" x 29" — —(102 x 76) (102 x 76) (991 x 737) (991 x 737)

0240 Sq./Rect. CSR3" x 3" 3" x 3" 39" x 29" or 34" x 49" 39" x 29" — —(76 x 76) (76 x 76) (991 x 737) or (991 x 737)

(864 x 1245)

STATIC FIRE DAMPERS • MIN./MAX. SIZES

STATIC CURTAIN TYPE FIRE DAMPERS(For use in static systems.)

MINIMUM AND MAXIMUM UL CLASSIFIED SIZES

Damper Types: Type A: Blades and frame in airstream. Type B: Blades out of airstream for minimal restriction of airflow. Type CR: Round enclosure withblades and frame out of airstream for maximum free area. Type CO: Oval enclosure with blades and frame out of airstream for maximum free area. Type CSR: Square or rectangular enclosure with blades and frame out of airstream for maximum free area.

SERIES/MODELTYPE

Revised April 19, 2005

Page 11: Fire Damper Nailor

D11

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

S

Damper Types: Type A: Blades and frame in airstream. Type B: Blades out of airstream for minimal restriction of airflow. Type CR: Round enclosure withblades and frame out of airstream for maximum free area. Type CO: Oval enclosure with blades and frame out of airstream for maximum free area. Type CSR: Square or rectangular enclosure with blades and frame out of airstream for maximum free area.

STATIC FIRE DAMPERS • MIN./MAX. SIZES

MINIMUM AND MAXIMUM UL CLASSIFIED SIZES

STATIC CURTAIN TYPE FIRE DAMPERS(For use in static systems.)

SINGLE SECTION MULTIPLE SECTION ASSEMBLY

MINIMUM SIZE MAXIMUM SIZE MAXIMUM SIZE

INSTALLATION INSTALLATION INSTALLATION

VERTICAL HORIZONTAL VERTICAL HORIZONTAL VERTICAL HORIZONTAL

4" x 4" 4" x 4" 60" x 48" or 24" x 60"0310 A (102 x 102) (102 x 102) (1524 x 1219) or

48" x 48"— —

(610 x 1524)(1219 x 1219)

4" x 4" 4" x 4" 48" x 48" 36" x 36" 108" x 72" 72" x 36"0510 A

(102 x 102) (102 x 102) (1219 x 1219) (914 x 914) (2743 x 1829) (1829 x 914)4" x 3" 4" x 4" 48" x 43" 36" x 32" 108" x 68" 72" x 32" or 64" x 36"

0520 B (102 x 76) (102 x 102) (1219 x 1092) (914 x 813) (2743 x 1727) (1829 x 813) or(1626 x 914)

0530 Round CR 3" dia. (76) 4" dia. (102) 42" dia. (1067) 31" dia. (787) 66" dia. (1676) 34" dia. (864)4" x 3" 5" x 4" 46" x 42" 34" x 31" 106" x 66" 70" x 31"

0530 Oval CO(102 x 76) (127 x 102) (1168 x 1067) (864 x 787) (2692 x 1676) (1778 x 787)

3" x 3" 4" x 4" 46" x 42" 34" x 31" 106" x 66" 70" x 31"0530 Sq./Rect. CSR

(76 x 76) (102 x 102) (1168 x 1067) (864 x 787) (2692 x 1676) (1778 x 787)60" x 48" or 24" x 60"

0540 A4" x 4"

— (1524 x 1219) or — — —(102 x 102)

(610 x 1524)4" x 4" 36" x 60"

0570 A(102 x 102)

—(914 x 1524)

— — —

4" x 3" 36" x 50"0580 B

(102 x 76)—

(914 x 1270)— — —

0590 Round CR 3" dia. (76) — 34" dia. (864) — — —4" x 3" 34" x 49"

0590 Oval CO(102 x 76)

—(864 x 1245)

— — —

3" x 3" 34" x 49"0590 Sq./Rect. CSR

(76 x 76)—

(864 x 1245)— — —

SERIES/MODELTYPE

Revised July 5, 2004

Page 12: Fire Damper Nailor

• STANDARD FRAME• FOR USE IN DYNAMIC

SYSTEMS• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor D0100 Series dynamic curtain fire dampers are UL/ULC approved for use where building codes require protection ofHVAC ductwork penetrations in walls, partitions or floors that have a fire resistance rating of 2 hours or less. Classified for use indynamic systems (max. 2000 fpm @ 4" w.g.) where the HVAC system remains operative in the event of a fire, the D0100 Seriesfeatures stainless steel closure springs for assured damper closure under airflow, corrosion resistant steel frame and blades forlasting performance, and choice of transition styles and factory installed sleeves to suit duct size, making installation fast andsimple.

MODELS: D0110 / D0114 TYPE AD0120 / D0124 TYPE BD0130 / D0134 TYPE CR/COD0140 TYPE CSR

Model D0110

D12

CURTAIN FIRE DAMPERS

D12

D

DYNAMIC FIRE DAMPERS • 1 1/2 HOURCU

RTA

INFI

RE

DA

MPER

S

D0110 D0120 D0130 D0140 (Type A) (Type B) (Type CR/CO) (Type CSR)

FRAME: 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide,

22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-formed G60 formed G60 formed G60 formed G60

galvanized steel galvanized steel galvanized steel; galvanized steel;out of airstream out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanized G60 galvanized steel steel steel

ENCLOSURE: Type B Type C Type CN/A 22 ga. (.085) Round or Oval Square or Rect.

galvanized steel 22 ga. (.085) 22 ga. (.085)galvanized steel galvanized steel

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available available

BLADE Stainless steel Stainless steel Stainless steel Stainless steelCLOSURE: closure springs closure springs closure springs closure springs

and galvanized and galvanized and galvanized and galvanizedsteel locking ramps steel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical Vertical Vertical Verticalor or or or

Horizontal Horizontal Horizontal Horizontal

INTEGRALSLEEVE: See Model See Model See Model22 ga (.085) x12”

(305) long D0114-12 DO124-12 DO134-12 Specify22 ga (.085) x14” SL

(356) long D0114-14 DO124-14 DO134-14 Option22 ga (.085) x16”

(406) long D0114-16 DO124-16 DO134-16

CONSTRUCTION DETAILS:

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

3" (76)

STAINLESS STEELCLOSURE SPRING

CURTAIN BLADELOCKING RAMP

VERTICAL MOUNT

TYPE A: MODEL D0110

HEI

GH

T =

NO

MIN

ALD

UC

T SI

ZE -

1/4"

(6)

INTERLOCKINGCURTAIN BLADES

HORIZONTAL MOUNT

STAINLESS STEELCLOSURE SPRING

CURTAIN BLADELOCKING RAMP

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

4 1/4"

(108)

ROLL-FORMEDFRAME

4 1/4" (108)

DU

CT

SIZE

- 1/

4" (6

)

For MIN./MAX. UL SIZES see chart on page D9.

Revised May 5, 2005

Page 13: Fire Damper Nailor

D13

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SDYNAMIC FIRE DAMPERS • 1 1/2 HOUR

For overall damper dimensions see sizing chart on page D48.

PERFORMANCE DATA:Curtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for the differentdamper types and static pressure losses for various velocities.

HOW TO SPECIFY

TYPE B: MODEL D0120

TYPE CR: MODEL D0130

TYPE CO: MODEL D0130

TYPE CSR WITH COLLAR(STANDARD):MODEL D0140

TYPE CSR WITHOUT COLLAR:

MODEL D0140

H =DUCT SIZE

+ 1/8" (3)

W = DUCT SIZE - 1/4" (6)

HH

W + 1 3/4" (44)

WW + 1 3/4" (44)

W

D + 1 3/4" (44)

D W + 1 3/4" (44)

WH

1"

TYPE B DAMPER FREE AREA TYPE B DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .17 .39 .62 .84 1.1 1.3 1.5 1.7 2.0 2.212 (305) .36 .83 1.3 1.8 2.3 2.7 3.2 3.7 4.1 4.618 (457) .54 1.3 2.0 2.7 3.4 4.2 4.9 5.6 6.3 7.124 (610) .73 1.7 2.7 3.7 4.6 5.6 6.6 7.5 8.5 9.530 (762) .92 2.1 3.4 4.6 5.8 7.0 8.3 9.5 10.7 11.936 (914) 1.1 2.6 4.1 5.5 7.0 8.5 9.9 11.4 12.9 14.442 (1067) 1.3 3.0 4.7 6.5 8.2 9.9 11.6 13.4 15.1 16.848 (1219) 1.5 3.5 5.4 7.4 9.4 11.4 13.3 15.3 17.3 19.2

54 (1372) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.5 21.7

TYPE A DAMPER FREE AREA TYPE A DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.812 (305) .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.6 4.018 (457) .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.224 (610) .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.430 (762) .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.636 (914) .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.842 (1067) 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.048 (1219) 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2

54 (1372) 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4

60 (1524) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7

To determine pressure drop across opendamper, calculate free area velocity asshown, find velocity on curve and readacross for s.p. differential.

Free Area Velocity (fpm) =

Example: 1-36" x 24" Damper required for8,500 cfm. (Type A)

FAV = 85005 sq. ft.

= 1700 fpm

1700 fpm located on the ‘A’ curve shows apressure drop of .07 in. wg.

cfm = cubic feet per minutefpm = feet per minute velocityS.P. = static pressure in inches water gaugeFAV = Free Area Velocity

Imperial System ShownTo convert to SI (metric) system:

Multiply cfm by .4719 for liters per secondfpm by .00508 for meters per secondin. wg. by .2486 for kilopascalssq. ft. by .0929 for square meters

cfmFree Area

.40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.80

.901.0

.30

.10

.01

600

700

800

900

1000

1500

2000

3000

4000

5000

Free Area VFree Area Velocity (fpm)elocity (fpm)

FREE AREA VELOCITYFREE AREA VELOCITYV.S. ST.S. STATIC PRESSURE DROPTIC PRESSURE DROP

Static Static Pressure Pressure Drop Drop (in. wg.)(in. wg.)

TYPE 'A'TYPE 'A'

TYPE 'B'TYPE 'B'

TYPE 'C'TYPE 'C'

TYPE C DAMPERS HAVE FREE AREA EQUAL TONOMINAL DUCT AREA.

To calculate Free Area of round duct: DIAMETER2 x .00545 = Free Area (sq ft.)

Revised May 5, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Dynamic rated fire dampers as manufactured byNailor Industries, meeting or exceeding the following criteria: Fire dampers shall meet the requirements of NFPA 90A and shallbe manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999,including Dynamic Closure Test (formerly the Operation Test). Dampers shall be classified for dynamic closure against anairflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential (across closed damper).Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to label verifying the airflow and closurepressure ratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For usein dynamic systems". Dampers marked "For use in static systems only" are not acceptable.Each fire damper shall be complete with a 165°F (74°C) UL Listed fusible link. Fire dampers shall each include a steel sleeve ofappropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordance withdamper manufacturer’s instructions. Contractor shall provide and install an access door at each fire damper, of appropriate sizeto allow for inspection, testing and fusible link replacement. Data submitted for approval shall include confirmation of ULqualifications in addition to manufacturer’s installation instructions. Each shipment of fire dampers shall include same installationinstructions. Dynamic rated fire dampers shall be Nailor Industries Models D0110 (Type A), D0120 (Type B), D0130 (Type C).

Page 14: Fire Damper Nailor

D14

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SDYNAMIC FIRE DAMPERS • 1 1/2 HOUR

INTEGRAL SLEEVE DYNAMIC FIRE DAMPERS (1 1/2 HOUR LISTING)

FOR USE IN DYNAMIC SYSTEMS.Nailor integral sleeve fire dampers ensure proper damper mounting in sleeve and can be shipped direct tojob site for immediate installation, eliminating costly and inconvenient shop handling. All units areconstructed with 22 ga. (0.85) roll-formed G60 galvanized steel integral sleeve available in 12" (305), 14"(356) or 16" (406) length. Optional 'Quick-Set' retaining angles are available to complete the installationpackage.

Type 'A' – Blades and frame in the airstream.Model: D0114Min. size - 6" x 6" (152 x 152)Max. size - 24" x 24" (610 x 610)

Type 'CR' – Round transition collars. Blades partially in airstreamModel: D0134Min. size - 4" dia. (102)Max. size - 20" dia. (508)

Type 'B' – Blades out of airstream.Model: D0124Min. size - 6" x 4" (152 x 102)Max. size - 24" x 21" (610 x 533)

W

H

LW

H

A

L

D +2"

(51)

1"(25)

D + 2" (51)

D

L

TYPE A: MODEL D0114 - 12/14/16 TYPE B: MODEL D0124 - 12/14/16

TYPE CR: MODEL D0134 - 12/14/16CONSTRUCTION DETAILS:

INTEGRALSLEEVE/FRAME: 22 ga. (0.85) roll-formed G60 galvanized steel.

D01 x 4 x -12 Length 12" (305)D01 x 4 x -14 Length 14" (356)D01 x 4 x -16 Length 16" (406)

BLADES: Curtain type interlocking blades, 22 ga. (0.85)roll-formed G60 galvanized steel.

FUSIBLE LINK: 165°F (74°C) standard. UL Listed. 212°F (100°C) available.

BLADECLOSURE: Vertical and Horizontal mount.Stainless steel closure springs and galvanized steellocking ramps.

Damper Height (H) Dim. 'A'5" thru 17" (127 thru 432) 2" (51)18" thru 21" (457 thru 533) 3" (76)

Revised July 8, 2004

Page 15: Fire Damper Nailor

HOW TO SPECIFY

D15

CURTAIN FIRE DAMPERS

D15

D

DYNAMIC FIRE DAMPERS • 1 1/2 HOURCU

RTA

INFIR

ED

AM

PER

S

INTEGRAL SLEEVE DYNAMIC FIRE DAMPERS

MODELS: D0114 - 12/14/16D0124 - 12/14/16D0134 - 12/14/16

Revised September 8, 2004

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Dynamic rated fire dampers as manufactured byNailor Industries, meeting or exceeding the following criteria: Fire dampers shall meet the requirements of NFPA 90A and shallbe manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999,including Dynamic Closure Test (formerly the Operation Test). Dampers shall be classified for dynamic closure against anairflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential (across closed damper).Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to label verifying the airflow and closurepressure ratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For usein dynamic systems". Dampers marked "For use in static systems only" are not acceptable.Each fire damper shall be complete with a 165°F (74°C) UL Listed fusible link. In addition, each fire damper shall be providedfrom the factory in an integral 22 ga. (0.85) galvanized steel sleeve of (specifier select one) 12" (305), 14" (356) or 16" (406)in length complete with Nailor 'Quick-Set' retaining angles, to ensure proper installation in accordance with dampermanufacturer’s instructions. Contractor shall provide and install an access door at each fire damper, of appropriate size to allowfor inspection, testing and fusible link replacement. Data submitted for approval shall include confirmation of UL qualificationsin addition to manufacturer’s installation instructions. Each shipment of fire dampers shall include same installation instructions.Integral sleeve Dynamic rated fire dampers shall be Nailor Industries Models D0114-12 or 14 or 16 (Type A), D0124-12 or 14or 16 (Type B), D0134-12 or 14 or 16 (Type C).

Page 16: Fire Damper Nailor

D16

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

• HYBRID DESIGN WITHINTEGRAL SLEEVE

• FOR USE IN DYNAMICSYSTEMS

• 1 1/2 HOUR RATING• UL 555 CLASSIFIED• VERTICAL MOUNT

The D0100HY hybrid fire dampers are UL approved for use where local building codes require the protection of HVAC ductworkpenetrations in walls and partitions that have a fire resistance rating of up to 2 hours. The D0100HYs are classified for use indynamic "fans on" systems where the HVAC system remains operative in the event of a fire. Damper closure under airflow isassured.Integral sleeve fire dampers offer convenience and labor savings. The costly requirement to field or shop fabricate custom sleevesis eliminated and dampers can therefore ship directly from the manufacturer to the job site – saving time and money. Optional "Quick-Set" retaining angles complete the installation package. Factory fabricated, sized and shipped with damper, theyinstall quickly, provide further labor savings and eliminate the need for any field fabrication.

MODELS: D0114HY TYPE AD0124HY TYPE BD0134HY TYPE C

Model D0114HY

D0114HY D0124HY D0134HY(Type A) (Type B) (Type C)

SLEEVE/ 12" (305) long x 20 ga. 12" (305) long x 20 ga. 12" (305) long x 20 ga.ENCLOSURE: (1.01) standard 14" (1.01) standard 14" (1.01) standard 14"

(356) or 16" (406) (356) or 16" (406) (356) or 16" (406)long available long available; long available;

Type B duct connections Type C duct connections

FRAME: 5" (127) deep max. 5" (127) deep max. 5" (127) deep max.roll-formed G60 roll-formed G60 roll-formed G60galvanized steel galvanized steel galvanized steel

BLADES: Minimum 22 ga. Minimum 22 ga. Minimum 22 ga.(0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

G60 galvanized steel G60 galvanized steel G60 galvanized steel

FUSIBLE LINK: 165°F (74°C) standard 165°F (74°C) standard 165°F (74°C) standard(UL Listed) 212°F (100°C) available 212°F (100°C) available 212°F (100°C) available

MOUNTING: Vertical mount only Vertical mount only Vertical mount only

SIZES: See maximum sizes shown below sketches.For widths 36'' (914) and under, minimum heightis 49'' (1245) (Type A). For widths over 36'' (914),minimum height is 25'' (635) (Type A).For smaller sizes see Model Series D0100.

CONSTRUCTION DETAILS:

Type 'A' Model: D0114HYMax. size: 72" x 60" (1829 x 1524)

W

H

L

Page 17: Fire Damper Nailor

INTEGRAL SLEEVE HYBRID DYNAMIC FIRE DAMPERS

MODELS: D0114HYD0124HYD0134HY

D17

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

S

Type 'B'Model: D0124HYMax. size: 72" x 54" (1829 x 1372)

Type 'CR' – Round transition collars (shown)Type 'CO' - Oval transition collarsModel: D0134HYCR Max. size - 53" dia. (1346)CO Max. size - 70" x 53" (1778 x 1346)

Damper Height (H) Dim. 'A'22" thru 25" (559 thru 533) 2" (51)26" thru 35" (660 thru 889) 3" (76)36" thru 44" (914 thru 1118) 4" (102)45" thru 53" (1143 thru 1346) 5" (127)

54" (1372) 6" (152)

A

W

H

L

L

D +2"

(51)

1"(25)

D + 2" (51)

D

HOW TO SPECIFY

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Dynamic rated hybrid fire dampers as manufacturedby Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall meet the requirements of NFPA 90A andshall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June1999, including Dynamic Closure Test (formerly the Operation Test). Dampers shall be classified for dynamic closure againstan airflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential (across closed damper).Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to label verifying the airflow and closurepressure ratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For usein dynamic systems". Dampers marked "For use in static systems only" are not acceptable.Each fire damper shall be complete with a 165°F (74°C) UL Listed fusible link. Fire dampers shall each include a steel sleeveof appropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordancewith damper manufacturer’s instructions. Contractor shall provide and install an access door at each fire damper, of appropriatesize to allow for inspection, testing and fusible link replacement. Data submitted for approval shall include confirmation of ULqualifications in addition to manufacturer’s installation instructions. Each shipment of fire dampers shall include sameinstallation instructions. Dynamic rated hybrid fire dampers shall be Nailor Industries Models D0114HY (Type A), D0124HY(Type B) and D0134HY (Type C).

MODELS: D0114HY, D0124HY, D0134HY – 1 1/2 HOUR RATED

Page 18: Fire Damper Nailor

• STANDARD FRAME• FOR USE IN DYNAMIC

SYSTEMS• 3 HOUR RATING• UL 555 CLASSIFIED

The Nailor D0500 Series dynamic curtain fire dampers are UL/ULC approved for use where building codes require protection ofHVAC ductwork penetrations in walls, partitions or floors that have a fire resistance rating of 4 hours or less. Classified for use indynamic systems (max. 2000 fpm @ 4" w.g.) where the HVAC system remains operative in the event of a fire, the D0500 Seriesfeatures stainless steel closure springs for assured damper closure under airflow, corrosion resistant steel frame and blades forlasting performance, and choice of transition styles and factory installed sleeves to suit duct size, making installation fast andsimple.

MODELS: D0510 TYPE AD0520 TYPE BD0530 TYPE CR/COD0530 TYPE CSR

Model D0510

D18

CURTAIN FIRE DAMPERS

D18

D

DYNAMIC FIRE DAMPERS • 3 HOURCU

RTA

INFI

RE

DA

MPER

S

D0510 D0520 D0530 D0530 (Type A) (Type B) (Type CR/CO) (Type CSR)

FRAME: 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide,22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-

formed G60 formed G60 formed G60 formed G60 galvanized steel galvanized steel galvanized steel; galvanized steel;

out of airstream out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanized G60 galvanizedsteel steel steel

ENCLOSURE: Type B Type C Type CN/A 22 ga. (.085) Round or Oval Square or Rect.

galvanized steel 22 ga. (.085) 22 ga. (.085)galvanized steel galvanized steel

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available available

BLADE Stainless steel Stainless steel Stainless steel Stainless steelCLOSURE: closure springs closure springs closure springs closure springs

and galvanized and galvanized and galvanized and galvanizedsteel locking ramps steel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical Vertical Vertical Verticalor or or or

Horizontal Horizontal Horizontal Horizontal

AVAILABLE Galvanized steel; Galvanized steel; Galvanized steel; Galvanized steel;SLEEVE: Specify SL Specify SL Specify SL Specify SL

Option Option Option Option

CONSTRUCTION DETAILS:

VERTICAL MOUNT

TYPE A: MODEL D0510

HEI

GH

T =

NO

MIN

ALD

UC

T SI

ZE -

1/4"

(6)

INTERLOCKINGCURTAIN BLADES

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

4 1/4"

(108)

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

4 1/4" (108)

DU

CT

SIZE

- 1/

4" (6

)

3" (76)

STAINLESS STEELCLOSURE SPRING

CURTAIN BLADELOCKING RAMP

For MIN./MAX. UL SIZES see chart on page D9.

Revised May 5, 2005

Page 19: Fire Damper Nailor

D19

CURTAIN FIRE DAMPERS

D19

D

DYNAMIC FIRE DAMPERS • 3 HOURCU

RTA

INFIR

ED

AM

PER

S

PERFORMANCE DATA:Curtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for thedifferent damper types and static pressure losses for various velocities.

TYPE B: MODEL D0520

TYPE CR: MODEL D0530

TYPE CO: MODEL D0530

TYPE CSR WITH COLLAR(STANDARD):MODEL D0530

TYPE CSR WITHOUT COLLAR:

MODEL D0530

HOW TO SPECIFY

H =DUCT SIZE

+ 1/8" (3)

W = DUCT SIZE - 1/4" (6)

HH

W + 1 3/4" (44)

WW + 1 3/4" (44)

W

D + 1 3/4" (44)

D W + 1 3/4" (44)

WH

1"

TYPE B DAMPER FREE AREA TYPE B DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .17 .39 .62 .84 1.1 1.3 1.5 1.7 2.0 2.212 (305) .36 .83 1.3 1.8 2.3 2.7 3.2 3.7 4.1 4.618 (457) .54 1.3 2.0 2.7 3.4 4.2 4.9 5.6 6.3 7.124 (610) .73 1.7 2.7 3.7 4.6 5.6 6.6 7.5 8.5 9.530 (762) .92 2.1 3.4 4.6 5.8 7.0 8.3 9.5 10.7 11.936 (914) 1.1 2.6 4.1 5.5 7.0 8.5 9.9 11.4 12.9 14.442 (1067) 1.3 3.0 4.7 6.5 8.2 9.9 11.6 13.4 15.1 16.848 (1219) 1.5 3.5 5.4 7.4 9.4 11.4 13.3 15.3 17.3 19.2

54 (1372) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.5 21.7

TYPE A DAMPER FREE AREA TYPE A DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.812 (305) .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.6 4.018 (457) .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.224 (610) .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.430 (762) .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.636 (914) .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.842 (1067) 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.048 (1219) 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2

54 (1372) 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4

60 (1524) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7

To determine pressure drop across opendamper, calculate free area velocity asshown, find velocity on curve and readacross for s.p. differential.

Free Area Velocity (fpm) =

Example: 1-36” x 24” Damper required for8,500 cfm. (Type A)

FAV = 85005 sq. ft.

= 1700 fpm

1700 fpm located on the ‘A’ curve shows apressure drop of .07 in. wg.

cfm = cubic feet per minutefpm = feet per minute velocityS.P. = static pressure in inches water gaugeFAV = Free Area Velocity

Imperial System ShownTo convert to SI (metric) system:

Multiply cfm by .4719 for liters per secondfpm by .00508 for meters per secondin. wg. by .2486 for kilopascalssq. ft. by .0929 for square meters

cfmFree Area

.40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.80

.901.0

.30

.10

.01

600

700

800

900

1000

1500

2000

3000

4000

5000

Free Area VFree Area Velocity (fpm)elocity (fpm)

FREE AREA VELOCITYFREE AREA VELOCITYV.S. ST.S. STATIC PRESSURE DROPTIC PRESSURE DROP

Static Static Pressure Pressure Drop Drop (in. wg.)(in. wg.)

TYPE 'A'TYPE 'A'

TYPE 'B'TYPE 'B'

TYPE 'C'TYPE 'C'

For overall damper dimensions see sizing chart on page D48.

TYPE C DAMPERS HAVE FREE AREA EQUAL TONOMINAL DUCT AREA.

To calculate Free Area of round duct: DIAMETER2 x .00545 = Free Area (sq ft.)

Revised May 6, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Dynamic 3 hour rated fire dampers as manufacturedby Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall meet the requirements of NFPA 90A andshall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June1999, including Dynamic Closure Test (formerly the Operation Test). Dampers shall be classified for dynamic closure againstan airflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential (across closed damper).Each fire damper shall bear a 3 hour fire resistance rating label, in addition to label verifying the airflow and closure pressureratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For use in dynamicsystems". Dampers marked "For use in static systems only" are not acceptable.Each fire damper shall be complete with a 165°F (74°C) UL Listed fusible link. Fire dampers shall each include a steel sleeve ofappropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordance withdamper manufacturer’s instructions. Contractor shall provide and install an access door at each fire damper, of appropriate size toallow for inspection, testing and fusible link replacement. Data submitted for approval shall include confirmation of UL qualificationsin addition to manufacturer’s installation instructions. Dynamic 3 hour rated fire dampers shall be Nailor Industries Models D0510(Type A), D0520 (Type B), D0530 (Type C).

Page 20: Fire Damper Nailor

• INTEGRAL SLEEVE FOR USE WITH GRILLE

• FOR USE IN DYNAMIC SYSTEMS

• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor D0100G Series dynamic integral sleeve fire dampers are designed for use in conjunction with a steel grille whenductwork terminates at an opening in a fire rated wall/partition. The D0100G Series is 1 1/2 hour UL labeled for use in 2 hour fireseparations or less and are classified for use in dynamic systems (max. 2000 fpm @ 4" w.g.) where the HVAC system remainsoperative in the event of a fire alarm. This unique product utilizes special grille mounting flanges on the sleeve that eliminate therequirement for unsightly retaining angles which commonly protrude from behind the grille. The steel grille installs over andcompletely conceals the mounting flanges for a clean, aesthetic finish. The fire damper is offset in the sleeve to accommodate asingle or double deflection supply air grille, single deflection supply air register or a return air grille or register. Countersunk screwholes in the the grille frame will match to mounting flanges when Nailor grille is ordered in conjunction with the damper assembly.The D0100G dampers feature stainless steel closure springs for assured closure under airflow, corrosion resistant steel frame,blades and sleeve for lasting performance, and a choice of transition styles and accessories making installation fast and simple.

MODELS: D0110G TYPE AD0120G TYPE BD0130G TYPE CR

Model D0110G

D20

CURTAIN FIRE DAMPERS

D20

D

DYNAMIC FIRE DAMPERS • GRILLE TABSCU

RTA

INFI

RE

DA

MPER

S

D0110G D0120G D0130G (Type A) (Type B) (Type CR)

FRAME: 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide,22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-

formed G60 formed G60 formed G60 galvanized steel galvanized steel galvanized steel;

out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanizedsteel steel

STANDARD 12" (305) x 22 ga. (0.85) 12" (305) x 22 ga. (0.85) 12" (305) x 22 ga. (0.85) SLEEVE: galvanized steel galvanized steel galvanized steel

with 3/4" (19) wide with 3/4" (19) wide with 3/4" (19) widegrille mounting flanges grille mounting flanges; grille mounting flanges;

Type B duct connection Type C duct connectionon one end on one end

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available

BLADE Stainless steel Stainless steel Stainless steelCLOSURE: closure springs closure springs closure springs

and galvanized and galvanized and galvanizedsteel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical or Horizontal Vertical or Horizontal Vertical or Horizontal

OPTIONAL Steel grille with correctly Steel grille with correctly Steel grille with correctlyGRILLE: located countersunk located countersunk located countersunk

screw holes; Select screw holes; Select screw holes; Selectmodel from Nailor Air model from Nailor Air model from Nailor AirDistribution Catalog Distribution Catalog Distribution Catalog

CONSTRUCTION DETAILS:

H

W

LS

4 1/4"(108)

H

4 3/4"(121)

4 1/4"(108)

3"(76)

12" (305)

TYPE A: MODEL D0110GFor MIN./MAX. UL SIZES see chart on page D9.

Revised May 5, 2005

Page 21: Fire Damper Nailor

D21

CURTAIN FIRE DAMPERS

D21

D

DYNAMIC FIRE DAMPERS • GRILLE TABSCU

RTA

INFIR

ED

AM

PER

S

OPTIONAL DAMPER / SLEEVES:

HOW TO DETERMINE SLEEVE LENGTH / DAMPER POSITION:

To calculate sleeve length, determine wall thickness and add 3" (76) minimum for rear retaining angles and ductconnection. Front of assembly fits flush with wall. Damper offset (dimension 'S') should accommodate grille selectiondepth, but fire damper position must remain within plane of wall.

FOR NON-STANDARD SLEEVE LENGTH, SPECIFY LENGTH.

FOR NON STANDARD DAMPER POSITION IN SLEEVE, SPECIFY DIMENSION 'S'.

OTHER OPTIONS / ACCESSORIES:

CODE DESCRIPTION

QUICK-SET ANGLE QS1 Single set of "Quick-Set" Retaining Angles for Rear Side

HEMMED SLEEVE HM1 Sleeve End Hemmed for Slip and Drive Connection

MICROSWITCH MS 24V MicroswitchMSE 120/24V Microswitch with Enclosure

DUCT 'A'HEIGHT (H) DIM.

6" thru 17" 2"(152 - 432) (51)

18" thru 21" 3"(457 - 533) (76)

4 3/4"(121)

4 1/4"(108)

S3" (76) STD.

12" (305)

A

H

4 3/4"(121)

4 1/4"(108)

12" (305)

DIA.

D +

2" (

51)

S3" (76) STD.

TYPE B DUCT CONNECTION ONONE END: MODEL D0120G

TYPE CR ROUND DUCT CONNECTIONON ONE END: MODEL D0130G

HOW TO SPECIFY

Revised July 8, 2004

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Dynamic rated fire dampers for use with grilles, asmanufactured by Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall meet the requirements ofNFPA 90A and shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for Fire Dampers - SixthEdition, June 1999, including Dynamic Closure Test (formerly the Operation Test). Dampers shall be classified for dynamicclosure against an airflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential (across closed damper).Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to label verifying the airflow and closurepressure ratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For usein dynamic systems". Dampers marked "For use in static systems only" are not acceptable.Each fire damper shall be complete with a 165°F (74°C) UL Listed fusible link. In addition, each fire damper shall be providedfrom the factory in an integral 22 ga. (0.85) galvanized steel sleeve with one 'Quick-Set' retaining angle and grille mountingflanges specially designed for use with a steel grille of minimum 26 ga. (.5) construction. Fire damper shall be offset in thesleeve an appropriate amount to maintain positioning of fire damper within plane of wall. Data submitted for approval shallinclude confirmation of UL qualifications in addition to manufacturer’s installation instructions. Fire dampers shall be installedin accordance with manufacturer’s instructions, and same installation instructions shall be included with each fire dampershipment. Dynamic rated fire dampers for use with steel grilles shall be Nailor Industries Models D0110G (Type A), D0120G(Type B transition), D0130G (Type C transition).

Page 22: Fire Damper Nailor

D22

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

• INTEGRAL "OUT OF WALL"SLEEVE FOR USE WITH GRILLE

• FOR USE IN DYNAMIC SYSTEMS

• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

MODEL: D0110GOW

Model D0110GOW

DYNAMIC FIRE DAMPERS • OUT OF WALL

The Model D0110GOW is an "out of wall or floor" integral sleeve dynamic curtain type fire damper, specifically designed for supplyor return ducts that terminate at a grille or register. For use where local building codes require the protection of HVAC ductworkpenetrations in walls, partitions or floors that have a fire resistance rating of up to two hours.

The D0110GOW design provides sufficient damper off-set to accommodate most commercial grille/register designs while ensuring anapproved installation in any fire partition or wall no matter how narrow. This model is particularly suited for use in common steel studdrywall partition designs, as narrow as 3 1/2" (89) where a traditional "within the plane of the wall" fire damper installation is not possible.

For MIN./MAX. UL SIZES see chart onpage D9.

FIRE DAMPER

THERMALINSULATION

H

WOPTIONAL

GRILLE/REGISTER

3/4" (19)FLANGE

MODEL D0110GOW

Revised May 5, 2005

D0110GOW (Type A)

FRAME: 4 1/4" (108) wide,22 ga. (0.85) roll-

formed G60galvanized steel

BLADES: Curtain type, inter-locking blades, 22 ga.

(0.85) roll-formedG60 galvanized

steel

STANDARD 10" (254) x 16 ga. (1.6) SLEEVE: galvanized steel

with 3/4" (19) widegrille mounting flanges;

intumescent thermalinsulation

on all four sides

FUSIBLE LINK: 165°F (74°C) Std.(UL Listed) 212°F (100°C)

available

BLADE Stainless steel closureCLOSURE: springs and galvanized

steel locking ramps

MOUNTING: Vertical or Horizontal

OPTIONAL Steel or aluminumGRILLE: grille or register;

Select model fromNailor Air Distribution

Catalog

CONSTRUCTION DETAILS:

Page 23: Fire Damper Nailor

D23

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SDYNAMIC FIRE DAMPERS • OUT OF WALL

MODEL: D0110GOW

VERTICAL MOUNT HORIZONTAL MOUNT

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Dynamic rated "out of wall" fire dampers for use withgrilles, as manufactured by Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall meet therequirements of NFPA 90A and shall be manufactured, tested and labeled in accordance with UL 555 Safety Standard for FireDampers - Sixth Edition, June 1999, including Dynamic Closure Test (formerly the Operation Test). Dampers shall be classifiedfor dynamic closure against an airflow velocity of 2000 fpm (10.16 m/s) at 4" w.g. (1 kPa) static pressure differential (acrossclosed damper).Each fire damper shall bear a UL 1 1/2 hour fire resistance rating label in addition to a label verifying the airflow and closurepressure ratings as established by the Dynamic Closure Test. Each fire damper shall also be marked with the words "For usein dynamic systems". Dampers marked "For use in static systems only" are not acceptable.Each fire damper shall be complete with a 165°F (74°C) UL Listed fusible link. In addition, each fire damper shall be providedfrom the factory in an integral 16 ga. (1.6) galvanized steel insulated sleeve with grille mounting flanges.Data submitted for approval shall include confirmation of UL qualifications in addition to manufacturer’s installation instructions.Fire dampers shall be installed in accordance with manufacturer’s instructions and same installation instructions shall beincluded with each fire damper shipment. Dynamic rated "out of wall" fire dampers shall be Nailor Industries ModelD0110GOW.

HOW TO SPECIFY

10" (254) STD. SLEEVE

4" (102)MAX.

3/4" (19) MIN. FLANGE

DUCTCONNECTION

10" (254) STD.

SLEEVE

3/4" (19) MIN. FLANGE

DUCTCONNECTION

REAR RETAININGANGLES (ALTERNATEMOUNTING METHOD)

4" (102)MAX.

Revised April 25, 2005

Page 24: Fire Damper Nailor

D24

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SDYNAMIC FIRE DAMPERS • SELECTION PROCEDURE

SELECTION PROCEDUREFOR DYNAMIC FIRE DAMPERS

Underwriters Laboratories Inc. Standard for Safety UL 555 evaluates fire dampers for use as either: (A) Fire dampersfor static systems – for HVAC systems that are automatically shut down in the event of a fire or for air transfer openingsin walls or partitions; (B) Fire dampers for dynamic systems – for HVAC systems that are operated in the event of a fire.Dynamic Fire Dampers are therefore required to close under airflow.All fire dampers must be labeled to indicate if they are to be used in static or dynamic systems. For dynamic rateddampers, this label must also indicate the maximum rated velocity through the open damper, and the maximumpressure differential across the closed damper.To attain approval for use in a dynamic system, UL Standard 555 requires that test dampers close three times (manuallyreleased) against their rated flow and shut-off pressure at ambient air temperature before heat is introduced to causethe fusible link to melt and close the damper one final time.All Nailor dynamic curtain type fire dampers have been tested to 2000 fpm (10.16 m/s) and 4" w.g. (1 kPa) staticpressure.

EXAMPLE #1: SINGLE SECTION FIRE DAMPERTo determine the maximum allowable airflow through the following damper:Type A damper 24" x 24". The maximum rated velocity is 2000 fpm. 24" x 24" is 4 sq. ft. (Width in inches x Height in inches dividedby 144 = sq. ft.), therefore, maximum allowable airflow is 2000 fpm x 4 sq. ft. = 8,000 cfm.

Check the maximum system pressure that could occur against a closed damper. Nailor dynamic fire dampers have been tested andare rated to close against 4" w.g.

36" (914)

32"(813)

Revised February 17, 2005

EXAMPLE #2: MULTIPLE SECTION FIRE DAMPERTo determine the maximum allowable airflow through the following multi-section damper assembly: Type A damper 36" x 32" opening (the assembly will consist of four 18" x 16" dampers); The maximum rated velocity is 2000 fpm.36" x 32" is 8 sq. ft., therefore, 2000 fpm x 8 sq. ft. = 16000 cfm. This is the maximum allowable airflow that may be passed throughthe 36" x 32" opening.

Check the maximum system pressure that could occur against a closed damper. Nailor dynamic fire dampers have been tested andare rated to close against 4" w.g.

24" (610)

24"(610)

Page 25: Fire Damper Nailor

D25

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SDYNAMIC FIRE DAMPERS

Revised February 17, 2005

www.nai lor.com

Notes:

Page 26: Fire Damper Nailor

• STANDARD FRAME• FOR USE IN STATIC

SYSTEMS• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor 0100 Series curtain fire dampers, for use in static "fans off" systems where the HVAC system shuts down in the eventof a fire, are UL/ULC approved to provide protection of HVAC ductwork penetrations in walls, partitions or floors that have a fireresistance rating of 2 hours or less. The 0100 Series features corrosion resistant steel frame and blades for performance that lasts,and a choice of transition styles and factory installed sleeves to suit duct size, making installation fast and simple.

MODELS: 0110 / 0114 TYPE A0120 / 0124 TYPE B0130 / 0134 TYPE CR/CO0140 TYPE CSR

Model 0110

D26

CURTAIN FIRE DAMPERS

D26

D

STATIC FIRE DAMPERS • 1 1/2 HOURCU

RTA

INFI

RE

DA

MPER

S

0110 0120 0130 0140 (Type A) (Type B) (Type CR/CO) (Type CSR)

FRAME: 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide,

22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-formed G60 formed G60 formed G60 formed G60

galvanized steel galvanized steel galvanized steel; galvanized steel;out of airstream out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanized G60 galvanizedsteel steel steel

ENCLOSURE: Type B Type C Type C

N/A 22 ga. (.085) Round or Oval Square or Rect.galvanized steel 22 ga. (.085) 22 ga. (.085)

galvanized steel galvanized steel

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available available

BLADE Vertical mount; gravity Vertical mount; gravity Vertical mount; gravity Vertical mount; gravityCLOSURE: Horizontal mount; Horizontal mount; Horizontal mount; Horizontal mount;

stainless steel closure stainless steel closure stainless steel closure stainless steel closuresprings with galvanized springs with galvanized springs with galvanized springs with galvanized

steel locking ramps steel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical Vertical Vertical Verticalor or or or

Horizontal Horizontal Horizontal Horizontal

INTEGRALSLEEVE: See Model See Model See Model22 ga (.085) x12"

(305) long 0114-12 O124-12 O134-12 Specify22 ga (.085) x14" SL

(356) long 0114-14 O124-14 O134-14 Option22 ga (.085) x16"

(406) long 0114-16 O124-16 O134-16

CONSTRUCTION DETAILS:

MODEL 0110V – VERTICAL MOUNT

TYPE A: MODEL 0110

HEIG

HT =

NOM

INAL

DUCT

SIZ

E - 1

/4" (

6)

INTERLOCKINGCURTAIN BLADES

3" (76)

MODEL 0110H – HORIZONTAL MOUNT

STAINLESS STEELCLOSURE SPRING

CURTAIN BLADELOCKING RAMP

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

4 1/4"

(108)

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

4 1/4" (108)

DUCT

SIZ

E - 1

/4" (

6)

For MIN./MAX. UL SIZES see chart on page D10.

Revised May 5, 2005

Page 27: Fire Damper Nailor

D27

CURTAIN FIRE DAMPERS

D27

D

STATIC FIRE DAMPERS • 1 1/2 HOURCU

RTA

INFIR

ED

AM

PER

S

TYPE B DAMPER FREE AREA TYPE B DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .17 .39 .62 .84 1.1 1.3 1.5 1.7 2.0 2.212 (305) .36 .83 1.3 1.8 2.3 2.7 3.2 3.7 4.1 4.618 (457) .54 1.3 2.0 2.7 3.4 4.2 4.9 5.6 6.3 7.124 (610) .73 1.7 2.7 3.7 4.6 5.6 6.6 7.5 8.5 9.530 (762) .92 2.1 3.4 4.6 5.8 7.0 8.3 9.5 10.7 11.936 (914) 1.1 2.6 4.1 5.5 7.0 8.5 9.9 11.4 12.9 14.442 (1067) 1.3 3.0 4.7 6.5 8.2 9.9 11.6 13.4 15.1 16.848 (1219) 1.5 3.5 5.4 7.4 9.4 11.4 13.3 15.3 17.3 19.2

54 (1372) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.5 21.7

TYPE A DAMPER FREE AREA TYPE A DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.812 (305) .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.6 4.018 (457) .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.224 (610) .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.430 (762) .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.636 (914) .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.842 (1067) 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.048 (1219) 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2

54 (1372) 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4

60 (1524) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7

To determine pressure drop across opendamper, calculate free area velocity asshown, find velocity on curve and readacross for s.p. differential.

Free Area Velocity (fpm) =

Example: 1-36” x 24” Damper required for8,500 cfm. (Type A)

FAV = 85005 sq. ft.

= 1700 fpm

1700 fpm located on the ‘A’ curve shows apressure drop of .07 in. wg.

cfm = cubic feet per minutefpm = feet per minute velocityS.P. = static pressure in inches water gaugeFAV = Free Area Velocity

Imperial System ShownTo convert to SI (metric) system:

Multiply cfm by .4719 for liters per secondfpm by .00508 for meters per secondin. wg. by .2486 for kilopascalssq. ft. by .0929 for square meters

cfmFree Area .40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.80

.901.0

.30

.10

.01

600

700

800

900

1000

1500

2000

3000

4000

5000

Free Area VFree Area Velocity (fpm)elocity (fpm)

FREE AREA VELOCITYFREE AREA VELOCITYV.S. ST.S. STATIC PRESSURE DROPTIC PRESSURE DROP

Static Static Pressure Pressure Drop Drop (in. wg.)(in. wg.)

TYPE 'A'TYPE 'A'

TYPE 'B'TYPE 'B'

TYPE 'C'TYPE 'C'

PERFORMANCE DATA:Curtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for thedifferent damper types and static pressure losses for various velocities.

TYPE C DAMPERS HAVE FREE AREA EQUAL TO NOMINAL DUCT AREA.

To calculate Free Area of round duct: DIAMETER2 x .00545 = Free Area (sq ft.)

HOW TO SPECIFY

TYPE B: MODEL 0120

TYPE CR: MODEL 0130

TYPE CO: MODEL 0130

TYPE CSR WITH COLLAR(STANDARD):MODEL 0140

TYPE CSR WITHOUT COLLAR:

MODEL 0140

H =DUCT SIZE

+ 1/8" (3)

W =DUCT SIZE - 1/4" (6)

HH

W + 1 3/4" (44)

WW + 1 3/4" (44)

W

D + 1 3/4" (44)

D W + 1 3/4" (44)

WH

1"

For overall damper dimensions see sizing chart on page D48.

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, fire dampers as manufactured by Nailor Industries,meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordance with UL 555Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have 1 1/2 hour fire resistance rating. Each fire dampershall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampers shall be suitablyconstructed for vertical or horizontal installation as required for each specific location.Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link. Firedampers shall each include a steel sleeve of appropriate length/gauge and retaining angles, supplied by damper manufacturerto ensure proper installation in accordance with damper manufacturer’s instructions. Contractor shall provide and install anaccess door at each fire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Informationsubmitted for approval shall include confirmation of UL qualifications, pressure drop data and manufacturer’s installationinstructions. Each shipment of fire dampers shall include same installation instructions. Fire dampers shall be Nailor IndustriesModels 0110 (Type A), 0120 (Type B), 0130 (Type C).

Revised May 5, 2005

Page 28: Fire Damper Nailor

D28

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SSTATIC FIRE DAMPERS • 1 1/2 HOUR

INTEGRAL SLEEVE STATIC FIRE DAMPERS (1 1/2 HOUR LISTING)

FOR USE IN STATIC SYSTEMS.Nailor integral sleeve fire dampers ensure proper damper mounting in sleeve and can be shipped direct tojob site for immediate installation, eliminating costly and inconvenient shop handling. All units areconstructed with 22 ga. (0.85) roll-formed G60 galvanized steel integral sleeve available in 12" (305), 14"(356) or 16" (406) length. Optional 'Quick-Set' retaining angles are available to complete the installationpackage.

Type 'CR' – Round transition collars. Blades partially in airstream.

Models: 0134V Vertical and 0134H HorizontalMin. size - Vertical 3" dia. (76)

Horizontal 4" dia. (102)Max. size - Vertical or Horizontal 42" dia. (1067)

D +2"

(51)

1"(25)

D + 2" (51)

D

L

TYPE C: MODEL 0134 - 12/14/16CONSTRUCTION DETAILS:

INTEGRALSLEEVE/FRAME: 22 ga. (0.85) roll-formed G60 galvanized steel.

01 x 4 x -12 Length 12" (305)01 x 4 x -14 Length 14" (356)01 x 4 x -16 Length 16" (406)

BLADES: Curtain type interlocking blades, 22 ga. (0.85)roll-formed G60 galvanized steel.

FUSIBLE LINK: 165°F (74°C) standard. UL Listed. 212°F (100°C) available.

BLADECLOSURE: Vertical mount model; gravity.Horizontal mount models are equipped withstainless steel closure springs and galvanized steellocking ramps.

Type 'A' – Blades and frame in the airstream.Models: 0114V Vertical and 0114H HorizontalMin. size - Vertical or Horizontal 4" x 4" (102 x 102)Max. size - Vertical or Horizontal 48" x 48" (1219 x 1219)

Type 'B' – Blades out of airstream.Models: 0124V Vertical and 0124H HorizontalMin. size - Vertical 4" x 3" (102 x 76)

Horizontal 4" x 4" (102 x 102)Max. size - Vertical or Horizontal 48" x 43" (1219 x 1092)

Damper Height (H) Dim. 'A'5" thru 17" (127 thru 432) 2" (51)18" thru 27" (457 thru 686) 3" (76)28" thru 36"(711 thru 914) 4" (102)

37" thru 43" (940 thru 1092) 5" (127)

W

H

L

W

H

A

L

TYPE A: MODEL 0114 - 12/14/16 TYPE B: MODEL 0124 - 12/14/16

Revised February 17, 2005

Page 29: Fire Damper Nailor

HOW TO SPECIFY

D29

CURTAIN FIRE DAMPERS

D29

D

STATIC FIRE DAMPERS • 1 1/2 HOURCU

RTA

INFIR

ED

AM

PER

S

INTEGRAL SLEEVE STATIC FIRE DAMPERS

MODELS: 0114 - 12/14/160124 - 12/14/160134 - 12/14/16

Revised April 26, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, integral sleeve fire dampers as manufactured byNailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled inaccordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 1 1/2 hour fireresistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mountingposition. Fire dampers shall be suitably constructed for vertical or horizontal installation as required for each specific location.Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link. Inaddition, each fire damper shall be provided from the factory in an integral 22 ga. (0.85) galvanized steel sleeve of (specifierselect one) 12" (305), 14" (356) or 16" (406) in length complete with Nailor 'Quick-Set' retaining angles, to ensure properinstallation in accordance with damper manufacturer’s instructions. Contractor shall provide and install an access door at eachfire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Information submitted for approvalshall include confirmation of UL qualifications, pressure drop data, and manufacturer’s installation instructions. Each shipmentof fire dampers shall include same installation instructions. Integral sleeve fire dampers shall be Nailor Industries Models 0114-12 or 14 or 16 (Type A), 0124-12 or 14 or 16 (Type B), 0134-12 or 14 or 16 (Type C).

Page 30: Fire Damper Nailor

• THINLINE FRAME• FOR USE IN STATIC

SYSTEMS • 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor 0200 Series Thinline curtain fire dampers are UL/ULC approved for use where building codes require the protection ofHVAC ductwork penetrations in walls, partitions or floors that have a fire resistance rating of 2 hours or less. The 0200 Series isclassified for use only in static "fans off" systems where the HVAC system is automatically shut down in the event of a fire alarm.The 0200 Series Thinline dampers are only 2" (51) deep making them ideal for installation in narrow fire rated partitions, transferduct openings, behind grilles or in any other application where space is limited. The 0200 Series feature corrosion resistant steelframe and blades for lasting performance, and choice of transition styles and factory installed sleeves to suit duct size, makinginstallation fast and simple.

MODELS: 0210 TYPE A0220 TYPE B0230 TYPE CR/CO0240 TYPE CSR

Model 0210

D30

CURTAIN FIRE DAMPERS

D30

D

STATIC FIRE DAMPERS • THINLINE • 1 1/2 HOURCU

RTA

INFI

RE

DA

MPER

S

0210 0220 0230 0240 (Type A) (Type B) (Type CR/CO) (Type CSR)

FRAME: 2" (51) wide, 2" (51) wide, 2" (51) wide, 2" (51) wide,

22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-formed G60 formed G60 formed G60 formed G60

galvanized steel galvanized steel galvanized steel; galvanized steel;out of airstream out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanized G60 galvanizedsteel steel steel

ENCLOSURE: Type B Type C Type CN/A 22 ga. (.085) Round or Oval Square or Rect.

galvanized steel 22 ga. (.085) 22 ga. (.085)galvanized steel galvanized steel

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available available

BLADE Vertical mount; gravity Vertical mount; gravity Vertical mount; gravity Vertical mount; gravityCLOSURE: Horizontal mount; Horizontal mount; Horizontal mount; Horizontal mount;

stainless steel closure stainless steel closure stainless steel closure stainless steel closuresprings with galvanized springs with galvanized springs with galvanized springs with galvanized

steel locking ramps steel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical Vertical Vertical Verticalor or or or

Horizontal Horizontal Horizontal Horizontal

AVAILABLE Galvanized steel; Galvanized steel; Galvanized steel; Galvanized steel;SLEEVE: Specify SL Specify SL Specify SL Specify SL

Option Option Option Option

CONSTRUCTION DETAILS:

MODEL 0210V – VERTICAL MOUNT

TYPE A: MODEL 0210

HEIGHT =NOMINAL

DUCTSIZE -1/4" (6)

INTERLOCKINGCURTAIN BLADES

MODEL 0210H – HORIZONTAL MOUNT

STAINLESS STEELCLOSURE SPRING

CURTAIN BLADELOCKING RAMP

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

2" (51)

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

DU

CT

SIZE

- 1/

4" (6

)

2" (51)

For MIN./MAX. UL SIZES see chart on page D10.

Revised May 5, 2005

Page 31: Fire Damper Nailor

D31

CURTAIN FIRE DAMPERS

D31

D

STATIC FIRE DAMPERS • THINLINE • 1 1/2 HOURCU

RTA

INFIR

ED

AM

PER

S

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

2" (51)

H =DUCTSIZE +1/8" (3) H

H

W + 1 3/4" (44)

WW + 1 3/4" (44)

W W + 1 3/4" (44)

WH

D + 1 3/4" (44)

D

1"

For overall damper dimensions, see sizing chart on page D49.

PERFORMANCE DATA:Curtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for thedifferent damper types and static pressure losses for various velocities.

TYPE A THINLINE DAMPER FREE AREA TYPE A THINLINE DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

6 12 18 24 30 36 40(152) (305) (457) (610) (762) (914) (1016)

6 (152) .12 .27 .44 .59 .75 .94 1.0212 (305) .27 .61 .93 1.36 1.7 2.1 2.418 (457) .42 .94 1.5 2.2 2.7 3.4 3.724 (610) .55 1.29 2.1 3.0 3.7 4.5 4.930 (762) .71 1.65 2.6 3.8 4.3 5.7 6.336 (914) .86 2.1 3.2 4.6 5.7 7.0 7.740 (1067) .93 2.3 3.5 5.1 6.3 7.6 8.848 (1219) 1.14 2.7 4.3 6.0 7.7 9.4

54 (1372) 1.32 3.1 4.9 6.9 8.8 10.7

60 (1524) 1.51 3.5 5.5 7.7 9.9 11.8

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

TYPE C DAMPERS HAVE FREE AREA EQUAL TO NOMINAL DUCT AREA.

To calculate Free Area of round duct: DIAMETER2 x .00545 = Free Area (sq ft.)

TYPE B THINLINE DAMPER FREE AREA TYPE B THINLINE DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 40(152) (305) (457) (610) (762) (914) (1016)

6 (152) .15 .32 .52 .69 .88 1.09 1.1712 (305) .31 .70 1.07 1.55 1.95 2.4 2.718 (457) .47 1.05 1.7 2.5 3.05 3.8 4.224 (610) .62 1.44 2.3 3.4 4.2 5.1 5.630 (762) .80 1.84 2.9 4.3 4.9 6.5 7.236 (914) .95 2.33 3.6 5.1 6.4 7.840 (1067) 1.0 2.5 3.8 5.6 7.0 8.548 (1219) 1.3 3.1 4.8 6.8 8.6 10.4

.40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.80

.901.0

.30

.10

.01

600

700

800

900

1000

1500

2000

3000

4000

5000

Free Area VFree Area Velocity (fpm)elocity (fpm)

FREE AREA VELOCITYFREE AREA VELOCITYV.S. ST.S. STATIC PRESSURE DROPTIC PRESSURE DROP

Static Static Pressure Pressure Drop Drop (in. wg.)(in. wg.)

TYPE 'A'TYPE 'A'

TYPE 'B'TYPE 'B'

TYPE 'C'TYPE 'C'

To determine pressure drop across opendamper, calculate free area velocity asshown, find velocity on curve and readacross for s.p. differential.

Free Area Velocity (fpm) =

Example: 1-36" x 36" Damper required for14,000 cfm. (Type A)

FAV = 14,0007 sq. ft.

= 2000 fpm

2000 fpm located on the ‘A’ curve shows apressure drop of .12 in. wg.

cfm = cubic feet per minutefpm = feet per minute velocityS.P. = static pressure in inches water gaugeFAV = Free Area Velocity

Imperial System ShownTo convert to SI (metric) system:

Multiply cfm by .4719 for liters per secondfpm by .00508 for meters per secondin. wg. by .2486 for kilopascalssq. ft. by .0929 for square meters

cfmFree Area

TYPE B: MODEL 0220

TYPE CR: MODEL 0230

TYPE CO: MODEL 0230

TYPE CSR WITH COLLAR(STANDARD):MODEL 0240

TYPE CSR WITHOUT COLLAR:

MODEL 0240

HOW TO SPECIFY

Revised May 5, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Thinline fire dampers as manufactured by NailorIndustries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordancewith UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have 1 1/2 hour fire resistance rating. Eachfire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampers shallbe suitably constructed for vertical or horizontal installation as required for each specific location.Thinline style fire damper frame shall be a maximum of 2" (51) in width, roll-formed from G60 galvanized steel. Blades shallbe Thinline type, roll-formed G60 galvanized steel. Each fire damper shall be complete with a (specifier select one) 165°F(74°C) or 212°F (100°C) UL Listed fusible link. Fire dampers shall each include a steel sleeve of appropriate length/gauge andretaining angles, supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer’sinstructions. Contractor shall provide and install an access door at locations where the fire damper cannot be accessed throughgrille or duct end opening, to allow for inspection, testing and fusible link replacement. Information submitted for approval shallinclude confirmation of UL qualifications, pressure drop data and manufacturer’s installation instructions. Each shipment of firedampers shall include same installation instructions. Thinline fire dampers shall be Nailor Industries Models 0210 (Type A),0220 (Type B), 0230 (Type C).

Page 32: Fire Damper Nailor

• WIDE FRAME• FOR USE IN STATIC

SYSTEMS• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor Model 0310 Wide Frame curtain fire damper is UL/ULC approved for use where local building codes require theprotection of HVAC ductwork penetrations in walls, partitions or floors that have a fire rating of 2 hours or less. The 0310 isclassified for use only in static "fans off" systems where the HVAC system is automatically shut down in the event of a fire alarm.

The 6" (152) wide frame design with 4 3/4" (121) blades, reduces the number of blades required in the curtain stack, thusincreasing the free area and reducing the pressure drop across the damper compared to standard Type A fire dampers. Theconstruction features corrosion resistant steel blades and frame designed for lasting performance, and available factory installedsleeves for fast, simple installation.

MODEL: 0310 TYPE A

Model 0310

D32

CURTAIN FIRE DAMPERS

D32

D

STATIC FIRE DAMPERS • WIDE FRAME • 1 1/2 HOURCU

RTA

INFI

RE

DA

MPER

S

HEI

GH

T =

NO

MIN

ALD

UC

T SI

ZE -

1/4"

(6)

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

6"

(152)

TYPE A: MODEL 0310

MODEL 0310V – VERTICAL MOUNT

INTERLOCKINGCURTAIN BLADES

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

DU

CT

SIZE

- 1/

4" (6

)

6" (152)

4 3/4" (121)

MODEL 0310H – HORIZONTAL MOUNT

STAINLESS STEELCLOSURE SPRING

CURTAIN BLADELOCKING RAMP

0310 (Type A)

FRAME: 6" (152) wide,22 ga. (0.85) roll

formed G60 galvanized steel

BLADES: Curtain type, inter-locking blades, 22 ga

(0.85) roll-formedG60 galvanized

steel

FUSIBLE LINK: 165°F (74°C) Std.(UL Listed) 212°F (100°C)

available

BLADE Vertical mount; gravityCLOSURE: Horizontal mount;

stainless steel closuresprings with galvanized

steel locking ramps

MOUNTING: Verticalor

Horizontal

AVAILABLE Galvanized steel;SLEEVE: Specify SL

Option

CONSTRUCTION DETAILS:

For MIN./MAX. UL SIZES see chart on page D11.

See Sizing Chart on page D50 for bladepack depth.

Revised May 5, 2005

Page 33: Fire Damper Nailor

HOW TO SPECIFY

D33

CURTAIN FIRE DAMPERS

D33

D

STATIC FIRE DAMPERS • WIDE FRAME • 1 1/2 HOURCU

RTA

INFIR

ED

AM

PER

S

MODEL: 0310

Revised April 26, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, wide frame fire dampers as manufactured by NailorIndustries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordancewith UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 1 1/2 hour fire resistance rating.Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampersshall be suitably constructed for vertical or horizontal installation as required for each specific location. Wide frame fire damperframe shall be 6" (152) in width, roll-formed from G60 galvanized steel. Blades shall be wide framed type to provide maximumfree area, roll-formed from G60 galvanized steel. Each fire damper shall be complete with a (specifier select one) 165°F(74°C) or 212°F (100°C) UL Listed fusible link. Fire dampers shall each include a steel sleeve of appropriate length/gauge andretaining angles, supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer’sinstructions. Contractor shall provide and install an access door at each fire damper, of appropriate size to allow for inspection,testing and fusible link replacement. Information submitted for approval shall include confirmation of UL qualifications andmanufacturer’s installation instructions. Each shipment of fire dampers shall include same installation instructions. Wide framefire dampers shall be Nailor Industries Model 0310.

Page 34: Fire Damper Nailor

• STANDARD FRAME• FOR USE IN STATIC

SYSTEMS• 3 HOUR RATING • UL 555 CLASSIFIED

The Nailor 0500 Series standard frame curtain fire dampers, for use in static "fans off" systems where the HVAC system shutsdown in the event of a fire, are UL/ULC approved to provide protection of HVAC ductwork penetrations in walls, partitions or floorsthat have a fire resistance rating of 4 hours or less. The 0500 Series features corrosion resistant steel frame and blades forperformance that will last, and a choice of transition styles and factory installed sleeves to suit duct size, making installation fastand simple.

MODELS: 0510 TYPE A0520 TYPE B0530 TYPE CR/CO0530 TYPE CSR

Model 0510

D34

CURTAIN FIRE DAMPERS

D34

D

STATIC FIRE DAMPERS • 3 HOURCU

RTA

INFI

RE

DA

MPER

S

0510 0520 0530 0530 (Type A) (Type B) (Type CR/CO) (Type CSR)

FRAME: 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide,22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-

formed G60 formed G60 formed G60 formed G60 galvanized steel galvanized steel galvanized steel; galvanized steel;

out of airstream out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanized G60 galvanizedsteel steel steel

ENCLOSURE: Type B Type C Type CN/A 22 ga. (.085) Round or Oval Square or Rect.

galvanized steel 22 ga. (.085) 22 ga. (.085)galvanized steel galvanized steel

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available available

BLADE Vertical mount; gravity Vertical mount; gravity Vertical mount; gravity Vertical mount; gravityCLOSURE: Horizontal mount; Horizontal mount; Horizontal mount; Horizontal mount;

stainless steel closure stainless steel closure stainless steel closure stainless steel closuresprings with galvanized springs with galvanized springs with galvanized springs with galvanized

steel locking ramps steel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical Vertical Vertical Verticalor or or or

Horizontal Horizontal Horizontal Horizontal

AVAILABLE Galvanized steel; Galvanized steel; Galvanized steel; Galvanized steel;SLEEVE: Specify SL Specify SL Specify SL Specify SL

Option Option Option Option

CONSTRUCTION DETAILS:

MODEL 0510V – VERTICAL MOUNT

TYPE A: MODEL 0510

HEI

GH

T =

NO

MIN

ALD

UC

T SI

ZE -

1/4"

(6)

INTERLOCKINGCURTAIN BLADES

3" (76)

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

4 1/4"

(108)

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

4 1/4" (108)

DU

CT

SIZE

- 1/

4" (6

)

For MIN./MAX. UL SIZES see chart on page D11.

Revised May 5, 2005

Page 35: Fire Damper Nailor

D35

CURTAIN FIRE DAMPERS

D35

D

STATIC FIRE DAMPERS • 3 HOURCU

RTA

INFIR

ED

AM

PER

S

H =DUCT SIZE

+ 1/8" (3)

W =DUCT SIZE - 1/4" (6)

HH

W + 1 3/4" (44)

WW + 1 3/4" (44)

W

D + 1 3/4" (44)

D W + 1 3/4" (44)

WH

1"

TYPE B DAMPER FREE AREA TYPE B DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .17 .39 .62 .84 1.1 1.3 1.5 1.7 2.0 2.212 (305) .36 .83 1.3 1.8 2.3 2.7 3.2 3.7 4.1 4.618 (457) .54 1.3 2.0 2.7 3.4 4.2 4.9 5.6 6.3 7.124 (610) .73 1.7 2.7 3.7 4.6 5.6 6.6 7.5 8.5 9.530 (762) .92 2.1 3.4 4.6 5.8 7.0 8.3 9.5 10.7 11.936 (914) 1.1 2.6 4.1 5.5 7.0 8.5 9.9 11.4 12.9 14.442 (1067) 1.3 3.0 4.7 6.5 8.2 9.9 11.6 13.4 15.1 16.848 (1219) 1.5 3.5 5.4 7.4 9.4 11.4 13.3 15.3 17.3 19.2

54 (1372) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.5 21.7

TYPE A DAMPER FREE AREA TYPE A DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 42 48 54 60 (152) (305) (457) (610) (762) (914) (1067) (1219)(1372) (1524)

6 (152) .14 .33 .52 .70 .89 1.1 1.3 1.5 1.7 1.812 (305) .31 .72 1.1 1.5 1.9 2.4 2.8 3.2 3.6 4.018 (457) .48 1.1 1.7 2.4 3.0 3.7 4.3 4.9 5.6 6.224 (610) .65 1.5 2.4 3.2 4.1 5.0 5.8 6.7 7.5 8.430 (762) .82 1.9 3.0 4.1 5.2 6.3 7.3 8.4 9.5 10.636 (914) .99 2.3 3.6 4.9 6.3 7.6 8.9 10.2 11.5 12.842 (1067) 1.2 2.7 4.2 5.8 7.3 8.8 10.4 11.9 13.4 15.048 (1219) 1.3 3.1 4.9 6.6 8.4 10.2 11.9 13.7 15.5 17.2

54 (1372) 1.5 3.5 5.5 7.5 9.5 11.5 13.5 15.5 17.5 19.4

60 (1524) 1.7 3.9 6.1 8.3 10.6 12.8 15.0 17.2 19.4 21.7

To determine pressure drop across opendamper, calculate free area velocity asshown, find velocity on curve and readacross for s.p. differential.

Free Area Velocity (fpm) =

Example: 1-36" x 24" Damper required for8,500 cfm. (Type A)

FAV = 85005 sq. ft.

= 1700 fpm

1700 fpm located on the ‘A’ curve shows apressure drop of .07 in. wg.

cfm = cubic feet per minutefpm = feet per minute velocityS.P. = static pressure in inches water gaugeFAV = Free Area Velocity

Imperial System ShownTo convert to SI (metric) system:

Multiply cfm by .4719 for liters per secondfpm by .00508 for meters per secondin. wg. by .2486 for kilopascalssq. ft. by .0929 for square meters

cfmFree Area

.40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.80

.901.0

.30

.10

.01

600

700

800

900

1000

1500

2000

3000

4000

5000

Free Area VFree Area Velocity (fpm)elocity (fpm)

FREE AREA VELOCITYFREE AREA VELOCITYV.S. ST.S. STATIC PRESSURE DROPTIC PRESSURE DROP

Static Static Pressure Pressure Drop Drop (in. wg.)(in. wg.)

TYPE 'A'TYPE 'A'

TYPE 'B'TYPE 'B'

TYPE 'C'TYPE 'C'

PERFORMANCE DATA:Curtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for thedifferent damper types and static pressure losses for various velocities.

TYPE C DAMPERS HAVE FREE AREA EQUAL TO NOMINAL DUCT AREA.

To calculate Free Area of round duct: DIAMETER2 x .00545 = Free Area (sq ft.)

HOW TO SPECIFY

TYPE B: MODEL 0520

TYPE CR: MODEL 0530

TYPE CO: MODEL 0530

TYPE CSR WITH COLLAR(STANDARD):MODEL 0530

TYPE CSR WITHOUT COLLAR:

MODEL 0530

For overall damper dimensions see sizing chart on page D48.

Revised May 5, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, 3 hour rated fire dampers as manufactured by NailorIndustries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled in accordancewith UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 3 hour fire resistance rating. Eachfire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Fire dampers shallbe suitably constructed for vertical or horizontal installation as required for each specific location.Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link. Firedampers shall each include a steel sleeve of appropriate length/gauge and retaining angles, supplied by damper manufacturerto ensure proper installation in accordance with damper manufacturer’s instructions. Contractor shall provide and install anaccess door at each fire damper, of appropriate size to allow for inspection, testing and fusible link replacement. Informationsubmitted for approval shall include confirmation of UL qualifications, pressure drop data and manufacturer’s installationinstructions. Each shipment of fire dampers shall include same installation instructions. Fire dampers shall be Nailor IndustriesModels 0510 (Type A), 0520 (Type B), 0530 (Type C).

Page 36: Fire Damper Nailor

• THINLINE FRAME • FOR USE IN STATIC

SYSTEMS• 3 HOUR RATING• UL 555 CLASSIFIED• VERTICAL MOUNT

The Nailor 0500 Thinline Series, Models 0570, 0580, and 0590 curtain fire dampers are UL/ULC approved for use where buildingcodes require the protection of HVAC ductwork penetrations in vertical fire separations (walls or partitions) that have a fireresistance rating of 4 hours or less. The 0500 Thinline Series is classified for use in static "fans off" systems where the HVACsystem is automatically shut down in the event of a fire alarm. These thinline dampers are only 2" (51) deep making them idealfor installation in narrow fire rated partitions, transfer duct openings, behind grilles or any other application where room is limited.The 0500 Series feature corrosion resistant steel frame and blades for lasting performance, and a choice of transition styles andfactory installed sleeves to suit duct size, making installation fast and simple.

MODELS: 0570 TYPE A0580 TYPE B0590 TYPE CR/CO0590 TYPE CSR Model 0570

D36

CURTAIN FIRE DAMPERS

D36

D

STATIC FIRE DAMPERS • THINLINE • 3 HOURCU

RTA

INFI

RE

DA

MPER

S

0570 0580 0590 0590 (Type A) (Type B) (Type CR/CO) (Type CSR)

FRAME: 2" (51) wide, 2" (51) wide, 2" (51) wide, 2" (51) wide,

22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-formed G60 formed G60 formed G60 formed G60

galvanized steel galvanized steel galvanized steel; galvanized steel;out of airstream out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanized G60 galvanizedsteel steel steel

ENCLOSURE: Type B Type C Type CN/A 22 ga. (.085) Round or Oval Square or Rect.

galvanized steel 22 ga. (.085) 22 ga. (.085)galvanized steel galvanized steel

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available available

BLADE CLOSURE: Gravity Gravity Gravity Gravity

MOUNTING: Vertical Vertical Vertical VerticalOnly Only Only Only

AVAILABLE Galvanized steel; Galvanized steel; Galvanized steel; Galvanized steel;SLEEVE: Specify SL Specify SL Specify SL Specify SL

Option Option Option Option

CONSTRUCTION DETAILS:

MODEL 0570V – VERTICAL MOUNT

TYPE A: MODEL 0570

INTERLOCKINGCURTAIN BLADES

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

DU

CT

SIZE

- 1/

4" (6

)

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

2" (51)

2" (51)

HEIGHT =NOMINAL

DUCTSIZE -1/4" (6)

For MIN./MAX. UL SIZES see chart on page D11.

Revised May 5, 2005

Page 37: Fire Damper Nailor

D37

CURTAIN FIRE DAMPERS

D37

D

STATIC FIRE DAMPERS • THINLINE • 3 HOURCU

RTA

INFIR

ED

AM

PER

S

PERFORMANCE DATA:Curtain type fire dampers impose minimal resistance to air flow in the system. The following charts indicate both free area for thedifferent damper types and static pressure losses for various velocities.

TYPE C DAMPERS HAVE FREE AREA EQUAL TO NOMINAL DUCT AREA.

To calculate Free Area of round duct: DIAMETER2 x .00545 = Free Area (sq ft.)

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

2" (51)

H =DUCTSIZE +1/8" (3) H

H

W + 1 3/4" (44)

WW + 1 3/4" (44)

W

W + 1 3/4" (44)

WH

D + 1 3/4" (44)

D

1"

TYPE A THINLINE DAMPER FREE AREA TYPE A THINLINE DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

6 12 18 24 30 36 40(152) (305) (457) (610) (762) (914) (1016)

6 (152) .12 .27 .44 .59 .75 .94 1.0212 (305) .27 .61 .93 1.36 1.7 2.1 2.418 (457) .42 .94 1.5 2.2 2.7 3.4 3.724 (610) .55 1.29 2.1 3.0 3.7 4.5 4.930 (762) .71 1.65 2.6 3.8 4.3 5.7 6.336 (914) .86 2.1 3.2 4.6 5.7 7.0 7.740 (1067) .93 2.3 3.5 5.1 6.3 7.6 8.848 (1219) 1.14 2.7 4.3 6.0 7.7 9.4

54 (1372) 1.32 3.1 4.9 6.9 8.8 10.7

60 (1524) 1.51 3.5 5.5 7.7 9.9 11.8

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

TYPE B THINLINE DAMPER FREE AREA TYPE B THINLINE DAMPER FREE AREA – sq. ft. sq. ft. DUCT WIDTH in inches (mm)DUCT WIDTH in inches (mm)

DUCT

HEI

GHT

in in

ches

(mm

)DU

CT H

EIGH

T in

inch

es (m

m)

6 12 18 24 30 36 40(152) (305) (457) (610) (762) (914) (1016)

6 (152) .15 .32 .52 .69 .88 1.09 1.1712 (305) .31 .70 1.07 1.55 1.95 2.4 2.718 (457) .47 1.05 1.7 2.5 3.05 3.8 4.224 (610) .62 1.44 2.3 3.4 4.2 5.1 5.630 (762) .80 1.84 2.9 4.3 4.9 6.5 7.236 (914) .95 2.33 3.6 5.1 6.4 7.840 (1067) 1.0 2.5 3.8 5.6 7.0 8.548 (1219) 1.3 3.1 4.8 6.8 8.6 10.4

.40

.02

.03

.04

.05

.06

.07

.08

.09

.20

.50

.60

.70

.80

.901.0

.30

.10

.01

600

700

800

900

1000

1500

2000

3000

4000

5000

Free Area VFree Area Velocity (fpm)elocity (fpm)

FREE AREA VELOCITYFREE AREA VELOCITYV.S. ST.S. STATIC PRESSURE DROPTIC PRESSURE DROP

Static Static Pressure Pressure Drop Drop (in. wg.)(in. wg.)

TYPE 'A'TYPE 'A'

TYPE 'B'TYPE 'B'

TYPE 'C'TYPE 'C'

To determine pressure drop across opendamper, calculate free area velocity asshown, find velocity on curve and readacross for s.p. differential.

Free Area Velocity (fpm) =

Example: 1-36” x 36” Damper required for14,000 cfm. (Type A)

FAV = 14,0007 sq. ft.

= 2000 fpm

2000 fpm located on the ‘A’ curve shows apressure drop of .12 in. wg.

cfm = cubic feet per minutefpm = feet per minute velocityS.P. = static pressure in inches water gaugeFAV = Free Area Velocity

Imperial System ShownTo convert to SI (metric) system:

Multiply cfm by .4719 for liters per secondfpm by .00508 for meters per secondin. wg. by .2486 for kilopascalssq. ft. by .0929 for square meters

cfmFree Area

HOW TO SPECIFY

TYPE B: MODEL 0580

TYPE CR: MODEL 0590

TYPE CO: MODEL 0590

TYPE CSR WITH COLLAR(STANDARD):MODEL 0590

TYPE CSR WITHOUT COLLAR:

MODEL 0590For overall damper dimensions, see sizing chart on page D49.

Revised May 5, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, 3 hour rated Thinline fire dampers as manufacturedby Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled inaccordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 3 hour fire resistancerating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position. Firedampers shall be suitably constructed for vertical or horizontal installation as required for each specific location.Thinline style fire damper frame shall be a maximum of 2" (51) in width, roll-formed from G60 galvanized steel. Blades shall beThinline type, roll-formed G60 galvanized steel. Each fire damper shall be complete with a (specifier select one) 165°F (74°C)or 212°F (100°C) UL Listed fusible link. Fire dampers shall each include a steel sleeve of appropriate length/gauge and retainingangles, supplied by damper manufacturer to ensure proper installation in accordance with damper manufacturer’s instructions.Contractor shall provide and install an access door at locations where the fire damper cannot be accessed through grille or ductend opening, to allow for inspection, testing and fusible link replacement. Information submitted for approval shall includeconfirmation of UL qualifications, pressure drop data, and manufacturer’s installation instructions. Each shipment of fire dampersshall include same installation instructions. 3 hour rated Thinline fire dampers shall be Nailor Industries Models 0570 (Type A),0580 (Type B), 0590 (Type C).

Page 38: Fire Damper Nailor

• WIDE FRAME • FOR USE IN STATIC

SYSTEMS• 3 HOUR RATING• UL 555 CLASSIFIED• VERTICAL MOUNT

The Nailor Model 0540 wide frame curtain fire damper is UL/ULC approved for use where building codes require the protection ofHVAC ductwork penetrations in vertical fire separations (walls or partitions) that have a fire resistant rating of 4 hours or less. The0540 is classified for use in static "fans off" systems where the HVAC system is automatically shut down in the event of a firealarm.The wide frame design reduces the number of blades required in the curtain stack, which increases the free area and reduces thepressure drop across the damper when compared to standard Type A curtain fire damper designs. The 0540 is ideal for use whenmaximum free area is desired in situations where space or design does not yield room for a Type B damper style. Featuringcorrosion resistant steel frame and blades for lasting performance, the Nailor Model 0540 is available with factory installed sleevefor fast and simple installation.

MODEL: 0540 TYPE A

Model 0540

D38

CURTAIN FIRE DAMPERS

D38

D

STATIC FIRE DAMPERS • WIDE FRAME • 3 HOURCU

RTA

INFI

RE

DA

MPER

S

0540 (Type A)

FRAME: 6" (152) wide,22 ga. (0.85) roll

formed G60 galvanized steel

BLADES: Curtain type, inter-locking blades, 22 ga

(0.85) roll-formedG60 galvanized

steel

FUSIBLE LINK: 165°F (74°C) Std.(UL Listed) 212°F (100°C)

availableBLADE CLOSURE: Gravity

MOUNTING: VerticalOnly

AVAILABLE Galvanized steel;SLEEVE: Specify SL

Option

CONSTRUCTION DETAILS:

TYPE A: MODEL 0540

MODEL 0540V – VERTICAL MOUNT

INTERLOCKINGCURTAIN BLADES

ROLL-FORMEDFRAME

UL LISTEDFUSIBLE LINK

(REPLACEABLE)

DU

CT

SIZE

- 1/

4" (6

)H

EIG

HT

= N

OM

INAL

DU

CT

SIZE

- 1/

4" (6

)

WIDTH = NOMINALDUCT SIZE - 1/4" (6)

6"

(152)

6" (152)

4 3/4" (121)

For MIN./MAX. UL SIZES see chart on page D11.

See Sizing Chart on page D50 for bladepack depth.

Revised May 5, 2005

Page 39: Fire Damper Nailor

D39

HOW TO SPECIFY

CURTAIN FIRE DAMPERS

D

STATIC FIRE DAMPERS • WIDE FRAME • 3 HOURCU

RTA

INFIR

ED

AM

PER

S

MODEL: 0540

Revised April 19, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, 3 hour rated wide frame fire dampers asmanufactured by Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested andlabeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 3 hour fireresistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mountingposition. Fire dampers shall be suitably constructed for vertical or horizontal installation as required for each specific location.Wide frame style fire damper frame shall be 6" (152) in width, roll-formed from G60 galvanized steel. Blades shall be wideframe type to provide maximum free area, roll-formed from G60 galvanized steel. Each fire damper shall be complete with a(specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link. Fire dampers shall each include a steel sleeveof appropriate length/gauge and retaining angles, supplied by damper manufacturer to ensure proper installation in accordancewith damper manufacturer’s instructions. Contractor shall provide and install an access door at each fire damper, of appropriatesize to allow for inspection, testing and fusible link replacement. Information submitted for approval shall include confirmationof UL qualifications and manufacturer’s installation instructions. Each shipment of fire dampers shall include same installationinstructions. 3 hour rated wide frame fire dampers shall be Nailor Industries Model 0540.

Page 40: Fire Damper Nailor

• INTEGRAL SLEEVE FORUSE WITH GRILLE

• FOR USE IN STATIC SYSTEMS

• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor 0100G Series integral sleeve fire dampers are designed for use in conjunction with a steel grille when ductworkterminates at an opening in a fire rated wall/partition. The 0100G Series is 1 1/2 hour UL labeled for use in 2 hour fire separationsor less and is classified for use in static "fans off" systems where the HVAC system shuts down in the event of a fire alarm. Thisunique product utilizes special grille mounting flanges on the sleeve that eliminate the requirement for unsightly retaining angleswhich commonly protrude from behind the grille. The steel grille installs over and completely conceals the mounting flanges for aclean, aesthetic finish. The fire damper is offset in the sleeve to accommodate a single or double defection supply air grille, singledeflection supply air register or a return air grille or register. Countersunk screw holes in the grille frame will match to mountingflanges when Nailor grille is ordered in conjunction with the damper assembly. The 0100G Series features corrosion resistant steel frame,blades and sleeve for performance that lasts, and a choice of transition styles and accessories making installation fast and simple.

MODELS: 0110G TYPE A0120G TYPE B0130G TYPE CR Model 0110G

D40

CURTAIN FIRE DAMPERS

D40

D

STATIC FIRE DAMPERS • GRILLE TABSCU

RTA

INFI

RE

DA

MPER

S

0110G 0120G 0130G (Type A) (Type B) (Type CR)

FRAME: 4 1/4" (108) wide, 4 1/4" (108) wide, 4 1/4" (108) wide,22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-

formed G60 formed G60 formed G60 galvanized steel galvanized steel galvanized steel;

out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga.G60 (0.85) roll-formed (0.85) roll-formed

galvanized steel G60 galvanized G60 galvanizedsteel steel

STANDARD 12" (305) x 22 ga. (0.85) 12" (305) x 22 ga. (0.85) 12" (305) x 22 ga. (0.85) SLEEVE: galvanized steel galvanized steel galvanized steel

with 3/4" (19) wide with 3/4" (19) wide with 3/4" (19) widegrille mounting flanges grille mounting flanges; grille mounting flanges;

type B duct connection type C duct connectionon one end on one end

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available

BLADE Vertical mount; gravity Vertical mount; gravity Vertical mount; gravityCLOSURE: Horizontal mount; Horizontal mount; Horizontal mount;

stainless steel closure stainless steel closure stainless steel closuresprings with galvanized springs with galvanized springs with galvanized

steel locking ramps steel locking ramps steel locking ramps

MOUNTING: Vertical or Horizontal Vertical or Horizontal Vertical or Horizontal

OPTIONAL Steel grille with correctly Steel grille with correctly Steel grille with correctlyGRILLE: located countersunk located countersunk located countersunk

screw holes; Select screw holes; Select screw holes; Selectmodel from Nailor Air model from Nailor Air model from Nailor AirDistribution Catalog Distribution Catalog Distribution Catalog

CONSTRUCTION DETAILS:

H

W

LS

4 1/4"(108)

H

4 3/4"(121)

4 1/4"(108)

3"(76)

12" (305)

TYPE A: MODEL 0110GFor MIN./MAX. UL SIZES see chart on page D10.

Revised May 5, 2005

Page 41: Fire Damper Nailor

D41

CURTAIN FIRE DAMPERS

D

STATIC FIRE DAMPERS • GRILLE TABSCU

RTA

INFIR

ED

AM

PER

S

OPTIONAL DAMPER / SLEEVES:

HOW TO DETERMINE SLEEVE LENGTH / DAMPER POSITION:

To calculate sleeve length, determine wall thickness and add 3" (76) minimum for rear retaining angles and ductconnection. Front of assembly fits flush with wall. Damper offset (dimension 'S') should accommodate grille selectiondepth, but fire damper position must remain within plane of wall.

FOR NON-STANDARD SLEEVE LENGTH, SPECIFY LENGTH.

FOR NON-STANDARD DAMPER POSITION IN SLEEVE, SPECIFY DIMENSION 'S'.

OTHER OPTIONS / ACCESSORIES:

CODE DESCRIPTION

QUICK-SET ANGLE QS1 Single set of "Quick-Set" Retaining Angles for Rear Side

HEMMED SLEEVE HM1 Sleeve End Hemmed for Slip and Drive Connection

MICROSWITCH MS 24V MicroswitchMSE 120/24V Microswitch with Enclosure

DUCT 'A'HEIGHT (H) DIM.

6" thru 17" 2"(152 - 432) (51)

18" thru 21" 3"(457 - 533) (76)

4 3/4"(121)

4 1/4"(108)

S3" (76) STD.

12" (305)

A

H

4 3/4"(121)

4 1/4"(108)

12" (305)

DIA.

D +

2" (

51)

TYPE B MODEL D 20G

S3" (76) STD.

TYPE B DUCT CONNECTION ONONE END: MODEL 0120G

TYPE C ROUND DUCT CONNECTIONON ONE END: MODEL 0130G

HOW TO SPECIFY

Revised February 17, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, fire dampers for use with grilles, as manufacturedby Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled inaccordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have 1 1/2 hour fire resistancerating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mounting position.Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link. Inaddition, each fire damper shall be provided from the factory in an integral 22 ga. (0.85) galvanized steel sleeve with one'Quick-Set' retaining angle, and grille mounting flanges specially designed for use with a steel grille of minimum 26 ga. (.5)construction. Fire dampers shall be offset in the sleeve an appropriate amount to maintain positioning of fire damper withinplane of wall. Data submitted for approval shall include confirmation of UL qualifications in addition to manufacturer’sinstallation instructions. Fire dampers shall be installed in accordance with manufacturer’s instructions, and same installationinstructions shall be included with each fire damper shipment. Fire dampers for use with steel grilles shall be Nailor IndustriesModels 0110G (Type A), 0120G (Type B transition), 0130G (Type C transition).

Page 42: Fire Damper Nailor

• INTEGRAL SLEEVE FOR USE WITH GRILLE

• THINLINE FIRE DAMPER• FOR USE IN STATIC

SYSTEMS• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Nailor 0200G Thinline Series integral sleeve fire dampers are designed for use in conjunction with a steel grille when ductworkterminates at an opening in a fire rated wall/partition. The 0200G Thinline Series is 1 1/2 hour UL labeled for use in 2 hour fireseparations or less and is classified for use in static "fans off" systems where the the HVAC system shuts down in the event of afire alarm. This unique product utilizes special grille mounting flanges on the sleeve that eliminate the requirement for unsightlyretaining angles which commonly protrude from behind the grille. The steel grille installs over and completely conceals themounting flanges for a clean, aesthetic finish. The 2" (51) deep thinline fire damper is offset in the sleeve to accommodate a singleor double deflection grille or register. Countersunk screw holes in the grille frame will match to mounting flanges when Nailor grilleis ordered in conjunction with the damper assembly. The 0200G Series features corrosion resistant steel frame, blades and sleevefor lasting performance, and a choice of transition styles and accessories making installation simple and fast.

MODELS: 0210G TYPE A0220G TYPE B0230G TYPE CR

Model 0210G

D42

CURTAIN FIRE DAMPERS

D42

D

STATIC FIRE DAMPERS • THINLINE • GRILLE TABSCU

RTA

INFI

RE

DA

MPER

S

0210G 0220G 0230G (Type A) (Type B) (Type CR)

FRAME: 2" (51) wide, 2" (51) wide, 2" (51) wide,22 ga. (0.85) roll- 22 ga. (0.85) roll- 22 ga. (0.85) roll-

formed G60 formed G60 formed G60 galvanized steel galvanized steel galvanized steel;

out of airstream

BLADES: Curtain type, inter- Out of airstream. Out of airstream.locking blades, 22 ga. Curtain type, inter- Curtain type, inter-

(0.85) roll-formed locking blades, 22 ga. locking blades, 22 ga.G60 galvanized (0.85) roll-formed (0.85) roll-formed

steel G60 galvanized G60 galvanizedsteel steel

STANDARD 12" (305) x 22 ga. (0.85) 12" (305) x 22 ga. ( 0.85) 12" (305) x 22 ga. ( 0.85) SLEEVE: galvanized steel galvanized steel galvanized steel

with 3/4" (19) wide with 3/4" (19) wide with 3/4" (19) widegrille mounting flanges grille mounting flanges; grille mounting flanges;

Type B duct connection Type C duct connectionon one end on one end

FUSIBLE LINK: 165°F (74°C) Std. 165°F (74°C) Std. 165°F (74°C) Std.(UL Listed) 212°F (100°C) 212°F (100°C) 212°F (100°C)

available available available

BLADE CLOSURE: Gravity Gravity Gravity

MOUNTING: For Vertical Mounting For Vertical Mounting For Vertical Mounting

OPTIONAL Steel grille with correctly Steel grille with correctly Steel grille with correctlyGRILLE: located countersunk located countersunk located countersunk

screw holes; Select screw holes; Select screw holes; Selectmodel from Nailor Air model from Nailor Air model from Nailor AirDistribution Catalog Distribution Catalog Distribution Catalog

CONSTRUCTION DETAILS:

H

W

LS

2"(51)

H

7"(178)

2"(51)

3"(76)

12" (305)

TYPE A: MODEL 0210GFor MIN./MAX. UL SIZES see chart on page D10.

Revised May 5, 2005

Page 43: Fire Damper Nailor

D43

CURTAIN FIRE DAMPERS

D43

D

STATIC FIRE DAMPERS • THINLINE • GRILLE TABSCU

RTA

INFIR

ED

AM

PER

S

OPTIONAL DAMPER / SLEEVES:

HOW TO DETERMINE SLEEVE LENGTH / DAMPER POSITION:

To calculate sleeve length, determine wall thickness and add 3" (76) minimum for rear retaining angles and ductconnection. Front of assembly fits flush with wall. Damper offset (dimension 'S') should accommodate grille selectiondepth, but fire damper position must remain within plane of wall.

FOR NON-STANDARD SLEEVE LENGTH, SPECIFY LENGTH.

FOR NON-STANDARD DAMPER POSITION IN SLEEVE, SPECIFY DIMENSION 'S'.

OTHER OPTIONS / ACCESSORIES:

CODE DESCRIPTION

QUICK-SET ANGLE QS1 Single set of "Quick-Set" Retaining Angles for Rear Side

HEMMED SLEEVE HM1 Sleeve End Hemmed for Slip and Drive Connection

MICROSWITCH MS 24V MicroswitchMSE 120/24V Microswitch with Enclosure

DUCT 'A'HEIGHT (H) DIM.

6" thru 9" 2"(152 - 229) (51)

10" thru 15" 3"(254 - 381) (76)

16" thru 19" 4"(406 - 483) (102) 7"

(178)2"

(51)

12" (305)

A

H

S3" (76) STD.

7"(178)

2"(51)

12" (305)

DIA.

D +

2" (

51)

S3" (76) STD.

TYPE B DUCT CONNECTION ONONE END: MODEL 0220G

TYPE C ROUND DUCT CONNECTIONON ONE END: MODEL 0230G

HOW TO SPECIFY

Revised February 17, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, Thinline fire dampers for use with grilles, asmanufactured by Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested andlabeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have a 1 1/2 hourfire resistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mountingposition.Thinline style fire damper frame shall be a maximum of 2" (51) in width, roll-formed from G60 galvanized steel. Blades shall beThinline type, roll-formed G60 galvanized steel. Each fire damper shall be complete with a (specifier select one) 165°F (74°C)or 212°F (100°C) UL Listed fusible link. In addition, each Thinline fire damper shall be provided from the factory in an integral22 ga (0.85) galvanized steel sleeve with one 'Quick-Set' retaining angle, and grille mounting flanges specially designed for usewith a steel grille of minimum 26 ga. (.5) construction. Fire damper shall be offset in the sleeve an appropriate amount to maintainpositioning of fire damper within plane of wall. Data submitted for approval shall include confirmation of UL qualifications inaddition to manufacturer’s installation instructions. Fire dampers shall be installed in accordance with manufacturer’sinstructions, and same installation instructions shall be included with each fire damper shipment. Thinline fire dampers for usewith steel grilles shall be Nailor Industries Models 0210G (Type A), 0220G (Type B transition), 0230G (Type C transition).

Page 44: Fire Damper Nailor

• INTEGRAL “OUT OF WALL” SLEEVE FOR USE WITHGRILLE

• FOR USE IN STATIC SYSTEMS

• 1 1/2 HOUR RATING• UL 555 CLASSIFIED

The Model 0110GOW is an "out of wall or floor" integral sleeve curtain type fire damper, specifically designed for supply or returnducts that terminate at a grille or register. For use where local building codes require the protection of HVAC ductwork penetrations inwalls, partitions or floors that have a fire resistance rating of up to two hours. The 0110GOW is classified for use only in static “fans off”systems where the HVAC system is automatically shut down in the event of a fire alarm.The 0110GOW design provides sufficient damper off-set to accommodate most commercial grille/register designs while ensuring anapproved installation in any fire partition or wall no matter how narrow. This model is particularly suited for use in common steel studdrywall partition designs, as narrow as 3 1/2" (89) where a traditional "within the plane of the wall" fire damper installation is notpossible.

MODEL: 0110GOW

Model 0110GOW

D44

CURTAIN FIRE DAMPERS

D44

D

STATIC FIRE DAMPERS • OUT OF WALLCU

RTA

INFI

RE

DA

MPER

S

FIRE DAMPER

THERMALINSULATION

H

WGRILLE/REGISTER

3/4" (19)FLANGE

0110GOW (Type A)

FRAME: 4 1/4" (108) wide,22 ga. (0.85) roll-

formed G60galvanized steel

BLADES: Curtain type, inter-locking blades, 22 ga.

(0.85) roll-formedG60 galvanized

steel

STANDARD 10" (254) x 16 ga. (1.6) SLEEVE: galvanized steel

with 3/4" (19) widegrille mounting flanges;

intumescent thermalinsulation

on all four sides

FUSIBLE LINK: 165°F (74°C) Std.(UL Listed) 212°F (100°C)

available

BLADE Vertical mount; gravityCLOSURE: Horizontal mount

stainless steel closuresprings with galvanized

steel locking ramps

MOUNTING: Vertical or Horizontal

OPTIONAL Steel or aluminumGRILLE: grille or register;

Select model fromNailor Air Distribution

Catalog

CONSTRUCTION DETAILS:

Revised April 25, 2005

MODEL: 0110GOW

For MIN./MAX. UL SIZES see chart on page D10.

Page 45: Fire Damper Nailor

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, “out of wall” fire dampers for use with grilles, asmanufactured by Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested andlabeled in accordance with UL 555 Safety Standard for Fire Dampers - Sixth Edition, June 1999, and shall have 1 1/2 hour fireresistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mountingposition.Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link. Inaddition, each fire damper shall be provided from the factory in an integral 16 ga. (1.6) galvanized steel insulated sleeve withgrille mounting flanges. Data submitted for approval shall include confirmation of UL qualifications in addition to manufacturer’sinstallation instructions. Fire dampers shall be installed in accordance with manufacturer’s instructions, and same installationinstructions shall be included with each fire damper shipment. “Out of wall” fire dampers shall be Nailor Industries Model0110GOW.

D45

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

S

HOW TO SPECIFY

STATIC FIRE DAMPERS • OUT OF WALL

10" (254) STD. SLEEVE

3/4" (19) MIN. FLANGE

4" (102) Max.

10" (254) STD.

SLEEVE

3/4" (19) MIN. FLANGE

4" (102) Max.

MODEL: 0110GOW

VERTICAL MOUNT HORIZONTAL MOUNT

Revised April 25, 2005

Page 46: Fire Damper Nailor

MODEL: 0130GC

Model 0130GC

The Nailor Model 0130GC has been specially designed for garbage chute applications. The damper casing is oversized to ensurethat the blade stack, fusible link and closure springs are unobstructed from falling waste. The round collar is slightly oversized fordirect attachment to the outside of the garbage chute. The 100% free area 0130GC also features corrosion resistant steelconstruction and is available in three standard sizes, 20" dia. (508), 22" dia. (559) and 24" dia. (610), as well as custom sizes.Damper has a 1 1/2 hour fire rating.

MODEL 12345-10SQUARE ROUND NECKSQUARE ROUND NECKSQUARE ROUND NECK

D46

CURTAIN FIRE DAMPERS

D46

D

STATIC FIRE DAMPERS • GARBAGE CHUTECU

RTA

INFI

RE

DA

MPER

S

MODEL 12345-10SQUARE ROUND NECKSQUARE ROUND NECKSQUARE ROUND NECK

• GARBAGE CHUTE FIRE DAMPER

• 1 1/2 HOUR RATING• 100% FREE AREA

0130GC

FRAME: 4 1/4" (108) wide,22 ga. (0.85) roll-

formed G60galvanized steel

BLADES: Curtain type, inter-locking blades, 22 ga.

(0.85) roll-formedG60 galvanized

steel

MOUNTING 22 ga (.085)COLLAR: galvanized steel;

round collar oversizedfor connection tooutside of chute

FUSIBLE LINK: 165°F (74°C) Std.(UL Listed) 212°F (100°C)

available

BLADE Stainless steelCLOSURE: closure springs

with galvanizedsteel locking clamps

MOUNTING: Horizontal Mount

STANDARD 20" (508) diameterSIZES: 22" (559) diameter

24" (610) diameterNote: Other sizes

available upon request

CONSTRUCTION DETAILS:

OVERALL WIDTH = NOMINAL + 3 3/4" (95)

I.D. = NOMINAL SIZE + 1/4" (6)

OVERALL HEIGHT = NOMINAL SIZE + 7 3/4" (197)

3 1/4" (83)

4 1/4" (109)

7" (178)

2" (51)

Page 47: Fire Damper Nailor

GARBAGE CHUTE FIRE DAMPER

MODEL 0130GC

D47

CURTAIN FIRE DAMPERS

D47

D

STATIC FIRE DAMPERS • GARBAGE CHUTECU

RTA

INFIR

ED

AM

PER

S

D47

HOW TO SPECIFY

Revised April 26, 2005

SUGGESTED SPECIFICATION:Provide and install, as shown on plans and as described in specifications, garbage chute type fire dampers as manufacturedby Nailor Industries, meeting or exceeding the following criteria: Fire dampers shall be manufactured, tested and labeled inaccordance with UL 555 Safety Standard for Fire Dampers – Sixth Edition, June 1999, and shall have a 1 1/2 hour fireresistance rating. Each fire damper shall bear a UL label verifying fire resistance rating in addition to intended mountingposition. Each fire damper shall be complete with a (specifier select one) 165°F (74°C) or 212°F (100°C) UL Listed fusible link.Garbage chute type fire dampers shall be equipped with closure springs and locking ramps suitable for horizontal mountingand shall be enclosed in a Type C housing, oversized to ensure all damper parts are not exposed to falling debris. Round collarof minimum 22 ga. (0.85) shall be provided on top side only, and shall be oversized for connection over chute.Information submitted for approval shall include confirmation of UL qualifications and manufacturer’s installation instructions.Each shipment of fire dampers shall include same installation instructions. Garbage chute type fire dampers shall be NailorIndustries Model 0130GC.

Page 48: Fire Damper Nailor

D48

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SCURTAIN FIRE DAMPERS

IMPERIAL METRIC IMPERIAL METRIC

TYPE A4" ➔ 60" 100 mm ➔ 1525 mm DUCT HEIGHT – 1/4" DUCT HEIGHT – 6 mm

NOTE: TYPE A DAMPER OVERALL WIDTH = DUCT OPENING – 1/4" (6 mm)

3" ➔ 17" 75 ➔ 425 mm DUCT HEIGHT + 2 1/8" DUCT HEIGHT + 54 mm18" ➔ 27" 450 ➔ 675 mm + 3 1/8" + 79 mm28" ➔ 36" 700 ➔ 925 mm + 4 1/8" + 105 mm

TYPE B 37" ➔ 45" 950 ➔ 1150 mm + 5 1/8" + 130 mm46" ➔ 54" 1175 ➔ 1375 mm + 6 1/8" + 156 mm

NOTE: TYPE B DAMPER OVERALL WIDTH = DUCT OPENING – 1/4" (6 mm)

3" ➔ 5" 75 ➔ 125 mm DUCT HEIGHT + 1 3/4" DUCT HEIGHT + 44 mm6" ➔ 17" 150 ➔ 425 mm DUCT HEIGHT + 2 3/4" DUCT HEIGHT + 70 mm

18" ➔ 27" 450 ➔ 675 mm + 3 3/4" + 95 mm

TYPE C 28" ➔ 36" 700 ➔ 900 mm + 4 3/4" + 121 mm37" ➔ 45" 925 ➔ 1150 mm + 5 3/4" + 146 mm46" ➔ 53" 1175 ➔ 1350 mm + 6 3/4" + 172 mm

NOTE: TYPE C DAMPER OVERALL WIDTH = DUCT OPENING + 1 3/4" (44 mm)

DUCT OPENING HEIGHT OVERALL HEIGHT

FIRE DAMPER SIZING CHART

FOR ALL STANDARD 4 1/4" (108) FRAME FIRE DAMPERS:

SERIES / MODELS: D0100, D0500, 0100, 0510, 0520, 0530.Use the following chart to determine overall dimensions for Type A, B, and C curtain type fire dampers:

""""

""""

""""

""""

OVE

RAL

L H

EIG

HT

TYPE A

HIGH HATHEIGHT

OVE

RAL

L H

EIG

HT

DU

CT

OPE

NIN

G

TYPE B

HIGH HATHEIGHT

OVE

RAL

L H

EIG

HT

DU

CT

OPE

NIN

G

1"

TYPE C

Revised February 17, 2005

SIZING CHART • STANDARD FRAME

Important Note: Type "B" and "C" overall height dimensions only apply to sizes that are singlesection high. For overall height dimensions for sizes that are multi-section in height, please contactfactory. Refer to individual model submittal drawings for maximum single section heights.

Page 49: Fire Damper Nailor

D49

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

FIRE DAMPER SIZING CHART

FOR ALL THINLINE 2" (51) FRAME FIRE DAMPERS:

SERIES / MODELS: 0200, 0570, 0580, 0590Use the following chart to determine overall dimensions for Type A, B, and C curtain type fire dampers:

OVE

RAL

L H

EIG

HT

TYPE A

HIGH HATHEIGHT

OVE

RAL

L H

EIG

HT

DU

CT

OPE

NIN

G

TYPE B

OVE

RAL

L H

EIG

HT

DU

CT

OPE

NIN

G

HIGH HATHEIGHT

OVE

RAL

L H

EIG

HT

DU

CT

OPE

NIN

G

1"

TYPE C

Revised February 17, 2005

IMPERIAL METRIC IMPERIAL METRIC

TYPE A4" ➔ 60" 100 mm ➔ 1525 mm DUCT HEIGHT – 1/4" DUCT HEIGHT – 6 mm

NOTE: TYPE A DAMPER OVERALL WIDTH = DUCT OPENING – 1/4" (6 mm)

3" ➔ 9" 75 ➔ 225 mm DUCT HEIGHT + 2 1/8" DUCT HEIGHT + 54 mm10" ➔ 15" 250 ➔ 375 mm + 3 1/8" + 79 mm16" ➔ 19" 400 ➔ 475 mm + 4 1/8" + 105 mm20" ➔ 25" 500 ➔ 625 mm + 5 1/8" + 130 mm

TYPE B 26" ➔ 31" 650 ➔ 775 mm + 6 1/8" + 156 mm32" ➔ 34" 800 ➔ 850 mm + 7 1/8" + 181 mm35" ➔ 40" 875 ➔ 1025 mm + 8 1/8" + 206 mm41" ➔ 46" 1050 ➔ 1175 mm + 9 1/8" + 232 mm47" ➔ 50" 1200 ➔ 1275 mm + 10 1/8" + 257 mm

NOTE: TYPE B DAMPER OVERALL WIDTH = DUCT OPENING – 1/4" (6 mm)

3" ➔ 9" 75 ➔ 225 mm DUCT HEIGHT + 2 3/4" DUCT HEIGHT + 70 mm10" ➔ 15" 250 ➔ 375 mm + 3 3/4" + 95 mm16" ➔ 19" 400 ➔ 475 mm + 4 3/4" + 121 mm20" ➔ 25" 500 ➔ 625 mm + 5 3/4" + 146 mm

TYPE C 26" ➔ 31" 650 ➔ 775 mm + 6 3/4" + 172 mm32" ➔ 34" 800 ➔ 850 mm + 7 3/4" + 197 mm35" ➔ 40" 875 ➔ 1025 mm + 8 3/4" + 222 mm41" ➔ 46" 1050 ➔ 1175 mm + 9 3/4" + 248 mm47" ➔ 49" 1200 ➔ 1250 mm + 10 3/4" + 273 mm

NOTE: TYPE C DAMPER OVERALL WIDTH = DUCT OPENING + 1 3/4" (44 mm)

DUCT OPENING HEIGHT OVERALL HEIGHT

""""""""

""""""""

""""""""

""""""""

SIZING CHART • THINLINE FRAME

Page 50: Fire Damper Nailor

D50

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

DUCT TYPE "A" BLADEOPENING OVERALL PACKHEIGHT HEIGHT DEPTH

(inches) (mm) (inches) (mm) (inches) (mm)

4 102 3 3/4 95 3/4 195 127 4 3/4 121 7/8 226 152 5 3/4 146 7/8 227 178 6 3/4 171 7/8 228 203 7 3/4 197 1 1/4 329 229 8 3/4 222 1 1/4 32

10 254 9 3/4 248 1 1/4 3211 279 10 3/4 273 1 3/8 3512 305 11 3/4 298 1 3/8 3513 330 12 3/4 324 1 3/8 3514 356 13 3/4 349 1 5/8 4115 381 14 3/4 375 1 5/8 4116 406 15 3/4 400 1 5/8 4117 432 16 3/4 425 1 3/4 4418 457 17 3/4 451 1 3/4 4419 483 18 3/4 476 1 3/4 4420 508 19 3/4 502 2 5121 534 20 3/4 527 2 5122 559 21 3/4 552 2 5123 584 22 3/4 578 2 5124 610 23 3/4 603 2 1/4 5725 635 24 3/4 629 2 1/4 5726 661 25 3/4 654 2 1/2 6427 656 26 3/4 679 2 1/2 6428 711 27 3/4 705 2 1/2 6429 737 28 3/4 730 2 1/2 6430 762 29 3/4 756 2 5/8 6731 787 30 3/4 781 2 5/8 6732 813 31 3/4 806 2 5/8 6733 838 32 3/4 832 2 5/8 6734 864 33 3/4 857 2 7/8 7335 889 34 3/4 883 2 7/8 7336 914 35 3/4 908 2 7/8 7337 940 36 3/4 933 3 1/8 7938 965 37 3/4 959 3 1/8 7939 991 38 3/4 984 3 1/8 7940 1016 39 3/4 1010 3 3/8 8641 1041 40 3/4 1035 3 3/8 8642 1067 41 3/4 1060 3 3/8 8643 1092 42 3/4 1086 3 3/8 8644 1117 43 3/4 1111 3 1/2 8945 1143 44 3/4 1137 3 1/2 8946 1168 45 3/4 1162 3 1/2 8947 1194 46 3/4 1187 3 3/4 9548 1219 47 3/4 1213 3 3/4 9549 1245 48 3/4 1238 3 3/4 9550 1270 49 3/4 1264 3 3/4 9551 1296 50 3/4 1289 3 7/8 9852 1321 51 3/4 1314 3 7/8 9853 1346 52 3/4 1340 3 7/8 9854 1372 53 3/4 1365 4 1/8 10555 1397 54 3/4 1391 4 1/8 10556 1423 55 3/4 1416 4 1/8 10557 1448 56 3/4 1441 4 1/8 10558 1473 57 3/4 1467 4 1/4 10859 1499 58 3/4 1492 4 1/4 10860 1524 59 3/4 1518 4 1/4 108

OVER

ALL

HEIG

HT

TYPE A

BLADEPACK

DEPTH

DAMPER OVERALL WIDTH= Duct Opening - 1/4" (6).

FIRE DAMPER SIZING CHART

BLADE PACK DEPTH FOR 6" (152) WIDE FRAME FIRE DAMPERS

MODELS: 0310 AND 0540 (TYPE A)

Revised February 17, 2005

SIZING CHART • WIDE FRAME

Page 51: Fire Damper Nailor

MODEL SERIES: (D)0100 / 0200 / 0300 / (D)0500OPTIONS/VARIABLES FOR CURTAIN FIRE DAMPERS

OPTIONS / VARIABLES: CODE DESCRIPTION

TRANSITION: CR Round Type C Transition(Type C Dampers Only) CO Oval Type C Transition

CSR Square / Round Type C Transition

PRESSURE: LP Unsealed; For Low Pressure Applications(Type C Dampers Only) HP Sealed; For High Pressure Applications

COLLAR: WC With Collars (Standard)(Type CSR Dampers Only) NC No Collars (Optional)

CLOSURE DEVICE: FL Fusible LinkEML Easy Maintenance LinkETL Electro-Thermal Link

CLOSURE TEMPERATURE: 165 165°F (74°C) Fusible Link212 212°F (100°C) Fusible Link

SLEEVE: OO No SleeveSL With Sleeve (Specify Sleeve Length)

SLEEVE GAUGE: NA Not Applicable (No Sleeve)10G 10 Gauge Sleeve14G 14 Gauge Sleeve16G 16 Gauge Sleeve18G 18 Gauge Sleeve20G 20 Gauge Sleeve22G 22 Gauge Sleeve

QUICK SET ANGLES: QS1 Single Set of "Quick Set" Retaining AnglesQS2 Pair of two "Quick Set" Retaining Angles

HEMMED SLEEVE: HM2 Both Ends Hemmed for Slip and Drive Connection (Type A and B only)

HM1 One End Hemmed for Slip and Drive Connection (Type G)

FLANGED SLEEVE: TDF1 Flanged on One EndTDF2 Flanged on Both Ends

PULL TAB: PT Pull Tab Release(Horizontal Mount Only)

MICROSWITCH: MS 24V MicroswitchMSE 120/24V Microswitch with Enclosure

HOW TO ORDER:Specify model/mounting and size, then select from each variable as applicable. Choose options as desired. Standardconstruction (default) is shown in highlighted box.

D51

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

Revised February 17, 2005

MODEL/MOUNTIN

G

SIZE

W X

H o

r DIA.

TRANSITIO

N

TYPE

PRESSURE

COLLAR

(Typ

e CSR o

nly)

CLOSURE DEVIC

E

CLOSURE

TEMPERATURE

SLEEVE

SLEEVE GAUGE

OPTIONS

ie: ie: CR LP WC FL 165 OO 20G QS10110V 24" X 12" CO HP NC EML 212 SL 22G QS2

or CSR ETL 18G HM118" dia. 16G HM2

(600 x 300 14G TDF1or 10G TDF2

450 dia.) PTMSMSE

TYPE C ONLY

Notes: 1. If SL (sleeve) is selected, specify sleeve length and gauge.2. Std. sleeve is 12" (305) long x 20 ga. (1.0). Factory mounted/integral sleeves are manufactured of 22 ga. (0.85) minimum.

HOW TO ORDER

OPTIONS/VARIABLES • HOW TO ORDER

Page 52: Fire Damper Nailor

D52

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

SLEEVE OPTIONS:

Fire dampers, in most cases, must be mounted in a steel sleeve and the damper/sleeve assembly is to be held in placein the wall, partition or floor by use of steel perimeter angles. This allows for the ductwork to 'break-away' from thesleeve should the ductwork fall during a fire, thus leaving the sleeve/fire damper intact in the opening to maintain theintegrity of the fire separation. Nailor factory furnished sleeves ensure proper fit to UL standards, allow for directshipment of dampers to jobsite eliminating the need for costly shop handling and provide for convenient, fastinstallation.

FOR NON-INTEGRAL SLEEVE MODELS

Dimensional Data:W = Nominal duct widthH = Nominal duct heightD = Nominal duct diameterL = Sleeve lengthO = Overall damper heightFor 'O' dimension and relationship toduct height, refer to the particulardamper model sizing chart.

Notes:1. Type CR duct collars are furnished 1/8" (3) undersize for duct

dimensions up to 36" dia. (914) and 1/4" (6) undersize onlarger sizes. Type CO and CSR duct collars are furnished1/8" (3) undersize for duct dimensions up to 36" x 24"(914 x 610) and 1/4" (6) undersize on larger sizes.Collars are 1 1/4" (32) minimum length.

2. For size limitations see MIN / MAX. UL SIZES chartsbeginning on page D9.

3. Dampers are centered in sleeve unless specifiedotherwise.

4. Multiple section damper assemblies are shipped knockeddown for field assembly.

TYPE 'A'BLADES AND FRAME IN AIRSTREAM TYPE 'B' BLADES OUT OF AIRSTREAM

W

HO

W

HO

W

H

STYLE 2 (STANDARD)STYLE 1 (OPTIONAL)

TYPE 'CR'ROUND TRANSITION COLLARS/DUCT.

100% FREE AREA.

O

D + 2" (51)

D

TYPE 'CSR'RECTANGULAR TRANSITION COLLARS/DUCT.

100% FREE AREA.

O

H

W + 2" (51)

W

LL

TYPE 'CO'FLAT OVAL TRANSITION COLLARS/DUCT.

100% FREE AREA.

W + 2" (51)

O

H

WL

LLL

Revised April 26, 2005

CURTAIN FIRE DAMPERS

Options and Variables

Page 53: Fire Damper Nailor

D53

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

SLEEVE OPTIONS:

OPTION CODE SLSLEEVE LENGTH

OPTION CODES10G, 14G, 16G, 18G, 20G, 22GSLEEVE GAUGE

OPTION CODES HM1, HM2HEMMED SLEEVE END(S)

When selecting sleeve option SL please specify sleeve length.Fire damper sleeves are required to extend out beyond the wall or flooropening an adequate amount in order to allow for fastening of perimeterangles to sleeve and connection to duct. UL 555 requires that the lengthof the sleeve extending beyond the wall or floor opening shall notexceed 6" (152) on each side for fire dampers intended for use withoutan actuator or factory installed access door in the sleeve.However, the sleeve may extend up to a maximum of 16" (406) beyondthe wall or floor on either side provided the extended side(s) is used toaccommodate an actuator or a factory mounted access door (See UL 555 Sixth Edition June 1999, Section 6.4).

Sleeves are available in lengths up to 36" (914).Standard sleeve is 12" (305) long x 20 ga. (1.0).

When selecting sleeve option SL please specify sleeve gauge ifother than standard.Nailor factory-fitted sleeves are constructed from quality galvanizedsteel and are available in 10 ga. through 22 ga. (3.5 through 0.85) asrequired for application. Standard sleeve is 12" (305) long x 20 ga.(1.0). Sleeves over 84" (2134) in width are minimum 18 ga. (1.3).Sleeve gauge must conform to SMACNA Duct Construction Standardsand shall not be less than the gauge of the duct to which it is attached,for sleeves exposed to the airstream.

In order to more easilyfacilitate connection to squareor rectangular ducts, Nailoroffers hemmed sleeve endssuitable for use as a'breakaway' connection onsleeves of up to a maximum20" (508) in height, inaccordance with ULrequirements. This allows "S"slips and flat drive slips to beused. Option Code HM1 willprovide only one end hemmed,suitable for use on sleeves thatterminate flush with a wall tofacilitate grille mounting forexample. Option Code HM2will provide both ends hemmedfor connection of ductwork toboth ends of sleeve.

FOR NON-INTEGRAL SLEEVE MODELS

Sleeve with Option Code HM2 shown.

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 54: Fire Damper Nailor

D54

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

RETAINING ANGLES:

OPTION CODES QS1, QS2'QUICK-SET' RETAINING ANGLES

BENEFITS:• Factory fabricated by the manufacturer to suit

the individual fire damper. • Dampers can ship directly to the job site

complete with all necessary installation sheet metal hardware (saves on double handling at contractor’s shop).

• Reduced cost when compared to conventional retaining angles.

• Only two sets of angles to handle per damper (rather than eight).

• Angles ship with individual damper - no sorting or matching.

• Pre-drilled holes on 8" (203) centers to ensure correct angle/sleeve attachment.

• Help ensure a correct installation as per U.L. approved installation instructions.

The majority of installing contractors view fire damper installation as a costly time consuming and troublesome procedure.Eight conventional angles must be custom fabricated for each damper either in a sheet metal shop or at the job site andsized to suit each individual damper. Invariably, they are mislaid or lost and must be matched to each factory supplieddamper. The Nailor "Quick-Set" solution solves the majority of problems. They are pre-formed to fit each damper andshipped with the individual damper units for ultimate convenience. Option Code QS1 provides a single set of angles for applications requiring angles on one side of the damper only. Option Code QS2 provides the complete kit of two sets of angles suitable for most applications that require angles on bothsides of the damper. "Quick-Set" angles are supplied with correctly spaced pre-drilled screw-holes to ensure a quick, easy and accurateinstallation for all Nailor fire dampers - no measuring required."Quick-Set" retaining angles when specified and supplied with Nailor integral sleeve fire dampers provide the "complete"installation package. Simple, fast, convenient.

FOR USE WITH ALL SLEEVED FIRE DAMPERS• Maximum size: 90" x 48" (2286 x 1219) or 48" x 90" (1219 x 2286).

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 55: Fire Damper Nailor

D55

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

SEALING OPTIONS FOR TYPE C DAMPERS:

OPTION CODE LPUNSEALED: FOR LOW PRESSURE

Standard construction on Type C fire dampers. Transition casing andcollars are unsealed. Suitable for use in most low pressureapplications involving static pressures up to 2" w.g. (5 kPa).

Sealed for use in medium andhigh pressure applications up to6" w.g. (1.5 kPa), Type C firedampers with HP option areexternally caulked to minimizeleakage through casing andcollars.

All Nailor curtain type firedampers are equipped asstandard with a UL Listed fusiblelink that will melt, or ‘fuse’, when itis subjected to it’s rated meltingtemperature, allowing the damperto close. 165°F (74°C) fusible linkis provided as standard. 212°F(100°C) is also available (SeeClosure Temperature Options).

OPTION CODE HPSEALED: FOR MEDIUM/HIGHPRESSURE

OPTION CODE FLFUSIBLE LINK

'C' PLATESFULLY CAULKED

BOTH COLLARSFULLY CAULKED

FRAME/CASINGCAULKED ASNECESSARY

CLOSURE DEVICES:

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 56: Fire Damper Nailor

D56

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

SUGGESTED SPECIFICATION: (Add to standard frame fire damper specifications):

Curtain type fire dampers shall each be equipped with factory installedEasy Maintenance Link (EML), as manufactured by Nailor Industries.EML shall be accessible from either side of damper and shall allow forreleasing, testing and relatching of blades with one hand.

CLOSURE DEVICES:

OPTION CODE EMLEASY MAINTENANCE LINK

Nailor’s Easy Maintenance Link provides a simple solution for theawkward task of manually testing curtain type fire dampers.NFPA Standard 90A, Appendix B, suggests examining and testing eachfire damper every two years to ensure proper operation, and theNational Fire Code of Canada states that fire dampers shall beinspected at intervals not greater than 12 months. Nailor’s EML allowsyou to release, test and reload a standard 4 1/4" (108) deep frame firedamper quickly and easily with one hand, even through the smallestaccess door. This saves time and money, and even encourages firedamper maintenance, ensuring the protection of building occupants.165°F (74°C) temperature rating is standard. 212°F (100°C) is alsoavailable. The EML is accessible from either side of the damper,providing safe and reliable convenience.

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 57: Fire Damper Nailor

D57

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

CLOSURE DEVICES:

OPTION CODE ETLELECTRO-THERMAL LINK

Nailor’s Electro-Thermal Link (ETL®) is a dual responsive fusible link thatmelts when either the link is subjected to local heat (165°F (74°C)) exactlythe same as an ordinary fusible link, or when an electrical impulse from anexternal source such as a smoke detector is sent to it. The ETL® can besubstituted for ordinary fusible links in existing or new installations of firedampers where it is desirable to improve life safety by making the firedamper respond to smoke in the early form of invisible products ofcombustion through ionization smoke detectors for example. The ETL®’s electro-response is the unique feature. It in itself is not smokeresponsive, but it’s power requirement is so low that it can be released by anelectrical impulse from any smoke detector’s power source. It is compatiblewith every smoke detector on the market in the United States today. Theoperating range is 6 to 30 volts AC or DC, less than 0.2 amperes of tripcurrent required (for 50 millisecond duration). The electrical response is a

trigger for the chemicalheating of the centerelement which is a self-contained exo-thermicreactor, yielding nonoise, smoke or gas…just quick heat to openthe link in about sevenseconds. The ETL®’sthermal response is thesame as that of ordinaryfusible links that have a165°F (74°C) and 40 lbs.rating.With it’s dual responsive-ness the ETL® can besubstituted for two otherdevices at a savings in

initial cost as well as operating cost and maintenance. It is built to zero defectstandards and to last at least fifty years and then still react properly, only onfire or smoke emergency. It is totally independent of power failures since itdraws power from the detector standby source if needed. The ETL® is listedby UL as a Fusible Link, however, with the ongoing development of dynamicsmoke control systems and building code changes, application and useshould be governed by acceptance of the local authority having jurisdiction.

SUGGESTED SPECIFICATION:(Add to standard frame fire damper specifications)Curtain type fire dampers, where indicated on plans and/or schedules, shalleach be equipped with factory installed Electro-Thermal Links (ETL®), assupplied by Nailor Industries. Operating range shall be 6 to 30 volts AC orDC, less than 0.2 amperes of trip current required (for 50 millisecondduration). Link shall open within seven seconds and shall have atemperature rating of 165°F (74°C) and a 40 lbs. strength rating.

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 58: Fire Damper Nailor

D58

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

S

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

Fusible links for curtain type fire dampers are available with a choice ofseveral melting temperature ratings. Nailor fire dampers are provided asstandard with 165°F (74°C) fusible link. Available 212°F (100°C) link can beinstalled on damper at time of manufacturing, or can be ordered separatelyas a replacement part for field installation as part of a regular maintenanceprogram or after a fire emergency (providing damper is still functional).The National Fire Protection Association Standard 90A states that"fusible links shall have a temperature rating approximately 50°F (28°C)above the maximum temperature that normally is encountered whenthe system is in operation or shut down, but not less than 160°F(71°C)." Adhering to this guideline helps prevent 'nuisance trips'resulting in unnecessary replacement costs and labor time.

OPTIONAL PULL-TAB RELEASE

Nailor’s Pull-Tab releasepermits easy resetting ofhorizontal fire dampers fromeither side of damper.Horizontal fire dampers arerequired to be installed with thelocking ramps on the top side.When testing / inspecting, accessfor unlocking the closed blades isrequired to be above the damperso that the blade pack can be"pushed down" and released offof the locking ramps for reset.This is not always possible orconvenient. Nailor’s PT optionprovides the solution. A 1 1/4"(32) dia. nickel plated steel pullring is fastened to the lockingblade on the downward facingside allowing for unlocking andresetting of the blades from belowthe fire damper, as well as fromabove. The PT option is availableon all Type A and Type Bhorizontal mount curtain firedampers.

OPTION CODES 165 & 212165 or 212°F FUSIBLE LINKS

OPTION CODE PTPULL-TAB RELEASE

To release locked blades simplytug Pull-Tab downward!

As of July 01 / 2002, UL 555 Safety Standard Sixth Edition(June 1999) requires that fire dampers for static systems have

a heat responsive device of minimum 160°F (71°C), maximum 212°F(100°C) rating. Fire dampers for dynamic systems must utilize160°F (71°C) minimum, 350°F (177°C) maximum rated devices. Notethat local building codes may also stipulate a maximum closuretemperature rating.

CLOSURE TEMPERATURES:

UL 555 Update

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 59: Fire Damper Nailor

D59

D

CURTAIN FIRE DAMPERSCU

RTA

INFIR

ED

AM

PER

SCURTAIN FIRE DAMPERS

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

OPTIONALMICROSWITCHES:

OPTION CODE MS24V MICROSWITCH

OPTION CODE MSE120/24V MICROSWITCH WITHENCLOSURE

Option Code MS provides anyNailor fire damper with a factorymounted micro switch suitable foruse in low voltage (24V)applications. Activated when thedamper blades are closed, theswitch can be used for statusindication of damper when wiredinto a control panel or can beutilized to shut a fan off uponclosure of damper. UL and CSAapproved single pole, double throwswitch is rated up to 15 amps. andcan be wired up as normally closedor normally open, depending uponapplication.

Option Code MSE, microswitchwith enclosure, provides a factorymounted micro switch similar toOption MS, except the MSE withits safety enclosure is suitable foruse in line voltage (120V)applications. Similarly, the MSEcan be used for status indication orfan shut down and also can bewired for normally closed ornormally open applications.Enclosure is tapped with 1/2 inchNPS threads for conduitconnection and is also providedwith an internal earthing (ground)screw.

FOR STATUS INDICATION OR FAN SHUT-OFF

CURTAIN FIRE DAMPERS

Options and Variables

Revised April 26, 2005

Page 60: Fire Damper Nailor

Nailor curtain type fire dampers are tested by and listed with Underwriters Laboratories Inc. and aremanufactured within UL procedural requirements. Approved variables including a variety of options are availableto suit specific applications.

D60

D

CURTAIN FIRE DAMPERSCU

RTA

INFI

RE

DA

MPER

SCURTAIN FIRE DAMPERS

FLANGED SLEEVE

OPTION CODES TDF1, TDF2TDF FLANGE

TDF (by Engle) and TDC(by Lockformer) proprietaryflange systems areapproved as breakawayconnections for connectinga factory sleeved (22 or 20gauge) Type A or B curtaintype fire damper toductwork. They may beused in place of theapproved slip joints shownin standard installationinstructions.

For Option TDF1 the sleeve is factory flanged on one end only.For Option TDF2 the sleeve is factory flanged on both ends.Note that the maximum wall/floor opening size permitted by UL, relative tothe damper size, may not physically allow the flange to fit through theopening. Consultation and co-ordination with the wall/floor contractor isrecommended. TDF1, flange on one end only, will permit the non-flangedend of the sleeve to fit through the opening.

Maximum TDF1/TDF2 Sleeve Size Allowed:

For Curtain Type Fire Damper: 60" wide x 60" high (1524 x 1524).

For Multi-Blade Type Fire Damper: 36" wide x 48" high (914 x 1219).

Revised February 17, 2005

CURTAIN FIRE DAMPERS

Options and Variables